HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (14).ACBK
ARCHITECT: Chamberlin Architects, P.C.
BY: Casey Sievila S:\1740 - Pitkin County Ambulance Facility\6. CONSTRUCTION\ASI\ASI#006.1740.doc
ARCHITECT'S
SUPPLEMENTAL INSTRUCTIONS
OWNER
ARCHITECT
CONTRACTOR
FIELD
OTHER
PROJECT: Aspen Ambulance District Facility
OWNER: Pitkin County, CO
TO: FCI Constructors, Inc.
3070 I-70 B, Bldg. A
Grand Junction, CO 81504
ARCHITECT'S SUPPLEMENTAL
INSTRUCTION NO: Six (6)
ARCHITECT: Chamberlin Architects
437 Main Street
Grand Junction, CO 81501
ARCHITECT'S PROJECT NO: 1740
DATE OF ISSUANCE: January 18, 2019, Revised 3/4/19
The Work shall be carried out in accordance with the following supplemental instructions issued in accordance with the Contract
Documents without change in Contract Sum or Contract Time. Proceeding in accordance with these instructions indicates your
acknowledgment that there will be no change in the Contract Sum or Contract Time.
Project Manual, Vol I
Section 10 2800 Toilet, Bath and Laundry Accessories, Part 2, section 2.2.B – owner to provide all soap dispensers. All
soap dispensers, paper towel dispensers and hand sanitizer dispensers shall be provided by the owner and installed by the
contractor.
Drawings
Sheet A102, The following locations for wall type 2A shall be the UL-U419 – 1 hour rated wall type as referenced in
detail 1/A001, all else shall be wall type 2:
Flex 206 along grid line E
Office 203 at gridline G and G.9
Office 212 at gridline G
Conference 214 at gridline F
Attachments: none, A001, A101, A102, A301, and A651
REVISION
ELEVATION
COLUMN GRID LOCATION
DOOR NUMBER
WINDOW TYPE
CENTER LINE
LINE OF WALL ABOVE OR HIDDEN LINE
BREAK LINE
MATCH LINE
ROOM NAME
ROOM NUMBER
BASIC WALL TYPE
A101
1
2
3
4
A
101A
Room
101
1
A101
TYP
1
A101
TYP
ANGLE
DIAMETER
PERPENDICULAR
PLATE
PLUS OR MINUS
FLOOR DRAIN
FIRE EXTINGUISHERFE
FD
1
1
100' 0"
TOP OF WALL
AL HM
INTERIOR WALL ELEVATION
REFERENCE DRAWING
REFERENCED SECTION NUMBER
SHEET NUMBER
REFERENCED DETAIL NUMBER
SHEET NUMBER
1. COMPLY WITH ALL MANUFACTURERS
RECOMMENDATIONS AND INDUSTRY STANDARDS
RELEVANT TO THE WORK HEREIN.
2. ALL DIMENSIONS ARE FROM FACE OF FINISH UNO.
3. ALL ALIGNMENTS ARE FACE OF FINISH UNO.
4. FIELD VERIFY ALL DIMENSIONS AND ROUGH
OPENINGS PRIOR TO FABRICATION AND/OR
INSTALLATION.
ABV above
ACC accessories
ADJ adjustable
AFF above finished floor
ALT alternate
AL aluminum
APC acoustical panel ceiling
ARCH architect (ural)
ASPH asphalt
A/C air conditioning
BCS baby changing station
BD board
BLDG building
BLKG blocking
BO bottom of
BRG bearing
CBU cemetitious backer unit
CG corner guard
CIP cast in place
CJ control joint
CLG ceiling
CLR clear (ance)
CMU concrete masonry unit
COL column
CONC concrete
CONT continuous or continue
CORR corridor
CPT carpet (ed)
CSMT casement
CT ceramic tile
CTR center
CU condenser unit
CWOG center wall on grid
DBL double
DEMO demolish / demolition
DF drinking fountain
DIM dimension (s)
DIR direction
DISP dispenser
DN down
DR door
DS downspout
DTL detail
DWG drawing
DWR drawer
E east
EA each
EC evaporative cooler
EG etched glass/glazing
EIFS exterior insul finish sys
EJ expansion joint
EL elevation
ELEC electric (al)
EM emergency
EWC electric water cooler
EWG end wall corner guard
EQ equal
EXG existing
EXH exhaust
EXP exposed
EXT exterior
FBO furnished by owner
FD floor drain
FDN foundation
FE fire extinguisher
FEC fire extinguisher cabinet
FEP finished end panel
FFE finished floor elevation
FIN finish
FLG flashing
FLR floor (ing)
FLUR fluorescent
FO face of
FRMG framing
FRP fiber reinforced plastic
FT foot (feet)
FTG footing
GA gage, gauge
GAL gallon
GALV galvanized
GB grab bar
GC general contractor
GL glass, glazing
GWB gypsum wallboard
