CHILLED WATER RETURN
CHILLED WATER SUPPLY
COLD WATER
COMPRESSED AIR
HOT WATER - DOMESTIC
HOT WATER - DOMESTIC,
HOT WATER CIRCULATING -
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
NITROUS OXIDE
OXYGEN
OVERFLOW STORM DRAIN PIPING
SANITARY SEWER
SANITARY VENT
SNOWMELT RETURN
SNOWMELT SUPPLY
STORM DRAIN PIPING
VACUUM
CWR
CWS
CA
HWR
HWS
G
NO
O
SWR
SWS
V
TEMPERATURE SHOWN
DOMESTIC
OST
SS
ST
ELBOW
ELBOW UP
ELBOW DOWN
TEE
TEE UP
TEE DOWN
GATE OR GLOBE VALVE
BALL VALVE
CHECK VALVE
SOLENOID VALVE
BUTTERFLY VALVE
RELIEF VALVE
BALANCING VALVE, CALIBRATED
ANGLE VALVE, GATE OR GLOBE
UNION
CONTROL VALVE, 2-WAY
CONTROL VALVE, 3-WAY
P-T PORT
STRAINER
THERMOMETER IN PIPELINE
PRESSURE REGULATING VALVE
HOSE BIBB
PRESSURE GAUGE
FLOOR DRAIN OR SHOWER DRAIN
FLOOR SINK
ROOF DRAIN
HORIZONTAL CLEANOUT
FLOOR CLEANOUT
TWO-WAY CLEANOUT
WASTE MRETURN OR EXHAUST DUCT
DOWN, DIMENSION ACROSS
LISTED FIRST
SUPPLY DUCT DOWN
SUPPLY DUCT UP
RETURN OR EXHAUST
DUCT UP
DUCT ELBOW, DIMENSION
OF SIDE SHOWN = 22"
FLEXIBLE DUCT
CONNECTION
MANUAL VOLUME
DAMPERS IN DUCTS
SIDEWALL RETURN OR
EXHAUST GRILLE RA-1, 12"Wx8"H
SIDEWALL SUPPLY GRILLE
OR REGISTER SA-1,
12"Wx8"H, 225 CFM
CEILING RETURN GRILLE
OR REGISTER RA-1, 12"x8"
CEILING SUPPLY DIFFUSER,
GRILLE, OR REGISTER SA-1,
24"x24", 225 CFM
FIRE DAMPER
COMBINATION
FIRE/SMOKE DAMPER
MOTORIZED CONTROL
DAMPER IN DUCT
22"x10"
22"x18"
T
H
T
H
THERMOSTAT / TEMPERATURE CONTROL
HUMIDISTAT OR HUMIDITY SENSOR
DUCT THERMOSTAT OR
TEMPERATURE SENSOR
DUCT HUMIDISTAT OR
HUMIDITY SENSOR
PIPING PIPING ACCESSORIES
ABBREVIATIONS
CONTROLS
DUCTWORK
M-1
A
1
1
SECTION INDICATOR
A = SECTION DESIGNATION
M-1 = SHEET DESIGNATION
KEYED NOTE DESIGNATION
DRAWING REVSION DESIGNATION
GENERAL SYMBOLS
M E C H A N I C A L A N D P L U M B I N G L E G E N D
SA-1 EQUIPMENT DESIGNATION (REFER TO
SCHEDULES AND SPECIFICATIONS)
F
F/S
12"x8"
RA-1
SA-1
225 CFM
12"x8"
12"x8"
RA-1
SA-1
225 CFM
24"x24"
DUCT, DIMENSION OF
SIDE SHOWN = 22"
22"x10"
110
REFRIGERATION LIQUIDRL
REFRIGERATION SUCTIONRS
DUCT ACCESSORIES
AND DIFFUSERS
GRILLES, REGISTERS,PIPING FITTINGS
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
BDD BACK DRAFT DAMPER
BFG BELOW FINISHED GRADE
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
COTG CLEANOUT TO GRADE
CV CIRCUIT VENT
CW COLD WATER
DB DRY BULB TEMPERATURE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EWT ENTERING WATER TEMPERATURE
FCO FLOOR CLEANOUT
°F DEGREES FAHRENHEIT
FA FRESH AIR TEMPERED
GC GENERAL CONTRACTOR
HW HOT WATER - DOMESTIC
HWC HOT WATER CIRCULATING - DOMESTIC
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LB POUNDS (WEIGHT)
MA MIXED AIR
MC MECHANICAL CONTRACTOR
NIC NOT IN CONTRACT
NK NECK (DUCT CONNECTION)
NTS NOT TO SCALE
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
PC PLUMBING CONTRACTOR
RA RETURN AIR
RDL ROOF DRAIN LEADER
RE:REFER TO
SA SUPPLY AIR
SDL STORM DRAIN LEADER
SS SANITARY SEWER
SWR SNOWMELT WATER RETURN
SWS SNOWMELT WATER SUPPLY
V VENT
VTR VENT THROUGH ROOF
WCO WALL CLEANOUT
W WASTE
WB WET BULB TEMPERATURE
TEMPERATURE SENSOR
PRESSURE SENSOR
CARBON DIOXIDE SENSOR
T
P
C
VIBRATION ISOLATOR
COLD WATER - FILTERED F
MODEL
BOILER SCHEDULE
TAG
BL-1
AREA SERVED
SNOW MELT
MANUFACTURER
LAARS NTH 850
V/PH/HZ
115/1/60
POWER REQUIRED
INPUT
MBH
WATER, STAINLESS STEEL, 95.7% EFFICIENCY
TYPE
578
FLOW/ P
MBH
553 43
GPM CONC.
FLUID
40
FT
10 SNOW MELT CONTROLLER
FLA
7.4
CONTROLS
1, 2
WEIGHT
LBS
503
NOTES
OUTPUT
BL-2 BUILDING MUA HEAT TRIANGLE TUBE SOLO 110 115/1/6074.8 71 8 40-INTEGRAL CONTROLLER-103 1, 2
AIR COOLED CONDENSING UNIT SCHEDULE
MANUFACTURER
CU-1
CU-3
CU-2
TAG
TRANEFR-1
FR-3
FR-2 TRANE
TRANE
FURNACE
37604TTX8060A1000B
MODEL
208-230/1/60-
AMBIENT
°F
POWER REQUIRED
V/PH/HZ MCA
CONTROLS
60 RE: SPECIFICATIONS
MOCP
2, 3332
2, 3
2, 3
WEIGHT
LBS NOTES
CONTROLS
MANUFACTURERTAGAREA SERVED
DUCT HEATING COIL SCHEDULE
MODEL
CFM NOTES / ACCESSORIESLBS
WEIGHTCAPACITY
MBH
EAT
°F
EWT
°FROWS
AIR DIFF
PRESSURE
IN. W.C.
WATER
FLOW
GPM
WATER DIFF
PRESSURE
FT
RUNOUT
PIPE SIZE
INCH
TYPE SIZE
INCHES
Cv
H E A T I N G C O N T R O L V A L V E
REFER TO SPECIFICATIONSHC-1 ERV-1 TRANE DT0B09012 --0.53-WAY BALL1/20.80.151160407.2270 -
INCHES
12 X 9
W X H
SIZE
FOOT
110
PER
FINS
MANUFACTURER
ENERGY RECOVERY VENTILATOR SCHEDULE
ERV-1
TAG AREA SERVED
FR-1 OFFICES RENEWAIRE (1) 1/2INDOOR, PARALLEL PLATES, SENSIBLE & LATENT
TYPE
EV 450 IN
MODEL
270
CFM
1.0
IN. W.C.
AIR FLOW POWER REQUIRED
SONES
SOUND
HP
MOTOR
-
dBA
115/1/60
V / PH / HZ
-15
MOCP
ACCESSORIES
LBS.
WEIGHTCONTROLS
320 1, 2, 3, 5
NOTES
ERV-2 FR-2 GROUND LEVEL RENEWAIRE (2) 3/4INDOOR, PARALLEL PLATES, SENSIBLE & LATENTHE1XRTV ECM 540 1.0 -208/230/1/60-15 320 1, 2, 3, 5
10.1
MCA
10.5
78
SENSIBLE
72
TOTAL
EFFECTIVENESS % (AHRI 1060)
74 68
61
TOTAL
58
WINTER SUMMER
ERV-2 FR-3 DORMITORY RENEWAIRE INDOOR, PARALLEL PLATES, SENSIBLE & LATENTEV 450 IN 330 1.0 -115/1/60-15 320 1, 2, 3, 510.1757059
REFER TO SPECIFICATIONSHC-2 ERV-2 TRANE DT0B12014 --0.53-WAY BALL1/2<1.01.50.0511604014.4540 -14 X 12 110
REFER TO SPECIFICATIONSHC-3 ERV-3 TRANE DT0B09012 --0.53-WAY BALL1/21.00.051160408.7330 -12 X 9 110
WATER, STAINLESS STEEL, 95% EFFICIENCY
PROP. GLY
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
NOMINAL
COOLING
CAPACITY
MBH
37604TTX8060A1000B208-230/1/60-60 RE: SPECIFICATIONS 332
37604TTX8060A1000B208-230/1/60-60 RE: SPECIFICATIONS 332
<1.0
<1.0
(1) 1/2
16.0
SEER
ARI
16.0
16.0
SCHEDULE NOTES:
1.LISTED PERFORMANCE IS AT 8000 FT ALTITUDE.
2.PROVIDE SPECIFIED EQUIPMENT OR APPROVED
EQUIVALENT BY OTHER MANUFACTURER.
3.LISTED PERFORMANCE IS AT SEA LEVEL.
4.PROVIDE WITH RETURN AIR DUCT SMOKE
DETECTOR TO SHUT DOWN FURNACE.
5.NORMALLY OPEN CONTROL VALVE.
6.BALANCE AIR VOLUME TO EQUAL KITCHEN
RANGE HOOD FAN EF-3.
7.REFER TO SPECIFICATIONS FOR REQUIRED
ACCESSORIES.
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
M001
MECHANICAL
LEGEND
2/27/2019
CHANGES COMPILED FOR
BUILDING DEPARTMENT-
08/13/2019
MANUFACTURER
EXHAUST FAN SCHEDULE
COOKEF-2
EF-3 RANGE HOOD WOLF
EF-1
TAG AREA SERVED
APPARATUS BAYS COOK
INLINE CENTRIFUGAL 115/1/605.05373 W0.375200
165SQN17D (VF)
-
-808331 600 --115/1/60--~3.0
1 HPCEILNG CENTRIFUGAL
TYPE
GC-188
MODEL
2700
CFM
0.75
IN. W.C.
AIR FLOW POWER REQUIRED
SONES
SOUND
HP OR W
MOTOR
69
dBA
208/3/60
V / PH / HZ
16.1 -
FLA
ACCESSORIES
<40
--
LBS.
WEIGHTCONTROLS
125 1, 2
1, 2
PROVIDED WITH HOOD BY G.C.
NOTES
RE: SPECIFICATIONS
RE: SPECIFICATIONS
CONTROLS
RE: SPECIFICATIONS
MANUFACTURER
FR-1
TAG
FR-3
FR-2
OFFICES
AREA SERVED
DORMITORY
GROUND FLOOR
FURNACE SCHEDULE
COOLING COIL
2200
2000
2000
BLOWER DATA
S9X2C100U4PSAA
S9X2C100D5PSAA
S9X2C100U4PSAA
MODEL
CFM
0.7 1
INCH W.C.
0.7
E.S.P.
