Request for Information 024
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 024 Date Created: 9/13/2018
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
ClarificationArchitecturalFoundation Dampproofing vs. Waterproofing
Company Name Contact Name Copies NotesCc:
Chamberlin Architects, Inc. Daniel Gartner 1
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ David Hale 1
Question Date Required: 9/20/2018
Please refer to attached.
1.) Wall section cut 2/A512 has a call out for dampproofing and points to the exterior face of the CMU block that will be
below grade. Detail call-out 1/A601 shows waterproofing on the concrete for this wall. Is the intent for both waterproofing
to be applied to the concrete foundation walls and damproofing to be installed over CMU that is below grade? Please
clarify.
2.) Wall section cut 3/A513 calls for dampproofing at the below grade foundation wall. This appears to be a mistake.
Please confirm waterproofing only per detail 1/A601 is required at this wall section cut.
Suggestion
Answer Date Answered: 9/17/2018
1. PROVIDE WATERPROOFING ONLY OVER CMU THAT IS BELOW GRADE. WATERPROOFING TO BE HELD
6-INCHES BELOW FINISHED GRADE.
2. PROVIDE WATERPROOFING ONLY AT BELOW GRADE FOUNDATION WALL ILLUSTRATED ON 3/A513.
WATERPROOFING TO BE HELD 6-INCHES BELOW FINISHED GRADE.
2018.09.17 - JONATHAN WEST
Prolog Manager Printed on: 9/17/2018 FCI_Integration Page 1