HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (79).ACBKDetailed, RFIs Grouped by RFI Number Request for Information 043 Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033 Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583 RFI #: 043 Date Created: 10/4/2018 Author Company Authored ByAnswer Company Answered By Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks 437 Main Street Grand Junction, CO 81501 P. O. Box 1767 Grand Junction, CO 81502 Co-Respondent Author RFI Number DisciplineSubject Category ClarificationArchitectural/StructuralStair 302 Structural Steel Company Name Contact Name Copies NotesCc: Chamberlin Architects, Inc. Daniel Gartner 1 FCI Constructors, Inc. - GJ Brady Blackmer 1 FCI Constructors, Inc. - GJ Brian Young 1 FCI Constructors, Inc. - GJ David Hale 1 Question Date Required: 10/11/2018 Please refer to the attached model. The questions below are related to the structural steel for Stair 302. 1. Please confirm the outside perimeter stringers will be exposed to view per 5/A652, while the inside stringers will be concealed within the gyp of the "divider" wall per 5/A651. 2. Per the spec's, the stringers are to be designed to limit deflection to L/240 or ¼", whichever is less. A C12x20.7 stair stringers are required, as it passes the L/240 requirement and barely passes ¼" deflection. 3. The lower flight of stairs will need a post located in the stud wall to support the 1st intermediate landing. The mid-flight of stairs will require hanger columns to support the 2nd intermediate landing. Please confirm the W12x19 (on Grid I, between 3.5-4.9) is adequate to support the roof column and also the loading from the stairs. MSW is conservatively figuring 7kips of loading at each hanger will be applied to the W12x19. 4. Please refer to 5/A651. The detail depicts a smaller stringer is to be used, however as discussed in item #2 a C12x20.7 is required. The C12x20.7 has a 3" flange width. This 3" flange will cause issue with anchoring the ½" plate that caps off the "divider" wall. Rather than using two separate pieces of wood blocking directly over the stud/channel, MSW would propose to use a 2x12 that would be ripped down to the required width, then the threaded studs used to attach the ½" plate to the 2x wood block would be offset as necessary to not interfere with the stringers. 5. Please advise what is desire for the stringer reveal at the exposed stringer, and also what is the reveal required for the interior stringer. Per 5/A651, the gyp is to be attached directly to the stringer. MSW would like to make sure there is enough channel at the nosing to allow for the gyp to attach. 