HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (33).ACBK ARCHITECT: Chamberlin Architects, P.C. BY: Jonathan West S:\1740 - Pitkin County Ambulance Facility\6. CONSTRUCTION\PROPOSAL REQUESTS\PR#021.1740.doc PROPOSAL REQUEST FIELD OWNER ARCHITECT CONTRACTOR PROJECT: Aspen Ambulance District Facility OWNER: Pitkin County 123 Emma Road, Suite #106 Basalt, CO 81621 TO: FCI Constructors, Inc. 3070 I-70 Business Loop Building A Grand Junction, CO 81504 PROPOSAL REQUEST NO: Twenty-one (21) DATE: March 11, 2019 ARCHITECT'S PROJECT NO: 1740 CONTRACT DATED: May 9, 2018 Please submit an itemized quotation for changes in the Contract Sum and/or Time incident to proposed modifications to the Contract Documents described herein. THIS IS NOT A CHANGE ORDER NOR A DIRECTION TO PROCEED WITH THE WORK DESCRIBED HEREIN. Drawings Sheet A101, Ground Level Floor Plan: 1. Relocate condenser units 1, 2 & 3 and the generator as illustrated in the attached revised Sheet. 2. Add (3) HSS8x8x1/4 columns at grid line 7 as illustrated in the attached Sheet. Sheet A102, Upper Level Floor Plan: 1. Add pre-finished standing seam metal roof w/ gutter & downspout between grids 6 & 7 and F & H as illustrated in the attached Sheet. Sheet A121, Ground Level RCP: 1. Add roof structure between grids 6 & 7 and F & H as illustrated in the attached Sheet. Sheet A141, Roof Plan: 1. Add roof below between grids 6 & 7 and F & H as illustrated in the attached Sheet. Sheet A201, South Elevation: 1. Add roof structure between grids F & H as illustrated in the attached Sheet. 2. Add PV array on the high roof between grids B & F as illustrated in the attached Sheet. Sheet A202, East Elevation: 1. Add roof structure between grids 6 & 7 as illustrated in the attached Sheet. Sheet A513, Section 2: 1. Add roof structure between grids 6 & 7 as illustrated in the attached Sheet. Sheet S102, Foundation Plan: 1. Add (3) HSS8x8x1/4 columns at grid line 7 as illustrated in the attached Sheet. ARCHITECT: Chamberlin Architects, P.C. BY: Jonathan West S:\1740 - Pitkin County Ambulance Facility\6. CONSTRUCTION\PROPOSAL REQUESTS\PR#021.1740.doc Sheet S103, Upper Level Framing Plan: 1. Add (1) HSS12x8x1/4 beam at grid line 7 as illustrated in the attached Sheet. 2. Add (6) sloped HSS6x3x1/4 beams between grids 6 & 7 and F & H as illustrated in the attached Sheet. Sheet S204, Typical Base Plate Details: 1. Add base plate Type J as illustrated in the attached Sheet. Sheet S301, Framing Sections: 1. Modify section 1 as illustrated in the attached Sheet. Sheet S303, Framing Sections: 1. Add sections 6, 7, 8 & 9 as illustrated in the attached Sheet. Sheet M101, Ground Level Mechanical Plan: 1. Relocate condenser units 1, 2 & 3 and associated underground refrigerant piping as illustrated in the attached revised Sheet. Sheet P101, Ground Level Plumbing Plan: 1. Revise underground natural gas piping to generator as illustrated in the attached revised Sheet. Sheet E201, Ground Level Power & Systems Plan: 1. Relocate condenser units 1, 2 & 3 and the generator as illustrated in the attached revised Sheet. Attachments: A101; A102; A121; A141; A201; A202; A513; S102; S103; S204; S301; S303; M101; P101; E201 A2021 A201 A202 A201 1 2 2 A B C D E G.9 I J 1 2 4 5 6 7 LOBBY 101 WOMEN 102 MEN 103 TRAINING ROOM 104 ELEC. 105 APPARATUS BAY #1 106 APPARATUS BAY #2 107APPARATUS BAY #3 108 APPARATUS BAY #4 109 APPARATUS BAY #5 110 APPARATUS BAY #6 111 DECON 112 READY ROOM 113 MEDICAL STORAGE 114 FITNESS 115 