0.7
1
1
HP MODEL
2TXCD061AC3CU
HEATING CAPACITY BLOWER MOTOR
OUTPUT (MINIMUM)
-
-
-
EAT db/wb °F
61
61
61
AHRI RATING
MBH
100
100
100
MBH
POWER REQUIRED
2 115/1/60
2
STAGES
2
115/1/60
115/1/60
V/PH/HZ
14.4
14.4
14.4
FLA
2, 3, 4
2, 3, 4
2, 3, 4
NOTES / ACCESSORIES
-
-
-
LBS
WEIGHT
GRILLES, REGISTERS AND DIFFUSERS SCHEDULE
TAG TYPESERVICE MOUNTING FINISHPATTERN
THROW
ACCESSORIES SIZESERIES #
KRUEGER
NOTES
100
HEATING CAPACITY
INPUT, MBH (SEA LEVEL)
SUPERIOR RADIANT
INFRARED HEATER SCHEDULE
106, 107
AREA SERVED
IR-1
TAG MANUFACTURER
UX-100 40FT U-TUBE
MODEL
LOW INTENSITY TUBULAR
TYPE
THERMOSTAT1
HEATING STAGES
1.0115/1/60
V / PH / HZ FLA
POWER REQUIRED
CONTROLS NOTES
TUBE LENGTH = 40 FT. NOTES 2, 3
175SUPERIOR RADIANT108-111IR-2 & IR-3 UX-175 60 FT U-TUBE THERMOSTAT11.0115/1/60
WEIGHT
LBS
277
205
LOUVER SCHEDULE
TAG TYPESERVICE MOUNTING FINISH ACCESSORIES SIZEMODEL NOTES
RELIEF & EXHAUST AIRLR-1 DRAINABLE STATIONARY LOUVER WALL ELF6350DMPCOLOR CHOSEN BY ARCHITECT RE: SPECIFICATIONS AS NOTED ON PLANS 2, 3
RUSKIN
INCH W.C.
0.10"WC @ 900 FT/MIN
PRESS. DROP
OZ./FT FREE AREA
< 0.18 @ 1250 FT/MIN
WATER ENTRY
2
SINGLE-STAGE IN-LINE
PUMP SCHEDULE
TAG
PC-1
PC-3
SERVICE
SNOW MELT BOILER BL-1
MANUFACTURER
GRUNDFOS
GRUNDFOS
MODEL
TP 32-80/2
POWER REQUIRED
V/PH/HZFT
TYPE
GPM
43
FLOW AND TDH
CONC.
40 3450
RPM
MOTOR
17 0.5 HP
MOTOR
HP OR W
WEIGHTCONTROLS
FLA
7.4 RE: SPECIFICATIONS
NOTES
1, 2
LBS
58
CANNED ROTOR IN-LINEUPS 32-80 F 115/1/608.2 40 -21 280 W -
1, 2
-
ANTIFREEZE ADDITIVE
TYPE
PROP GLY
PROP GLYBUILDING HEAT
CONTROLSMANUFACTURER
CH-1
TAG
STAIR 303
AREA SERVED
TRANE
FAN COIL AND CABINET HEATER SCHEDULE
B L O W E R
FFFB0301
MODEL
CFM INCH W.C.
E.S.P.HP
1, 2, 5
NOTES / ACCESSORIES
-
LBS
WEIGHTCAPACITY
MBH
EAT
°F
EWT
°F
ROWS AIR DIFF
PRESSURE
IN. W.C.
WATER
FLOW
GPM
WATER DIFF
PRESSURE
FT
RUNOUT
PIPE SIZE
INCH
TYPE SIZE
INCH
Cv
H O T W A T E R C O I L H E A T I N G C O N T R O L V A L V E
DRIVE
POWER
V/PH/HZ
11/23-WAY ZONE1/25.91.0-21406010.0115/1/60DIRECT0.130-300
SUPPLY SA-1 DIFFUSER, ROUND NECK, SINGLE FACEPLATE CEILING, T-BAR PLQ-23BRITISH WHITE4-WAY -AS NOTED ON PLANS STEEL. NOTE 2
SUPPLY SA-2 AIR FOIL BLADES, 3/4" CENTERS, VERTICAL FRONT, DOUBLE DEFLECTION SIDEWALL AF880V-F22ADJUSTABLE -STEEL, 1-1/4" FRAME. NOTE 2BRITISH WHITE AS NOTED ON PLANS
SA-3 SUPPLY
SA-4
HARD CEILING, PLASTER FRAMESUPPLY SA-5 DIFFUSER, ROUND NECK, SINGLE FACEPLATE PLQ-23-OBDBRITISH WHITE4-WAY PLASTER FRAME, DAMPER AS NOTED ON PLANS STEEL, LAY INTO 12"x12" PLASTER FRAME. NOTE 2
CEILING, T-BARRETURN RA-1 GRILLE, 1/2" CUBE CORE EGC5-F22BRITISH WHITEN/A -AS NOTED ON PLANS ALUMINUM. NOTE 2
STEEL, HORIZONTAL FIXED, 1-1/4" FRAME. NOTE 2RETURN RA-2 AIR FOIL BLADES, 3/4" CENTERS, 45° ANGLE SIDEWALL AFCS80-F22BRITISH WHITEN/A -AS NOTED ON PLANS
EXHAUSTEA-1
SPLIT SYSTEM SCHEDULE
SS-1 DAIKIN FTXS09DVJU / RXS09DVJU
AREA SERVEDTAG MANUF.MODEL
8.5 10 208-230/1/60 5 15 WIRED T'STAT OUTDOOR = 74, INDOOR = 17 2, 4
NET TOTAL
COOLING CAP.
MBH (SEA LEVEL)
HEATING CAP.
MBH
POWER REQUIRED
V/PH//HZ MOCP
UNITUNIT
MCA
CONTROLS WEIGHT
LBS
NOTES
211 I.T.
APPARATUS BAYS
ALUMINUM, HORIZONTAL 35° BLADES, 1/2" CENTERS. NOTE 2GRILLE, SIDEWALL, 35° DEFLECTION.HARD CEILING OR DUCT S585HBRITISH WHITEN/A -AS NOTED ON PLANS
CURVED INDIVIDUALLY ADJUSTABLE BLADES CEILING, T-BAR 180-F231-WAY BRITISH WHITE OBD AS NOTED ON PLANS STEEL, 24"x12" LAY-IN PANEL. NOTE 2SUPPLY
SUPPLY DIFFUSER, RECTANGULAR NECK, BEVELED FRAME DUCT SHPC-F21BRITISH WHITE4-WAY OBD AS NOTED ON PLANS STEEL, ADJUSTABLE VERTICAL THROW. NOTE 2
DUCT OR GYPGRILLE, 1/2" CUBE CORE EGC5-F22BRITISH WHITEN/A -AS NOTED ON PLANS ALUMINUM. NOTE 2RETURN RA-3
EXHAUSTEA-2 CEILING, T-BARGRILLE, 1/2" CUBE CORE EGC5-F22BRITISH WHITEN/A -AS NOTED ON PLANS ALUMINUM. NOTE 2
FC-1 KITCHEN MAKEUP AIR TRANE BCHD024A2**--M02Z000--BB-1, 2, 5, 618021/23-WAY BALL3/42.43.90.284140-1513.3115/1/60DIRECTECM 1/2 0.75500-600
SUPPLY SA-6 HEAVY DUTY, SINGLE DEFLECTION, HORIZONTAL BLADES SIDEWALL 480HBRITISH WHITEADJUSTABLE -AS NOTED ON PLANS STEEL, BLADES ON 1/2" CENTERS, 1 1/2" FRAME. NOTE 2
LOW INTENSITY TUBULAR TUBE LENGTH = 60 FT. NOTES 2, 3
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
RE: SPECIFICATIONS
CANNED ROTOR IN-LINECP-1 DOMESTIC HW RECIRC GRUNDFOS UP15-10B5/LC 115/1/602--4.3 1/25 HP -1, 2-NONE
RE: SPECIFICATIONS
INLINE CENTRIFUGAL
SUPPLY SA-7 AIR FOIL BLADES, 3/4" CENTERS, VERTICAL FRONT, DOUBLE DEFLECTION SIDEWALL AF880V-F22-OBDADJUSTABLE OBD STEEL, 1-1/4" FRAME. NOTE 2BRITISH WHITE AS NOTED ON PLANS
TRANE
TRANE
TRANE 2TXCD061AC3CU
2TXCD061AC3CU15
15
15
MOCP
0.35
0.30
0.30
AIR PRESS DROP
INCH W.C.
PC-4 GRUNDFOS CANNED ROTOR IN-LINEUPS 32-80 F 115/1/608.2 40 -21 280 W --PROP GLYBUILDING HEAT RE: SPECIFICATIONS
1, 2
SINGLE-STAGE IN-LINEPC-2 SNOW MELT SLAB GRUNDFOS TP 32-160/2 43 40 345036 0.75 HP 9.6 RE: SPECIFICATIONS 1, 260PROP GLY
115/1/60
RE: SPECIFICATIONS
115/1/60
2, 7SP-1 HYDROMATIC SUBMERSIBLECSS-3V 115/1/6020--19 0.3 HP --NONEELEVATOR PIT RE: SPECIFICATIONS
SCHEDULE NOTES:
1.LISTED PERFORMANCE IS AT 8000 FT ALTITUDE.
2.PROVIDE SPECIFIED EQUIPMENT OR APPROVED
EQUIVALENT BY OTHER MANUFACTURER.
3.LISTED PERFORMANCE IS AT SEA LEVEL.
4.PROVIDE WITH RETURN AIR DUCT SMOKE
DETECTOR TO SHUT DOWN FURNACE.
5.NORMALLY OPEN CONTROL VALVE.
6.BALANCE AIR VOLUME TO EQUAL KITCHEN
RANGE HOOD FAN EF-3.
7.REFER TO SPECIFICATIONS FOR REQUIRED
ACCESSORIES.
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
M002
MECHANICAL
SCHEDULES
2/27/2019
CHANGES COMPILED FOR
BUILDING DEPARTMENT-
08/13/2019
A B C D E H I J
1
2
4
5
6
7
LOBBY
101
WOMEN
102
MEN
103
TRAINING
ROOM
104
ELEC.
