Page: - 1 HOUR RATED FLOOR ASSEMB 2
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a cut sheet on the
whisper mat demonstrating an
IIC rating of 50 or greater at this
floor configuration.
3 Fifth Ave Drawings.pdf (7)
Page: - 1 HOUR RATED FLOOR ASSEMB 2
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide the original installation
instructions for a listed 1 hour
fire, STC 50 rated wall
assembly.
Page: 1 - EXISTING FLOOR PLAN
File Name: 3 Fifth Ave Drawings.pdf
Subject: asbestos
Author: nickt
Color:
Provide an asbestos abatement
clearance report.
Page: 2 - DEMOLITION FLOOR PLAN
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
Mantle, surround, and hearth
extension must comply with the
installation instructions of the
factory built firebox.
Demonstrate compliance. If no
manufacturer instructions can be
found, demonstrate compliance
with the requirements of 2015
IBC chapter 21.
1 HOUR RATED FLOOR ASSEMBLY55 STC
1 HOUR RATED WALL ASSEMBLY55 STC
Sketch "NOT FOR CONSTRUCTION" without ASI no.
DETAILSketch Name:1 HOUR RATED ASSEMBLIES
Project Name:Project Number:800 S. MILL STREET, UNIT 10-BN/A
Sketch No. - Item No.:
ASI Reference:
04/11/2018
A-1N/A
Date:
Scale:1" = 1'-0"A-1Drawing Sheet / SpecSection:300 S. SPRING ST. SUITE 201ASPEN, CO 81611(970) 710-2938
THUNDERBOWL ARCHITECTS
EXISTING GYP. WALL BOARD IN ADJACENT UNIT. NOT TO BE DISTURBED.
EXISTING(ADJACENT UNIT)PROPOSED
EXISTINGEXISTING(ADJACENT UNIT)
EXISTING STAGGERED STUDS. NOT TO BE DISTURBED.
EXISTING GYP. WALL BOARD TO BE REMOVED (THIS UNIT ONLY)
EXISTING INSULATION TO REMAIN. REPLACE AS NECESSARY
ALL EXISTING PLYWOOD NOT TO BE DISTURBED.
REPLACE ALL EXISTING GYP. WALL BOARD W/58" TYPE "X" GYP. WALL BOARD TO MEET 55 STC RATING
WOOD FLOORTILE FLOOR
EXISTING(ADJACENT UNIT BELOW)
EXISTING GYP. WALL BOARD IN ADJACENT UNIT. NOT TO BE DISTURBED.
NEW WOOD FLOOR ASSEMBLY
NEW 12" WHISPER MAT, ASTM E90
EXISTING INSULATION TO REMAIN.
ALL EXISTING PLYWOOD SUB-FLOOR NOT TO BE DISTURBED.
EXISTING FLOOR STRUCTURE TO REMAIN.
NEW TILE FLOOR ASSEMBLY
1A-1
2A-1 1" = 1'-0"
1" = 1'-0"Provide a cut sheet onthe whisper matdemonstrating an IICrating of 50 or greaterat this floorconfiguration.
1 HOUR RATED FLOOR ASSEMBLY55 STC
1 HOUR RATED WALL ASSEMBLY55 STC
Sketch "NOT FOR CONSTRUCTION" without ASI no.
DETAILSketch Name:1 HOUR RATED ASSEMBLIESProject Name:Project Number:800 S. MILL STREET, UNIT 10-BN/A
Sketch No. - Item No.:ASI Reference:
04/11/2018
A-1N/A
Date:
Scale:1" = 1'-0"A-1Drawing Sheet / SpecSection:300 S. SPRING ST. SUITE 201ASPEN, CO 81611(970) 710-2938
THUNDERBOWLARCHITECTS
EXISTING GYP. WALL BOARD IN ADJACENT UNIT. NOT TO BE DISTURBED.
EXISTING(ADJACENT UNIT)PROPOSED
EXISTINGEXISTING(ADJACENT UNIT)
EXISTING STAGGERED STUDS. NOT TO BE DISTURBED.
