HomeMy WebLinkAboutFile Documents.219 E Durant Ave.0130.2016 (23).ARBK F5689.17-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to PLITEQ INC. Series/Model: Daltile Type X3 Porcelain Tile on GenieMat™ RST05 - Wire Hung Ceiling Specimen Type: Concrete on Steel Decking Overall Size: 3023 mm by 3632 mm (119" by 143") STC 60 IIC 53 Test Specimen Identification: Floor Topping: 7.8 mm (0.31") Daltile Type X3 Porcelain Tile Floor Underlayment: 4.97 mm (0.2") Pliteq GenieMat™ RST05 Rubber Underlayment Concrete Slab: 101.6 mm (4") Standard 4000 PSI Concrete Deck: 50.8 mm (2") 18 Gage Vulcraft 2VLI Composite Floor Deck Main Beams: 38.1 mm (1.5") Clark-Dietrich U-Channel Cold Rolled Channel Cross Beams: 22.2 mm (0.87") 20 Gage Drywall Furring Channel Ceiling: 15.9 mm (0.63") USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel Reference should be made to Intertek-ATI Report F5689.17-113-11 for complete test specimen description. This page alone is not a complete report. 130 Derry Courtaa York, PA 17406aa p. 717.764.7700 f. 717.764.4129www.archtest.com · www.intertek.com/building F5689.17-113-11-R0 Page 1 of 4 Acoustical Performance Test Report PLITEQ INC. 1370 Don Mills Road Toronto, Ontario M3B 3N7 CANADA Report F5689.17-113-11 Test Date 04/11/16 Report Date 05/03/16 Project Scope Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct airborne sound transmission loss and impact sound transmission tests. The complete test data is included as attachments to this report. The client provided the test specimen. The specimen was constructed on the date of testing. Test Methods The acoustical tests were conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions ASTM E 413-10, Classification for Rating Sound Insulation ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC) ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods Test Procedure All testing was conducted in the VT test chambers at Intertek-ATI located in York, Pennsylvania. The microphones were calibrated before conducting the tests. The airborne transmission loss test was conducted in accordance with the ASTM E 90 test method using the single direction method. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Four sound pressure level measurements were made simultaneously in both rooms,at each of five microphone positions. 130 Derry Courtaa York, PA 17406aa p. 717.764.7700 f. 717.764.4129www.archtest.com · www.intertek.com/building F5689.17-113-11-R0 Page 2 of 4 Test Procedure (Continued) The impact sound transmission test was conducted in accordance with the ASTM E 492 test method. Two background noise sound pressure level, two sound pressure level measurements with the tapping machine operating at each position specified by ASTM E 492, and five sound absorption measurements were conducted at each of five microphone positions. The air temperature and relative humidity conditions were monitored and recorded during all measurements. Test Conditions Source Room Receive Room Average Temperature 19.9°C (67.9°F)Average Temperature 19.4°C (66.9°F) Average Relative Humidity 56%Average Relative Humidity 56% Test Calculations The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated in accordance with ASTM E 413 and ASTM E 989, respectively. Test