105
APPARATUS
BAY #1
106
APPARATUS
BAY #2
107APPARATUS
BAY #3
108
APPARATUS
BAY #4
109
APPARATUS
BAY #5
110
APPARATUS
BAY #6
111
DECON
112
READY
ROOM
113
MEDICAL
STORAGE
114
FITNESS
115
STAIR
302
ELEVATOR
301
STAIR
303
3
STORAGE
116
F
0
G
GROUND LEVEL MECHANICAL PLAN
IR-1IR-2
IR-3
CH-1
UNDER STAIRS
SS-1
8'-0" AFF
COMBUSTION AIR AND EXHAUST
THROUGH WALL >10' HORIZONTALLY
FROM AIR INTAKE ABOVE WITH
CENTERLINE AT 13'-6" AFF (TYP OF 3)
CU-3
SA-2
12"x12"
430 CFM
20"x20" SA AND
RA THROUGH
FLOOR ABOVE
14"Ø RA UP THROUGH
FLOOR ABOVE
SA-1
14"Ø
735 CFM
SA-3
9"x9"
240 CFM
SA-3
9"x9"
230 CFM
SA-1
6"Ø
75 CFM
SA-5
6"Ø
50 CFM
SA-5
6"Ø
30 CFM
EA-1
6"x6"
70 CFM
EA-1
6"x6"
70 CFM
EA-1
6"x6"
40 CFM
0'8'
4'OARAEAFACU-2 CU-1
RA-2
18"x18"
RA-1
24"x24"
RA-3
10x10"
RA-3
10x10"
RA-1
12"x24"
SA-5
6"Ø
100 CFM
T
M
T
12"Ø
AT 12'-0" AFF
AT 12'-0" AFF
12"Ø SPIRAL10"Ø SPIRAL6"Ø SPIRAL
20"x20"
12"Ø
6"Ø SPIRAL
10"Ø SPIRAL
M
6"Ø SPIRAL
8"Ø SPIRAL
ERV-2
20"x20"
HC-2
12"Ø
14"x12"
EA-2
24"x12"
320 CFM
12"Ø EA AND OA
THROUGH FLOOR
ABOVE
6"Ø
6"Ø
T
SWSSWRSWSSWRSWSSWR
SWSSWR2"
PIPING THROUGH
FLOOR ABOVE
EF-1
13'-4" AFF
22"x22"
EA-1
36"x20"
SA-2
22"x26"
2700 CFM OA
17"x22" RADIUSED ELBOW
TO 17"x22" THROUGH
FLOOR ABOVE
28"x15" OA
EF-2
13'-4" AFF6"Ø EA
BDD
22"x26" BDD
VENT HOOD (TYP OF 3)
INTAKE HOOD (TYP OF 3)
ALL REFRIGERANT PIPING ON GALVANIZED STRUT
ANCHORED IN PLACE AND COVERED WITH 18 GAUGE
GALVANIZED HAT CHANNEL PROTECTIVE LID CAPABLE OF
WITHSTANDING HUMAN FOOT TRAFFIC
30 CFM
SA-1
14"Ø
735 CFM
RA-1
24"x12"
6"Ø
T
TT
RADIANT TUBE
CENTERLINE AT 12'-4" AFF RADIANT TUBE
CENTERLINE AT 12'-4" AFF
RADIANT TUBE
CENTERLINE AT 12'-4" AFF
12"Ø
4"Ø
UNDERCUT
8"Ø, Voa=185CFM
4"Ø, Voa=
35CFM
10"Ø, Voa=320CFM
14"x26" OA FROM
ABOVE TO 22"x26"
13'-4" AFF FACING DOWN
DIRECTING AIR EAST
PIPING THROUGH
STRUCTURE
REFRIGERANT PIPING
UP IN WALL TO NEAR
STRUCTURE ABOVE
REFRIGERANT PIPING
THROUGH FLOOR ABOVE
M
1/2" HWS AND
HWR ON WALL
BOLT CONDENSING UNIT TO
HOUSEKEEPING PAD IN FOUR PLACES (TYP)
12" LONG 4" FLEX DUCT
24" LONG TYPE B
4" FLEX VENT
12" LONG 4" FLEX DUCT
24" LONG TYPE B
4" FLEX VENT
12" LONG 4" FLEX DUCT
24" LONG TYPE B
4" FLEX VENT
1
233
4
HOUSEKEEPING PAD (TYP)
12"Ø
3/4" HWS AND HWR
FROM ABOVE
PROVIDE RESTRAINTS
ATTACHED TO WALL AND
ANCHOR SS-1 TO SHELF.
CARBON MONOXIDE DETECTOR
FOR EF-1 CONTROL AND
ALARM, ℄ AT 5'-0" AFF
AT 12'-0" AFF
AT 12'-0" AFF
1/2" HWS AND
HWR FROM ABOVE
10"Ø
SUPPORT ON TRAPEZE
WITH < 12" LONG RODS AND
SWIVELS AT ENDS OF RODS
12"Ø BYPASS
AND DAMPER
M
4
4
GENERATOR
INSTALL PIPING
NEXT TO WALL
17
KEYED NOTES
1.INSTALL TOP OF UNIT AT 2" BELOW JOISTS. HANG FROM JOISTS WITH RODS
AND B-LINE CHSCS SERIES ISOLATORS AT FOUR CORNERS. INSTALL STRUT
BRACING TO STRUCTURE IN NORTH-SOUTH AND EAST-WEST DIRECTIONS WITH
B-LINE SERIES CNNK PADS AT BRACE CONNECTION POINTS .
2.REFER TO IR-1 INFRARED HEATER SUPPORT DETAIL ON SHEET M301.
3.REFER TO IR-2 AND IR-3 INFRARED HEATER SUPPORT DETAIL ON SHEET M301.
4.SUPPORT ON TWO STRUT SPANNING ACROSS AND ANCHORED TO TWO
JOISTS. INSTALL B-LINE SERIES RM-D NEOPRENE MOUNTS ANCHORED TO FAN
AND STRUT.
NOTED OTHERWISE.
GENERAL NOTES APPLICABLE TO ALL MECHANICAL PLANS
THE MECHANICAL CONTENT OF THIS DRAWING IS DIAGRAMMATIC AND NOT
NECESSARILY TO SCALE.
THE CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS TO LOCATIONS OF
DUCTWORK, EQUIPMENT, PIPING, AND SUPPORTS IN ORDER TO COORDINATE
WITH BUILDING CONSTRUCTION AND WORK OF OTHER TRADES.
ALL BRANCH DUCTS SERVING ONE DIFFUSER OR EXHAUST GRILLE SHALL
INCLUDE A VOLUME DAMPER AT THE BRANCH DUCT POINT OF ORIGIN,
UNLESS THE GRILLE OR DIFFUSER HAS BEEN SPECIFIED TO INCLUDE A
BALANCING DAMPER.
BRANCH DUCTS SERVING SINGLE DIFFUSERS SHALL BE SIZED TO MATCH THE
DIFFUSER NECK SIZE UNLESS OTHERWISE INDICATED.
ALL FLOOR PENETRATIONS SHALL BE FINISHED WITH FIRE STOP MATERIALS
IN ACCORDANCE WITH THE SPECIFICATIONS.
INDICATED DUCT DIMENSIONS ARE SHEET METAL DIMENSIONS.
ROUND DUCTS ARE INDICATED USING SINGLE LINE.
REFER TO SCHEDULES AND SPECIFICATIONS FOR EQUIPMENT AND
MATERIALS OF CONSTRUCTION.
AIR VOLUME INDICATED FOR SA DIFFUSERS AND SA GRILLES INCLUDES AIR
FROM FURNACE AND VENTILATION AIR FROM ERV.
INDICATED MOUNTING HEIGHTS ARE TO BOTTOM OF EQUIPMENT UNLESS
NOTED OTHERWISE.
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
M101
GROUND LEVEL
MECHANICAL PLAN
PR#020 02/27/20194
17 PR#021 3/11/2019
RE: RFI-154. Per RFI-154 IR-1 is to
be reconfigured to be 20' long single
radiant tube with a 20' long reflector
installed on grid line E. No longer a
U-Tube.
08/13/2019
A B C D E H I J
1
2
4
5
6
7
WAITING
201
OFFICE
203
OFFICE
204
OFFICE
205
FLEX
206
MECH/ELEC
209
CORRIDOR
210
STOR.
213
OFFICE
212
CONFERENCE
214
LIBRARY /
REPORTS
215
CORRIDOR
220
UNIFORM
LOCKERS
221
LAUNDRY
222
CORRIDOR
224
SHOWER
225
SHOWER
226
SHOWER
227
BUNK RM
229
BUNK RM
230
BUNK RM
231
BUNK RM
232
STORAGE
228
3
TOILET
208
IT
211
DINING
217
DAYROOM
216
KITCHEN
218
MECH
223
F
PANTRY
219
STAIR
303
STAIR
302
ELEVATOR
301
0
G
DECK
233
UPPER LEVEL MECHANICAL PLAN
BL-1
LR-1
11'-11"x2'-9 3/4"
SS-1
LR-1
36"x132"
LR-1
36"x30"
4"Ø DRYER VENT
DUCT 36" AFF
14"Ø SPIRAL OA
THROUGH STRUCTURE
SA-2
16"x14"
710 CFM
SA-1
6"Ø
105 CFM
SA-1
8"Ø
135 CFM
SA-1
6"Ø
100 CFM
SA-1
6"Ø
110 CFM
SA-4
12"x6"
150 CFM
SA-4
20"x8"
315 CFM
SA-4
16"x8"
265 CFM
SA-2
24"x12"
910 CFM
SA-2
18"x12"
580 CFM
SA-1
6"Ø
100 CFM
SA-1
8"Ø
120 CFM
SA-1
6"Ø
100 CFM
SA-1
6"Ø
70 CFM
SA-1
6"Ø
80 CFM
14"Ø SPIRAL SA
THROUGH STRUCTURE
12"Ø SPIRAL RA
THROUGH STRUCTURE
12"Ø EA FROM
HOOD
0'8'
4'
PC-1
BL-2 COMBUSTION EXHAUST AND
AIR PIPING AT 7'-2" AFF. INSULATE
INDOOR COMBUSTION AIR PIPING.
BL-2
PC-3
EA-1
6"x6"
70 CFM
EA-1
8"x8"
70 CFM
EA-1
8"x8"
70 CFM
EA-1
8"x8"
70 CFM
OARA
EAFA
SA-2
14"x14"
170 CFM
12" SPIRAL RA
8"Ø, Voa=200CFM
FR-1
FR-2FR-3
DX-1
DX-2DX-3
ERV-1
AT FLOOR
SA-2
32"x24" AT 8" AFF
600 CFM
(2) 5"x14" DUCTS
DOWN IN WALL
BL-1 COMBUSTION EXHAUST AND
AIR PIPING AT 7'-2 AFF. INSULATE
INDOOR COMBUSTION AIR PIPING.
TA-1
6"Ø
TA-1
6"Ø
TA-1
6"Ø
RA-2
24"x18"
RA-1
24"x12"
15"x26"32"x24"
M
M
M
M
M
M
MM
ERV-3
HC-3
RA-1
24"x12"
50 CFM
RA-1
24"x12"
FC-1
M BDD
TA-1
6"Ø
RA-2
6"x6"
16"x16"
9"Ø
16"x15"M M M
12"Ø
M
(3) 3" COMBUSTION AIR AND
(3) 3" COMBUSTION EXHAUST
THROUGH JOISTS TO AND FROM
FURNACES. INSULATE INDOOR
COMBUSTION AIR PIPING.
MINIMIZE NUMBER OF ELBOWS.