6. What is the reveal dimension from the stair nosings up-to the top of the ½" plate on the "divider" wall? 7. PR #10 has eliminated the wood treads and now the polished concrete will be used. Is it acceptable to have a 1" return on the stair pans at the nosing? This 1" return will be exposed. a. Slip resistant nosings are not supplied by MSW. Prolog Manager Printed on: 10/18/2018 FCI_Integration Page 1 Request for Information 043 Detailed, RFIs Grouped by RFI Number 8. Since the interior stair stringers are to be concealed within the "divider" wall, there is a challenge to make the mid-flight stair nosings work out correctly. The layout shows the nosing to be held at the same location as the face of the gypboard. This is causing the nosings to extend past the ends of the stringers by 5/8" at these landings (thickness of the gypboard). Is this really what is wanted? Is there a way to shrink the tread width of the stairs and increase the thickness of the divider wall to allow for the mid-flight tread to frame into the stringer? 9. Blackened steel was excluded and shop primer was figured in MSW's proposal. Please confirm this is acceptable. (Note. MSW will not provide blackened steel. As an alternate, MSW could provide a High Performance Primer for additional costs.) 10. MSW will provide countersunk holes for wood infill on guard railing posts. MSW is figuring one, countersunk, hole for a 1/8" wood screw for each piece of wood infill. 11. Please supply a detail on how the stair guardrail is to transition onto the upper floor level (how 5/A651 transitions to 5/A611). It appears that the "divider" wall will have a reveal that is greater than what the guardrail will have at the upper floor. Per 5/A611, the guardrail at the upper floor level is to be a C7x9.8 with a 1" reveal above the slab. This transition from the floor guardrail to the stair/"divider" wall guardrail will need to be worked out…especially at the base of the guardrail, as the stair guardrail is depicted to incorporate 12 wood infills (2/A651) whereas the floor guardrail is depicted to have 16 wood infills (5/A611) a. 12 Sloping wood infills vs 16 flat wood infills 12. 2/A651 shows the general locations of the guardrail posts. Currently there is no post shown at the locate where the wood infills "bend" from flat to sloping. Please confirm a post is not wanted here, and if one is needed please is the bend is the wood is to be held at the stair nosing line. (each bend is directly above the other as depicted in 2/A651) Suggestion Answer Date Answered: 10/18/2018 1. CONFIRMED. 2. OK. 3. CONFIRMED. PROVIDE SKETCH FOR REVIEW & APPROVAL. 4. THIS IS ACCEPTABLE. 5. AT EXPOSED STRINGERS, REFER TO DETAIL 6/A652. 6. DIMENSION IS 2-9/16 INCH. 7. STAIR PAN TO MATCH PROFILE SHOWN ON DETAIL 6/A612. 8. STAIR TREAD TO ALIGN WITH 'DIVIDER' WALL DEPTH AS ILLUSTRATED IN THE CDS. 9. EXPOSED STEEL TO BE PAINTED P6 AS INDICATED IN ADDENDUM #2 DATED MAY 25, 2018. EXPOSED STEEL TO BESHOP PRIMED. 10. GC TO CONFIRM WITH SUBCONTRACTOR PROVIDING & INSTALLINGWWOOD INFILL. REFER TO ATTACHED REVISED SHEET A406, DETAIL 11 AND ATTACHED REVISED SHEET A611, DETAIL 5. 