Specimen Materials and Installation Details Material Dimensions (mm/inch) Thickness (mm/inch)Manufacturer and Series Quantity Average Weight Porcelain Tile 304.8 by 304.8 12 by 12 7.8 / 0.31 Daltile Type X3 10.98 m² 118.19 ft² 15.7 kg/m² 3.22 lb/ft² Note: Laticrete Permacolor grout was placed into the 6.35 mm (1/4") joints between the ceramic tile and wiped clean. The ceramic tile was placed with light pressure onto a bed of Laticrete Platinum 254 mortar on the underlayment. The mortar was set using a 6.35 mm by 6.35 mm (1/4"by 1/4") trowel. Both the grout and mortar were allowed to cure to manufacturer's specifications. Rubber Underlayment 3023 by 914.4 119 by 36 5 / 0.2 Pliteq GenieMat™ RST05 10.98 m² 118.19 ft² 4.93 kg/m² 1.01 lb/ft² Note: Adhered to the concrete slab with Pliteq GenieMat FAS-2 adhesive, using a manufacturer- supplied trowel, per manufacturer's specifications. Standard 4000 PSI Concrete 3023 by 3632 119 by 143 101.6 / 4 N/A 10.98 m² 118.19 ft² 180.42 kg/m² 36.95 lb/ft² Note: Poured directly on the floor deck and allowed to cure for a minimum of 28 days. Composite Floor Deck 3023 by 3632 119 by 143 50.8 / 2 18 Gage Vulcraft 2VLI 10.98 m² 118.19 ft² 12.74 kg/m² 2.61 lb/ft² Note: Installed per manufacturer's specifications in a test frame with the top of the concrete flush with the source room.All seams and gaps underneath the deck were plugged with backer rod and sealed with Pecora AC-20 Acoustical Sealant. Cold Rolled Channel 14.3 by 3632 0.6 by 143 38.1 / 1.5 Clark-Dietrich U-Channel 10.9 lin m 35.8 lin ft 0.69 kg/m 0.46 lb/ft Note: Eye hooks were attached to the bottom of the concrete at twelve locations in a 610 mm by 1219 mm (24"by 48")pattern.12 gage hanger wire was fed through eye hooks and wrapped around the channel. The measured steel thickness of the channels was 2.0 mm (0.08"). Page 3 of 4 Test Specimen Materials and Installation Details (Continued) Material Dimensions (mm/inch) Thickness (mm/inch)Manufacturer and Series Quantity Average Weight F5689.17-113-11-R0 20 Gage Drywall Furring Channel 3023 by 63.6 119 by 2.5 22.2 / 0.87 N/A 21.2 lin m 69.4 lin ft 0.57 kg/m 0.38 lb/ft Note: Fastened to the U-Channel on 610 mm (24") centers with 11.11 mm (7/16") self tapping #6 screws. The measured steel thickness is 1.2 mm (0.05"). Gypsum Panel 1219 by 3023 48 by 119 15.9 / 0.63 USG SHEETROCK® Brand FIRECODE® C Core 10.98 m² 118.19 ft² 11.9 kg/m² 2.44 lb/ft² Note: The gypsum panels were fastened to the furring channels on 304.8 mm (12") centers along the channel with 25.4 mm (1")#6 fine-thread drywall screws. The seams of the gypsum panels were sealed with Pecora AC-20 FTR caulk and covered with pressure sensitive tape. The perimeter was sealed with Sikaflex 15LM Construction Sealant. Comments The total weight of the floor/ceiling assembly was 2497.7 kg / 5506.8 lbs. Intertek-ATI will store samples of the test specimen for four years. Photographs of the test specimen are included in the attachments. The client did not supply drawings of the test specimen. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory.It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. FOR INTERTEK-ATI: Cody R. Snyder Jordan Strybos Technician II - Acoustical Testing Project Manager - Acoustical Testing Attachments (6 Pages): This report is complete only when all attachments are included. * Stated by Client/Manufacturer N/A - Non Applicable F5689.17-113-11-R0 Page 4 of 4 Revision Log Revision Date Page(s) Description R0 05/03/16 N/A Original Report Issue This report produced from controlled document template ATI 00629(d), Revised 02/09/15. F5689.17-113-11-R0 Attachments Instrumentation Instrument Manufacturer Model ATI Number Date of Calibration Data Acquisition Unit National Instruments PXI-1033 63763 06/14 * Microphone Calibrator Norsonic 1251 INT00127 01/16 Receive Room Microphone Scantek 378B20 63748 05/15 Receive Room Microphone PCB Piezotronics 378B20 63744 05/15 Receive Room Microphone PCB Piezotronics 378B20 63745 05/15 Receive Room Microphone PCB Piezotronics 378B20 63746 05/15 Receive Room Microphone PCB Piezotronics 378B20 63747 05/15 Receive Room Environmental Indicator Comet T7510 63810 63811 10/15 10/15 Source Room Microphone PCB Piezotronics 378B20 63738 04/15 Source Room Microphone PCB Piezotronics 378B20 63739 04/15 Source Room Microphone PCB Piezotronics 378B20 63740 04/15 Source Room Microphone PCB Piezotronics 378B20 63742 04/15 Source Room Microphone Scantek 378B20 63741 04/15 Source Room Environmental Indicator Comet T7510 63812 11/15 Tapping Machine Look Line s.r.l.EM50 (TM50)65351 02/16 * The calibration frequency for this equipment is every two years per the manufacturer's recommendation. Test Chambers VT Receive Room Volume 155.77 m³ (5500.85 ft³) VT Source Room Volume 190 m³ (6709.79 ft³) Page 1 of 6 STC Rating (Sound Transmission Class) Deficiencies (Sum of Deficiencies) Rw Rating (Sound Reduction Index) F5689.17-113-11-R0 AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 04/11/16 Data File No.F5689.17 Client Pliteq Inc. Description 7.8 mm (0.31") Daltile Type X3 Porcelain Tile, 4.97 mm (0.2") Pliteq GenieMat™RST05 Rubber Underlayment, 101.6 mm (4") Standard 4000 PSI Concrete, 50.8 mm (2") 18 Gage Vulcraft 2VLI Composite Floor Deck, 38.1 mm (1.5") Clark-Dietrich U- Channel Cold Rolled Channel, 22.2 mm (0.87") 20 Gage Drywall Furring Channel, 15.9 mm (0.63") USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel Specimen Area 10.98 m² Technician Cody R. Snyder Freq Background Absorption Source Receive Specimen TL 95%Number SPL SPL SPL Confidence of (Hz)(dB)(m²)(dB)(dB)(dB)Limit Deficiencies 50 37.1 29.1 101 68 30 5.30 - 63 35.1 28.5 101 63 35 3.90 - 80 32.0 18.9 109 69 39 4.60 - 100 32.4 13.0 107 67 40 2.40 - 125 28.9 11.0 105 65 41 1.00 3 160 22.9 9.8 107 65 44 1.40 3 200 19.4 11.8 104 60 45 1.50 5 250 27.5 11.5 104 58 47 1.00 6 315 16.7 12.4 106 57 49 1.30 7 400 14.9 9.7 104 51 56 0.90 3 500 20.2 9.6 104 46 59 0.60 1 630 15.5 9.0 106 48 60 0.60 1 800 16.4 9.1 105 44 63 0.50 0 1000 15.9 9.0 104 42 64 0.40 0 1250 9.9 8.9 104 40 67 0.50 0 1600 7.4 9.0 104 39 67 0.30 0 2000 4.5 9.8 104 40 66 0.30 0 2500 4.4 10.5 102 37 67 0.50 0 3150 3.9 11.5 102 32 70 0.50 0 4000 4.8 13.0 104 31 72 0.40 0 5000 5.4 14.9 104 29 74 0.60 - 6300 5.8 19.4 98 20 77 0.70 - 8000 6.1 24.7 96 16 78 0.80 - 10000 7.0 31.3 91 8 80 0.60 - 60 29 60 Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow. 2) Specimen TL levels listed in red indicate the lower limit of the