EXISTING GYP. WALL BOARD TO BE REMOVED (THIS UNIT ONLY)
EXISTING INSULATION TO REMAIN. REPLACE AS NECESSARYALL EXISTING PLYWOOD NOT TO BE DISTURBED.
REPLACE ALL EXISTING GYP. WALL BOARD W/58" TYPE "X" GYP. WALL BOARD TO MEET 55 STC RATING
WOOD FLOORTILE FLOOR
EXISTING(ADJACENT UNIT BELOW)
EXISTING GYP. WALL BOARD IN ADJACENT UNIT. NOT TO BE DISTURBED.
NEW WOOD FLOOR ASSEMBLY
NEW 12" WHISPER MAT, ASTM E90
EXISTING INSULATION TO REMAIN.
ALL EXISTING PLYWOOD SUB-FLOOR NOT TO BE DISTURBED.
EXISTING FLOOR STRUCTURE TO REMAIN.
NEW TILE FLOOR ASSEMBLY
1A-1
2A-1 1" = 1'-0"
1" = 1'-0"
Provide the originalinstallation instructionsfor a listed 1 hour fire,STC 50 rated wallassembly.
PROJECT:VOGEL RESIDENCE
by the users (contractors, millwork manufacturers, etc.) to ensure the design is adequate for the intended use.
These drawings will be revised periodically and it shall be the re-sponsibility of the receiver of these drawings to keep them current with any updates.
2. Cabinetry Notes:
Millwork manufacturer to field verify all dimensions prior to building cabinetry.
EXISTING FLOOR PLAN
Scale: 1/4” = 1’-0”
Provide an asbestos abatement
clearance report.
02/12/18
12/20/1701/12/1801/16/18
DRW NO:DATE:DRAWING TITLE:PROJECT:VOGEL RESIDENCE
ng Notes:
nished for ensions c. All d or cal-d. Use of g design e checked s, millwork ensure the he intended
evised be the re-er of these current with
o field verify uilding
2DEMOLITION FLOOR PLAN
ON FLOOR PLAN
g A-1
Rating
sembly.
all and
s.4/16/2018
06/08/2018
Mantle, surround, and hearth extensionmust comply with the installationinstructions of the factory built firebox.Demonstrate compliance. If nomanufacturer instructions can be found,demonstrate compliance with therequirements of 2015 IBC chapter 21.
EXISTING WOOD FIREPLACE TO REMAIN
NOTED ON DRAWINGS 3 and 14
SEE ATTACHED CLEARANCE LETTER
SEE DETAIL 3/SK-01 INCLUDED IN DRAWING PACKAGE
8.21.2018
SEE ATTACHED Proflex 90 spec
Page: 2 - DEMOLITION FLOOR PLAN
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide more information on the
attic and the proposed water
heater relocation. This building is
Type VA construction and is
multifamily. To locate
mechanical equipment in the
attic, the attic above the unit
must be separated from adjacent
units and from adjacent attics
serving other units by 1 hour fire
resistant construction (2015 IBC
420). Additionally, the roof
structure must have a 1 hour fire
rating (2015 IBC 711.2.6).
Provide access and service
space in accordance with 2015
IMC 306; demonstrate
combustion air needs are met
per 2015 IFGC 304; and
demonstrate exhaust termination
is located in accordance with
2015 IMC 501.3.1. Detail
whether this is to be a new water
heater or reuse the old one.
Provide a drain pan per 2015
IPC 504.7.
Page: 2 - DEMOLITION FLOOR PLAN
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
This is a Type VA building,
requiring the floor/ceiling
assembly to be 1 hour fire rated
(2015 IBC 601). Provide a listed
1 hour fire rated ceiling
assembly.