11. PROVIDE 1-INCH REVEAL BETWEEN STAIR STRINGER AND TOP TREAD TO ALIGN WITH 1-INCH" REVEAL AT C7X9.8. REFER TO ATTACHED REVISED SHEET A651, DETAIL 5. 12. MODIFYYGUARDRAIL POST LAYOUT AS ILLUSTRATED IN THE ATTACHED REVISED SHEET A651, DETAIL 2. 2018.10.18 --JONATHAN WEST Prolog Manager Printed on: 10/18/2018 FCI_Integration Page 2 5/A652 per Jonathan W. 6 FEP UC REF FEP 9 A622 ________________________________________ 12 A622 ________________________________________ 3 A621 ________________________________________ 7 A621 ________________________________________ 7 A622 ________________________________________ 4 A622 ________________________________________ FILLER 2' - 0"2' - 9"1' - 6"1' - 6"2' - 6"1' - 7"9"2' - 6"1' - 8"2' - 10"2' - 1 1/2"2' - 9"1' - 6"1' - 6"2' - 6"1' - 7"6"CYPHER LOCK (TYP OF 5) APROXIMATE AREA OF COUNTERTOP MEDICATION DISPENSER OUTLINE OF DOOR OPEN BASE, RE: FIN PLANS 4' - 6" WIRE SHELVING W/ BINS, RE: FURNITURE PLANS 6 BASE, RE: FIN PLANS 3' - 0"2' - 6" C LIGHT FIXTURES, RE: ELEC DEEP WALL MOUNT OPEN LOCKERS W/ POWER BAR DEEP WALL MOUNT OPEN LOCKERS W/O POWER BAR DEEP WALL MOUNT OPEN LOCKERS W/ BACKBOARD RACK AND BASKET 6' - 0"1' - 0"JUNCTION BOXES @ POWER BAR LOCATIONS , RE: ELEC C (6) 24" X 36" DEEP WALL MOUNT OPEN LOCKERS W/ TOPSIDE STORAGE SHELF LIGHT FIXTURES, RE: ELEC AIR RETURN, MATCH HEIGHT OF LIGHTS, RE: MECH 5 6 LIGHT FIXTURES, RE: ELEC AIR RETURN, MATCH HEIGHT OF LIGHTS, RE: MECH (4) 24" X 36" DEEP WALL MOUNT OPEN LOCKERS W/ TOPSIDE STORAGE SHELF 7' - 0"MOBILE 02 CYLINDER SYSTEM 56 4"6' - 0"8"(3) 6' X 2' WALL MOUNT SLINGER TOOL GRID PANEL W/ SLINGER TOPSIDE WALL MOUNT SHELF ABOVE BASE, RE: FIN PLANS OXYGEN STORAGE ENCLOSURE, PROVIDE DOORS, TOPSIDE SHELF, AND ONE SHELF ABOVE TANKS. OMIT BOTTOM SHELF SO TANKS CAN REST ON FLOOR EQEQEQEQ STANDARDS AND BRACKETS, (TYP) RE: SPECS. PROVIDE BLOCKING 6 MELAMINE ADJUSTABLE SHELVES, CONNECT AT SHELF SEAMS FOR STABILITY (TYP) 2' - 0" 12 CONNECT SHELVES WHERE THEY MEET AT CORNER FOR STABILITY (TYP) BASE; RE: FINISH PLAN 2' - 0 1/2" I 5 A611 ________________________________________ STL BEAM, RE: STR (PNT P6) STL CHANNEL, PNT P6 WD SLATS (TYP of 15) WELDED STL ANGLE FRAME, PNT P6 STL 2" X 1/4" PLATE VERTICAL WELDED TO STL ANGLE, PNT P6 (TYP OF 3) DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSBIM 360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt10/18/2018 11:30:54 AMA406 OCTOBER 16, 2018 1740 CASTLE CREEK ROAD ASPEN, COLORADO INTERIOR ELEVATIONS PROJECT STATUS: 100% CD SH JW ASPEN AMBULANCE DISTRICT FACILITY 0'2'4'0'2'4' A406 MEDICAL STORAGE - WEST1 0'2'4'0'2'4' A406 MEDICAL STORAGE - SOUTH2 0'2'4'0'2'4' A406 MEDICAL STORAGE - NORTH3 0'2'4'0'2'4' A406 MEDICAL STORAGE - EAST4 0'2'4'0'2'4' A406 READY ROOM - NORTH5 0'2'4'0'2'4' A406 READY ROOM - SOUTH6 0'2'4'0'2'4' A406 READY ROOM - EAST7 0'2'4'0'2'4' A406 READY ROOM - WEST8 0'2'4'0'2'4' A406 PANTRY 219 - NORTH9 0'2'4'0'2'4' A406 PANTRY 219 - WEST10 0'2'4'0'2'4' A406 WAITING 201 - NORTH IE11 NO: ISSUED FOR: DATE: 10 RFI#043 10/18/18 10 BASE, RE: FIN SCHED WOOD SLAT (1 -1/2" X 1 -3/4") FINISH NAILED TO WD BACKER 3/4" PWD W/ WD VENEER ACOUSTICAL BLANKET, RE: SPECS TV SCREEN OR OTHER, MOUNTED TO PWD 2 ACOUSTICAL BLANKET, RE: SPECS WOOD SLAT (1 -1/2" X 1 -3/4") FINISH NAILED TO WD BACKER 3/4" PWD W/ WD VENEER WD BACKER (1X4), PNT P6 WD BACKER (1X4), PNT P6 1/4"5/8" GYP BD ON 3 5/8" METAL STUDS @ 24" OC MAX, RE: RCP FOR ELEVATIONS 3 5/8" METAL STUD KICKERS, BRACED TO STRUCUTRE AT 48" OC MAX 6" METAL STUD HEADER METAL STUDS @ 16" OC MAX 5/8" GYP BD ON 3 5/8" METAL STUDS @ 24" OC MAX, RE: RCP FOR ELEVATIONS GYP BD ON 3 5/8" METAL STUDS @ 24" OC MAX, RE: RCP FOR ELEVATIONS CLG GRID EDGE TRIM, SHADOW LINE MOLDING RE: SPEC APC, RE: RCP FOR ELEVATION 6" MTL STUD HEADER METAL STUDS @ 16" OC MAXMIN6"WOOD SLAT (1 -1/2" X 1 -3/4") 3 BLACKENED STL HSS 3" X 3" 1/8" W/ 3" X 3" X 1/8" ATTACHMENT PLATES WELDED @ 16" O.C. ACOUSTICAL BLANKET, RE: SPECS WD BACKER (1X4), PNT P6 CONT WD BACKER (1X4), PNT P6 REVEAL1/4"REVEAL 1/4"4"1/2" WD 1 TRIM WITH 5/8" BLOCKING BEHIND. 1/8" RADIUS AT TOP OF TRIM AS SCHED FLOOR TILE OVER CONCRETE METAL EDGE STRIP COVE, RE: SPECS WALL TILE OVER BACKER ALIGN, SET TRIM IN MORTAR BED TO ALIGN WITH FACE OF TILE SO IT DOESN'T BECOME A DIRT COLLECTION AREA METAL EDGE STRIP OUTSIDE CORNER, RE: SPECS WALL TILE OVER BACKER WALL TILE OVER BACKER METAL EDGE STRIP BULLNOSE, RE: SPECS WALL TILE OVER BACKER PAINT ADJACENT GWB SHOWER UNIT, RE: SPECS METAL EDGE STRIP OUTSIDE CORNER, RE: SPECS WALL TILE OVER BACKER WALL TILE OVER BACKER SHOWER UNIT FLANGE SEAL STL C7 X 9.8 CHANNEL, PNT P6 CONC SLAB, RE: STR STL BEAM, RE: STR (PNT P6) HORIZONTAL STL 2" X 2" X 1/4" ANGLE, PNT P6 WD 1 1/2" X 1 3/4" SLATS FASTENED @ LANDING SIDE W/ COUNTERSUNK SCREWS THROUGH STL ANGLE (TYP of 15) VERTICAL STL 2" X 2" X 1/4" ANGLE BEYOND, PNT P6 3 5/8" MTL STUD KICKERS, BRACED TO STRUCT @ 48" O.C. MAX 6" MTL STUD HEADER 3-5/8" MTL FRM'G @ 16" O.C. MAX 5/8" GWB, PNT3' - 6"TYP1"1"DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSBIM 360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt10/18/2018 11:37:43 AMA611 OCTOBER 16, 2018 1740 CASTLE CREEK ROAD ASPEN, COLORADO INTERIOR DETAILS PROJECT STATUS: 100% CD SH JW ASPEN AMBULANCE DISTRICT FACILITY 0'6"1'0'6"1' A611 FEATURE WALL @ TV1 0'3"6"0'3"6" A611 GYP BOARD SOFFIT AT GYP CLG (TYP)9 0'3"6"0'3"6" A611 GYP BOARD SOFFIT TO SAG10 0'3"6"0'3"6" A611 FEATURE WALL CORNER DETAIL2 0'3"6"0'3"6" A611 WOOD BASE TRIM8 0'3"6"0'3"6" A611 TILE BASE DETAIL3 0'3"6"0'3"6" A611 TILE OUTSIDE CORNER DETAIL7 0'3"6"0'3"6" A611 TILE TOP OF WAINSCOT DETAIL4 0'3"6"0'3"6" A611 TILE DETAIL @ SHOWER6 0'6"1'0'6"1' A611 WOOD SLAT RAIL DETAIL5 NO: ISSUED FOR: DATE: 10 RFI#043 10/18/18 10 