transmission loss. 3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied ATI 00614 Revised 02/09/15 Page 2 of 6 F5689.17-113-11-R0 AIRBORNE SOUND TRANSMISSION LOSS ASTM E 90 Test Date 04/11/16 Data File No.F5689.17 Client Pliteq Inc. Description 7.8 mm (0.31") Daltile Type X3 Porcelain Tile, 4.97 mm (0.2") Pliteq GenieMat™RST05 Rubber Underlayment, 101.6 mm (4") Standard 4000 PSI Concrete, 50.8 mm (2") 18 Gage Vulcraft 2VLI Composite Floor Deck, 38.1 mm (1.5") Clark-Dietrich U- Channel Cold Rolled Channel, 22.2 mm (0.87") 20 Gage Drywall Furring Channel, 15.9 mm (0.63") USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel Specimen Area 10.98 m² Technician Cody R. Snyder ATI 00614 Revised 02/09/15 Page 3 of 6 0 10 20 30 40 50 60 70 80 90 100 631252505001000200040008000Sound Transmission Loss (dB)Frequency (Hz) Airborne Sound Transmission Loss Specimen TL Contour Curve IIC Rating (Impact Insulation Class) Deficiencies (Sum of Deficiencies) F5689.17-113-11-R0 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 04/11/16 Data File No.F5689.17 Client Pliteq Inc. Description 7.8 mm (0.31") Daltile Type X3 Porcelain Tile, 4.97 mm (0.2") Pliteq GenieMat™RST05 Rubber Underlayment, 101.6 mm (4") Standard 4000 PSI Concrete, 50.8 mm (2") 18 Gage Vulcraft 2VLI Composite Floor Deck, 38.1 mm (1.5") Clark-Dietrich U- Channel Cold Rolled Channel, 22.2 mm (0.87") 20 Gage Drywall Furring Channel, 15.9 mm (0.63") USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel Specimen Area 10.98 m² Technician Cody R. Snyder Freq Background SPL Absorption Normalized Impact SPL 95%Number Confidence of (Hz)(dB)(m²)(dB)Limit Deficiencies 50 37.2 31.4 63 3.6 - 63 35.1 45.5 62 4.3 - 80 32.3 19.1 55 2.2 - 100 30.8 11.7 56 3.0 0 125 30.0 10.3 56 2.6 0 160 23.2 9.9 58 2.0 0 200 18.5 11.4 58 1.2 0 250 27.8 11.4 63 1.1 4 315 16.9 12.0 59 0.7 0 400 16.0 9.7 58 1.2 0 500 20.8 9.4 56 0.7 0 630 15.4 9.1 62 0.6 6 800 17.4 9.1 59 0.7 4 1000 17.3 8.9 55 0.3 1 1250 10.0 9.0 52 0.5 1 1600 7.5 9.1 50 0.6 2 2000 4.6 9.8 52 0.4 7 2500 4.3 10.5 46 0.3 4 3150 4.1 11.4 40 0.5 1 4000 4.8 13.1 33 0.4 - 5000 5.4 15.2 28 0.5 - 6300 5.8 19.2 20 0.6 - 8000 6.1 24.9 13 0.5 - 10000 7.1 31.6 11 0.5 - 53 30 Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow. ATI 00615 Revised 02/09/15 Page 4 of 6 F5689.17-113-11-R0 IMPACT SOUND TRANSMISSION ASTM E 492 Test Date 04/11/16 Data File No.F5689.17 Client Pliteq Inc. Description 7.8 mm (0.31") Daltile Type X3 Porcelain Tile, 4.97 mm (0.2") Pliteq GenieMat™RST05 Rubber Underlayment, 101.6 mm (4") Standard 4000 PSI Concrete, 50.8 mm (2") 18 Gage Vulcraft 2VLI Composite Floor Deck, 38.1 mm (1.5") Clark-Dietrich U- Channel Cold Rolled Channel, 22.2 mm (0.87") 20 Gage Drywall Furring Channel, 15.9 mm (0.63") USG SHEETROCK® Brand FIRECODE® C Core Gypsum Panel Specimen Area 10.98 m² Technician Cody R. Snyder ATI 00615 Revised 02/09/15 Page 5 of 6 10 20 30 40 50 60 70 80 90 100 1100 10 20 30 40 50 60 70 80 90 100 631252505001000200040008000Impact Insulation Class (IIC)Sound Pressure Level (dB)Frequency (Hz) Impact Sound Transmission Normalized Impact SPL Contour Curve F5689.17-113-11-R0 Photographs Source Room View of Test Specimen Installation Page 6 of 6 Receive Room View of Test Specimen Installation