STAIR 302 ELEVATOR 301 STAIR 303 303A 303C 112 114 115A115B 101B 113 102 103 3 105 MAIN WATER SERVICE & FIRE SPRINKLER RISER AREA A301 1 A651 1 A652 1 A403 1 A403 3 4 A301 2 A405 2 3 4 1 A407 2 4 1 3 3 A513 ________________________________________ 1 A513 ________________________________________ STORAGE 116 116 2C 2 5 7 7 5 11 5 F 11 4A 4A 4A 2B 2A 2 CU (TYP of 3), RE: MECH 109110111 108 107 106 9 5 104B 10 11 9A A404 2 A404 1 2B 5 9 A612 3 1B 0 10' - 0"6' - 9"4' - 3 1/4"11' - 10"22' - 5"3' - 6"1' - 0"59' - 9 1/4"128' - 0"9 3/4"9' - 2 1/2"50' - 7"9 1/4"2' - 0"3' - 4"15' - 4"68' - 0"24' - 8"3' - 8 3/4"11' - 9"1' - 0" 3' - 4"14' - 0"4' - 0"14' - 0"4' - 0"14' - 0"4' - 0"14' - 0"4' - 0"10' - 0"4' - 0"10' - 0"14' - 0"4' - 1 3/4"3' - 4"7' - 2"9 3/4"9 3/4"9' - 2 1/2"2' - 8"3' - 4"6 3/4"1' - 0"9' - 4"21' - 1 1/2"13' - 4"G 2 A511 ________________________________________ 2 A513 ________________________________________2 A512 ________________________________________ ALIGN CENTER ON GRID LINE 3 A511 ________________________________________ 1 A512 ________________________________________ 9 5/8"18' - 6 3/8"18' - 0"18' - 0"18' - 0"14' - 0"14' - 0"10' - 11 3/8"6' - 4 5/8"10' - 1 5/8" 8' - 6 1/4"18' - 0"18' - 0"18' - 0"16' - 0"14' - 0"6' - 8 1/4" 3' - 4"22' - 8"3' - 4"5' - 4"20' - 8"10' - 0"1' - 4"3' - 4"8"28' - 0"3 3/4"10' - 0 3/4"12' - 0"8' - 0 3/4"9' - 9"22' - 10 3/4"5' - 10 1/2"CONC RAMP W/ STL TUBE HANDRAILS, RE: CIVIL UP UP 106A 101A A03A03A04 A01 A02 B01 B02 GENERATOR, RE: ELEC ALIGN28' - 8"9' - 4"UP A652 2 2D 2C2D GAS METER LOCATION, RE: MECH DOOR SHOWN FOR REFERENCE, LOCATED @ LANDING ABV 4' LONG CONC WHEEL STOPS DOWELED INTO CONC SLAB, COORDINATE FINAL LOCATION W/ OWNER'S VEHICLES (TYP OF 4) 1 A511 ________________________________________ 104A 129' - 7 1/4" ALIGN MASONRY & CONC 2A 2A 2A 2A 4' - 2 1/4" 5' - 0"6' - 6 3/8" 1' - 0" 1 ASK-01 ________________________________________ 44 6' - 1 5/8" 3.5 17' - 4"20' - 0"35' - 1"3' - 2"19' - 11"15 15 15 15 15 ASK-09 2 ASK-091 6' - 0"3' - 0"3' - 0"3' - 0"5' - 0" HHS COL, RE: STRUCT, PNT 17 1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE ARCHITECT PRIOR TO CONTINUING CONSTRUCTION. 2. ITEMS NOT NOTED ON THE DRAWINGS SHALL BE CONSIDERED THE SAME AS NOTED ITEMS WHICH ARE GRAPHICALLY REPRESENTED IN THE SAME MANNER. 3. PROVIDE TREATED SOLID WOOD BLOCKING FOR ALL WALL EQUIPMENT, TOILET ACCESSORIES, MILLWORK AND OTHER WALL MOUNTED ITEMS. SEE ELEVATIONS AND EQUIPMENT SPECIFICATIONS FOR ADDITIONAL INFORMATION. 4. CONTRACTOR SHALL CAULK AT THE INTERFACE OF INTERIOR FACES OF DOOR FRAMES WITH ADJACENT MATERIALS THOUGH JOINT MAY NOT BE VISIBLE. 5. PROVIDE TRANSITION STRIPS BETWEEN FLOOR MATERIALS OF DISSIMILAR HEIGHTS. CENTER TRANSITION STRIPS UNDER DOORS OR OTHER PLACES OUT OF SIGHT. 6. PROVIDE POSITIVE SLOPE ON ALL FLOOR DRAINS, MINIMUM OF1/8” PER FOOT. SLOPE FLOOR ALL AROUND FROM ADJACENT WALLS TO FLOOR DRAINS, DO NOT DEPRESS ONLY THE AREA IMMEDIATELY AROUND THE DRAIN. 7. REFER TO THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR THE LOCATIONS OF PIPING, VENTS, DUCTS, CURBS, FANS AND OTHER ITEMS WHICH PENETRATE THE ROOF PLANE. 8. DOOR JAMB LOCATION OFF FACE OF WALL IS 4", TYPICAL, UNLESS NOTED OTHERWISE. DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:04:01 AMA101 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO GROUND LEVEL FLOOR PLAN PROJECT STATUS: 100% CD SH JW ASPEN AMBULANCE DISTRICT FACILITY 0'4'8'0'4'8' A101 GROUND LEVEL FLOOR PLAN1 GENERAL NEW CONSTRUCTION NOTES NO: ISSUED FOR: DATE: 4 RFI-009 08/10/18 15 ASI#06 3/4/19 17 PR#021 3/11/19 4 ..1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE ARCHITECT PRIOR TO CONTINUING CONSTRUCTION. 