MEMORANDUM
600 East Hopkins Avenue, Suite 303
Aspen, Colorado 81611
PH / FX 970 925 1125
daverybak.com
TO: Justin Hahn, Plans Examiner, City of Aspen
FROM: Dave Rybak
DATE: April 6, 2018
RE: 535 E. Hyman Unit 103 – Frame
Permit #0024.2018.ACBK, Rev 1 Comment Response
COMMCheck Comments:
1. Provide cutsheets on the current limiting devices.
Current Limiting device cut sheet attached.
2. Provide a cutsheet on this fixture high lighting maximum fixture wattage and NRTL
listing
Fixture D has been revised, Cut Sheet provided, with wattage and U.L. notes.
3. Current limiter wattages for CL1 and CL3 do not match what is called out on sheet E200.
Revise on or the other.
Current Limiter wattages are listed in flag notes 2, 3 & 4 on sheet E-200. Listed
wattages correspond with those listed on COMMCheck.
Plan Set Comments:
4. Where is your point of sale located? It must be on the accessible route and meet the
requirements of 2009 ANSI 904.
Point of sale will be hand held portable devices. No fixed location.
5. Provide a mechanical plan showing compliant supply and return air throughout the
space as this is the initial occupation of the unit.
The Fan Coil Unit was installed under permit #0086.2017.ACBK. Duct installation,
and termination devices are being installed via supplemental information to the
Mechanical Permit of that Master Permit, by the Landlord, prior to Tenant
Improvements, per their lease agreement. Submitted Mech Plans accompany this
memorandum.
04/10/2018