Request for Information 046
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 046 Date Created: 10/10/2018
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
ClarificationStructuralSteel Material Clarification
Company Name Contact Name Copies NotesCc:
Chamberlin Architects, Inc. Daniel Gartner 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ David Hale 1
Question Date Required: 10/17/2018
1. The elevator guiderail columns are called out as a HSS10x3x5/16. Our material supplier has only HSS10x3x¼". Would
this by chance be acceptable? (1/4" wall thickness in lieu of 5/16"?)
2. On sheet S104, there is a W18x40 on Grid 4, that extends from A.9 and then past Grid E. This requires MSW to try and
find a 65-0 piece of material. To locate this length, we would have to get in a mill rolling which may result in a delay of
getting this beam to the site.
Please confirm if there may be an alternate means of framing the roof at this beam to separate then 65-0 beam length into
two separate pieces?
Suggestion
Answer Date Answered: 10/22/2018
1. HSS10x3x1/4 will not work. Can HSS10x3x3/8 be obtained?
2. Yes, we can splice the W18x40 3'-6 west of Grid D.
Prolog Manager Printed on: 10/22/2018 FCI_Integration Page 1