GYP gypsum
HAS headed anchor stud
HB hose bibb
HCP handicap (ed)
HDR header
HDW hardware
HM hollow metal
HOR horizontal
HR hose reel
HSS hollow structural sections
HT height
HVAC heating /ventilation /air conditioning
HWD hardwood
INCL include (d) (ing)
INSUL insulate (d) (ing)
INT interior
INV invert
JST joist
JT joint
L length, angle
LAM laminate (d)
LAV lavatory
LB pound
LF lineal foot
LG laminated glass, glazing
LIN linoleum
LT light
MA match
MAS masonry
MATL material
MAX maximum
MB marker board
MECH mechanic (al)
MFR manufacture (r) (d)
MH manhole
MIN minimum
MISC miscellaneous
MLD molding, moulding
MO masonry opening
MT mount (ed) (ing)
MTL metal
N north
N/A not applicable
NIC not in contract
NOM nominal
NTS not to scale
NECY necessary
OC on center (s)
OD outside diameter
OFCI owner furnished,
contractor installed
OFD overflow drain
OFOI owner furnished,
owner installed
OH overhead
OL occupant load
OLF occupant load factor
OPG opening
OPH opposite hand
OPP opposite
OSB oriented strand board
OTA open to above
OTS open to structure
PB particle board
PERF perforate (d)
PERIM perimeter
PG pattern glass
PLAM plastic laminate
PLT plate
PNL panel
PNT paint (ed)
PR pair
PROJ projector, projection
PSF pounds per square foot
PSI pounds per square inch
PT pressure treated
PTD paper towel dispenser
PTN partition
PVC polyvinyl cholride
PVMT pavement
PWD plywood
QT quarry tile
R riser, radius
RB rubber base
REC recycling
RCMD recommend (ed) (ations)
RE reference
REF refrigerator
REIN reinforce (d) (ing)
REQ required
REV revision (s), revised
RD roof drain
RFG roofing
RH robe hook
RM room
RO rough opening
ROW right of way
RR restroom
RTU roof top unit
RUB rubber
S south
SAG susp acoustic grid
SC shower curtain rod & hooks
SCH schedule
SD soap dispenser
SHT sheet
SHTG sheathing
SIM similar
SND sanitary napkin dispenser
SNV sanitary napkin vendor
SPEC specification
SPKR speaker
SQ square
SS solid surface
SST stainless steel
STD standard
STL steel
STOR storage
STR structural
SUSP suspended
T tread
TB towel bar
TEL telephone
TG tempered glass
THK thick
T.O.top of
TOC top of concrete
TOS top of steel
TOW top of wall
TPD toilet paper dispenser
TS tube steel
TYP typical
T&G tongue and groove
UCR undercounter refigerator
UNO unless noted otherwise
VB vapor barrier
VCT vinyl composition tile
VERT vertical
VIF verify in field
VM vending machine
VNL vinyl sheet
VTR vent through roof
W west, wide, width
W/with
WB wood base
WC watercloset
WD wood
WDW window
WF wide flange
WG wire glass
W/O without
WP waterproof (ing)
WR waste receptacle
WRB weather resistive barrier
WWM welded wire mesh
WALL TYPE NOTES:
1. ALL EXTERIOR WALL TYPES ARE SHOWN WITH
THE EXTERIOR WALL FACING RIGHT UNLESS
OTHERWISE NOTED.
2. PROVIDE GLASS MAT WATER-RESISTANT BACKER
BOARD IN LIEU OF GYPSUM WALL BOARD BEHIND
ALL WALL TILE.
3. GYPSUM BOARD SHALL BE MOISTURE-RESISTANT
AT THE FOLLOWING LOCATIONS: WALLS AND
CEILINGS OF ALL RESTROOMS AND SHOWERS
4. WALL TYPE CHANGES OCCUR AT CORNERS OR
INTERSECTIONS OF WALLS UNLESS NOTED
OTHERWISE.
3-5/8" MTL STUDS
@ 16" O.C.
5/8" GYP BD, EA SIDE.
(ONE SIDE @ 1A)
SOUND ATTN BATTS
5"
ACOUSTICAL SEALANT,
EA SIDE. FIRE CAULK IN
LIEU OF @ FIRE
RARTED LOCATIONS
MTL RUNNER CHANNEL
FLOOR LINE1/2"METAL DECK
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
CONT FIRE
CAULK GWB TO
DISSIMILAR
MATERIALS, EA
SIDE
UL -U419 -1/2 HR RATED, STC: 49
6" MTL STUDS
@ 16"O.C.
5/8" GYP BD, EA SIDE
(ONE SIDE @ 2A)
SOUND ATTN
BATTS
7 1/4"
METAL DECK
ACOUSTICAL
SEALANT, EA SIDE
MTL RUNNER CHANNEL
FLOOR LINE1/2"CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
1"2A: UL -U419 -1 HR RATED @ STAIR, ELEVATOR,
FLEX 206, OFFICE 203, 212 AND CONFERENCE 214
15
6" MTL STUDS @ 16" O.C.
