Request for Information 041
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 041 Date Created: 10/1/2018
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
ClarificationArchitecturalCMU Masonry at OH Doors
Company Name Contact Name Copies NotesCc:
Chamberlin Architects, Inc. Daniel Gartner 1
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ David Hale 1
Question Date Required: 10/8/2018
Please refer to the attached drawing
Please see the questions below regarding the CMU masonry at the OH door openings:
1. Per detail 2 and detail 6 on sheet A702, bullnose split face CMU is required where the CMU veneer returns back for the
OH door openings. Per correspondence from the CMU veneer supplier this morning, it was stated that they do not make a
split face bull nose CMU. Please confirm it is acceptable not to use any bull nose split face CMU block on this project as
the plans call out.
2. Per detail 6 on sheet A702 CMU masonry is shown to return to the building behind the split face veneer. Is these CMU
to be the grey ground face CMU black or the 4" split face veneer. (see attached mark up)
3. If the block that returns to the building is grey ground face CMU will the exposed block be required to be painted to
match the interior of the apparatus bays? Please confirm finish of the exposed CMU.
Suggestion
Answer Date Answered: 10/1/2018
1. IT IS ACCEPTABLE TO NOT USE ANY BULL NOSE SPLIT-FACE CMU. PLEASE DISREGARD ANY REFERENCE TO
BULL NOSE IN THE CDS.
2. PROVIDE 4" SPLIT-FACE CMU VENEER AT THESE LOCATIONS.
3. THE EXPOSED ENDS OF THE 8" CMU (INTERIOR BLOCK) IS TO BE PAINTED. THE DESIGN TEAM WILL
CONFIRM THE P# AFTER WE HAVE REVIEWED THE METAL WALL PANEL SUBMITTAL.
2018.10.01 - JONATHAN WEST
Prolog Manager Printed on: 10/1/2018 FCI_Integration Page 1
7
CONT BACKER ROD &
SEALANT (TYP)
HM FRAME, PNT
DOOR, RE: SCHED4"CONT SEALANT (TYP)
PRE FINISHED MTL EDGE CAP W/
WEEP HOLES, RIVET TO MTL PANEL
@ 12" O.C. W/ CONT SEALANT TAPE
THERMALLY BROKEN 'C' GIRT
WEATHER BARRIER FLASHING, LAP
OVER MTL SILL FLASHING FLANGE
PRE FINISHED MTL FLASHING W/
WEEP HOLES
PRE FINISHED MTL DRIP FLASHING
W/ HEMMED EDGE
6
PRE FINISHED MTL TRIM
7
CONT BACKER ROD &
SEALANT (TYP)
HM FRAME, PNT
DOOR, RE: SCHED2"CONT SEALANT (TYP)
PRE FINISHED MTL EDGE
CAP, RIVET TO MTL PANEL
@ 12" O.C. W/ CONT
SEALANT TAPE
THERMALLY BROKEN 'C' GIRT
PRE FINISHED MTL FLASHING
2"
6
9
CONT BACKER ROD &
SEALANT (TYP)
HM FRAME, PNT
DOOR, RE: SCHED4"STL ANGLE, RE: STR (PNT)
CONT
SEALANT (TYP)
WEATHER BARRIER OVER
WEATHER BARRIER
FLASHING
WEATHER BARRIER
FLASHING
THROUGH WALL WEEPS
& FLASHING
1' - 3"
6
9
CONT BACKER ROD &
SEALANT (TYP)
WEATHER BARRIER
FLASHING
HM FRAME, PNT
DOOR, RE: SCHED
GL
CONT
SEALANT (TYP)
BULLNOSE EDGE
2"2"
6
11
WEATHER BARRIER OVER WEATHER
BARRIER FLASHING
STL ANGLE & PLATE, RE: STR (PNT)
OH DOOR, RE: SCHED
0
WEATHER BARRIER FLASHING
THROUGH WALL WEEPS
& FLASHING
GROUT CAVITY SOLID BELOW
FLASHING
6
11
OH DOOR, RE: SCHEDULE
0
CONT BACKER ROD &
SEALANT
RETURN CMU
VENEER @ JAMB
6" DIA CONCRETE
FILLED BOLLARD.
ALIGN WITH DOOR
OPENING
1
1' - 0"1' - 6"
BULLNOSE EDGE 3"1
1/2"2"SEALANT, EA
SIDE (TYP)
HM FRAME,
PNT
DOOR, RE:
SCHED
2
1
1/2"2"SEALANT, EA
SIDE (TYP)
HM FRAME,
PNT
DOOR, RE:
SCHED
2
3
2"SEALANT, EA
SIDE (TYP)
HM FRAME,
PNT
DOOR, RE:
SCHED
3
2"SEALANT, EA
SIDE (TYP)
HM FRAME,
PNT
DOOR, RE:
SCHED
2
OVERHEAD
DOOR, RE:
SCHED
MTL STUD
HEADER, RE:
STRUC
2
DOOR, RE:
SCHED
CORNER GAURD
@ BOTH SIDES
DOUBLE STUD AT
JAMB, TYP.
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTSBIM 360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt9/25/2018 8:49:25 AMA702
05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
DOOR DETAILS
PROJECT STATUS: 100% CD
KH JW
ASPEN
AMBULANCE
DISTRICT FACILITY
0'3"6"0'3"6"
A702
HM DOOR HEAD @ WALL TYPE 73
0'3"6"0'3"6"
A702
HM DOOR JAMB @ WALL TYPE 74
0'3"6"0'3"6"
A702
HM DOOR HEAD @ WALL TYPE 91
0'3"6"0'3"6"
A702
HM DOOR JAMB @ WALL TYPE 92
0'3"6"0'3"6"
A702
OH DOOR HEAD @ WALL TYPE 55
0'3"6"0'3"6"
A702
OH DOOR JAMB @ WALL TYPE 56
0'3"6"0'3"6"
A702
HM DOOR HEAD @ WALL TYPE 1 & 27
0'3"6"0'3"6"
A702
HM DOOR JAMB @ WALL TYPE 1 & 28
0'3"6"0'3"6"
A702
HM DOOR HEAD @ WALL TYPE 39
0'3"6"0'3"6"
A702
HM DOOR JAMB @ WALL TYPE 310
0'3"6"0'3"6"
A702
OH DOOR HEAD @ WALL TYPE 211
0'3"6"0'3"6"
A702
OH DOOR JAMB @ WALL TYPE 212
NO: ISSUED FOR: DATE:
6 PR#010 9/25/2018
6
Is this CMU grey ground face or
is this the split face veneer?If this is the grey ground face
block, will this be painted block?
Split face CMU is not made
is a bullnose version.