PC-4
T T
T
T
T
T
T
T
M
8"Ø10"Ø
6"Ø, 75CFM
SA-1
6"Ø
80 CFM
SA-1
6"Ø
80 CFM
RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
9"Ø
8"Ø
5"Ø5"Ø
5"Ø
6"Ø
6"Ø
6"Ø
8"Ø 9"Ø
12"Ø
6"Ø
6"Ø
6"Ø
6"Ø
6"Ø
8"Ø
RA-2
14"x14"
8"Ø
8"Ø
6"Ø, Voa=100CFM
6"Ø 8"Ø
12"Ø
14"Ø RA
FROM BELOW
10"Ø SPIRAL RA
32"Ø SPIRAL EA
6"Ø SPIRAL FA
16"Ø SPIRAL SA
32"Ø SPIRAL OA
3
14"Ø SPIRAL SA
T
14"Ø SPIRAL OA
16"Ø SPIRAL
8"Ø
6"Ø
6"Ø
2" SWS AND SWR
THROUGH FLOOR
7"Ø
6"Ø
7"Ø
15"x5" ABOVE BEAM
10"Ø
7"Ø
EF-3
SUSPEND FROM JOISTS
SA-5
6"Ø
30 CFM
4"Ø
3"Ø, Voa=15CFM
10"Ø
3"Ø, Voa=25CFM
SA-7
10"x8"
150 CFM
10"Ø
3"Ø, Voa=25CFM
3"Ø, Voa=25CFM
3"Ø, Voa=15CFM
3"Ø, Voa=15CFM
3"Ø, Voa=15CFM
T
HC-1
LR-1
9'-1"x2'-9 3/4"
LR-1
8'-4"x2'-9 3/4"
LR-1
9'-9-1/2"x2'-9 3/4"
17"x22" EA THROUGH FLOOR
BELOW, TRANSITION TO 36"x30"
INTO LOWER 30" OF LOUVER
HWS
HWR
HWS
HWR
HWSHWRHWRHWSHWR
HWS
12"Ø
14"x26"
14"x26" THROUGH
FLOOR BELOW
36"x30" TO 36"x26"
1
2
4
5
6
7
20"x18" RA
20"x18" SA
10'-6" AFF
18"Ø
5"Ø OA
REFRIGERANT PIPING
FROM BELOW TO DX COILS
10
8HWRHWS RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
RA-1
24"x12"
RANGE HOOD
PC-2
COORDINATE LOCATION OF
FURNACES WITH STRUCTURE
ABOVE AND BELOW
11
11
12
ANCHOR TO WALL PER
BL-2 INSTALLATION
INSTRUCTIONS
ATTACH BL-1 TO
HOUSEKEEPING PAD WITH
3/8" CONCRETE ANCHORS
12"Ø
1/2" HWS AND HWR DOWN IN
WALL THROUGH FLOOR
36"x30" TO UPPER 30" OF
LOUVER FOR EF-3 AND ERV-3 EA
10"Ø
3
9
14
13
11
(3) ZONE CONTROLLERS
14"x11"
HWSHWR
COVER NO AIRFLOW AREAS
WITH SHEET METAL
72"x34"x34"
60"x34"x34"
EA-2
12"x24"
120 CFM
20"x20" UP
BETWEEN JOISTS
24"x20" UP TO
BETWEEN JOISTS
1"
1/2"
1"
1"
1"
3/4"
M
M
15
151634"x40" OA DOWN
32"x40" EA UP
32"x24"
10"Ø SLEEVE AROUND COLUMN
SEALED TO WALLS OF PLENUM.
INSULATE SLEEVE WITH 2"
THICK DUCT WRAP.
AIR INTAKE >10FT EAST
OF IR-1 COMBUSTION
EXHAUST BELOW
NO FLEXIBLE DUCT SHALL BE USED AS
PART OF FR-3 AND ERV-3 SYSTEM. ALL
BRANCH DUCTS TO GRILLES AND
DIFFUSERS ASSOCIATED WITH FR-3 AND
ERV-3 SHALL BE GALVANIZED SHEET METAL
OF NO LESS THAN 26 GAGE THICKNESS.
7"Ø
6"Ø
9"Ø
10"Ø 7"Ø RA
NO FLEXIBLE DUCT SHALL BE USED ABOVE
OFFICES 203, 204, 205 AND FLEX 206. ALL
BRANCH DUCTS TO GRILLES AND DIFFUSERS
SHALL BE GALVANIZED SHEET METAL OF NO
LESS THAN 26 GAGE THICKNESS.
7"Ø
6
6
14"x9" OD, 12"x7" ID
DUCTBOARD SOUND ELBOW
IN WALL ABOVE CEILING
18"
6
KEYED NOTES
1.12"Ø EA THROUGH FLOOR BELOW.
2.12"Ø OA THROUGH FLOOR BELOW.
3.6"Ø EA FROM TOILET 208 TO ERV-1 RA INLET.
4.20"x18" EA ABOVE 20"x18" OA SERVING FR-1.
5.20"x18" EA ABOVE 20"x18" OA SERVING FR-3.
6.20"x18" OA SERVING FR-2.
7.20"x18" EA SERVING FR-2.
8.12"x9" FRESH AIR FROM ERV-1 THROUGH HC-1 AND UP TO 11'-6" AFF.
9.10"Ø EA FROM ERV-1 TO EA MAIN.
10.3/4" HWS AND HWR DOWN THROUGH FLOOR.
11.HANG FROM JOISTS WITH RODS AT FOUR CORNERS. INCLUDE B-LINE CHSCS
SERIES ISOLATORS AND STRUT BRACING TO STRUCTURE IN NORTH-SOUTH
AND EAST-WEST DIRECTIONS.
12.SUPPORT WITH FOUR B-LINE SERIES RM-D NEOPRENE MOUNTS ANCHORED
TO ERV AND FLOOR.
13.10"Ø RA TO ERV-1.
14.10"Ø OA TO ERV-1.
15.12"Ø BYPASS DAMPER.
16.40"x18" EA ABOVE AND 40"x18" OA BELOW.M102
UPPER LEVEL
MECHANICAL PLAN
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
PR#020 02/27/20194
PR#025 04/11/20195
RFI#130 05/01/20196
Per RFI-124 FCI suggests roughing in for a
destratification fan to be hung from structure at
the second level above Lobby 101, so if in the
event AAD would like to
have a destratification installed in the future,
the installation of the fan would be less
intrusive. Additionally the conduit and
j-box that would serve this fan could be painted
during the current project and would not stand
out or have to be painted if in fact a fan was
added in the future. This rough-in location for
a future destratification fan in the lobby is
acceptable.
Per RFI-131 It was confirmed
that the combustion air and
combustion exhaust piping
cannot be routed through the
roof due to snow accumulation.
Per the installation instructions
the piping length is an
acceptable length for the given
furnace. The piping must have
downward slope toward the
furnace in order to return
condensate to the furnace or
indoor disposal. If condensate
discharfes from the piping the
snorkel option shown in the
installation instructions will be
nevessary
RE: RFI-168. Per RFI-168 the duct shown
on the drawings will be removed and a 6"
duct will penetrate the west wall and
transition to a 12" above the Uniform
Lockers ceiling.
08/13/2019
MECHANICAL SITE PLAN
SNOW MELT MANIFOLDS AND
ENCLOSURE FOR (11) LOOPS (#1 - #11)
0'16'
8'
2" SWS AND SWR PRE-
INSULATED hePEX TUBING AT
24" BELOW FINISHED GRADE
CABLE TO SNOW MELT
CONTROLLER IN MECH 223
SNOW / ICE /
TEMPERATURE SENSOR
3/4" hePEX TUBING
SPACED AT 9" O.C.
ENCLOSURE WITH SNOW MELT
MANIFOLDS FOR (10) LOOPS
(#12 - #21) AND 2" BALL VALVES
ON SWS AND SWR TO
MANIFOLDS FOR LOOPS #1 - #11
LOOP #1
LOOP #21
SNOW TUBING MELT LOOPS
I.D.LENGTH, FT.FLOW, GPM
1 284 2.31
2 283 2.30
3 248 2.02
4 239 1.94
5 233 1.89
6 230 1.87
7 227 1.85
8 226 1.84
9 225 1.83
10 225 1.83
11 225 1.83
12 210 1.71
13 208 1.69
14 206 1.67
15 204 1.66
16 202 1.64
17 201 1.63
18 202 1.64
19 204 1.66
20 206 1.67
21 207 1.68
EMBED TUBING IN
CONCRETE UNDER
TRENCH DRAIN. RE: CIVIL
290' LOOP #22
290' LOOP #23
ENCLOSURE WITH SNOW MELT MANIFOLDS
FOR (2) LOOPS (#22 AND #23) AND 1" BALL
VALVES ON SWS AND SWR TO MANIFOLDS.
ALIGN SE CORNER WITH END OF WALL.
1" SWS AND SWR PRE-
INSULATED hePEX TUBING AT
24" BELOW FINISHED GRADE
LOOPS #1 - #11 SHALL BE NORTH OF
PROPERTY LINE AND LOOPS #12 - #21
SHALL BE SOUTH OF PROPERTY LINE
2" SWS AND SWR PRE-
INSULATED hePEX
TUBING AT 24" BELOW
FINISHED GRADE
20"x30"
18"x20"
FR-3
WAFFLE PAD AT EACH CORNER,
MASON SUPER W
DX COIL
DX COIL
DX COIL
FR-1
30"x30"x2" FILTER
30"x30"x2" FILTER
30"x30"x2" FILTER
FR-2
20"x30"
20"x30" RA
21"x22"
20"x25"
WAFFLE PAD AT EACH CORNER,
MASON SUPER W
20"x25"
18"x22" MA
20"x20" SA AND RA
FURNACE SYSTEMS NORTH ELEVATION
0'8'
4'
20"x18" OA
20"x18" EA
20"x18" EA
20"x18" OA
20"x18" EA
20"x18" OA
TRANSITION
16"x25"16"x25"
RA DUCT FOR FR-3
NOT SHOWN
14"Ø RA
TRANSITION
1243 0
EA
FARA
OA
ANCHOR FURNACE TO
WALL STUDS WITH STRUT
AND B-LINE SERIES RM
NEOPRENE MOUNTS
EA MAIN
FR-1
1243 0
ANCHOR FURNACE TO
WALL STUDS WITH STRUT
AND B-LINE SERIES RM
NEOPRENE MOUNTS
FR-2
1243 0
ANCHOR FURNACE TO
WALL STUDS WITH STRUT
AND B-LINE SERIES RM
NEOPRENE MOUNTS
FR-3
OA MAIN
M201
MECHANICAL SITE
PLAN, SECTIONS,
AND ELEVATIONS
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
FR-1 SYSTEM SECTION FR-2 SYSTEM SECTION FR-3 SYSTEM SECTION
0'8'
4'
0'8'
4'
0'8'
4'
2/27/2019
CHANGES COMPILED FOR
BUILDING DEPARTMENT-
Revised per ASI-005
Revised per PR-005
08/13/2019
BOILER PIPING DETAIL
NO SCALE
PRESSURE GAUGE THERMOMETER
AIR SEPARATOR
WITH VENT
VIBRATION ISOLATOR
1" HWS
1" HWR
1" HWS
1" HWS
GAS
RELIEF VALVE,
PIPE TO FLOOR
DRAIN
P-T PORT
FAN COIL MOUNTING DETAIL
NO SCALE
FAN COIL
CONDENSATE DRAIN PIPING
WITH TRAP AND CLEANOUT
FITTING FOR UNITS WITH
COOLING COIL
VIBRATION ISOLATORS
AND THREADED RODS
FLEXIBLE DUCT
CONNECTION ON SUPPLY
AND RETURN CONNECTIONS
IN-LINE PUMP DETAIL
NO SCALE
SHUTOFF VALVE
STRAINER
SHUTOFF VALVE
PRESSURE GAUGE
FLEXIBLE PIPE
CONNECTION
FLEXIBLE PIPE
CONNECTION
CHECK VALVE
PUMP
PIPE SUPPORT
PIPE SUPPORT
SUPPORT PUMP UNDER
CENTER OF GRAVITY
DUCT MAIN
HARD ROUND DUCT
HARD ELBOW (TYPICAL)
CEILING GRILLE INSTALLATION DETAIL
BRANCH RETURN DUCT AND
NO SCALE
CEILING
1" DUCTBOARD BOX OR
SHEETMETAL PLENUM
WITH DUCTLINER
FLEX DUCT,
< 3 FT LONG
CEILING GRILLE
PAINT INTERIOR
FLAT BLACK
SPIRAL DUCT AND
SUPPORT DETAIL
NO SCALE
THREADED ROD ANCHORED
TO STRUCTURE ABOVE, < 12" LONG.
