HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0071.2018 (32).ACBKEng Comments Ambulance Facility Rd 1 Page: [3] C-101 EXISTING CONDITIONS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Existing sewer lateral does not appear to be shown and sewer main appears to be incomplete. Please shown the full alignment for the sanitary sewer system. Also please clarify the work on this utility on subsequent sheets as applicable, including demolition overall site plan, profile sheets, etc. 2018-05-09 AADF 100% CD Civil Set.pdf (56) Page: [3] C-101 EXISTING CONDITIONS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please clarify what this utility labeled "ET" is as it is not included in the legend. Page: [3] C-101 EXISTING CONDITIONS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Show existing stormwater conveyance systems on this sheet or on a separate sheet with labels for structures, pipes, etc. Page: [4] C-102 OVERALL SITE PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Water service alignment appears incomplete. Please revise to show complete alignment. Page: [4] C-102 OVERALL SITE PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Show continuation of pedestrian route to hospital campus. Page: [4] C-102 OVERALL SITE PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf If dashed line around the perimeter designates an easement boulder wall cannot encroach in it. If this is the setback of the property, confirm with Zoning that wall is allowed. Alternatively if this the adjacent property, provide letter that this is acceptable. Page: [5] C-103 DEMO PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Demo existing sewer for HHS Building? Page: [5] C-103 DEMO PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf 2 inch saw cut does not appear to be needed. Page: [7] C-105 PARKING LOT LAYOUT & SIGNAGE File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Indicate the raised will be striped. 233.02'233.02' S S S C CT Existing sewer lateral does not appear to beshown and sewer main appears to be incomplete. Please shown the full alignment forthe sanitary sewer system. Also please clarifythe work on this utility on subsequent sheets asapplicable, including demolition overall siteplan, profile sheets, etc. 199.49' 199.49'Please clarify what this utility labeled "ET" is as it is not included in the legend. Show existing stormwater conveyance systems on this sheet or on a separate sheet with labels for structures, pipes, etc. WV WV WV Water service alignment appears incomplete. Please revise to show complete alignment. WV WV AL LOOP ROAD Show continuation of pedestrian route to hospital campus. If dashed line around the perimeterdesignates an easement boulder wall cannot encroach in it. If this is the setback of the property, confirmwith Zoning that wall is allowed.Alternatively if this the adjacent property, provide letter that this is acceptable.XXXX XX Demo existing sewerfor HHS Building? WV WV WV 2 inch saw cut does not appear to be needed.compactcompactSPEEDHUMP Indicate the raised will be striped. Existing pipes and structures have been labeled on this sheet. This is an electric and telephone line. This linetype has been added to the legend. As discussed at meeting on 6/19, this saw cut is necessary to ensure a clean line on the outside of the milled joint A note has been added to abandon existing service in place, and to cap and plug at the sewer main We looked into this and determined that striping shouldn't be necessary here since the road is one way. The pedestrian route towards the hospital has been added (striping and the ramp/sidewalk location on the opposites side of the road). The ramp has been shifted over ~4' to line up with the existing striping and our plans now call for the road to be re-striped. The water main in HLR has been fixed to connect to the water main in Castle Creek Rd. The existing sewer pipe has been fixed here and the sewer service has been added per ACSD service maps. All other sheets have been updated accordingly. This dashed line represents the set back. The ditch at this location is a man-made anomaly. The proposed sidewalk and boulder wall is not changing grade by more than 30" from historic (without the man-made ditch) 06/26/2018 Page: [7] C-105 PARKING LOT LAYOUT & SIGNAGE File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide stop sign(s) and stop bar from exit road to Doolittle drive Page: [7] C-105 PARKING LOT LAYOUT & SIGNAGE File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Provide signage detail(s) for accessible parking. Page: [12] C-110 AADF GRADING File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Mark exact location of grade break in drive. Page: [12] C-110 AADF GRADING File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Include scale and north arrow. Page: [13] C-111 AADF PERIMETER DRAIN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide a detail for foundation drain drywell. Page: [13] C-111 AADF PERIMETER DRAIN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Include scale and north arrow. Page: [14] C-112 PARKING LOT GRADING PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Light