5/8" GYP BD
1/2" EXT SHEATHING
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
AIR SPACE
4" CMU VENEER
1' - 4 1/4"
VAPOR BARRIER
MASONRY VENEER
TIES @ 16" VERTICALLY
& HORIZONTALLY
6
6" MTL STUDS @ 16" O.C.
(10" @ 6A)
5/8" GYP BD
1/2" EXT SHEATHING
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
PRE-FINISHED HORIZONTAL MTL
PNL ATTACHED TO THERMALLY
BROKEN 'Z' CLIPS SPACED
VERTICALLY @ 24" O.C.
VAPOR BARRIER
6
6
8" CIP CONC, RE: STR
GL
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
OMIT WEATHER BARRIER & XPS INSULATION @
WALL TYPE 8A
10 1/2"6
6
11" @ 3A
10"
(2) 3-5/8" MTL
STUDS @ 16" O.C.
5/8" GYP BD,
EA SIDE
SOUND ATTN
BATTS
ACOUSTICAL
SEALANT, EA SIDE.
FIRE CAULK IN LIEU
OF @ FIRE RARTED
LOCATIONS
MTL RUNNER CHANNEL
FLOOR LINE
METAL DECK
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
UL -U493 -1 HR RATED, STC-59
CONT FIRE
CAULK GWB TO
DISSIMILAR
MATERIALS, EA
SIDE
1 - 1/2" AIR SPACE (2
1/2" @ 3A)
ALUM STOREFRONT,
NON-THERMALLY
BROKEN
UNINSULATED GLAZING
METAL DECK
1"4 1/2" (6" @ 4A)
ACOUSTICAL
SEALANT, EA SIDE
FLOOR LINE
WALL TYPE ABV,
1 @ 4 1/2", 2 @ 6"2
1
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
6" MTL STUDS SISTERED TO
6" MTL STUDS @ 16" O.C.
5/8" GYP BD
1/2" EXT SHEATHING.
5/8" EXT SHEATHING @ 7A
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
PRE-FINISHED VERTICAL MTL
PNL ATTACHED TO THERMALLY
BROKEN 'Z' GIRTS SPACED
HORIZONTALLY @ 24" O.C.
VAPOR BARRIER
1' - 4 3/4"
UL -U419 -1 HR RATED @ 7A
6
6
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
8" CONC (12" CONC
@ 9A), RE: STR
AIR SPACE
4" CMU VENEER
1' - 5 5/8"
1-HR RATED, per TABLE 721.1(2), 4-1.1.
MASONRY VENEER TIES
@ 16" VERTICALLY &
HORIZONTALLY
GL
6
8" CMU, RE: STR
7/8" MTL FURRING
CHANNELS @ 16" O.C.
@ 10A
5/8" GYP BD @ 10A
9 1/4"
6" MTL STUDS
@ 16"O.C.
5/8" GYP BD, EA SIDE
SOUND ATTN
BATTS
7 3/4"
METAL DECK
ACOUSTICAL
SEALANT, EA SIDE
MTL RUNNER CHANNEL
FLOOR LINE1/2"1/2" PWD
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
2.5" THK (R-15 MIN) RIGID
INSULATION W/ TAPED &
SEALED SEAMS
8" CMU, RE: STR
AIR SPACE
4" CMU VENEER
1' - 4 1/2"
MASONRY VENEER
TIES @ 16" VERTICALLY
& HORIZONTALLY
6
6" MTL STUDS @ 16"O.C.
5/8" GYP BD, ONE SIDE
SOUND ATTN BATTS
METAL DECK
ACOUSTICAL SEALANT,
EA SIDE
MTL RUNNER CHANNEL
FLOOR LINE1/2"4" CMU VENEER
1/2" PWD.
5/8" EXT SHEATHING @ 2D
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
MASONRY VENEER
TIES @ 16" VERTICALLY
& HORIZONTALLY
1' - 0 3/4"
UL -U419 -1 HR RATED @ 2D
12" CIP CONC,
RE: STR
GL
ACOUSTICAL
SEALANT, ONE
SIDE.
FLOOR LINE
METAL DECK
CONT COMPRESSIBLE
INSULATION IN DECK
FLUES
ACOUSTICAL
SEALANT, ONE
SIDE.
7/8" MTL FURRING
CHANNEL @ 16"
O.C.
5/8" GYP BD, ONE
SIDE.
NOT USED
2-1/2" MTL STUDS
@ 16" O.C.
5/8" GYP BD, ONE SIDE
ACOUSTICAL SEALANT,
ONE SIDE.
MTL RUNNER CHANNEL
FLOOR LINE
METAL DECK
CONT COMPRESSIBLE
INSULATION IN DECK FLUES
MTL STUD SLIP TRACK
@ METAL DECK
ACOUSTICAL
SEALANT, ONE
SIDE.