2. ITEMS NOT NOTED ON THE DRAWINGS SHALL BE CONSIDERED THE SAME AS NOTED ITEMS WHICH ARE GRAPHICALLY REPRESENTED IN THE SAME MANNER. 3. PROVIDE TREATED SOLID WOOD BLOCKING FOR ALL WALL EQUIPMENT, TOILET ACCESSORIES, MILLWORK AND OTHER WALL MOUNTED ITEMS. SEE ELEVATIONS AND EQUIPMENT SPECIFICATIONS FOR ADDITIONAL INFORMATION. 4. CONTRACTOR SHALL CAULK AT THE INTERFACE OF INTERIOR FACES OF DOOR FRAMES WITH ADJACENT MATERIALS THOUGH JOINT MAY NOT BE VISIBLE. 5. PROVIDE TRANSITION STRIPS BETWEEN FLOOR MATERIALS OF DISSIMILAR HEIGHTS. CENTER TRANSITION STRIPS UNDER DOORS OR OTHER PLACES OUT OF SIGHT. 6. PROVIDE POSITIVE SLOPE ON ALL FLOOR DRAINS, MINIMUM OF1/8” PER FOOT. SLOPE FLOOR ALL AROUND FROM ADJACENT WALLS TO FLOOR DRAINS, DO NOT DEPRESS ONLY THE AREA IMMEDIATELY AROUND THE DRAIN. 7. REFER TO THE MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR THE LOCATIONS OF PIPING, VENTS, DUCTS, CURBS, FANS AND OTHER ITEMS WHICH PENETRATE THE ROOF PLANE. 8. DOOR JAMB LOCATION OFF FACE OF WALL IS 4", TYPICAL, UNLESS NOTED OTHERWISE. A2021 A201 A202 A201 1 2 2 A B C D E G.9 I J 1 2 4 5 6 7 WAITING 201 OFFICE 203 OFFICE 204OFFICE 205 FLEX 206 MECH/ELEC 209 CORRIDOR 210 STOR. 213 OFFICE 212 CONFERENCE 214 LIBRARY / REPORTS 215 CORRIDOR 220 UNIFORM LOCKERS 221 LAUNDRY 222 CORRIDOR 224 SHOWER 225 SHOWER 226 SHOWER 227 BUNK RM 229 BUNK RM 230 BUNK RM 231 BUNK RM 232 STORAGE 228 206 205 204 203 214 212 219 221 220 225 226 227 228 229 230 231 232 303D OPEN TO BELOW CANOPY OUTLINE 3 TOILET 208 IT 211 DINING 217 DAYROOM 216 KITCHEN 218 209208 211 MECH 223 213 A301 3 A301 4 A407 9 10 8 11 A302 1 3 A513 ________________________________________ 1 A513 ________________________________________ F 223 222 PANTRY 219 2A 2A 7 6 6 6 6 7 6 6 7 1 1 1A 1A 11 2A 2A 2A 1 12 3A 2 1 2 11 2 1 11 1 1A1A 1A1A 22 1 B03 B06 B07 B08 B16 B17B18B18B19 B20B21 A4077 6 5 2 A302 7 216 201 4 2A 2A A202 4 6 7 A651 4 A652 3 STAIR 303 STAIR 302 ELEVATOR 301 0 1' - 0"8' - 9"3' - 0"60' - 3 1/4"1' - 0"7' - 4"1' - 0"2' - 2"4' - 5 1/2"2' - 2"1' - 0"9' - 1"9 3/4"2' - 2"5' - 9 3/4"2' - 2"1' - 0"15' - 7"2 3/4"9 3/4"9' - 0"12' - 8 3/4"3' - 0"19' - 0"16' - 0 1/2"11 1/2"1' - 4"13' - 4 3/4"1' - 0"2' - 2"8' - 6"2' - 2"6' - 6"4' - 4"1' - 4"15' - 9 1/4"1' - 0" 14 1' - 0"29' - 4 1/4"3' - 6"4' - 5"34' - 2 3/4" G 5 3 ALIGNALIGN8' - 1 3/4"9' - 9 1/2"9' - 9 1/2" 1 2 A511 ________________________________________ 2 A513 ________________________________________ CTR WALL ON GRID LINE CTR WALL ON GRID LINE CTR WALL ON GRID LINE CTR WALL ON GRID LINE 2 A512 ________________________________________ 3 A511 ________________________________________ A732 3 1 A512 ________________________________________ 18' - 6 1/4"18' - 0"18' - 0"18' - 0"14' - 0"14' - 0"10' - 11 1/2"6' - 4 3/4"10' - 1 1/2" 128' - 0"10' - 0"6' - 9"4' - 3 1/4"11' - 10"22' - 5"4' - 6"59' - 9 1/4"33' - 7 1/2"10' - 5"1' - 9"3' - 0"1' - 6"9' - 6"9 3/4"8' - 0 1/4"6' - 10 1/4"5' - 10 1/2"5' - 10 1/4"8' - 1 1/4"4' - 9 1/2"10' - 1"9' - 5"9' - 5"9' - 0"2' - 11 1/2"4' - 5 3/4"11' - 11 1/2"4' - 6 1/4"13' - 11 3/4"4' - 6"13' - 8 1/2"CTR WALLS ON GRID LINES CTR WALL ON GRID LINE CTR WALL ON GRID LINE A732 2 A732 6 A733 1 DN A05 7A 7A A406 11 DECK 233 B07 B07 B07 B09 B23 B22 A301 5 B10 B11 B12 B13 B14 B23 B23 GWB SOFFIT OVER ENTRY BELOW A732 4 1 A644 ________________________________________ 