pole in curb & gutter? Not shown on other details. Page: [14] C-112 PARKING LOT GRADING PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Light pole in correct location? Please relocate out of path of travel. Page: [14] C-112 PARKING LOT GRADING PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Where does ribbon curb stop and start? Please provide detail. Page: [14] C-112 PARKING LOT GRADING PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Where are break points from catch to spill curb & gutter?WRONGWAYPlease provide stop sign(s) and stop bar from exit road to Doolittle drive Provide signage detail(s) for accessible parking. ASPE S Mark exact location of grade break in drive. Include scale and north arrow. A P D Please provide a detail for foundation drain drywell. Include scale and north arrow. Light pole in curb & gutter? Not shown on other details. Light pole in correct location? Please relocate out of path of travel. Where does ribbon curb stop and start? Please provide detail. Where are breakpoints from catch to spill curb & gutter? These have been added to sheet C-105. The location of the stop sign follows the MUTCD (section 2B-10 #13) Signs details for accessible parking spaces have been added This has been added A detail has been added to sheet C-111 This has been added This light fixture will be demoed, the plans have been fixed to represent this This light fixture will be demoed, the plans have been fixed to represent this Labels have been added to this area to distinguish the extents of ribbon vs spill vs catch curb and a detail for the ribbon curb has been added on sheet C-501 These transitions have been labeled. As discussed at the meeting on 6/19, there is no exact grade break, the snow-melted slab needs to be warped to match the existing grade at the hospital loop road and the FFE at the bays. The point of 0% slope (towards the building) has been labeled to clarify. 06/26/2018 Page: [15] C-113 PARKING LOT LOOP P&P 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please show utilities in parking lot loop profiles on plan view also. Page: [17] C-115 PARKING LOT TURNING File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Provide an exhibit that shows there are no obstructions within the sight triangle, 30 feet from the intersection, as defined in the CoA Design Standards #ENG-206A. Page: [18] C-116 UTILITY LAYOUT File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Space trees away from water service. Page: [18] C-116 UTILITY LAYOUT File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Sanitary & Water appear to lack 10 feet of separation. Page: [18] C-116 UTILITY LAYOUT File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Are existing electric & gas running through retaining wall? If so, shoring documents do not match civil documents, coordinate appropriately. Page: [18] C-116 UTILITY LAYOUT File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Space trees away from water service. Page: [18] C-116 UTILITY LAYOUT File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Tree on northeast side of parking lot is too close to water line. Page: [19] C-117 DRY UTILITY RELOCATION PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Clarify the purpose of this easement. Is access to gasline also included? Page: [19] C-117 DRY UTILITY RELOCATION PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Easement lines appear incorrect and must include the new transformer. Transformer easements shall be sized to include adequate clearance zones. Page: [19] C-117 DRY UTILITY RELOCATION PLAN File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Similar to the existing electric and gas lines, note on this sheet that the FO line will be removed following new FO utility work. Please show utilitiesin parking lot loopprofiles on plan viewalso. Provide an exhibit that shows there are no obstructions within the sight triangle, 30 feet from the intersection, as defined in the CoA Design Standards #ENG-206A. S S Space trees away from water service. S S Sanitary & Water appear to lack 10 feet of separation. Are existing electric &gas running through retaining wall? If so, shoring documents do not match civil documents, coordinateappropriately. Space trees away from water service.DOOLIT Tree on northeast side of parking lot is too close to water line. Clarify the purpose of this easement. Is access to gasline also included?compactcompactASPEN AMBU DISTR CASTLE C ASPEN, C Easement lines appear incorrect and must include the new transformer. Transformer easements shall be sized to include adequate clearance zones. Similar to the existing electric and gas lines, note on this sheet that the FO line will be removed following new FO utility work. Utilities have been added to these sheets in plan view. Exhibits have been added to C-115 showing the sight triangles for Doolittle and HLR intersections As discussed on 6/19/18, the service tie-ins cannot be moved since no work is being done in the HHS building. We have called for the sewer service to be encased in flow fill here (see C-120, C-203). Existing gas and electric will be abandoned prior