FULLY ADHERED SINGLE PLY
ROOF MEMBRANE
1/2" COVER BOARD
R-35 RIGID INSULATION
VAPOR BARRIER
MTL ROOF DECK, RE: STR
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt 3/4/2019 11:35:13 AM
A001
JANUARY 22,
2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
NOTES, SYMBOLS,
ABBREVIATIONS
AND WALL TYPES
PROJECT STATUS: 100% CD
SH JW
ASPEN
AMBULANCE
DISTRICT FACILITY
SYMBOLS GENERAL NOTESARCHITECTURAL ABBREVIATIONS
0'6"1'0'6"1'A001
WALL TYPES1
WALL TYPE 1 & 1A WALL TYPE 2 & 2A WALL TYPE 5 WALL TYPE 6 & 6A
WALL TYPE 8 & 8A
WALL TYPE 3 & 3A WALL TYPE 4 & 4A
WALL TYPE 7 &7A WALL TYPE 9 & 9A WALL TYPE 10 & 10A
WALL TYPE 2B
WALL TYPE 11
WALL TYPE 2C & 2D
WALL TYPE 12
WALL TYPE 1B
WALL TYPE 13 WALL TYPE 14
CLASS 'A' ROOF ASSEMBLY
NO: ISSUED FOR: DATE:
2 Response to City of Aspen
Review Comments
7/16/18
6 PR#010 9/25/18
15 ASI#06 3/4/19
2
A2021
A201
A202
A201
1
2
2
A B C D E G.9 I J
1
2
4
5
6
7
LOBBY
101
WOMEN
102
MEN
103
TRAINING
ROOM
104
ELEC.
105
APPARATUS
BAY #1
106
APPARATUS
BAY #2
107APPARATUS
BAY #3
108
APPARATUS
BAY #4
109
APPARATUS
BAY #5
110
APPARATUS
BAY #6
111
DECON
112
READY
ROOM
113
MEDICAL
STORAGE
114
FITNESS
115
STAIR
302
ELEVATOR
301
STAIR
303
303A
303C
112
114
115A115B
101B
113
102
103
3
105
MAIN WATER SERVICE & FIRE
SPRINKLER RISER AREA
A301
1
A651
1
A652
1
A403
1
A403
3
4
A301
2
A405
2
3
4 1
A407
2
4
1
3
3
A513
________________________________________
1
A513
________________________________________
STORAGE
116
116
2C
2
5
7
7
5
11
5
F
11
4A
4A
4A
2B
2A
2
CU (TYP of 3),
RE: MECH
109110111 108 107 106
9
5
104B
10
11
9A
A404
2
A404 1
2B
5
9
A612
3
1B
0
10' - 0"6' - 9"4' - 3 1/4"11' - 10"22' - 5"3' - 6"1' - 0"59' - 9 1/4"128' - 0"2' - 10"3' - 2"9 3/4"9' - 2 1/2"50' - 7"9 1/4"2' - 0"3' - 4"15' - 4"68' - 0"24' - 8"3' - 8 3/4"11' - 9"1' - 0"
3' - 4"14' - 0"4' - 0"14' - 0"4' - 0"14' - 0"4' - 0"14' - 0"4' - 0"10' - 0"4' - 0"10' - 0"14' - 0"4' - 1 3/4"3' - 4"7' - 2"9 3/4"9 3/4"9' - 2 1/2"2' - 8"3' - 4"6 3/4"1' - 0"9' - 4"21' - 1 1/2"13' - 4"G 2
A511
________________________________________
2
A513
________________________________________2
A512
________________________________________
ALIGN
CENTER ON
GRID LINE
3
A511
________________________________________
1
A512
________________________________________
9 5/8"18' - 6 3/8"18' - 0"18' - 0"18' - 0"14' - 0"14' - 0"10' - 11 3/8"6' - 4 5/8"10' - 1 5/8"
8' - 6 1/4"18' - 0"18' - 0"18' - 0"16' - 0"14' - 0"6' - 8 1/4"
3' - 4"22' - 8"3' - 4"5' - 4"20' - 8"10' - 0"1' - 4"3' - 4"8"28' - 0"3 3/4"10' - 0 3/4"12' - 0"8' - 0 3/4"9' - 9"22' - 10 3/4"5' - 10 1/2"CONC RAMP W/ STL
TUBE HANDRAILS,
RE: CIVIL
UP
UP
106A 101A
A03A03A04
A01
A02
B01
B02
GENERATOR, RE: ELEC
ALIGN28' - 8"9' - 4"UP
A652
2
2D 2C2D
3' - 0"3' - 0"3' - 11"5' - 0"8' - 8"3' - 0"
GAS METER
LOCATION, RE: MECH
DOOR SHOWN FOR REFERENCE,
LOCATED @ LANDING ABV
4' LONG CONC WHEEL STOPS
DOWELED INTO CONC SLAB,
COORDINATE FINAL LOCATION W/
OWNER'S VEHICLES (TYP OF 4)
1
A511
________________________________________
104A
129' - 7 1/4"
ALIGN MASONRY & CONC
2A
2A
2A
2A
4' - 2 1/4"
5' - 0"6' - 6 3/8"
1' - 0"
1
ASK-01
________________________________________
44
6' - 1 5/8"
3.5
17' - 4"20' - 0"35' - 1"3' - 2"19' - 11"15
15
15
15
15
1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION
FROM THE ARCHITECT PRIOR TO CONTINUING CONSTRUCTION.