2 A644 ________________________________________ 4 A644 ________________________________________ 3/4"x36" FIXED & SLIDING DOOR GLASS PANELS10' - 11"10' - 11"10' - 6 1/2"A733 1 OPP SLOPE TYP 1 A511 ________________________________________ 6A 215 A703 17 ROOF DRAINS BELOW, TYP OF 6. SLOPE 1/4":12" TOWARDS DRAINS 24"x24" CONC PAVERS ON ADJUSTABLE PEDESTALS ON SINGLE PLY ROOF MEMBRAN ON 1/2" COVER BOARD ON HIGH DENSITY RIGID INSULATION RD RD RDRD RD RD 3.5 17 9 A653 ________________________________________ SIM PRE-FINISHED STANDING SEAM MTL ROOF SST PIPE SNOW GUARD PRE-FINISHED MTL GUTTER W/ DOWNSPOUT DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:29:51 AMA102 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO UPPER LEVEL FLOOR PLAN PROJECT STATUS: 100% CD SH PH ASPEN AMBULANCE DISTRICT FACILITY GENERAL NEW CONSTRUCTION NOTES 0'4'8'0'4'8' A102 UPPER LEVEL FLOOR PLAN1 NO: ISSUED FOR: DATE: 17 PR#021 3/11/19 SS PS SS SS SGYP BD, PAINT LEGEND RECESSED DOWNLIGHT, RE: ELEC PENDANT DOWNLIGHT, RE: ELEC 2X2 SUSPENDED ACOUSTIC GRID. BALANCE TILE AND GRID AT EDGES IN ROOMS, UNO. 2'X2' RECESSED LIGHT, RE: ELEC SUSPENDED LOBBY PENDANT, RE: ELEC HIGH BAY LIGHT, RE: ELEC PENDANT DIRECTIONAL DOWNLIGHT, RE: ELEC PENDANT, RE: ELEC LINEAR LED PENDANT FIXTURE, RE: ELEC EXIT SIGN, INDICATING DIRECTIONAL ARROW & SIGN ORIENTATION, RE: ELEC SUPPLY AIR GRILLE, RE: MECH EXHAUST FAN, RE: MECH NOTE: CENTER LIGHT FIXTURES IN SPACE AS SHOWN ON REFLECTED CEILING PLANS WHEN LIGHT FIXTURES ARE NOT DIMENSIONED. (TYP) CEILING MOUNTED PROJECTOR RETURN AIR GRILLE, RE: MECH READING LIGHT WALL SCONCE, RE: ELEC UNDERCABINET LIGHT RE: ELEC S CEILING MOUNTED SPEAKER OCCUPANCY SENSOR, RE: ELECSMOKE DETECTOR, RE ELEC 1' X 4' SUSPENDED FIXTURE, RE: ELEC 2' X 4' RECESSED OR SUSPENDED FIXTURE, RE: ELEC RECTANGULAR WALL SCONCE, RE: ELEC WALL SCONCE (SINGLE), RE: ELEC WALL SCONCE (DOUBLE), RE: ELEC P 1'X4' RECESSED LIGHT, RE: ELEC NL WALL MOUNTED NIGHT LIGHT, RE: ELEC WD EXTERIOR SOFFIT ART LIGHT, RE: ELEC P PHOTO CELL, RE: ELEC 3" X 6' FIXTURE, RE: ELEC A B C D E G.9 I J 1 2 4 5 6 7 3 OTS OTSOTS READY ROOM 113 FITNESS 115 TRAINING ROOM 104 STORAGE 116 ELEC. 105 ELEVATOR 301 STAIR 302 LOBBY 101 MEN 103 WOMEN 102 APPARATUS BAY #1 106 APPARATUS BAY #2 107 APPARATUS BAY #3 108 APPARATUS BAY #4 109 APPARATUS BAY #5 110 APPARATUS BAY #6 111 DECON 112 MEDICAL STORAGE 114 STAIR 303 OTS OTA WALL MOUNTED LIGHT ACTIVATED WHEN DOOR OPENS 9' - 0" 9' - 0" 9' - 0" F OTS 13' - 0"EQEQ11' - 0" 7' - 0 1/2" 9 A611 ________________________________________ 10 A611 ________________________________________ 5 A611 ________________________________________ EQ 8' - 0"8' - 0"EQ 0 EQEQEQ 4' - 0"EQ EQ EQ EQ4' - 0"EQG 5' - 0"10' - 0"10' - 0"5' - 0" SPEAKER, RE: ELEC 2' - 0"6' - 0"6' - 0"2' - 0"EQEQOTS EQ10' - 0"EQEQ 7' - 0"7' - 0" EQ EQEQEQ8' - 0" EQ 8' - 0"EQ EQEQEQ EQ EQEQEQ EQ EQ10' - 0"EQEQEQEQ EQ EQ 4' - 8"EQ 4' - 8"15' - 0"15' - 0"ART LIGHT, RE: ELEC OTS EQ EQ (TYP) ALIGN 9' - 0" TYP 11' - 7 1/2" PRE FINISHED MTL SOFFIT FLASHING PERIMETER WD 1x6 PLANK SOFFIT1 A642 ________________________________________ 3.5 1 ASK-05 ________________________________________ HHS BEAM, RE: STRUCT (TYP, PNT) ROOF DECK, RE: STRUCT (PNT)17 DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:13:38 AMA121 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO GROUND REFLECTED CEILING PLANS PROJECT STATUS: 100% CD SH JW ASPEN AMBULANCE DISTRICT FACILITY 0'4'8'0'4'8' A121 GROUND LEVEL RCP1 NO: ISSUED