HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (49).ACBKDetailed, RFIs Grouped by RFI Number
Request for Information 015
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 015 Date Created: 8/24/2018
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
ConfirmationElectricalHHS & AADF Electrical Service
Company Name Contact Name Copies NotesCc:
Chamberlin Architects, Inc. Daniel Gartner 1
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ David Hale 1
Question Date Required: 8/31/2018
Please refer to attached drawing
Sheet E002 shows the new electrical disconnect, meter and CT's entering the existing Health & Human Services building
on the far southwest corner of the building. We have found that the existing MDP in the building is actually further north,
on the lower level under the west entrance. The existing conduit enters the MDP from the bottom, which is approximately
10' deep and the electrical room walls are very crowded making core drilling difficult and would likely require relocating
piping or equipment. In an effort to eliminate a deep excavation or additional core holes on the west side of the building we
have confirmed with Holy Cross that we can install the disconnect, meter and CT's on the west island in the parking lot
where the new transformer is to be placed (see attached drawing). Libby with Holy Cross has confirmed that the layout will
work for them. We will likely need to add some bollards to the island and Holy Cross will determine the quantity and
placement with us on site. We are proposing to tie to the existing conduits when the current transformer is removed and
pull new feeders from the island to the MDP. Please confirm that this plan is acceptable.
Suggestion
Answer Date Answered:
This is acceptable to me.
WLM 8/25/18
Prolog Manager Printed on: 8/27/2018 FCI_Integration Page 1
compact compactcompactcompactE
Tap Box
(2) - 3" to AAD
building service
Light Pole
CT / Meter
600A fused
disconnect
(2) 3" pvc
(2) 3" pvc to HHS
building service
Here is the proposed layout for the transformer island @ Aspen
Ambulance. Let me know if this set up will work for Holy Cross and we will
run it by the design team also.
If this layout works, what will the requirement be for bollards?