to construction of these retaining walls. This is only a Holy Cross easement since the gas line at this point is only a service line. The easement is not exclusive and Holy Cross is okay with the gas line and other utilities being within the easement as long as required clearances are met (which they are). This easement has been corrected to include the transformer (both on our plans and in the preliminary plat). Holy cross has approved of the size of the easement around the transformer. This note for the electric and gas lines now includes the fiber as well. All trees have been moved to provide at least 5' of clearance from the HHS water service. These trees have been moved to the east 2' to provide additional clearance from the water service. The clearance from the water service to the tree trunks is now 7' which allows for ample space in the event that the water service requires maintenance. These trees have been moved out of the water easement. 06/26/2018 Page: [20] C-118 STORM SYSTEM LAYOUT - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide elevations and slopes for the trench drain and Pipe 24. Page: [20] C-118 STORM SYSTEM LAYOUT - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Provide a detail or spec for the splash block. Page: [20] C-118 STORM SYSTEM LAYOUT - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf No profiles/elevations/slopes are provided for Pipes 20-23 and Inlets 2-4. Page: [20] C-118 STORM SYSTEM LAYOUT - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Based on the drainage report, it appears this is the roof connection for sub-basin 1.6. Please verify this or clarify where the roof drains to. Page: [20] C-118 STORM SYSTEM LAYOUT - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please label tie-in manhole for Pipe 19 on plan view. Page: [21] C-119 STORM SYSTEM LAYOUT - 2 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide more information for the 15" ADS pipe and FES south of the exit drive. Page: [21] C-119 STORM SYSTEM LAYOUT - 2 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Remove infrastructure out of sidewalk. Page: [21] C-119 STORM SYSTEM LAYOUT - 2 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Identify the locations of HLR EX PIPE-1, HLR EX PIPE-2, and Doolittle EX PIPE. Page: [22] C-120 SANITARY SEWER PLAN & PROFILE File Name: 2018-05-09 AADF 100% CD Civil Set.pdf 18 inches of separation between water and sanitary required. Identify the clearance shown. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Include shut-off instructions for main line to cut in tee. Please provide elevations and slopes for the trench drain and Pipe 24. Provide a detail or spec for the splash block. S No profiles/elevations/slopesare provided for Pipes 20-23and Inlets 2-4. compact Based on the drainage report, it appears thisis the roof connection for sub-basin 1.6.Please verify this or clarify where the roofdrains to. Please label tie-inmanhole for Pipe 19on plan view. Please provide more information for the 15" ADS pipe and FES south of the exit drive. Remove infrastructure out of sidewalk. WV WV WV Identify the locations of HLR EX PIPE-1, HLR EX PIPE-2, and Doolittle EX PIPE. 18 inches of separation between water and sanitary required. Identify the clearance shown. Include shut-off instructions for main line to cut in tee. A profile has been added for the trench drain and pipe 24 showing elevations and slopes (see sheet C-201). Specifications for the size and material of the splash block has been added to this callout. The downspout location for sub-basin 1.6 has been labeled on plan view and profile view (on the east side of pipe 11) and identified as the POC for this sub-basin to clarify this point. This manhole has been labeled in plan view. As discussed at meeting on 6/19, the manhole slab will be 8" below grade and will not interfere with the construction of the sidewalk (will still have 4" concrete and 4" of road base over the slab). A profile for these pipes/inlets has been added to sheet C-202 These existing pipes and HLR EX Inlet have been labeled on this sheet. The separation here has been increased to 13" and labeled. We have updated the plans to call for encasement of the water line and for a stick of C900 to be centered on the crossing. The shutoff instruction are included in step 2. A reference to this has been added to step 1 as discussed. These sections of the storm system are too short to profile. Inlet dimensions, materials, pipe slopes etc. have been added for these pipes and inlets in plan view on C-118. 06/26/2018 Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf These notes appear to be misplaced. Please revise. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Maintain same separation from footer to allow for maintenance and constructibility. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Provide encasement of line to prevent cross connection. Ten feet either side of connection. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Appears to be a deflection in the pipe. How is this accomplished? Please show bends or allowable deflection joint-to-joint. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Optimize layout of utilities to minimize number of crossings. Page: [23] C-121 WATERLINE P&P File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Valve wrench will not turn without some separation from the valve and the hydrant. Page: [25] C-201 STORM SYSTEM PROFILES-1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please label Bend 5 in Profile 1. Page: [25] C-201 STORM SYSTEM PROFILES-1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please show electric crossing in Profile 2. Page: [25] C-201 STORM SYSTEM PROFILES-1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Not sure what downspout connection shown in Pipe 11 in Profile 1 is for. Page: [25] C-201 STORM SYSTEM PROFILES-1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please label Pipe 14 in Profile 1. These notes appear to be misplaced. Please revise. Maintain same separation from footer to allow for maintenance and constructibility. Provide encasement of line to prevent cross connection. Tenfeet either side ofconnection. Appears to be a deflection in the pipe. How isthis accomplished? Please show bends orallowable deflection joint-to-joint. Optimize layout of utilities to minimize number of crossings. Valve wrench will notturn without someseparation from the valve and the hydrant. Please label Bend 5 in Profile 1. Please show electric crossing in Profile 2. Not sure what downspout connection shown in Pipe 11 in Profile 1 is for. Please label Pipe 14 in Profile 1. These notes are correct, the band labels in this profile are for the water line top of pipe (right) and the proposed grade (left). We discussed this issue with the Architect and advocated for moving the riser further into the building. This could not be accommodated and they believe that as designed, there is sufficient space between the footer and riser to construct and maintain this pipe. We have updated the plans to call for encasement of the sewer service with flow fill 10' either side of the crossing. The profile now states to deflect the pipe past the gate valve as necessary. The change in grade here corresponds to a 1.7° deflection which is well within the allowable range for ductile iron pipe. As discussed at meeting on 6/19, the utilities in this location cannot be moved to reduce the number of crossings. The layout of this hydrant assembly has been altered to allow for more space to operate the valve (1.4'). Bend 5 has been labeled in profile 1. The electric and gas crossings have been labeled on profile 2 As mentioned previously, this is the downspout connection from the portion of the roof that makes up sub-basin 1.6. This has been clarified on the profile and in plan view. This pipe has been labeled on profile 1 06/26/2018 Page: [25] C-201 STORM SYSTEM PROFILES-1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide elevations for vertical bends in Profile 1. Page: [26] C-202 STORM SYSTEM PROFILES-2 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please show fiber and water crossings in HLR Pipe 1 Profile. Page: [28] C-401 GRADING DETAILS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Include scale and north arrow. Page: [28] C-401 GRADING DETAILS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf ADA grading detail for ramp at southeast corner of site appears to be missing. Please provide. Page: [28] C-401 GRADING DETAILS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Remove infrastructure out of sidewalk. Page: [28] C-401 GRADING DETAILS File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Where applicable, the City prefers wings in-lieu of curbs next to landscape areas to lower the trip hazard potential. Page: [29] C-501 DETAILS - 1 File Name: 2018-05-09 AADF 100% CD Civil Set.pdf Please provide height of raised crosswalk section from asphalt. Typical installation following AASHTO standards is 3 inches. Any higher than 3 inches the fire trucks have issues with losing equipment driving over them as well as plow truck blades jarring. Page: 10 File Name: 2018-05-09 Ambulance Facility Final Drainage Report.pdf Can Doolittle Pond detain area routed to it? Provide calculations if so. 2018-05-09 Ambulance Facility Final Drainage Report.pdf (4) Page: 12 File Name: 2018-05-09 Ambulance Facility Final Drainage Report.pdf There appears to be errors in the contributing sub-basins column, particularly AADF Pipes 2, 3, 4, and 5. Please revise and clarify as needed. Page: 15 File Name: 2018-05-09 Ambulance Facility Final Drainage Report.pdf Provide detail on which entity is going to upkeep storm system onsite, CDS, Doolittle Pond, and any changes to AVH pond changes. Please provideelevations for verticalbends in Profile 1. Please show fiber and water crossings in HLR Pipe 1 Profile. Include scale and north arrow. ADA grading detail for ramp at southeast corner of site appears to be missing. Please provide. Remove infrastructure out of sidewalk.7\44 - Pitkin Ambulance Facility\04-DWG\04-Sheetset\SS-AADF Grading Details.dwgWhere applicable, theCity prefers wingsin-lieu of curbs next tolandscape areas tolower the trip hazardpotential. Please provide height of raised crosswalk section from