HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0071.2018 (11).ACBKStructural Plan Review
July 3, 2018
Review/Report is based on structural Construction Documents prepared by Lindauer-Dunn, Inc.,
Structural Engineers, dated 05/09/2018 (100% CD) and architectural drawings prepared by
Chamberlin Architects, dated 05/09/2018 and received via electronic transfer on 06/20/2018.
Structural drawings are stamped and signed by the engineer of record.
Project Name: Aspen Ambulance District Facility
Project Location: 401 Castle Creek Road, Aspen, CO 81611
Review based on International Building Code (IBC) Edition: 2015
Building Construction Type: Structure consists of metal deck on steel joists and beams at the
roof level with a structural concrete slab on metal decking supported by steel joists and beams
at the upper level. The lower level ambulance apparatus bays and classroom areas floor system
is a concrete slab on grade. Foundation system is concrete foundation walls and footings. Lateral
system consists of structural steel braced frames.
Building Department Jurisdiction: Aspen Building Department
Risk Category: IV (IBC 2015 Table 1604.5)
Basic Wind Speed: 120 mph (ultimate)
Exposure: B
Seismic Site Class: D
Importance Factor: Ie = 1.5
Snow Load: 75 psf uniform
Ground Snow Load: 100 psf
Importance Factor: Is = 1.2
Frost Depth: 36”
Structural Review Comments:
1. Sheet S-100 General Notes: Please provide soils report referenced in the general notes
for review.
P a g e | 2
2. Sheet S-100 Entry Canopy Framing Plan: The column sizes for the canopy support framing
do not appear to be noted on plan. Please provide.
3. Sheet S-103 Upper Floor Framing Plan: The lateral loads being transferred into Braced
Frame #1 at the elevator/stair openings appear to be very high. Please provide
calculations and details that indicate how these lateral loads are transferred into the
braced frame without a floor diaphragm.
4. Sheet S-202 Braced Frame Details/Elevations: The overturning forces at Braced Frame
#1 and #6 appear to be very high. Please provide calculations that indicate the standard
anchor bolt with standard hook only as detailed on A/S203 is adequate to resist the
overturning loads.
Plan Review by:
Dan C. Donegon, P.E.
HCDA Engineering, Inc.
(719) 633-7784
ddonegon@hcdaengineering.com