FOR: DATE: 17 PR#021 3/11/19 ..A B C D E G.9 I J 1 2 4 5 6 7 3SLOPE 1 1/2 :12SINGLE PLY ROOF MEMBRANE ON PROTECTION BOARD ON RIGID INSULATION F PRE FINISHED MTL GUTTER & DOWNSPOUTS2 A641 ________________________________________ CANOPY BELOW, RE: 0 G DECK BELOW CRICKET AT ELEVATOR ROOF SLOPE 1/4 :12VTR, RE: PLUMB VTR, RE: PLUMB 2 A641 ________________________________________ ANTENNA MOUNT PRE-FINISHED METAL GRAVEL STOP WITH CONTINUOUS GALV CLEATPRE-FINISHED METAL GRAVEL STOP WITH CONTINUOUS GALV CLEAT GUTTER HIGH POINT SST PIPE SNOW GUARDS /2 A141 1 A641 ________________________________________ 3 A641 ________________________________________ 3 A641 ________________________________________ OPP 4 A641 ________________________________________ 3.5 9 DOWNSPOUT 9 DOWNSPOUT GUTTER TRANSITION9 PV ARRAY 27' - 0"6' - 0"4' - 0"63' - 0" 17 ROOF BELOW 1. MINIMUM INSULATION THICKNESS AT INTERNAL ROOF DRAINS SHALL BE 4 INCHES. 2. PROVIDE POSITIVE DRAINAGE AT ALL AREAS OF ROOF. PONDING OF WATER IS NOT ACCEPTABLE. 3. SEE REFLECTED CEILING PLANS FOR ADDITIONAL DIMENSIONS. 4. SLOPE ALL GUTTERS TO DOWNSPOUTS MINIMUM 1/16 INCH PER FOOT. 5. ALL EQUIPMENT CRICKETS SHALL BE SLOPED 1/4 INCH PER FOOT. G.9 I J 1 2 0 SLOPE 1/4" / 12" 1 A642 ________________________________________ PRE-FINISHED MTL ROOF EDGE FLASHING PRE-FINISHED MTL SCUPPER 1 ASK-03 ________________________________________6"DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:32:19 AMA141 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO ROOF PLAN PROJECT STATUS: 100% CD JW, SH JW ASPEN AMBULANCE DISTRICT FACILITY 0'4'8'0'4'8' A141 ROOF PLAN1 GENERAL ROOF NOTES NO: ISSUED FOR: DATE: 9 RFI#018 10/16/18 17 PR#021 3/11/19 0'2'4'0'2'4' A141 CANOPY ROOF PLAN - REVISED2 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" ABCDEG.9IJ F B06B07B08 B03 EGRESS EGRESS CMU BLOCK METAL; TYPE 2 LOUVERED VENTS; NON- DUCTED AREAS W/ GRILLS TO MATCH, RE: MECH CMU BLOCK ALUM STOREFRONT ENTRY GARAGE DOORS, RE: SCHED. METAL; TYPE 1 METAL; TYPE 1 LOUVERED VENTS FDC INTAKE HOOD, CENTER ON BLOCK (TYP OF 3) RE, MECH KITCHEN HOOD EXHAUST ALUM BREAK MTL COLUMN WRAP CONC FILLED STL PIPE BOLLARD, TYP OF 12 (PNT), 36" H x 6" DIA SET IN 12" DIA CONC @ 36" DEEP PRE FINISHED MTL ROOF EDGE FLASHING EXISTING GRADE FINISHED GRADE, RE: CIVIL 33' HEIGHT LIMIT CJ IN CMU CJ IN CMUCJ IN CMU G PRE FINISHED MTL & WD CANOPY CJ IN CMU PRE FINISHED MTL DRIP EDGE SILL FLASHING PRE FINISHED MTL DRIP EDGE SILL FLASHING ALUM STOREFRONT WINDOW LIGHT FIXTURE, RE: ELEC WATER HEATER EXHAUSTS, RE: MECH B07B07B07 B01 B09 10' - 0" MIN SEPARATION ELECTRICAL OUTLET, RE: ELEC (TYP)HOSE BIB, RE: PLUMB 10' - 0"VENT HOOD, CENTER ON BLOCK (TYP OF 3) RE, MECH 131' - 10" T.O. ROOF 113' - 4 1/2" T.O. CANOPY 1' - 9 3/4"EQEQ B04 1 5 1616 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" A B C D E G.9 I JF B17B18B18B19B20B21 METAL; TYPE 1 ALUM STOREFRONT WINDOW METAL; TYPE 2 CMU BLOCK METAL; TYPE 1 STL GUARDRAIL, SPACE VERTICALS @ 48" O.C. & CENTER ON CMU JOINTS CMU BLOCK WINDOWS BEYOND ROOF MEMBRANE CONC SIDEWALK RAMP FINISH GRADE, RE: CIVIL EXISTING GRADE 33' HEIGHT LIMIT CONCRETE SIDEWALK; RE: CIVIL STL RAMP HANDRAIL RE: LAND CJ IN CMU G ELEVATOR OVERRUN PRE FINISHED MTL DRIP EDGE SILL FLASHING RAMP LIGHTS RE: ELEC TYP3' - 6"CONC RETAINING WALL, RE: STR. SLOPE TOP (@ 42" ABV) W/ CIVIL RAMP GRADE B22 B14 B15 HOSE BIB, RE: PLUMB, CTR ON LIGHT FIXTURE ELECTRICAL OUTLET, RE: ELEC (TYP) PRE FINISHED MTL GUTTER & DOWNSPOUTS 109' - 6 3/4" DOOR