NUTS AND
WASHERS ABOVE
AND BELOW BAND
GALVANIZED STEEL BAND
ENCIRCLING DUCT
SUPPLY DUCT,
ROUND SPIRAL
1 1/2"
CEILING
DIFFUSER OR
REGISTER
FLEX DUCT,
MAXIMUM 3 FT LONG
HARD ELBOW
HARD ROUND DUCT
DUCT MAIN
SPIN-IN FITTING WITH
BALANCING DAMPER
BRANCH SUPPLY DUCT
INSTALLATION DETAIL
NO SCALE
BRANCH SUPPLY DUCT
INSTALLATION DETAIL
HARD ROUND DUCT
HARD ELBOW
FLEX DUCT, MAXIMUM
3 FT LONG
DIFFUSER OR
REGISTER CEILING
NO SCALE
FC-1, HC-1, HC-2, AND HC-3 HEATING COIL
NO SCALE
MIXING VALVE PIPING SCHEMATIC
OUTLET
INLETHWS
HWR C
NC
NO
HEATING
COIL
P-T PORT (TYPICAL)
CALIBRATED BALANCING
VALVE
MANUAL AIR VENTCONTROL VALVE
BYPASS VALVE WITH
MEMORY STOP
SNOW MELT BOILER PIPING DETAIL
NO SCALE
PRESSURE GAUGE
HOUSEKEEPING PAD
THERMOMETER
1-1/4" VIBRATION ISOLATOR
PUMP
GAS
RELIEF VALVE,
PIPE TO FLOOR
DRAIN
P-T PORT (TYP)
2" SWR
2" SWS TO AND SWR FROM
SNOW MELT TUBING MANIFOLDS
1/2" FPT FOR TEMPERATURE
SENSOR WELL (TYP)
PC-1
T
T
T
SLAB MOISTURE AND
TEMPERATURE SENSOR
ET-1
EXPANSION TANK
2" SWS
2"
2"
2"
2"2"
PC-2
T
PROPYLENE GLYCOL
SOLUTION FEEDER SYSTEM
1/2"
AS-1
PC-3
PC-4
ET-2
EXPANSION TANK
BL-2
<12"
AS-2
DIVERTING VALVE PIPING SCHEMATIC
CH-1 HEATING COIL
NO SCALE
OUTLET
INLET
HWS
HWR
C
NC
NO
HEATING
COIL
BALANCING VALVE
P-T PORT (TYP.)
BOILER PRIMARY LOOP
PIPING SHALL BE COPPER
PROPYLENE GLYCOL
SOLUTION FEEDER SYSTEM
1/2"
AS-2
AIR SEPARATOR
WITH VENT
NOTE: THIS DETAIL IS ONLY FOR SNOWMELT
TUBING INSTALLATION AND IS NOT INTENDED
TO INDICATE SLAB CONSTRUCTION DETAILS.
WIRE TIES TO MESH
OR REBAR OR
PLASTIC STAPLES
INTO INSULATION
NO SCALE
TUBINGCONCRETE SLAB
SLAB INSULATION
BASE MATERIAL
UNDERSLAB INSULATION DETAIL
SNOWMELT TUBING WITH
EDGE INSULATION
NO SCALE
IN RECESSED ENCLOSURE DETAIL
SNOWMELT MANIFOLD
SWIVEL FITTING AT ATTACHMENT
TO BUILDING STRUCTURE
ATTACH TO BUILDING
STRUCTURE
DUCT SUPPORT STRAPS < 12" LONG
ATTACHED TO STRUCTURE ABOVE
DUCT SUPPORT STRAPS < 12" LONG
ATTACHED TO STRUCTURE ABOVE
DUCT SUPPORT STRAPS < 12" LONG
ATTACHED TO STRUCTURE ABOVE
CROSS BRACE IN
TWO DIRECTIONS
CONTROL VALVE
C-TYPE BEAM CLAMPS AND LARGE
FLANGE CLAMPS SHALL BE EQUIPPED
WITH RESTRAINING STRAPS.
C-TYPE BEAM CLAMPS AND LARGE
FLANGE CLAMPS SHALL BE EQUIPPED
WITH RESTRAINING STRAPS.
1" HWS
SF-2
SF-1
BL-1
BYPASS VALVE WITH
MEMORY STOP
DUCT MAIN
SPIN-IN FITTING WITH
BALANCING DAMPER
DUCT MAIN
HARD ELBOW (TYPICAL)
AND CEILING GRILLE INSTALLATION DETAIL
FR-3/ERV-3 SYSTEM RA AND EA BRANCH DUCT
NO SCALE
CEILING
SHEETMETAL PLENUM
WITH DUCTLINER
SHEET METAL DUCT
26 GAGE OR HEAVIER
PAINT INTERIOR
FLAT BLACK
CEILING
DIFFUSER OR
REGISTER
HARD ELBOW
DUCT MAIN
SPIN-IN FITTING WITH
BALANCING DAMPER
FR-3/ERV-3 SYSTEM BRANCH
SA DUCT INSTALLATION DETAIL
NO SCALE
DUCT SUPPORT STRAPS < 12" LONG
ATTACHED TO STRUCTURE ABOVE
DUCT SUPPORT STRAPS < 12" LONG
ATTACHED TO STRUCTURE ABOVE
SHEET METAL DUCT
26 GAGE OR HEAVIER
RETURN OR EXHAUST
CEILING GRILLE
5
STRUT ANCHORED
TO JOISTS
TUBULAR
INFRARED HEATER HANGER PROVIDED
WITH HEATER
THREAEDED EYE BOLT
WITH NUTS ABOVE AND
BELOW STRUT
STRUT ANCHORED
TO JOISTS
TUBULAR
INFRARED HEATER HANGER PROVIDED
WITH HEATER
#2 CHAIN (TYP)
45°
SNAP HOOKS (TYP)
HANGER PROVIDED
WITH HEATER
#2 CHAIN ATTACHED TO CENTER
OF HEATER HANGER (TYP)
SNAP HOOKS AT
BOTH ENDS (TYP)
BOTTOM CHORD OF JOIST
TUBULAR
INFRARED HEATER
DIAGONAL BRACING TYPICAL FOR
SUPPORTS AT FOUR END HANGERS
STRUT ANCHORED TO JOIST
IR-2 AND IR-3 INFRARED
SCALE: 1/2" = 1'-0"
IR-1 INFRARED HEATER SUPPORT DETAIL
SOUTH ELEVATION WEST ELEVATION
SCALE: 1/2" = 1'-0"
HEATER SUPPORT DETAIL
SOUTH ELEVATION
45°
EXPANSION JOINT
TUBING
HEATED OUTDOOR SLAB
BASE MATERIAL REINFORCING
MESH OR REBAR
SNOWMELT TUBING INSTALLATION AND
EXPANSION JOINT INTERFACE DETAIL
NO SCALE
WIRE TIES TO MESH
OR REBAR OR
PLASTIC STAPLES
INTO INSULATION
NOTE: THIS DETAIL IS ONLY FOR SNOWMELT
TUBING INSTALLATION AND IS NOT INTENDED
TO INDICATE SLAB CONSTRUCTION DETAILS.
LEGEND FOR CONTROLS DIAGRAMS
FOAM INSULATION, R10
RETURN MANIFOLD WITH LOOP
BALANCING VALVES, LOOP ISOLATION
VALVES, DRAIN AND VENT VALVE
SUPPLY MANIFOLD WITH
LOOP ISOLATION VALVES,
DRAIN AND VENT VALVE
SWR TO BUILDING
SWS FROM BUILDING
IRRIGATION VALVE BOX AND
LID PER SPECIFICATIONS. SET
IN GROUND WITH RIM 1" ABOVE
ADJACENT FINAL GRADE.
TUBING PENETRATING
SIDE OF BOX
SWS AND SWR WITH BALL
VALVES AND PIPING TO
NORTH MANIFOLDS.
M301
MECHANICAL
DETAILS
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
PR#025 04/11/20195
08/13/2019
T
PT HL
FM
T
DM
H
FR
TEMPERATURE SENSOR PROBE IN THERMAL WELL
TEMPERATURE SENSOR PROBE
CENTRIFUGAL PUMP
DIFFERENTIAL PRESSURE TRANSMITTER
3-WAY BALL VALVE AND ACTUATOR
AIR FILTER
AIR FLOW MEASUREMENT STATION
CENTRIFUGAL FAN
DAMPER AND ACTUATOR
2-WAY BALL VALVE AND ACTUATOR
HEATING OR COOLING COIL,
FR = FURNACE, DX = DX COOLING COIL
LEGEND FOR CONTROLS DIAGRAMS
VFDVARIABLE FREQUENCY DRIVE
AI DDC I/O (AI = ANALOG INPUT, AO = ANALOG OUTPUT,
BI = BINARY INPUT, BO = BINARY OUTPUT)
CURRENT SENSING SWITCHCSS
T TEMPERATURE CONTROLLER WALL MOUNTEDCO2CARBON DIOXIDE TRANSMITTER - WALL MOUNTED
OCCUPANCY SENSOR
C
CARBON DIOXIDE SENSOR - DUCT MOUNTED
MC MAGNETIC MOTOR CONTACTOR
MS MAGNETIC MOTOR STARTER
SC SOLID STATE SPEED CONTROL, LINE VOLTAGEHFRRA
TO EA MAIN DUCT
NO SCALE
FURNACE AND CONDENSING UNIT CONTROL DIAGRAM
T
EA
DUCT SMOKE DETECTOR
FROM OA MAIN DUCT OA
TAI
DM
CDXEA
VENTILATION AIR
TO ZONES
OA
RA
NO SCALE
ENERGY RECOVERY VENTILATOR CONTROL DIAGRAM
DM DM
EF
SF
CONTROL WITH FANS
HX
NO SCALE
INFRARED HEATER CONTROL DIAGRAM
IR
HEATER
T
NO SCALE
FC-1 AND KH-1 CONTROL DIAGRAM
SW
SC
H
WTR
SAFROM OA MAIN
OA
DM
T
AI
SC
FC-1 KH-1
EF
T
AI
MC
BO
PC-2 PC-1
T
AI
T MOISTURE AND
TEMPERATURE SENSOR,
EMBEDDED IN SLAB
NO SCALE
SNOW MELT SYSTEM CONTROL DIAGRAM
BL-1
BOILER
FACTORY BOILER
CONTROLS
MC
SF-1
FEEDER
LOW PRESSURE CONTACTS
T
BOILER HWS SENSOR
B0
FIRE ENABLE
T
PC-3
NO SCALE
HYDRONIC HEATING SYSTEM CONTROL DIAGRAM
BL-2
BOILER
FACTORY BOILER
CONTROLS
MC
SF-2
FEEDER
LOW PRESSURE CONTACTS
T
BOILER HWS SENSOR
SC-1
SNOW MELT
CONTROLLER
MATAI TAITAI
TO ECONOMIZER
CONTROL MODULE
TO ZONE CONTROLLER
TO ZONE CONTROLLER
FROM ECONOMIZER
CONTROL MODULE AO
FAN CONTROL FROM
ZONE CONTROLLER
TO ECONOMIZER
CONTROL MODULE
BO
BO
HEAT STAGES FROM
ZONE CONTROLLER
BO
BO
BOCOOL STAGES FROM
ECONOMIZER CONTROL MODULE
CONDENSING
UNIT
BO
BOCOOL STAGES FROM
ZONE CONTROLLER
ECONOMIZER
CONTROL
MODULE
SA
DMFURNACE
ZONE
CONTROLLER
DM
THERMOSTAT,
ONE PER ZONE
DAMPER, ONE
PER ZONE
BYPASS DAMPER
STATIC PRESSURE
CONTROLLER
TIME
CLOCK
HWS
CONTROL WITH FANS
HWR
PC-4
BOILER HWR SENSOR
MC
AUTOMATIC ALTERNATING
PUMP CONTROL
STARTER?