2. ITEMS NOT NOTED ON THE DRAWINGS SHALL BE CONSIDERED THE SAME
AS NOTED ITEMS WHICH ARE GRAPHICALLY REPRESENTED IN THE SAME
MANNER.
3. PROVIDE TREATED SOLID WOOD BLOCKING FOR ALL WALL EQUIPMENT,
TOILET ACCESSORIES, MILLWORK AND OTHER WALL MOUNTED ITEMS.
SEE ELEVATIONS AND EQUIPMENT SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
4. CONTRACTOR SHALL CAULK AT THE INTERFACE OF INTERIOR FACES OF
DOOR FRAMES WITH ADJACENT MATERIALS THOUGH JOINT MAY NOT BE
VISIBLE.
5. PROVIDE TRANSITION STRIPS BETWEEN FLOOR MATERIALS OF
DISSIMILAR HEIGHTS. CENTER TRANSITION STRIPS UNDER DOORS OR
OTHER PLACES OUT OF SIGHT.
6. PROVIDE POSITIVE SLOPE ON ALL FLOOR DRAINS, MINIMUM OF1/8” PER
FOOT. SLOPE FLOOR ALL AROUND FROM ADJACENT WALLS TO FLOOR
DRAINS, DO NOT DEPRESS ONLY THE AREA IMMEDIATELY AROUND THE
DRAIN.
7. REFER TO THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS
FOR THE LOCATIONS OF PIPING, VENTS, DUCTS, CURBS, FANS AND
OTHER ITEMS WHICH PENETRATE THE ROOF PLANE.
8. DOOR JAMB LOCATION OFF FACE OF WALL IS 4", TYPICAL, UNLESS NOTED
OTHERWISE.
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt 3/4/2019 1:04:22 PM
A101
JANUARY 22,
2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
GROUND LEVEL
FLOOR PLAN
PROJECT STATUS: 100% CD
SH JW
ASPEN
AMBULANCE
DISTRICT FACILITY
0'4'8'0'4'8'A101
GROUND LEVEL FLOOR PLAN1
GENERAL NEW CONSTRUCTION NOTES
NO: ISSUED FOR: DATE:
4 RFI-009 08/10/18
15 ASI#06 3/4/19
4
..1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION
FROM THE ARCHITECT PRIOR TO CONTINUING CONSTRUCTION.
2. ITEMS NOT NOTED ON THE DRAWINGS SHALL BE CONSIDERED THE SAME
AS NOTED ITEMS WHICH ARE GRAPHICALLY REPRESENTED IN THE SAME
MANNER.
3. PROVIDE TREATED SOLID WOOD BLOCKING FOR ALL WALL EQUIPMENT,
TOILET ACCESSORIES, MILLWORK AND OTHER WALL MOUNTED ITEMS.
SEE ELEVATIONS AND EQUIPMENT SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
4. CONTRACTOR SHALL CAULK AT THE INTERFACE OF INTERIOR FACES OF
DOOR FRAMES WITH ADJACENT MATERIALS THOUGH JOINT MAY NOT BE
VISIBLE.
5. PROVIDE TRANSITION STRIPS BETWEEN FLOOR MATERIALS OF
DISSIMILAR HEIGHTS. CENTER TRANSITION STRIPS UNDER DOORS OR
OTHER PLACES OUT OF SIGHT.
6. PROVIDE POSITIVE SLOPE ON ALL FLOOR DRAINS, MINIMUM OF1/8” PER
FOOT. SLOPE FLOOR ALL AROUND FROM ADJACENT WALLS TO FLOOR
DRAINS, DO NOT DEPRESS ONLY THE AREA IMMEDIATELY AROUND THE
DRAIN.
7. REFER TO THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS
FOR THE LOCATIONS OF PIPING, VENTS, DUCTS, CURBS, FANS AND
OTHER ITEMS WHICH PENETRATE THE ROOF PLANE.
8. DOOR JAMB LOCATION OFF FACE OF WALL IS 4", TYPICAL, UNLESS NOTED
OTHERWISE.
A2021
A201
A202
A201
1
2
2
A B C D E G.9 I J
1
2
4
5
6
7
WAITING
201
OFFICE
203
OFFICE
204OFFICE
205
FLEX
206
MECH/ELEC
209
CORRIDOR
210
STOR.