asphalt. Typical installation following AASHTO standards is 3 inches. Any higher than 3 inches the fire trucks have issues with losing equipment driving overthem as well as plowtruck blades jarring. the existing street inlet in Doolittle Drive as a form of water bed area flowing into Doolittle Pond. The unit was designed in event for subbasin 2.1 (the contributing subbasin) equal to 0.46 the 100-year storm event of 1.57 cfs. A Contech CDS2015-5 has and a maximum bypass capacity of 10.0 cfs and is therefore y will range in size from 8 to 18 inches. Grates used for 8” drain sins will have grates matching the drainage basin size. These area her the landscaping or hardscaping around the site. The inlets ediately to the west of the facility as well as from some of the nding the facility. An eight-inch trench drain will capture runoff Can Doolittle Pond detain area routed to it? Provide calculations if so. Contibuting Sub-Basins Design Flow Rate Qdes1.1-1.2 0.86 1.1-1.3 0.86 1.1-1.4 0.86 1.1-1.5 0.86 1.1-1.6 0.861.1-1.3 1.03 1.1-1.3 1.03 1.1-1.3 1.03 1.1-1.4 1.13 There appears to be errors in the contributing sub-basins column, particularly AADF Pipes 2, 3, 4, and 5. Please revise and clarify as needed. avoid its use. An agreement to avoid the use of salt for deicing will be part of the mainte as already been agreed to by Pitkin County Facility management. Provide detail on which entity is going to upkeep storm systemonsite, CDS, Doolittle Pond, and any changes to AVH pond changes. Invert elevations have been added to vertical bends in this profile. These have been added to the profile As mentioned previously, the slab of this manhole will not interfere with the sidewalk, there will be 4" of road base between the sidewalk and the manhole slab The height of this raised cross walk varies (it is about 5.5" at the centerline). We discussed the design with Parker Lathrop on 6/20 and he is alright with the height. We looked into wings at these location. With the parking lot behind the landing on the east side and 3' sidewalk heading north for the west side, wings will not work in these locations. This grading detail has been provided Scales and north arrows have been added to these details This column has been fixed to correctly reflect the contributing basins As discussed on 6/19, Doolittle pond only has water treatment capacity. A section discussing the function of this pond due to the proposed development has been added to section 4.2.3. This has been addressed in section 6.2 of the drainage report 06/26/2018 Page: 15 File Name: 2018-05-09 Ambulance Facility Final Drainage Report.pdf Please provide summary of where snow storage will be generally located and where if moved offsite. Page: 7 File Name: AADF geotech report.pdf Include hydraulic conductivity and include testing method, location, and depth of test(s), per URMP requirements. AADF geotech report.pdf (1) Page: 2 File Name: AADF survey 100% cd set.pdf Show all existing easements. It appears some are missing, including water service and a power line easement. AADF survey 100% cd set.pdf (2) Page: 2 File Name: AADF survey 100% cd set.pdf It appears that some utilities are not included in this survey, such as water main and service and sanitary sewer service. Please revise to include this. Page: 1 File Name: Fire Calcs 1.PDF Please provide more detail and explanation of why a 6 inch diameter supply line is required. Fire Calcs 1.PDF (1) eicing will be part of the maintenance plan agement. Please provide summary of where snow storage will be generally located and where if moved offsite. Include hydraulic conductivity and includetesting method, location, and depth oftest(s), per URMP requirements. Show all existing easements. It appears some are missing,including water service and a power line easement. It appears that some utilities are not included in this survey, such as water main and service and sanitary sewer service. Please revise toinclude this. Calculation Date: 3/22/2018 PreAction System:N/A Please provide more detail and explanation of why a 6 inch diameter supply line is required. Erosion Control Comments 1 - North Vehicle Tracking Pad: This pad will be used for vehicles accessing the west side of the site (the AADF building and HLR improvements). It is sufficiently sized to ensure a full wheel rotation for traffic traveling in this direction. The pedestrian route from the bus stop to the hospital is located to the east of this pad, therefore the traveling public will not be adversely impacted by this tracking pad. 2 - Southeast Vehicle Tracking Pad: The east edge of this pad has been moved to the west to keep it out of the westernmost wheel path for Doolittle Drive. A letter from CTL Thompson with this has been included. We reviewed the fire calcs and ran a headloss calculation which have been included with this submittal. These calculations show that a 4" service will be sufficient. Our plans have been updated to reflect this. The improvement survey plat has been updated with these easements. These utilities have been added to the improvement survey plat. This has been addressed in section 6.1 of the drainage report. 06/26/2018