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" 5 3 STL ANGLE FRAME, PNT P6 STL HANDRAIL, PNT P6 WD SLATS STL PLATE, PNT P6 11" EA 13 TREADS @ 5 A651 ________________________________________ A612 7 A652 5 A731 3 108' - 0" LANDING 1 109' - 1 3/4" LANDING 2@ 7" MAX EA12 RISERS2 RISERS @ 7" MAX EA@ 7" MAX EA14 RISERSSTRINGER RECESSED IN WALL E Q E Q E Q 10 G.9 I J 5 3 STAIR 302 ELEVATOR 301 2 A651 ________________________________________ 8' - 11 3/4" 2 2 2 2 5 7 7 3 A651 ________________________________________ FD ELEVATOR POWER UNIT, RE: ELEC 2 UP 1' - 0"4' - 2 1/4"11"4' - 2 1/4" 3A 4' - 2 1/4"1 ASK-01 ________________________________________ 3.5 I J 4 5 3 2 A651 ________________________________________ DN A612 9 STAIR 302 A651 6 A612 8 7 7 2 2 2 4' - 2 1/4"11"4' - 2 1/4"4' - 2 1/4"3.5 MAIN FLOOR 100' - 0" UPPER LEVEL 116' - 0" 3 ADHERED SHEET WATERPROOFING (RE: SPECS) @ PERIMETER OF CONC PIT, LAP OVER FOUNDATION CONC JOINT W/ CONT HYDROSTOP, RE: SPECS MTL STUD HEADER, RE: STR FIRE CAULK GWB TO MTL DECK (TYP) GWB ON 1-5/8" MTL STUDS W/ BATT INSULATION SAG CLG, RE: RCP 22 13 2 SUSPENDED GWB CLG, RE: RCP SUMP PUMP BEYOND FLOOR DRAIN SLOPE CONC TO DRAIN, 1/8":12" FIRE PROOF ROOF DECK TO 1-HR ABV ELEVATOR SHAFT CLR12' - 8"MIN2" CLRSLOPE 1/4" : 12"A641 4 3.5 HORIZONTAL STL 2" X 2" X 1/4" ANGLE, PNT P6 STL POST 2" X 2" X 1/4" ANGLE BEYOND, FULL-WELD ON STL PLATE, PNT P6 3 STL STRINGER RECESSED IN WALL POLISHED CONC STAIR TREAD WD 1 1/2" X 1 3/4" SLATS FASTENED @ LANDING SIDE W/ COUNTERSUNK SCREWS THROUGH STL ANGLE (TYP of 12) STL HANDRAIL, PNT P6 1/2" STL PLATE, PNT P6 J-TRIM EDGE, EA SIDE STL & CONC STAIR PAN CONT 2X WD BLK'G 3 5/8" MTL FRM'G @ 16" O.C. 5/8" GWB PNT P6 NUT W/ LOCK WASHER (TYP) 3/8" DIA ALL THREAD @ 24" O.C. WELDED TO STL PLT (TYP)1"TYP1"3 1/4"1/4"1/4"1/4" 2"x2"x1/4" STL POST, PNT P6 VERTICAL 2"x2"x1/4" STL ANGLE, PNT P6 WD 1 1/2" X 1 3/4" SLATS FASTENED @ LANDING SIDE W/ COUNTERSUNK SCREWS THROUGH STL ANGLE STL PLATE BELOW, PNT P6 EQEQEQ EQ DRAWN BY:CHECKED BY: SHEET NO: PROJECT NO: DATE: CHAMBERLIN ARCHITECTS 437 Main St. Grand Junction, Colorado 81501 T 970.242.6804 725 Saint Joseph St., Suite B1 Rapid City, South Dakota 57701 T 605.355.6804 www.chamberlinarchitects.com E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N C 2016 CHAMBERLIN ARCHITECTSBIM 360://1740 - Pitkin County Ambulance Facility/1740-PCAF_CA.rvt10/18/2018 11:41:29 AMA651 OCTOBER 16, 2018 1740 CASTLE CREEK ROAD ASPEN, COLORADO STAIR 302 & ELEVATOR PLANS & SECTIONS PROJECT STATUS: 100% CD SH, PH JW ASPEN AMBULANCE DISTRICT FACILITY 0'2'4'0'2'4' A651 STAIR 302 SECTION @ STEPS2 0'2'4'0'2'4' A651 ENLARGED PLAN - STAIR 302/ELEVATOR MAIN FLOOR1 0'2'4'0'2'4' A651 ENLARGED PLAN - STAIR 302 UPPER LEVEL4 0'1'2'0'1'2' A651 ELEVATOR SECTION3 0'6"1'0'6"1' A651 STAIR RAIL DETAIL5 0'3"6"0'3"6" A651 STAIR RAIL DETAIL @ POST6 NO: ISSUED FOR: DATE: 10 RFI#043 10/18/18 10