213
OFFICE
212
CONFERENCE
214
LIBRARY /
REPORTS
215
CORRIDOR
220
UNIFORM
LOCKERS
221
LAUNDRY
222
CORRIDOR
224
SHOWER
225
SHOWER
226
SHOWER
227
BUNK RM
229
BUNK RM
230
BUNK RM
231
BUNK RM
232
STORAGE
228
206 205 204 203
214 212
219
221
220
225
226
227
228
229
230
231
232
303D
OPEN
TO BELOW
CANOPY
OUTLINE
3
TOILET
208
IT
211
DINING
217
DAYROOM
216
KITCHEN
218
209208
211
MECH
223
213
A301
3
A301
4
A407
9
10
8 11
A302
1
3
A513
________________________________________
1
A513
________________________________________
F
223 222
PANTRY
219
2A 2A
7
6
6
6
6
7 6 6
7
1
1
1A
1A
11
2A
2A
2A 1
12
3A
2
1
2
11
2
1
11
1
1A1A
1A1A
22
1
B03 B06 B07 B08
B16
B17B18B18B19
B20B21
A4077
6
5
2
A302
7
216
201
4
2A
2A
A202
4
6
7
A651
4
A652
3
STAIR
303
STAIR
302
ELEVATOR
301
0
1' - 0"8' - 9"3' - 0"60' - 3 1/4"1' - 0"7' - 4"1' - 0"2' - 2"4' - 5 1/2"2' - 2"1' - 0"9' - 1"9 3/4"2' - 2"5' - 9 3/4"2' - 2"1' - 0"15' - 7"2 3/4"9 3/4"9' - 0"12' - 8 3/4"3' - 0"19' - 0"16' - 0 1/2"11 1/2"1' - 4"13' - 4 3/4"1' - 0"2' - 2"8' - 6"2' - 2"6' - 6"4' - 4"1' - 4"15' - 9 1/4"1' - 0"
14
1' - 0"29' - 4 1/4"3' - 6"4' - 5"34' - 2 3/4"
G
5 3 ALIGNALIGN8' - 1 3/4"9' - 9 1/2"9' - 9 1/2"
1
2
A511
________________________________________
2
A513
________________________________________
CTR WALL ON
GRID LINE
CTR WALL ON
GRID LINE
CTR WALL ON
GRID LINE CTR WALL ON
GRID LINE
2
A512
________________________________________
3
A511
________________________________________
A732
3
1
A512
________________________________________
18' - 6 1/4"18' - 0"18' - 0"18' - 0"14' - 0"14' - 0"10' - 11 1/2"6' - 4 3/4"10' - 1 1/2"
128' - 0"10' - 0"6' - 9"4' - 3 1/4"11' - 10"22' - 5"4' - 6"59' - 9 1/4"33' - 7 1/2"10' - 5"1' - 9"3' - 0"1' - 6"9' - 6"9 3/4"8' - 0 1/4"6' - 10 1/4"5' - 10 1/2"5' - 10 1/4"8' - 1 1/4"4' - 9 1/2"10' - 1"9' - 5"9' - 5"9' - 0"2' - 11 1/2"4' - 5 3/4"11' - 11 1/2"4' - 6 1/4"13' - 11 3/4"4' - 6"13' - 8 1/2"CTR WALLS ON
GRID LINES
CTR WALL ON
GRID LINE
CTR WALL ON
GRID LINE
A732
2
A732
6
A733
1
DN
A05
7A
7A
A406
11
DECK
233
B07 B07 B07 B09
B23
B22
A301
5
B10
B11
B12
B13
B14
B23
B23
GWB SOFFIT OVER
ENTRY BELOW
A732
4
1
A644
________________________________________
2
A644
________________________________________
4
A644
________________________________________
3/4"x36" FIXED & SLIDING
DOOR GLASS PANELS10' - 11"10' - 11"10' - 6 1/2"A733
1 OPP
SLOPE
TYP
1
A511
________________________________________
6A 215
A703
17
ROOF DRAINS BELOW, TYP OF 6.