STARTER?
FROM SC-1
TO SC-1 TO SC-1
AO
FIRE MODULATION
FROM SC-1
FROM SC-1
M401
CONTROLS
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
08/13/2019
>10'-0"
A B C D E H I J
1
2
4
5
6
7
LOBBY
101
WOMEN
102
MEN
103
TRAINING
ROOM
104
ELEC.
105
APPARATUS
BAY #1
106
APPARATUS
BAY #2
107APPARATUS
BAY #3
108
APPARATUS
BAY #4
109
APPARATUS
BAY #5
110
APPARATUS
BAY #6
111
DECON
112
READY
ROOM
113
MEDICAL
STORAGE
114
FITNESS
115
STAIR
302
ELEVATOR
301
STAIR
303
3
STORAGE
116
F
0
G
GROUND LEVEL PLUMBING PLAN
IR-3
FIRE SPRINKLER
MAIN RISER
MAIN WATER SERVICE
LV-1
LV-1
FD-1
2"
WC-1
WC-1
FD-1
2"
SK-1
MS-1
SK-2
TD-1
L=20'-0'
TD-1
L=20'-0'
TD-1
L=20'-0'
TD-1
L=20'-0"
TD-1
L=13'-4"
TD-1
L=13'-4"
SO-1
BELOW GRADE
(3) 2" V. COMBINE
AT 6" AFF.
4" W FROM
ABOVE
ES-1
FD-2
2"
GAS METER. CONNECTED
LOAD = 2442 MBH (SEA LEVEL).
SERVICE PRESSURE = 2 PSIG
SK-4
HB-2
60" AFF
HB-1
18" AFF
HB-1
18" AFF
6" FIRE AND DOMESTIC WATER
MAIN. INSTALL THRUST BLOCKS AS
DESCRIBED IN CIVIL DOCUMENTS.
RE: CIVIL FOR CONTINUATION
SP-1
4" BUILDING SEWER. RE:
CIVIL FOR CONTINUATION
GGGGGGG
1/2" GAS UP THROUGH
FLOOR ABOVE
3/4" (2 PSIG) GAS UP
THROUGH FLOOR ABOVE
3/4" LOW PRESSURE GAS
UP THROUGH FLOOR
1" HW AND 1-1/4"
CW UP THROUGH
FLOOR ABOVE
1/2" 2 PSIG GAS ABOVE SLAB TO
GENERATOR. PROVIDE BALL
VALVE AND PRV. INSTALL VALVES
AND GAS LINE ACCESSORIES
PROVIDED WITH GENERATOR.
0'8'
4'
FD-2
2"
1/4" HW UP THROUGH
FLOOR ABOVE
FS-1
3"
2" W BELOW
FLOOR
SP-1 INDIRECT
TO FS-1
2-1/2" CV,
3" WCO
3"
2-1/2" CV
4"
3"3"
3"3"3"3"
3"
3" SEWER. RE: CIVIL
FOR CONTINUATION
2-WAY COTG
2" CV, 2" WCO
G G
2"
3/4"
1-1/2"
1-1/4"1-1/4"
1/2" THROUGH
FLOOR ABOVE
1/2"
1-1/4" CW UP THROUGH
FLOOR ABOVE
3" W FROM
ABOVE, 4" WCO
1-1/2"
2-1/2"
2-1/2" V UP THROUGH
FLOOR ABOVE
WHA, PDI SIZE A
WHA, PDI SIZE B
1-1/4"
3"
3/4" GAS UP THROUGH
FLOOR ABOVE
IR-1
IR-2
2"
3/4" HWC UP THROUGH
FLOOR ABOVE
3/4"
1"
3/4"
RDL RDL RDL RDL
RDLRDLRDLRDLRDLRDL3"
3" RDL FROM DECK DRAIN
ABOVE (TYP OF 6)
3"
3"
3" RDL
BELOW FLOOR
3" RDL TO UNDERGROUND
STORM SEWER. RE: CIVIL FOR
DEPTH AND CONTINUATION.
2"
3" RDL DOWN
IN WALL
1/4"1/4"
1-1/2"
INSTALL ES-1
MIXING VALVE ON
WALL AT 8'-0" AFF
2"
1-1/2"
2" V UP THROUGH
FLOOR ABOVE
1-1/2"
2"COMBINATION WASTE
AND VENT SYSTEM
2" CV, 4" WCO
1-1/2" W AND V,
1-1/2" WCO
2" CO
4"4" WCO
FIRE DEPT. CONN.G3/4" (2 PSIG)
1/2" (2 PSIG)
BALL VALVE, PRV, AND TEES
(TYPICAL AT ALL PRV LOCATIONS)
3/4" (2 PSIG)
3/4" (2 PSIG)
G
3/4" (2 PSIG)1/2" (2 PSIG)
1/2" (2 PSIG)
1-1/4" (2 PSIG)
1/2" (2 PSIG)1/2" (2 PSIG)
BALL VALVES AT 8'-0" AFF
ON HW AND CW TO HB-2
1-1/4" (2 PSIG)
1/2" (2 PSIG)
1/2" (2 PSIG)
(2) 3/4" IRRIGATION SUPPLIES.
RE: LANDSCAPE DRAWINGS FOR
DEPTH AND CONTINUATION.2"
MINIMUM COVER 5 FT.
6'
6" PIPE THROUGH FLOOR
EWC-1
WATER FILTER
GLASS
FILLER
HR-1
80" AFF FFFF
FFFFFF1/2" THROUGH
FLOOR ABOVE
1/2"
1/2"
3/4"
F
1/2" THROUGH
FLOOR ABOVE
HB-2
60" AFF
HR-1
80" AFF
1/2" GAS UP THROUGH FLOOR
ABOVE TO OUTDOOR GRILLE
AND GAS SOLENOID VALVE WITH
3/4" ORIFACE AND 1/2"
CONNECTIONS CONTROLLED BY
ALERTING SYSTEM
1/2" GAS UP THROUGH
FLOOR ABOVE TO RANGE
AND GAS SOLENOID VALVE
WITH 3/4" ORIFACE AND 1/2"
CONNECTIONS CONTROLLED
BY ALERTING SYSTEM
3/4"
3/4"1"
G
G
PIPE PRV VENT TO ABOVE
MAXIMUM SNOW LEVEL
MANHOLES FLUSH
WITH FINISHED GRADE
3/4"
3/4" (2 PSIG)
GENERATOR
3/4" TYPE L COPPER
BETWEEN AND
THROUGH JOISTS
FLEX CONNECTOR
BALL VALVE DRAIN AT
BASE OF CA 3/4" RISERAIR
COMP
FEMALE QUICK CONNECT
ON WALL AT 8'-0" AFF
CA DROP TO QUICK
CONNECT, RE:
DETAIL 1 / P301
1/2" TYPE L COPPER
THROUGH JOISTS
1/2" TYPE L COPPER
THROUGH JOISTS
3/4" TYPE L COPPER
THROUGH JOISTS
CA CA CA CA CA CA CA CA CA CA
CACAREEL WITH 100' CA HOSE AT
80" AFF, REELCRAFT MODEL
81100 OLP OR EQUIVALENT.
FEED FROM 1/2" CA DROP
WITH BALL VALVE.
6
CA DROP TO QUICK
CONNECT, RE:
DETAIL 1 / P301
CA DROP TO QUICK
CONNECT, RE:
DETAIL 1 / P301
TEE TO FEMALE
QUICK CONNECTOR
TEE TO FEMALE
QUICK CONNECTOR
GENERAL NOTES APPLICABLE TO ALL PLUMBING PLANS
THE MECHANICAL CONTENT OF THIS DRAWING IS DIAGRAMMATIC
AND NOT NECESSARILY TO SCALE.
THE CONTRACTOR SHALL MAKE MINOR ADJUSTMENTS TO
LOCATIONS OF DUCTWORK, EQUIPMENT, PIPING, AND SUPPORTS IN
ORDER TO COORDINATE WITH BUILDING CONSTRUCTION AND WORK
OF OTHER TRADES.
REFER TO ARCHITECTURAL DRAWINGS FOR ALL FLOOR DRAIN,
FLOOR SINK, AND TRENCH DRAIN DIMENSIONED LOCATIONS.
INSTALL BALL VALVES ON WATER SUPPLY TO ALL HOSE BIBS AND
WALL HYDRANTS.
REFER TO SCHEDULES AND SPECIFICATIONS FOR EQUIPMENT AND
MATERIALS OF CONSTRUCTION.
JOINTS IN COMPRESSED AIR (CA) PIPING SYSTEM SHALL BE
SOLDERED OR THREADED.6
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
P101
GROUND LEVEL
PLUMBING PLAN
17 PR#021 3/11/2019
6 RFI 119 5/01/2019
Per RFI-077 (1) HB-1 to
be added in this location
as shown on A201.
08/13/2019
A B C D E H I J
1
2
4
5
6
7
WAITING
201
OFFICE
203
OFFICE
204
OFFICE
205
FLEX
206
MECH/ELEC
209
CORRIDOR
210
STOR.
213
OFFICE
212
CONFERENCE
214
LIBRARY /
REPORTS
215
CORRIDOR
220
UNIFORM
LOCKERS
221
LAUNDRY
222
CORRIDOR
224
SHOWER
225
SHOWER
226
SHOWER
227
BUNK RM
229
BUNK RM
230
BUNK RM
231
BUNK RM
232
STORAGE
228
3
TOILET
208
IT
211
DINING
217
DAYROOM
216
KITCHEN
218
MECH
223
F
PANTRY
219
STAIR
303
STAIR
302
ELEVATOR
301
0
G
DECK
233
UPPER LEVEL PLUMBING PLAN
FR-1FR-2FR-3
WC-2
SH-1
LV-2
WC-2
SH-1
LV-2
WC-2
SH-2
LV-2
WB-1
32" AFF
SK-3
WC-3
LV-3
4" W MAIN DOWN
TO GROUND LEVEL
FS-1
2"
FD-2
2"
HB-1
18" AFF
RANGE
FD-1
2"
2-1/2" CV
1-1/2" V
CONNECT HW AND W
FOR DISHWASHER
2" COMBINATION
DRAIN AND VENT
2" V AND 3" WCO3"
1/2" GAS
FROM BELOW
CW TO HB-1 WITH BALL
VALVE BELOW SINK
1/2" GAS
FROM BELOW
WB-3
32" AFF
DRYER
WASHER
1/2" HW AND CW
FROM BELOW
1/4" HW FROM
BELOW
1-1/4" CW AND 1"
HW FROM BELOW
WB-2
WB-2
WB-3
AT 8" AFF
2" CV, 2" WCO
1-1/2" V
0'8'
4'
SK-4
3/4" GAS
FROM BELOW
BL-2
1-1/4"1"
3/4"
MS-1
1"
1"
3"
3"
3" W DOWN
3" VTR
2-1/2" V FROM BELOW
UP TO 3" VTR
1/4" CW
1-1/4" CW
FROM BELOW
3"
2-1/2" FROM CV
FD-1
2"
WH-1 WH-2
G
BL-1
G
3/4" HWC
FROM BELOW
CP-1
GAS FROM BELOW
1-1/4"
3/4"
DD-1
3"
DD-1
3"
DD-1
3"
DD-1
3"
DD-1
3"
DD-1
3"
WATER HEATER CONCENTRIC
VENT FITTING AT 14'-0" AFF (TYP
OF 2). INSULATE INDOOR
COMBUSTION AIR PIPING.