Page: 3 - FLOOR PLAN
File Name: 3 Fifth Ave Drawings.pdf
Subject: PlanCheck
Author: nickt
Color:
It appears that you are replacing
the exterior doors. Note that they
must have a U factor of 0.28 or
less on the plans. (Ordinance
40, 2016)
02/12/18
12/20/1701/12/1801/16/18
DRW NO:DATE:DRAWING TITLE:PROJECT:VOGEL RESIDENCE
General Notes1. Construction Drawing Notes:
These drawings are furnished for information only. All dimensions shown are sheet specific. All dimensions shall be read or cal-culated and never scaled. Use of these drawings (including design and dimensions) must be checked by the users (contractors, millwork manufacturers, etc.) to ensure the design is adequate for the intended use.
These drawings will be revised periodically and it shall be the re-sponsibility of the receiver of these drawings to keep them current with any updates.
2. Cabinetry Notes:Millwork manufacturer to field verify all dimensions prior to building cabinetry.
2DEMOLITION FLOOR PLAN
DEMOLITION FLOOR PLANScale: 1/4” = 1’-0”
See Drawing A-1 For 1 Hour Rating & Sound Assembly.
Demising Wall and
Floor Details.4/16/2018
06/08/2018
Provide more information on the attic and the proposed water heater relocation. This building isType VA construction and is multifamily. To locate mechanical equipment in the attic, the atticabove the unit must be separated from adjacent units and from adjacent attics serving other unitsby 1 hour fire resistant construction (2015 IBC 420). Additionally, the roof structure must have a1 hour fire rating (2015 IBC 711.2.6). Provide access and service space in accordance with 2015IMC 306; demonstrate combustion air needs are met per 2015 IFGC 304; and demonstrateexhaust termination is located in accordance with 2015 IMC 501.3.1. Detail whether this is to bea new water heater or reuse the old one. Provide a drain pan per 2015 IPC 504.7.
02/12/18
12/20/1701/12/1801/16/18
DRW NO:DATE:DRAWING TITLE:PROJECT:VOGEL RESIDENCE
ing Notes:
rnished for mensions fic. All ad or cal-ed. Use of ing design be checked ors, millwork ensure the the intended
revised be the re-ver of these current with
to field verify building
2DEMOLITION FLOOR PLAN
ON FLOOR PLAN”
g A-1
Rating
ssembly.
Wall and
s.4/16/2018
06/08/2018
This is a Type VAbuilding, requiring thefloor/ceiling assemblyto be 1 hour fire rated(2015 IBC 601).Provide a listed 1 hourfire rated ceilingassembly.
02/12/18
12/20/1701/12/1801/16/18 DRW NO:DATE:DRAWING TITLE:PROJECT:VOGEL RESIDENCE
General Notes1. Construction Drawing Notes:
These drawings are furnished for information only. All dimensions shown are sheet specific. All dimensions shall be read or cal-culated and never scaled. Use of these drawings (including design and dimensions) must be checked by the users (contractors, millwork manufacturers, etc.) to ensure the design is adequate for the intended use.These drawings will be revised periodically and it shall be the re-sponsibility of the receiver of these drawings to keep them current with any updates.
2. Cabinetry Notes:
Millwork manufacturer to field verify all dimensions prior to building cabinetry.
3FLOOR PLAN
FLOOR PLANScale: 1/4” = 1’-0”
It appears that you arereplacing the exteriordoors. Note that theymust have a U factorof 0.28 or less on theplans. (Ordinance 40,2016)
EXISTING EXTERIOR DOORS TO REMAIN
NOTED ON DRAWING 2
SEE DETAIL 3/SK-01
SEE DETAIL 1/SK-01 AS NOTED ON DRAWING 3a
399 CFM RANGE HOOD
NOTED ON DRAWING 3
NEW WATER HEATER w/DRAIN PAN
NOTED ON DRAWING 3a
5/8 DRYWALL ALL WALLS,
TYP. UNLESS NOTED
NOTED ON DRAWINGS 3
STRUCTURAL FRAMING
SEE DRAWINGS S1,S2,and S3
MECH ACCESS
NOTED ON DRAWING 3a