Loading...
HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (72).ACBKDetailed, RFIs Grouped by RFI Number Request for Information 036 Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033 Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583 RFI #: 036 Date Created: 9/24/2018 Author Company Authored ByAnswer Company Answered By Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks 437 Main Street Grand Junction, CO 81501 P. O. Box 1767 Grand Junction, CO 81502 Co-Respondent Author RFI Number DisciplineSubject Category ClarificationStructuralVertical Brace Clarifications #2 Company Name Contact Name Copies NotesCc: FCI Constructors, Inc. - GJ Brady Blackmer 1 FCI Constructors, Inc. - GJ Brian Young 1 FCI Constructors, Inc. - GJ David Hale 1 Chamberlin Architects, Inc. Daniel Gartner 1 Question Date Required: 10/1/2018 Please see the questions below pertaining to the vertical brace structural steel. 5. There are (5) columns on Grid I.9. the column on I.9 & 2.1 is a stacked column, where the W10x30 bears on the low column and the upper column bears on the W10x30. However, S103 appears to want stacked columns on the remaining (4) columns to the south of 2.1. Please confirm these (4) columns are to extend from the foundation up-to the roof in one piece, and the beams are to frame into the columns with shear tabs. 6. There is a column on Grid G.9 & 4.9. S103 depicts this as a stacked column where the W12x19 on Grid 4.9 runs over the column. Please confirm this column is to extend from the foundation up-to the roof in one piece, and the beams are to frame into the column with shear tabs. 7. There is a column on Grid G.9 & 5.9. S103 calls for a stacked column with an HSS5x5x1/4 low, the W14 bearing on top of the HSS5x5x1/4, and then a HSS5x5x5/16 bearing on top of the W14. Please confirm whether there is to actually have stacked columns or if the HSS5x5x1/4 column is to extend from the foundation up-to the roof in one piece, and the beams are to frame into the column with shear tabs. Suggestion Answer Date Answered: 9/28/2018 5. The columns at Grids 2.1 and 3 are stacked, the others are continuous. 6. This column is not continuous. 7. They are stacked columns. The lower column should also be 5/16" wall thickness. Prolog Manager Printed on: 9/28/2018 FCI_Integration Page 1