2-1/2"
2-1/2"
2" V FROM
BELOW
2"
3" WCO
CO UNDER SINK
2" CV, 3" WCO
GAS GRILLE BALL
VALVE AND QUICK
CONNECT AT 18" AFF
3/4"1/2"
G G
3/4" GAS
FROM BELOW
3/4"
1/2" GAS AND
PRV FOR BL-2
SK-5
PIPE CONDENSATE DRAINS
FROM FURNACES AND DX
COILS TO FLOOR SINK
GLASS FILLER
WB-2
℄ 41" AFF
℄ 41" AFF
℄ 41" AFF
1/2" FILTERED CW
FROM BELOW
1/2" FILTERED CW
FROM BELOW
1/4"
1-1/2"
2"
1/2"1/2"
P102
UPPER LEVEL
PLUMBING PLAN
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
CONDENSATE
PIPING
CHANGED TO WC-3
PER PR-017.
Per RFI-072 LV-1 sink
to be used in 208.
RE: RFI-102. RFI-102
clarifies WB-1 & WB-3
RE: RFI-151. Per RFI-151
the shower enclosure will be
deleted and the walls will be
T2-4 and the floor will be tile
T-1.
RE: RFI-153. Per RFI-153 the
water heater vents are to
penetrate the west wall of the
building at 10' AFF (Upper
Floor)
08/13/2019
A B C D E H I J
1
2
4
5
6
7
3
F
0
G
ROOF PLUMBING PLAN
0'8'
4'
3" VTR
3" VTR
P103
ROOF PLUMBING
PLAN
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
C 2016 CHAMBERLIN ARCHITECTS05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
08/13/2019
1XP
TWO-WAY CLEANOUT TO GRADE DETAIL
FINISHED GRADE
THREADED CLEANOUT CAP
AND CLEANOUT FITTING
PIPE OF APPROPRIATE
LENGTH TO EXTEND TO
HORIZONTAL PIPING BELOW
HORIZONTAL WASTE PIPING
REQUIRING CLEANOUT
WHERE CLEANOUT IS NOT
INSTALLED IN CONCRETE
BY OTHERS, PROVIDE
SQUARE CONCRETE PAD
CLEANOUT TO GRADE (C.O.T.G.) DETAIL
cotg-detail.dwgNO SCALE
FINISHED GRADE
THREADED CLEANOUT CAP
AND CLEANOUT FITTING
PIPE OF APPROPRIATE
LENGTH TO EXTEND TO
HORIZONTAL PIPING BELOW
HORIZONTAL WASTE PIPING
REQUIRING CLEANOUT IF CLEANOUT IS AT UPPER
END OF LINE, THIS FITTING
IS 1/8 BEND INSTEAD OF TEE
WHERE CLEANOUT IS NOT
INSTALLED IN CONCRETE
BY OTHERS, PROVIDE 16"
SQUARE CONCRETE PAD
DISHWASHER WASTE CONNECTION DETAIL
NO SCALE
1 1/2" P-TRAP AND
WASTE PIPING
dishwasher.dwg
DISHWASHER WASTE HOSE
INSERTED 2" INTO OPEN
STAND-PIPE
COUNTER TOP ABOVE
DISHWASHER
OPEN WYE
8" MINIMUM
DISHWASHER WASTE HOSE
CLAMPED TO UNDERSIDE OF
COUNTER ABOVE
FLOOR CLEANOUT (F.C.O.) DETAIL
fco-detail.dwgNO SCALE
THREADED CLEANOUT CAP, CLEANOUT FITTING,
AND ACCESS COVER AS SPECIFIED. COVER
SHALL BE FLUSH WITH FINISHED FLOOR.
PIPE OF APPROPRIATE
LENGTH TO EXTEND TO
WASTE PIPING BELOW
FINISHED FLOOR
PIPING DETAIL
gas-water-htr-2.dwgNO SCALE
PIPE RELIEF
DISCHARGE TO
FLOOR DRAIN
T & P RELIEF
VALVE
DIELECTRIC UNIONS AT
WATER HEATER
CONNECTIONS
UNION
WATER HEATER
1" HW
3/4" HWC
1" CW
GAS SUPPLY
PIPING
DUAL GAS WATER HEATER
DRAIN VALVE,
PIPE TO FLOOR
DRAIN
SAND AND OIL INTERCEPTOR DETAIL
ANCHOR PIPING TO
GREASE INTERCEPTOR.
SEAL PIPE PENETRATIONS.
3" INLET
2" VENTS
FINISHED GRADE
NOT TO SCALE
CAST IRON MANHOLE COVER AND RING,
GASKETED, AIR TIGHT AND SECURED
WITH 5 SIDED FASTENERS (TYP. OF 2)
CLEANOUT
GRADE
CONCRETE MANHOLE
RINGS
3" OUTLET
INTERCEPTOR
VENTS UP INSIDE BUILDING
THROUGH ROOF. COMBINE
AT 6" AFF.
6"
>18">24"
4"Ø OPENING
CLEANOUT
VENT OUTSIDE OF
MANHOLES, NOT THROUGH
LIQUID LEVEL
SUMP PUMP DETAIL
NO SCALE
ALARM FLOAT
SUMP PUMP WITH
FLOAT SWITCH
SUMP BASIN
WASTE AND VENT PIPING
ROUTED AS SHOWN ON PLAN
GAS-TIGHT LID WITH
SEALED PENETRATIONS
POWER AND
ALARM CABLES
ELEVATOR PIT FLOOR
FLOOR DRAIN WITH
RUBBER TRAP SEAL
GAS-TIGHT INLET
VENT THROUGH ROOF DETAIL
NO SCALE
ROOF JACK RECOMMENDED BY ROOFING
MATERIAL MANUFACTURER OR SPECIFIED
BY ARCHITECT. FLASH AND SEAL PER
ARCHITECTURAL SPECIFICATIONS.
VENT PIPE, MINIMUM OF
3" PIPE SIZE
12" MINIMUM
ROOF
INSULATE 5 FT LENGTH
OF VENT BELOW ROOF
WATER SERVICE PIPING DETAIL
water-svc-2.dwgNO SCALE
PRESSURE GAUGE,
0-200 PSIG
PRESSURE
GAUGE, 0-100 PSIG
3/4" PRV SET
AT 70 PSIG
1-1/4" PRV SET
AT 65 PSIG
3/4"
3/4"
1-1/2
2"
2" RPZ BACKFLOW
PREVENTER ASSEMBLY. PIPE
RELIEF INDIRECT TO FS-1
PVC PIPE SLEEVE
AND MECHANICAL
SLEEVE SEAL (TYP)
4"
WATER METER
PROVIDED BY
UTILITY CO
WALL CLEANOUT (W.C.O.) DETAIL
wco-detail.dwgNO SCALE
CLEANOUT TEE WITH
CLEANOUT PLUG
WALL COVER AND
SCREW PER
SPECIFICATIONS
WALL
FLOOR
WASTE PIPE TO
BELOW FLOOR
WASTE OR VENT PIPING
IF APPLICABLE
FIRE SPRINKLER MAIN
RISER DEVICES. RE:
SPECIFICATIONS
FLOOR
CLOSED BYPASS VALVE.
REMOVE HANDLE.
CP-1
ET-3
ACID NEUTRALIZER
(TYP)
PIPE COMBUSTION
CONDENSATE TO
FLOOR DRAIN (TYP)
CO
1-1/2"1/2" FPT
BLOW-OUT
2" TO FIXTURES
WH-1 WH-2
3/4" COPPER
TO IRRIGATION
RE: LANDSCAPE DRAWINGS FOR
CONTINUATION AND BACKFLOW PROTECTION
WATER METER
PROVIDED BY
UTILITY CO
3/4"
WATER FILTER
SERVING EWC-1,
DF-1, GLASS FILLERS,
COFFEE, AND ICE
3/4"
3/4"
AQUASTAT
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
ALUMINUM 3-1/4" DEEP CHANNEL
WITHOUT HOLES, B-LINE MODEL
B11AL OR EQUIVALENT
INFRARED HEATER,
NOT PRESENT IN
ALL LOCATIONS
OPEN SIDE OF CHANNEL
FACING SOUTH
CONDUIT AND 200°C RATED
WIRING DEEP INSIDE CHANNEL
FOR ELECTRICAL DROP
1/2" COPPER COMPRESSED
AIR PIPING INSIDE CHANNEL
WIRING BOX FOR CORD
CONNECTION AT 7'-0" AFF
COMPRESSED AIR FEMALE 1/4"
INDUSTRIAL INTERCHANGE QUICK
CONNECT FITTING, AT 6'-8" AFF
ANCHOR CHANNEL TO STRUCTURE
ABOVE AND CROSS BRACE IN
NORTH-SOUTH AND EAST-WEST
DIRECTIONS TO PREVENT
CONTACT WITH HEATER
DETAIL 1 / P301 CA DROP ELEVATION
SCALE: 1/2" = 1'-0"
CORD FOR
BATTERY CHARGER
6
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
P301
PLUMBING DETAILS
2/27/2019
CHANGES COMPILED FOR
BUILDING DEPARTMENT-
6 5/01/2019RFI 119
08/13/2019
MS-1
SK-1
FD-2
SH-1
WC-1 WC-1 FD-1
LV-1
FD-1
LV-1
LV-2
FD-2WC-3
LV-2 SK-3
SH-1 WC-2
LV-2LV-2
SH-1 WC-2FD-1 MS-1 FD-1
SK-4 WB-1
FD-2
SK-4 SK-2
GROUND FLOOR LEVEL
UPPER FLOOR LEVEL
TD-1 FS-1TD-1TD-1TD-1TD-1TD-1
SO-14"W TO BUILDING SEWER
BEYOND FOUNDATION 3" W BEYOND FOUNDATION
WC-2
FD-2
SP-1
SOIL, WASTE, AND VENT FLATOMETRIC
NO SCALE
2-1/2" CV
2-1/2"
3"VTR
1-1/2"2" CV 2" CV
2-1/2"2-1/2"
2"2" CV
3"VTR
2-1/2"
2"2" CV
1-1/2"
1-1/2"1-1/2"2-1/2"
CV
2-1/2"
CV
2"
2"
2"4"
11
2"2"4"
4"
3"
4"
4"2"11
4"
4"2"3"
2"3"3"3"3"2"3"2"3"2"
2"2"
11
2"11
2"
11
2"11
2"11
2"11
4"11
4"11
4"11
4"11
2"
11
4"3"3"3"3"3"3"
3"
3"
3"
3"
4"
3"
4"
ELEVATOR PIT
UPPER FLOOR LEVEL
GROUND FLOOR LEVEL
11
2"
SP-1 INDIRECT
DISCHARGE TO FS-1
3" WCO
1-1/2" WCO
3" WCO
3" WCO
2-WAY COTG4" WCO
WCO
4" WCO WCO 4" WCO
4"
CO
3" FCO 3" FCO
1-1/4"1-1/4"
3/4"
HB-1
1"
WC-1
1/4"
LV-1
2"
MAIN
WATER
SERVICE
1/4"
LV-1
1"
WC-1
1/2"
SK-2
1"
WC-3
1/2"
HB-1
1/2"
HB-2
1/2"
SK-3
1-1/4"
3/4"
ES-1
1/2"
SK-1
1/2"
MS-1
1/2"
HB-2 SK-4
1/2"
1/2"
WB-1
3/4"
HB-1
1/2"
SK-4
1/2"
MS-1
1/2"
BL-1
1/2"
LV-2WC-2SH-1LV-2WC-2SH-1WB-2WB-2LV-2WC-2SH-1WH-2WH-1
1-1/4"
1/4"
LV-3
1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1/2"1"1"
1/4"1/4"
1-1/4"1-1/4"2"1-1/2"1-1/2"1-1/4"1-1/4"3/4"3/4"
3/4"3/4"1-1/4"1-1/4"1"1"
COLD WATER FLATOMETRIC
NO SCALE
GROUND FLOOR LEVELGROUND FLOOR LEVEL
UPPER FLOOR LEVELUPPER FLOOR LEVEL 1/2"1/4"1/4"
GLASS
FILLER
AT SK-5WB-1WB-1
1/2"
SK-5
1/4"
WB-1
1/2"FFF
EWC-1
1/2"
GLASS
FILLER
AT SK-2
1/2"
3/4"1/2"FILTER
METERED
IRRIGATION
SUPPLIES
3/4"3/4"
1/2"
HB-2 FF3/4"
1/2"
1/2"
WB-1
3/4"
SK-4MS-1SH-1LV-2SH-1LV-2
1/2"
SH-1
1"
WH-2
1"
WH-1 1/2"
SK-31"
LV-1LV-1SK-2HB-2 SK-4SK-1ES-1MS-1
1/2"
HB-2
1/4"
LV-3
LV-2
1/2"3/4"1/2"1/2"1/2"1/2"1/4"1/4"
1/2"1/2"1/2"1/2"1/2"1/2"1/2"
CP-1
3/4"
3/4"1"1"
3/4"3/4"3/4"1"
HOT WATER FLATOMETRIC
NO SCALE
GROUND FLOOR LEVELGROUND FLOOR LEVEL
UPPER FLOOR LEVELUPPER FLOOR LEVEL
HB-2
1/2"
1"
1/2"
SK-5
1/2"
3/4"
DRAWN BY:CHECKED BY:
SHEET NO:
PROJECT NO:
DATE:
CHAMBERLIN ARCHITECTS
437 Main St.
Grand Junction, Colorado 81501
T 970.242.6804
725 Saint Joseph St., Suite B1
Rapid City, South Dakota 57701
T 605.355.6804
www.chamberlinarchitects.com
E N H A N C I N G E V E R Y D A Y L I V I N G T H R O U G H D E S I G N
05/09/2018
1740
CASTLE CREEK ROAD
ASPEN, COLORADO
PROJECT STATUS: 100% CD
DCR DCR
ASPEN
AMBULANCE
DISTRICT FACILITY
NO:ISSUED FOR:DATE:
356 ECHO CANYON COURT, GRAND JUNCTION, CO 81507-9584
PHONE 970-434-9819 / CELL 970-260-1781 / clintral@bresnan.net
RALSTON MECHANICAL CONSULTING, LLC
Engineering for HVAC, Refrigeration, and Plumbing
P401
PLUMBING
FLATOMETRICS
Per RFI-123 there
are only the two HB-2
hose bibs shown on
P101.
08/13/2019
Per Pre-Bid Question#58 - The MDPbusses have beenoversized toaccommodate futurephotovoltaic powerinput. The 600 ampmain switch iscorrect.Drawing E001, One Line Diagram: Revise the rating of the feeder to panel ‘LB’ as follows: 1. Change feeder conductor size to 350 MCM copper. 2. Change feeder conduit size to 3”. PR-06 has modified thefeeder to the LB panel.08/13/2019
Per Pre-Bid Question#6 - It is contractorschoice item fortemporary power whereever is more efficient topower parking lot lights,electrical, and new trashenclosure.Per Pre-Bid Question#59 - The PVC sizeis 3/4"Per Pre-Bid Question#60 - The storagebuilding needspower. Circuiting isshown in thedumpster enclosureelectrical plan.Per Pre-Bid Question#61 - An all-in-onemeter/switch isacceptable if it isacceptable to HolyCross. The exact locationon the building will bedetermined prior to thestart of construction.Trash Enclosure layoutupdated per PR-02Per RFI-015 -Electrical disconnectand metering serviceexplained.Per RFI-149 it was confirmedthat the LFL2 light fixture wouldbe deleted and a light would be installed at thetop of the pole to illuminate theflag. The power that was goingto be used for the LFL2 fixture will now be used for theflag pole fixture. Per discussionsduring the OAC meeting, it wasconfirmed that the new light will be the dual light, hardwired option from AmericanBeacon.08/13/2019
508/13/2019
Per RFI-121 Per conversations withthe Owner it was requested that alight switch is to be added withinCorridor 220 near door 303D in order for AAD Staff to be able tocontrol lights from this location aswell, so if they are exiting the stairsat the upper level they are able to exit the stair andimmediately turn on lights if needed.Please confirm this change isacceptable.Per RFI-133 Change the3 type 'LAY3' fixtures totype 'LDL2' in order toprovide better headclearance under the patiocanopy.Per RFI -141 it wasconfirmed that the (3)type F light fixtureswill be deleted and(1) 72" long LAR3light fixture will beadded at thislocation. The LAR3light fixture is to bewall mounted at 7'-0"AFF to the "PortraitWall" per interiorelevation 5 on sheetA405.08/13/2019
Per Pre-bid Question #57 - The Emergencyservice disconnect onthe outside of thebuilding at column 5between lines I and J.Per ASI-004 the power layout forthe north wall has been revised.Please refer to ASI-004.Per RFI-048 the elevator call-out line can be runthrough V.O.I.P. It must have equipment that cancommand the line when required.Per RFI-049, access control is deleted from 105,209, 223. All keypads will be deleted, power transferare verified, door release buttons are verified, REXare verified and door contacts are verified. Pleaserefer to RFI-049.RE: RFI-086. Emergencyphone added to wall.3'-10" AFF.Per RFI-109 Deacon 112 - change outlet on thenorth wall to a quad outlet andchange elevation to 24" AFF.Medical Storage 114 - Relocate theoutlet on the south awall to the northwall and change to a quad outlet.Ready Room 113 - Add a quadoutlet on the north wall of the room.Wire new quad outlet on the northwall in the ready room to panel 'LA'Circuit #13.Training Room 104 - Change themulti-media outlet from the northwall to the south wall.Per RFI-111 - Theemergency switch isto be mounted on theEast wall of the lobbyjust to the south ofwindow BO2.Additionally a volumeswitch is to beinstalled at this samelocation to controlsound level of theceiling mountspeaker for the lobby.RE: RFI-152. Per RFI-152,additional overhead doorcontrol stations will be added inthis location as well as directlynorth of door 101BRE" RFI-164. Per RFI-164 a new camera to beadded to the southwest corner of the canopy facingthe northeast corner. New light fixture to be installedon the north wall.08/13/2019
RE: RFI-090. PerRFI-090 a doorrelease for door 101to be added here.RE: RFI-091. PerRFI-091 (2) receptacleswill be added to the Stair303 upper landing.Per RFI-109 The following changes areacceptable.Storage 213 - Change from a jamb lightswitch to an OCC sensor for light operation. Office 212 - Outlets to be mounted at 70" AFFto be consistent with the other offices. Stair 302 - Move the outlet from the toplanding to the intermediate landingWaiting 201 - Make the card reader to thestorefront mullion from the north wall.Waiting 201 - Relocate the door releasebutton to the wall north of door 201 on thewest side of the door. Flex 206 - Rough-in Flex room for both bunkroom and Office configuration.Storage 228 - Change from a jamb lightswitch to an OCC sensor for light operation.Per RFI -113 In our experience, 75’ isas far as one should be from a WAP. For full coverage on both floors, werecommend transmitters be added at Corridor 207at column intersection 2.5 & G.5 andin Corridor 224 at column intersection2.75 & A.75.Per RFI -114 It is assumed that the Wolfinline blower provided for the hood willinclude a speed control. The speedcontrol shall not be mounted on the hood.The speed control shall be mounted nearthe fan above the ceiling for use by theTest and Balance Contractor to set thefan air flow according to the drawings.The fan speed shall not be useradjustable. The timer switch shall allow the user to select a duration ofoperation for the fan EF-3 and for fan coilFC-1Per RFI -132 It wasconfirmed that the owneragrees with adding thecable tray to the IT roomper the layout attached.FCI will proceed with theaddition of the cable trayper the attached sketch.08/13/2019
08/13/2019
RE: RFI-094. Per RFI-094the alerting systemdoorbell will be deleted.RE: RFI-092. Per RFI-092the video messenger willbe moved to grid B and anew monitor will be addedto grid ERE: RFI-103. PerRFI-103 the alertingsystem to change tobunk room style.Per RFI-115 There are no fire/smoke dampers orsmoke dampers to close so the fire alarm systemdoes not control these. The furnaces are to be shut down in the event thatsmoke is detected in the return air ducts. Thisshut-down can be either hard wired interlock withthe smoke detectors or the fire alarm system canperform the shut-down. The fire alarm system willbe monitoring the smoke detectors. The furnacesmay also be shut down on all the other detectorsthat the fire alarm submittal Sequence ofOperations lists. The fire alarm system isdesign-build so the fire alarm contractor should do whatever is required by code.Per RFI-111 The speakers in commonareas on the upper level are to be onseparate zones to control audible leelsThe volume controls for this speaker areto be accommodated by the amplifier atthe head end equipment if enough outputports are present in the amplifier provided. If there are not enough output ports onthis amplifier volume controls are to berack mounted near the alerting systemhead end within IT 211.Per RFI-111 The volume controlswitch is to be deleted at theoutdoor location. Volume control forthe outdoor speaker is to beprogrammed at the Alerting Systemhead end equipment located withinIT 211. The speaker in this locationis to be ceiling mounted within theT&G canopy. The TAM controllerfor this speaker is to be mounted inCorridor 220 above the ceiling.Per RFI-111 The VMSS monitorin corridor 220 is to be a 32"monitor. Monitors in theapparatus bay are to bemounted at 10'AFF to Center ofmonitor. The turnout Timerslocated within the ApparatusBay are to be installed directlybelow the VMSS monitors.Per RFI-111 The Dorm Remotethat is to be provided in FlexRoom 206 can control volumeoutput for this space. PerRFI-103 a separate volumecontrol switch was to beprovided. Because volume forthe alerting system can be adjusted fromthe dorm remote, the additionalswitch is not required at FlexRoom 206.Per RFI-111 receptacle is shown to belocated in the main electrical room on the 1stfloor which is not consistent with low voltageor alerting system drawings. Perconversation with low voltage systems on site4/11/19, it was confirmed that head endequipment for the alerting system will require3 dedicated circuits. Circuits are to be fedfrom EM panel. 2EA circuits are to beprovided for UPS devices for the AlertingSystem. UPS's for this system will be rackmounted within IT Room 211. The otherreceptacle which is also to be fed from an EMcircuit is for the transformer for the ApplianceController. The Appliance Controller andtransformer will be located within IT 211.08/13/2019
08/13/2019
08/13/2019
1. Drawing E403, Fire Alarm Riser: Move the heat detector in the elevator equipment room to the elevator pit (the location of the elevator controller). PR-07 added the following:1. Distribution panel ‘MDP’: Change the circuit breaker sizes shown for CU-1, CU-2 & CU-3 to 50 amps 2 pole. 2. Panel ‘LA’: Change the circuit breaker size shown for EF-1 from 15 amp 3 pole to 20 amp 2 pole. Per PR-09Per PR-0908/13/2019
08/13/2019
Per PR-07: Add GFCI Tripping to Circuit #251. Change the circuit breaker sizes shown for CU-1, CU-2 & CU-3 to 50 amps 2 pole. 2. Change the circuit breaker size shown for EF-1 from 15 amp 3 pole to 20 amp 2 pole. 3. Change the combination starter listed for EF-1 to a combination disconnect – the motor being suppled has embedded thermal overcurrent protection. Per PR-0908/13/2019