SILL DISCHARGE DOWNSPOUT ONTO SPLASH BLOCK ROOF MOUNTED ANTENNA 131' - 10" T.O. ROOF 126' - 3" T.O. ROOF 125' - 5" T.O. ROOF 1 1 17 PV ARRAY DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:17:53 AMA201 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO EXTERIOR ELEVATIONS PROJECT STATUS: 100% CD SH, KH JW ASPEN AMBULANCE DISTRICT FACILITY 0'4'8'0'4'8' A201 NORTH ELEVATION1 0'4'8'0'4'8' A201 SOUTH ELEVATION2 NO: ISSUED FOR: DATE: 1 Addendum #2 05-25-2018 5 RFI-005 8-13-18 16 PR#020 3/5/19 17 PR#021 3/11/19 UPPER LEVEL 116' - 0" 1245673 MAIN FLOOR FINISH 100' - 0 1/4" METAL, TYPE 1 CMU BLOCK ALUM STOREFRONT WINDOW METAL, TYPE 2 STL TUBE GUARD RAIL METAL, TYPE 1 33' HEIGHT LIMIT ALUM BREAK MTL COLUMN WRAP PRE FINISHED MTL & WD CANOPY ALUM STOREFRONT ALUMINUM BREAK MTL COLUMN WRAP EXISTING GRADE, RE: CIVIL FINISHED GRADE RE: CIVIL 0 MECHANICAL UNITS & GENERATOR, RE: MECH & ELEC FURNACE EXHAUSTS, RE: MECH ALUM STOREFRONT WINDOWS PRE FINISHED MTL SILL DRIP EDGE FLASHING LIGHT FIXTURE, RE: ELEC CMU CONTROL JOINT ELEVATOR BEYOND ADA DOOR OPERATOR ELECTRICAL OUTLET, RE: ELEC (TYP) PRE FINISHED MTL FOOR EDGE FLASHING 131' - 10" T.O. ROOF CONC FOUNDATION STEP, WEEPS & FLASHING ABV 125' - 5" T.O. ROOF 126' - 3" T.O. ROOF 113' - 4 1/2" T.O. CANOPY 1 3.5 PV ARRAY BEYOND 17 HSS COL, RE: STRUCT (PNT) HSS BEAM, RE: STRUCT (PNT) ROOF DECK, RE: STRUCT (PNT) PRE-FINISHED STANDING SEAM MTL ROOF MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" 1 2 4 5 6 73 EGRESSEGRESSEGRESS METAL; TYPE 1 STL TUBE GUARDRAIL (PNT) METAL; TYPE 2 CMU BLOCK FINISH GRADE, RE: CIVIL 33' HEIGHT LIMIT FROM EXISTING GRADE EXISTING GRADE, RE: CIVIL PRE FINISHED MTL ROOF EDGE FLASHING 0 CJ IN CMU ELEVATOR BEYOND ALUM STOREFRONT WINDOW PRE FINISHED MTL SILL DRIP EDGE FLASHING B23B23 131' - 10" T.O. ROOF 125' - 5" T.O. ROOF WEEPS & FLASHING B23 1 1 3.5 PV ARRAY UPPER LEVEL 116' - 0" 5 6 7 ELECTRICAL OUTLET, RE: ELEC (TYP) PRE-FINISHED METAL SILL FLASHING UPPER LEVEL 116' - 0" D B21 B20 UPPER LEVEL 116' - 0" 4567 ELECTRICAL OUTLET, RE: ELEC (TYP) DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:21:55 AMA202 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO EXTERIOR ELEVATIONS PROJECT STATUS: 100% CD KH JW ASPEN AMBULANCE DISTRICT FACILITY0'4'8'0'4'8' A202 EAST ELEVATION1 0'4'8'0'4'8' A202 WEST ELEVATION2 0'4'8'0'4'8' A202 EXTERIOR ELEVATION - COVERED PATIO - EAST3 0'4'8'0'4'8' A202 EXTERIOR ELEVATION - COVERED PATIO - NORTH4 0'4'8'0'4'8' A202 EXTERIOR ELEVATION - COVERED PATIO - WEST5 NO: ISSUED FOR: DATE: 1 Addendum #2 05-25-2018 5 RFI-005 8-13-18 17 PR#021 3/11/19 5 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" 1 0 A733 3 A641 1 CONC FILLED BOLLARD, PNT 7 11 PRE FINISHED MTL ROOF EDGE SINGLE PLY ROOF MEMBRANE ON 1/2" COVER BOARD ON RIGID INSULATION ALUM STOREFRONT WINDOW PRE FINISHED ALUM BRK MTL SOFFIT & DRIP EDGE FLASHING STL BEAM, RE: STR PRE FINISHED MTL SILL FLASHING LOUVER, RE: MECH SAG CLG, RE: RCP BUNK RM 229 APPARATUS BAY #6 111 7 STL BEAM, RE: STR A702 5 INSULATED SECTIONAL GARAGE DOOR PERIMETER DRAIN W/ FILTER FABRIC, RE: CIVIL RIGID PERIMETER INSULATION CONC FOUNDATION W/ DAMPPROOFING, RE: STR 131' - 10" T.O. ROOF 128' - 1" T.O. LOUVER 125' - 1 1/4" WINDOW HEAD 119' - 5 1/2" WINDOW SILL 112' - 0" DOOR HEAD A601 1 A601 7 SIM A731 2 1 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" A A601 7 A601 5 A601 9 SAG CLG, RE: RCP STL JOIST, RE: STR PRE FINISHED MTL FLASHING W/ CONT CLEAT WALL BASE, RE: FIN PLAN THRU WALL MASONRY