SLOPE 1/4":12" TOWARDS DRAINS
24"x24" CONC PAVERS ON ADJUSTABLE PEDESTALS
ON SINGLE PLY ROOF MEMBRAN ON 1/2" COVER
BOARD ON HIGH DENSITY RIGID INSULATION
RD RD
RDRD
RD RD
3.5
16
9
A653
________________________________________
SIM
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt 3/4/2019 1:26:14 PM
A102
JANUARY 22,
2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
UPPER LEVEL
FLOOR PLAN
PROJECT STATUS: 100% CD
SH PH
ASPEN
AMBULANCE
DISTRICT FACILITY
GENERAL NEW CONSTRUCTION NOTES
0'4'8'0'4'8'
A102
UPPER LEVEL FLOOR PLAN1
NO: ISSUED FOR: DATE:
16 PR#020 2/28/19
G.9 I J
1
2
3
A402
1
MEN
103
WOMEN
102
2
A402
A4046
LOBBY
101
3
4
5
12
11
4
3
A4021A402
2SIM
OPH
1' - 8 3/4"1' - 6"3' - 4 1/2"7' - 0"MIN CLR1' - 6"MIN CLR
5' - 0"
HD
HD
1' - 6"6' - 10"6' - 8"1' - 4"2' - 0"2C
2C
2A
2
2
2A
10
11
5
5
4A
102
103
101B
4' - 0"1' - 0"1' - 6"4' - 0"1' - 0"5' - 0"
UP
1A
RECESSED
ENTRY MAT
1B
TPD1
TPD1
WR1
WR1
SD
SD
0
G
B01
B02
4' - 8 1/4"3' - 10"1' - 8"5' - 1 1/4"4' - 2 1/4"
19' - 5 1/2"3 3/4"3 3/4"8' - 8 1/4"7' - 7 1/4"5' - 3 1/2"SIM
OPH
17' - 4"BUILD WALL TIGHT TO
STL BRACE STR
6' - 11 3/4"
A01
A02A612
2
A612
1
CTR WALL ON
GRID LINE ALIGN3' - 6"3' - 6"
ALIGN
A721
3
FD
FD
FLOOR SINK,
RE: PLUMB
A732
7
A732
1
A732
8
A612
5
1
A511
________________________________________
2A
2A2A
A
A A
A
15
15
15
15
E
3
TOILET
208
F
A4022A402
1
SIM 1, 2 OPH
A402 11A402
12
MIN CLR5' - 0"A405
8
A405
6
A4055A4057
HD
1' - 6"5' - 0 1/2"2' - 0"
33
33
2
12
2
1
1' - 6"
209208
211
IT
211
MECH/ELEC
209
TPD1
SD
WR1 G
3' - 0 1/4"8' - 9 3/4"9' - 4 1/2"18' - 4"1' - 10 1/4"7' - 4"5' - 4"31' - 6"
FD
B C
1
A402 10
9SHOWER
227
8
7
RH 1' - 5"2' - 7"A406
9
10
PANTRY
219
1A
1A
1
1
2
7
1
2
227
219
TPD2
WR2
SD
4' - 0"3' - 0 1/4"0
6' - 10 1/2"7' - 6"6' - 9"3' - 0 1/4"4' - 0"3' - 6"A731
4
C D
4
6
7
A402
6
5
DECON
112
MEDICAL
STORAGE
114
READY
ROOM
113
A406 4
2
1
3
A406
6
EMERGENCY SHOWER AND
EYEWASH, RE: PLUMB
MOP SINK, RE: PLUMB
DECON SINK,
RE: PLUMB
UC REF (1)
A406
5
A406 7
A4068
2
2
2
2C
2B
9
113
114
5' - 6"4' - 0"
112
2A
14
9
9
1' - 9"1' - 9"
WIRE SHELVING
BY OTHERS (PART
OF FURNITURE
PACKAGE)
CLR
1' - 6"5' - 0"DOUBLE SLINGER WORK STATION WITH
NO UPPER UNIT, ONLY WORKSURFACE
WITH STORAGE BELOW.
(3) 24" x 24"
DEEP WALL
MOUNT OPEN
LOCKERS
(4) 24" X 36"
DEEP WALL
MOUNT OPEN
LOCKERS W/
TOPSIDE
STORAGE
SHELF
(6) 24" X 36" DEEP WALL
MOUNT OPEN LOCKERS W/
TOPSIDE STORAGE SHELF
(3) 6' X 2' SLINGER WALL
MOUNT TOOL GRID
PANEL W/ SLINGER
TOPSIDE STORAGE
SHELF ABOVE
6' - 3"5' - 0"OXYGEN TANK STORAGE (TANKS
RESTING ON FLOOR W/ (2) 24" x 24"
DEEP WALL MOUNTOPEN LOCKERS
WITH TOPSIDE STORAGE SHELF AND
DOORS. NO BOTTOM, OPEN.)
