HomeMy WebLinkAboutFile Documents.520 E Hyman Ave.0158.2018 (9).ARBKMarkup Summary Mechanical Permit Documents 11-6-2018
Page Label: M2.1 ROOF HVAC PLAN
Page Index: 4
Checkmark: Unchecked
Author: bobn
Date: 11/6/2018 12:28:29 PM
Color:
File Name: Mechanical Permit Documents.pdf
Mechanical Permit Documents.pdf (1)
20.0 ft
20.0 ft
20.0 ft
Please reference Section26.575.020.(F),Measuring BuildingHeights.4, Allowed Exceptions to HeightLimitations.(a) and (e). All chimneys,flues, vents, and similar ventingapparatus should be set back from anystreet facing facade of the building aminimum of 20 feet and the footprintshould be minimized and combined tothe greatest extent practicable. AC Unitsand other mechanical equipment, shallbe set back from any street facing facadeof the building a minimum of 15 feet.
20.0 ft
15.0 ft
15.0 ft
15.0 ft
15.0 ft
R+B: Please see attached revised A7.12
Drawing, Detail #7. all ductwork that falls
within the 20'-0" setback shall be installed
below roof finish and shall not extend
beyond the existing parapet height.
12/27/2018