WEEPS & GALV MTL FLASHING PERIMETER DRAIN W/ FILTER FABRIC, RE:CIVIL RIGID PERIMETER INSULATION CONC FOUNDATION WALL W/ DAMPPROOFING, RE: STR A601 1 GRADE, RE: CIVIL A601 4 SIM PRE FINISHED BRK MTL SOFFIT & DRIP EDGE FLASHING STL SHELF ANGLE, RE: STR PRE FINISHED MTL ROOF EDGE FLASHING SINGLE PLY ROOF MEMBRANE ON 1/2" COVER BOARD ON RIGID INSULATION 7 1-5/8" MTL STUDS @ 16" O.C. IN BEAM FLANGE 6 9A BUNK RM 231 APPARATUS BAY #6 111 A641 3 SLOPES T.O. ROOF 123' - 0" T.O. WALL RECESS 119' - 5 1/4" B.O. WALL RECESS 7 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" 67 A601 6 A601 9 A601 2 RIGID PERIMETER INSULATION THRU WALL MASONRY WEEPS & GALV MTL FLASHING CONC SOG (RE: STR) ON VAPOR BARRIER MTL STUD SLIP TRACK @ JOIST ATTACHMENT 1-5/8" MTL STUD W/ FRM'G @ 16" O.C. W/ BATT INSULATION IN BEAM FLANGE STL BEAM, RE: STR STL FLOOR JOIST, RE: STR GWB SOFFIT ON 3-5/8" MTL STUD FRM'G @ 16" O.C. SAG CLG, RE: RCP 5 6 7 SINGLE PLY ROOF MEMBRANE ON 1/2" COVER BOARD ON RIGID INSULATION SAG CLG, RE: RCP STL BEAM & JOISTS, RE: STR WALL BASE, RE: FIN PLAN FLOOR FINISH, RE: FIN PLAN RETAINING WALL, RE: STR. CHAMFER CORNERS 3/4" CONC RAMP, RE: CIVIL RAMP HANDRAIL RE: LAND. GRAVEL WITH AREA DRAIN, RE: CIVIL A641 2 PERIMETER DRAIN W/ FILTER FABRIC, RE: CIVIL CONC FOUNDATION W/ DAMPPROOFING, RE: STR PRE FINISHED BRK MTL SOFFIT & DRIP EDGE FLASHING PRE FINISHED MTL SILL FLASHING SST SNOW GUARDS PRE FINISHED MTL GUTTER CONFERENCE 214 TRAINING ROOM 104 A601 1 SIM 119' - 5 1/2" B.O. WALL RECESS 123' - 0" T.O. WALL RECESS 125' - 5" T.O. ROOF 1 PRE-FINISHED MTL GUTTER HSS BEAM, RE: STRUCT (PNT) HSS COL BEYOND, RE: STRUCT (PNT) HSS BEAM, RE: STRUCT (PNT) ROOF DECK, RE: STRUCT (PNT) PRE-FINISHED STANDING SEAM MTL ROOF PNL ON ROOFING UNDERLAYMENT ON CONT ICE & WATER SHIELD ON 1/2" PT PWD ON 1-1/2" RIGID INSULATION CU-2 12 1-1/2 SST SNOW GUARD PRE-FINISHED MTL DOWNSPOUT 1' - 9"7" A653 7 SIM 16 DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSA360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt3/11/2019 11:26:31 AMA513 March 11, 2019 1740 CASTLE CREEK ROAD ASPEN, COLORADO WALL SECTIONS PROJECT STATUS: 100% CD PH DG ASPEN AMBULANCE DISTRICT FACILITY 0'1'2'0'1'2' A513 WALL SECTION - NORTH 21 0'1'2'0'1'2' A513 WALL SECTION - WEST3 0'1'2'0'1'2' A513 WALL SECTION - SOUTH @ TRAINING 1042 NO: ISSUED FOR: DATE: 1 Addendum #2 05-25-2018 17 PR#021 3/11/19 11I.9I.9IIG.9G.9GGFFEEDDCCBA.1A.12.13445.95.9127' - 6"18' - 3 3/8" 18' - 0" 18' - 0" 18' - 0" 14' - 0" 14' - 0" 11' - 2 3/8" 6' - 1 5/8" 9' - 10 5/8"60' - 5 5/8"10' - 9 1/4" 37' - 9"1' - 0"8 3/8"59' - 9 1/4"10' - 3" 6' - 6" 4' - 3 1/4" 4' - 9 7/8" 7' - 0 1/4" 22' - 4 7/8" 3' - 6"1' - 0"8 3/8"128' - 10"15' - 9" 5' - 0 3/8" 15' - 6" 18' - 0" 18' - 0" 14' - 0" 14' - 0" 11' - 2 3/8" 6' - 1 5/8" 9' - 10 5/8" 1' - 1"2' - 3 3/8" 14' - 0" 2' - 0" 2' - 0" 14' - 0" 2' - 0" 2' - 0" 14' - 0"2' - 0" 2' - 0" 14' - 0" 2' - 0" 2' - 0" 10' - 0" 2' - 0" 2' - 0" 12' - 0"10"1' - 1"1' - 0"SLOPESLOPESLOPESLOPEAPPARATUS BAY6" CONCRETE SLABON GRADE5S300TYP.T.O. SLAB @ DRAINEL. 99'-10 1/4"SLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPESLOPE(TYP.)6' - 8 7/8"(TYP.)6 1/4"(TYP.)6' - 8 7/8"2' - 0" 10' - 0" 4' - 0" 10' - 0"2' - 0"4' - 8 7/8"6 1/4"4' - 8 7/8"4' - 8 7/8"6 1/4"4' - 8 7/8"(TYP.)6' - 8 7/8"(TYP.)2' - 9 7/8"(TYP.)3' - 9 1/8"(TYP.)6' - 8 7/8"(TYP.)4' - 8 7/8"(TYP.)2' - 9 7/8"(TYP.)4' - 8 7/8"(TYP.)3' - 6"4" CONCRETE SLABON GRADE3S3001S3002S3003S3004' - 10 3/4"7S3003.5G.8G.8B.1A.9CCBBBAABCC4S300TYP.HSS5X5X1/4(B)HSS6X6X1/4(D)HSS6X6X1/4(D)TOPSTEPT.O. WALLEL. 