MINI MOBILE
STORAGE FOR 02
CYLINDER SYSTEMCLR1' - 0"2C
SLOPE SLOPE
CTR WALL FRM'G
ON COLUMN GRID
DRINKING FOUNTAIN W/
BOTTLE FILL, RE PLUMB
B
3
SHOWER
225
4' - 0"3' - 5 1/2"
225
1
2
1A
1A
1
1A1A
1
A402 13
14
15
RH
WR2
TPD23' - 0 1/4"1' - 6"DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt 3/4/2019 1:28:33 PM
A301
JANUARY 22,
2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
ENLARGED FLOOR
PLANS
PROJECT STATUS: 100% CD
SH JW
ASPEN
AMBULANCE
DISTRICT FACILITY
0'2'4'0'2'4'A301
ENLARGED PLAN - LOBBY / RESTROOMS1
0'2'4'0'2'4'A301
ENLARGED PLAN - UPPER TOILET3
0'2'4'0'2'4'A301
ENLARGED PLAN - TYPICAL SHOWER4
0'2'4'0'2'4'A301
ENLARGED PLAN - READY ROOM2
NOTE: SLOPE 1/8" PER FOOT TO FDNOTE: SLOPE 1/8" PER FOOT TO FD
0'2'4'0'2'4'A301
SHOWER 225 - ENLARGED PLAN5
NO: ISSUED FOR: DATE:
15 ASI#06 3/4/19
MAIN FLOOR100' - 0"
UPPER LEVEL
116' - 0"
5 3
STL ANGLE
FRAME, PNT P6
STL HANDRAIL,
PNT P6
WD SLATS
STL PLATE,
PNT P6
11" EA
13 TREADS @
5
A651
________________________________________
A612
7
A652
5
A731
3
108' - 0"
LANDING 1
109' - 1 3/4"
LANDING 2@ 7" MAX EA12 RISERS2 RISERS @ 7" MAX EA@ 7" MAX EA14 RISERSSTRINGER RECESSED
IN WALL
EQ
EQ
EQ
10
G.9 I J
5
3
STAIR
302
ELEVATOR
301
2
A651
________________________________________
8' - 11 3/4"
2A
2A
2A
2A
5
7
7
3
A651
________________________________________
FD
ELEVATOR POWER
UNIT, RE: ELEC
2A
UP 1' - 0"4' - 2 1/4"11"4' - 2 1/4"
3A
4' - 2 1/4"3.5
15
15
15
15
15
I J
4
5
3
2
A651
________________________________________
DN
A612
9
STAIR
302
A651
6
A612
8
7
7
2
2A
2A
4' - 2 1/4"11"4' - 2 1/4"4' - 2 1/4"3.5
MAIN FLOOR100' - 0"
UPPER LEVEL
116' - 0"
3
ADHERED SHEET
WATERPROOFING (RE: SPECS)
@ PERIMETER OF CONC PIT,
LAP OVER FOUNDATION
CONC JOINT W/ CONT HYDROSTOP,
RE: SPECS
MTL STUD HEADER, RE: STR
FIRE CAULK GWB TO MTL DECK (TYP)
GWB ON 1-5/8" MTL STUDS
W/ BATT INSULATION
SAG CLG, RE: RCP
22
13
2
SUSPENDED GWB
CLG, RE: RCP
SUMP PUMP BEYOND
FLOOR DRAIN
SLOPE CONC TO DRAIN, 1/8":12"
FIRE PROOF ROOF DECK TO
1-HR ABV ELEVATOR SHAFT
CLR12' - 8"MIN2" CLRSLOPE 1/4" : 12"A641
4 3.5
HORIZONTAL STL 2" X 2" X
1/4" ANGLE, PNT P6
STL POST 2" X 2" X 1/4"
ANGLE BEYOND, FULL-WELD
ON STL PLATE, PNT P6
3
STL STRINGER RECESSED
IN WALL
POLISHED CONC STAIR TREAD
WD 1 1/2" X 1 3/4" SLATS FASTENED
@ LANDING SIDE W/ COUNTERSUNK
SCREWS THROUGH STL ANGLE
(TYP of 12)
STL HANDRAIL, PNT P6
1/2" STL PLATE, PNT P6
J-TRIM EDGE, EA SIDE
STL & CONC STAIR PAN
CONT 2X WD BLK'G
3 5/8" MTL FRM'G @ 16" O.C.
5/8" GWB
PNT P6
NUT W/ LOCK WASHER (TYP)
3/8" DIA ALL THREAD @ 24" O.C.
WELDED TO STL PLT (TYP)1"TYP1"3
1/4"1/4"1/4"1/4"
2"x2"x1/4" STL
POST, PNT P6
VERTICAL 2"x2"x1/4"
STL ANGLE, PNT P6
WD 1 1/2" X 1 3/4" SLATS
FASTENED @ LANDING SIDE
W/ COUNTERSUNK SCREWS
THROUGH STL ANGLE
STL PLATE BELOW, PNT P6 EQEQEQ EQ
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt 3/4/2019 1:34:33 PM
A651
JANUARY 22,
2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
STAIR 302 &
ELEVATOR PLANS
& SECTIONS
PROJECT STATUS: 100% CD
SH, PH JW
ASPEN
AMBULANCE
DISTRICT FACILITY
0'2'4'0'2'4'
A651
STAIR 302 SECTION @ STEPS2
0'2'4'0'2'4'
A651
ENLARGED PLAN - STAIR 302/ELEVATOR MAIN FLOOR1
0'2'4'0'2'4'A651
ENLARGED PLAN - STAIR 302 UPPER LEVEL4
0'1'2'0'1'2'
A651
ELEVATOR SECTION3
0'6"1'0'6"1'A651
STAIR RAIL DETAIL5
0'3"6"0'3"6"A651
STAIR RAIL DETAIL @ POST6
NO: ISSUED FOR: DATE:
10 RFI#043 10/18/18
15 ASI#06 3/4/19
10