Loading...
HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0024.2019 (99).ACBKDetailed, RFIs Grouped by RFI Number Request for Information 062 Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033 Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583 RFI #: 062 Date Created: 11/19/2018 Author Company Authored ByAnswer Company Answered By Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ Sam Meeks 437 Main Street Grand Junction, CO 81501 P. O. Box 1767 Grand Junction, CO 81502 Co-Respondent Author RFI Number DisciplineSubject Category ClarificationArchitecturalChannel Frame Mirrors Company Name Contact Name Copies NotesCc: FCI Constructors, Inc. - GJ Brady Blackmer 1 FCI Constructors, Inc. - GJ Brian Young 1 FCI Constructors, Inc. - GJ David Hale 1 FCI Constructors, Inc. - GJ Nick Stokes 1 Question Date Required: 11/26/2018 It appears the channel frame mirrors are shown to be installed per elevations on A402 at the following restrooms/shower rooms, and at the following sizes. However, there are no channel framed mirrors called out in specification sections 088300 or 102800. Please confirm channel framed mirrors are wanted as follows and sizes are correct. Women 102, Men 103, Toilet 208 - 18" x 36" Shower 225, 226, 227 - 24" x 42" FCI will submit on a channel framed mirror product for approval. Suggestion Answer Date Answered: 11/19/2018 The mirrors and trim are specified in section 088300. The sizes listed above are correct. These sizes do meet typical sizes for channel frame mirrors and they would be an acceptable substitute if they meet the performance and material requirements of section 088300. Casey Sievila, Chamberlin Architects 11/19/18 Prolog Manager Printed on: 11/19/2018 FCI_Integration Page 1