Request for Information 057
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 057 Date Created: 11/6/2018
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
ConfirmationArchitectural/StructuralElevator Pit & Hoistway Dimensions
Company Name Contact Name Copies NotesCc:
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ David Hale 1
Question Date Required: 11/13/2018
Please refer to attached.
Per the returned elevator submittal, the dimensions of the elevator hoistway have changed to match the architectural
dimensions. Per the structural drawings, the elevator pit is shown to have dimensions of 8'-4" x 5'-9". The architectural
drawings show the hoistway with dimensions of 8'-11 3/4" x 6'-5" which do not line up with the dimensions of the elevator
pit. It has been confirmed by the design team that it will be acceptable to have the elevator pit dimensions per the
structural drawings and the elevator hoistway dimensions per the architectural drawings. It has also been confirmed with
Thyssen Krupp, the elevator supplier that these dimensions will be acceptable for the elevator install.
Suggestion
Answer Date Answered:
This RFI is for confirmation only. No response is required.
Prolog Manager Printed on: 11/6/2018 FCI_Integration Page 1
G.9 I
ELEVATOR
301
8' - 11 3/4"
2
2
2
3
A651
________________________________________
FD
ELEVATOR POWER
UNIT, RE: ELEC
2
Elevator Hoistway Dimensions Detail 1 on sheet A6516'-5"8'-11 3/4"
8' - 4" 11' - 7 1/4"5' - 9"TOP
STEPHSS5X5X3/8(D)HSS5HSS5HSS5X5X5/16(D) 3/8" 7 5/8"
8
S300
TYP.3' - 8 3/4"2' - 0 1/4"HSS10X3X5/16(F)HSS10X3X5/16(F) 1/2" 2 1/8"2 1/8" 5 1/2"
P-6
P-6
F.D.
SEE
MECH.
Elevator Pit Dimensions Structural Sheet S1025-9"8'-4"
1
Sam Meeks
From:Perlinger, Christopher <Chris.Perlinger@thyssenkrupp.com>
Sent:Tuesday, November 6, 2018 8:58 AM
To:Sam Meeks
Cc:Brian Young; Drago, Alfred (AJ)
Subject:RE: Aspen Ambulance - Elevator Dimensions
Agreed.
Regards
Chris Perlinger, LEED Green Associate
New Equipment Sales
ET-AMS/FLD
T: +1 720 274 3494, M: +1 720 354 2817, chris.perlinger@thyssenkrupp.com
From: Sam Meeks <smeeks@fciol.com>
Sent: Tuesday, November 6, 2018 8:48 AM
To: Perlinger, Christopher <Chris.Perlinger@thyssenkrupp.com>
Cc: Brian Young <BYoung@fciol.com>
Subject: Aspen Ambulance - Elevator Dimensions
Chris,
Thanks for calling me back this morning. I just wanted to follow up on our conversation regarding the dimensions for the
elevator pit and the elevator hoistway at the Aspen Ambulance Facility. Per our conversation you have confirmed that
the dimensions for the elevator pit can stay at the 8’-4” x 5’-9” as shown on the TKE shop drawings dated 7/19/2018.
You have also confirmed that the dimensions for the elevator hoistway can be changed to 8-11 ¾” x 6’-5” as marked up
by the architect on the TKE shop drawings. You also stated that FCI will need to make sure that there are not any ledges
within the elevator hoistway larger than 4” as this is a code regulation. FCI will issue a confirming RFI to the design team
to make sure everyone is on the same page.
Thanks
Sam Meeks
Engineer
FCI Constructors, Inc.
P.O. Box 1767 (81502)
3070 I-70 B, Bldg. A
Grand Junction, CO 81504
P. (970) 434-9093 F. (970) 434-7583 C. (970) 618-8817
www.fciol.com
Focused On Your Vision