Request for Information 080
Aspen Ambulance District Facility FCI Constructors, Inc. - GJProject # 10-17-033
Aspen, CO 81611 Tel: 970-434-9093 Fax: 970-434-7583
RFI #: 080 Date Created: 1/30/2019
Author Company Authored ByAnswer Company Answered By
Chamberlin Architects, Inc. Jonathan West FCI Constructors, Inc. - GJ David Hale
437 Main Street
Grand Junction, CO 81501
P. O. Box 1767
Grand Junction, CO 81502
Co-Respondent Author RFI Number
DisciplineSubject Category
DirectionStructuralCover for Mechanical Equipment
Company Name Contact Name Copies NotesCc:
FCI Constructors, Inc. - GJ Brady Blackmer 1
FCI Constructors, Inc. - GJ Brian Young 1
FCI Constructors, Inc. - GJ Sam Meeks 1
Question Date Required: 2/6/2019
Please refer to attached.
During the 1/29/2019 OAC Meeting it was discussed that the mechanical condensing units that are to be installed on the
southeast corner of the building will need something to protect them from snow falling off the roof. Rich with Pitkin County
commented that the cover structure must be designed to withstand someone standing on the structure. Please provide
details and a design for a structure that would protect the condensing units from falling snow.
Suggestion
Answer Date Answered: 3/13/2019
1. REFER TO PROPOSAL REQUEST #021 DATED 3/11/19 FOR DESIGN & DETAILS OF ROOF STRUCTURE.
2. RELOCATE GENERATOR AND CONDENSER UNITS 1-3 AS INDICATED IN PROPOSAL REQUEST #021. THE
GENERATOR MANUFACTURER (CUMMINS) ADVISES AGAINST A ROOF ABOVE THIS PIECE OF EQUIPMENT.
THEIR (CUMMINS) CONCERN IS WITH OVERHEATING AND RE-ASPIRATING PRODUCTS OF COMBUSTION - THE
GENERATOR DISCHARGES UP.
2019.03.11 - JONATHAN WEST