100'-0"T.O. WALLEL. 100'-2"6"8"1' - 0"TOPSTEP1' - 10 3/8"1' - 4 3/8"BOTTOMSTEPT.O. WALLEL. 116'-8"T.O. FOOTINGEL. 99'-2"2' - 2"T.O. WALLEL. 116'-8"1' - 0"8"6"TOPSTEPHSS6X6X3/8(C)HSS6X6X1/2(C)CTOPSTEPT.O. WALLEL. 109'-8"T.O. WALLEL. 115'-8 1/2"(TYP. U.N.O.)2' - 4"T.O. FOOTINGEL. 99'-2"1' - 6 3/8"14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0" 4' - 0" 14' - 0"2' - 0"D1HSS6X6X3/8(D)HSS6X6X1/2(C)HSS6X6X1/2(C)TOPSTEPT.O. RETAINING WALLEL. 114'-0"1' - 0"6"8"1' - 0"T.O. WALLEL. 109'-6"1' - 4 7/8"BOTTOMSTEPE8' - 4" 11' - 7 1/4"5' - 9"10' - 6 3/4"HSS6X6X1/4(C)TOPSTEPHSS5X5X1/4(B)HSS6X6X1/4(C)3' - 0"4' - 1 3/4"8' - 8 7/8"3"B1' - 4"(TYP.)1' - 4"T.O. WALLEL. 100'-8"4' - 4 3/8"40' - 2 1/4"6' - 9"9' - 2"HSS6X6X3/8(C)T.O. WALLEL. 100'-3"TOPSTEPT.O. FOOTINGEL. 97'-0" (TYP.)HSS6X6X1/2(C)HSS5X5X3/8(B)T.O. FOOTINGEL. 96'-0"HSS5X5X3/8(D)HSS5X5X5/16(E)HSS5X5X5/16(E)HSS5X5X5/16(D)T.O. WALLEL. 100'-0" (TYP.)T.O. FOOTINGEL. 97'-0" (TYP.)HSS6X6X1/2(D)CCCCCC(TYP.)1' - 4"(TYP. U.N.O.)2' - 4"HSS6X6X5/16(D)CDDDHSS6X6X1/2(C)DDDT.O. INT. FOOTINGEL. 99'-2"(TYP. U.N.O.)HSS6X6X3/8(C)HSS6X6X1/2(C)HSS6X6X3/8(C)20' - 8"67' - 2 3/4"24' - 8" 16' - 3 1/4"(TYP.)1' - 4"8 3/8" 7 5/8"6S3003 5/8"HSS6X6X3/8(C)8S300TYP.9S300HSS6X6X3/8(C)HSS6X6X5/16(C)HSS6X6X3/8(C)HSS6X6X3/8(C)HSS6X6X3/8(C)P-3T.O. PILASTEREL. 99'-4" (TYP.)P-1AP-1P-1P-1P-1P-1T.O. PILASTEREL. 99'-4" (TYP.)BB9' - 1 1/8"TRENCHDRAINRE: ARCH.(TYP.)P-4NOTE:SEE SHEET S105FOR RETAININGWALL DETAILS3' - 8 3/4"2' - 0 1/4"NOTE:DEPRESS SLABFOR MATSEE ARCH.CONTROLJOINT(TYP.)(TYP.)12'-0" MAX15' - 0" 18' - 0" 20' - 6 3/8"BHSS6X6X3/8(C)BDEPRESS STEMWALL ANDDROP TOP REINF.8" MAX. @ DOOR OPENINGS(TYP.)D14' - 4 3/8" 10' - 7 5/8"6"6"CONCRETE TIE BEAM1'-0" WIDE x 1'-0" DEEP(T.O. TIE BEAM = 99'-4")HSS10X3X5/16(F)HSS10X3X5/16(F)HSS5X5X3/8(C)5 1/2" 2 1/8"2 1/8" 5 1/2"S100ATYP.6 3/8"P-51' - 1"P-6AP-6P-6P-6P-7P-5F.D.SEE MECH.18"ØSUMP PITAAHHJJ510"3"66004.9210S30077F.1P-810"3"3"P-93"4"2' - 0 1/8"11S300P-2P-218' - 8"1' - 4"1S2012S2011' - 0"T.O. WALLEL. 115'-6"TOPSTEPFT.O. FOOTINGEL. 99'-4"STAIR LANDINGCOLUMNSRE: STEEL SHOPDRAWINGS4"1' - 6 1/2"8' - 10" 2' - 3 1/8"1' - 3 7/8"HSS8X8X1/4(J)HSS8X8X1/4(J)HSS8X8X1/4(J)DRAWN BY:CHECKED BY:SHEET NO:PROJECT NO:DATE:CHAMBERLIN ARCHITECTS437 Main St.Grand Junction, Colorado 81501T 970.242.6804725 Saint Joseph St., Suite B1Rapid City, South Dakota 57701T 605.355.6804www.chamberlinarchitects.comE N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G NC 2016 CHAMBERLIN ARCHITECTS802 Rood AvenueGrand Junction, CO 81501PHONE: 970-241-0900FAX: 970-243-2430www.lindauerdunn.comC:\Users\JeffGrna\Documents\17.085-PCAF-S17_jgrna.rvt3/5/2019 10:05:14 AMS10207/16/1817.085CASTLE CREEK ROADASPEN, COLORADOFOUNDATION PLANPROJECT STATUS: 100% CDJDGFNRASPEN AMBULANCEDISTRICT FACILITY1. TOP OF SLAB ELEVATION = 100'-0" (TYP. U.N.O.).2. REINFORCE 4" CONCRETE SLABS ON GRADE W/ #3 @ 12 EA. WAY. PLACE REINFORCEMENT IN TOP HALF OF SLAB ON CHAIRS. DO NOT LOCATE REINFORCEMENT BY LIFTING DURING CONCRETE PLACEMENT.3. REINFORCE 6" CONCRETE SLAB W/ #4 @ 10 EACH WAY, TOP AND BOTTOM. OMIT CONTROL JOINTS AT 8" SLAB.4. VERIFY DOOR OPENING LOCATIONS AND ROUGH OPENING DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO CONSTRUCTION.5. PROVIDE (2) #5x TOP AT DOOR DEPRESSIONS. PROVIDE #4x DOWELS @ 16 INTO INTERIOR SLABS.NORTH2'-0" 2'-0"2'-0"2'-0" 3/16" = 1'-0"FOUNDATION PLANNO: ISSUED FOR: DATE:2 Revision 05/29/188 RFI #33 09/25/1810 Stair Add. 10/30/1813 PR #21 02/28/1913