HomeMy WebLinkAboutFile Documents.232 E Main St.0005-2021-BCOM (11)COMcheck Software Version 4.1.4.3
Envelope Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Location:Aspen, Colorado
Climate Zone:7
Construction Site:
232 E. MAIN STREET ASPEN,
ASPEN, CO 81611
Owner/Agent:
J.P. MORGAN CHASE BANK
232 EAST MAIN STREET LLC
2001 N. HALTED #304
CHICAGO, IL 60614
MHUNT@MDEVCO.COM
Designer/Contractor:
EARL G. WONG
STANTEC ARCHITECTURE INC,
PITTSBURGH, PA
Project Information
Energy Code:
CHASE MAIN AND MONARCH
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Additional Efficiency Package(s)
Building Area Floor Area
Unspecified 0
Envelope Assemblies
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
Envelope TBD: Invalid building envelope area type (see project screen)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
141 ofPage02/24/2021
COMcheck Software Version 4.1.4.3
Mechanical Compliance Certificate
Project Title:
2015 IECC
Project Type:New Construction
Location:Aspen, Colorado
Climate Zone:7
Construction Site:
232 E. MAIN STREET ASPEN,
ASPEN, CO 81611
Owner/Agent:
J.P. MORGAN CHASE BANK
232 EAST MAIN STREET LLC
2001 N. HALTED #304
CHICAGO, IL 60614
MHUNT@MDEVCO.COM
Designer/Contractor:
EARL G. WONG
STANTEC ARCHITECTURE INC,
PITTSBURGH, PA
Project Information
Energy Code:
CHASE MAIN AND MONARCH
High efficiency HVAC. Systems that do not meet the performance requirement will be identified in the mechanical requirements checklist
report.
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each - Central Furnace, Gas, Capacity = 8 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency: 88.00 % Et or 85.8% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 8 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 16.50 SEER, Required Efficiency: 15.40 SEER
Fan System: None
1 RTU-1 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 9 kBtu/h
Proposed Efficiency = 95.00% Et, Required Efficiency: 88.00 % Et or 85.8% AFUE
Cooling: 1 each - Single Package DX Unit, Capacity = 9 kBtu/h, Air-Cooled Condenser, Air Economizer
Proposed Efficiency = 17.50 SEER, Required Efficiency: 15.40 SEER
Fan System: None
1 RTU-2 (Single Zone):
Split System Heat Pump
Heating Mode: Capacity = 1 kBtu/h,
Proposed Efficiency = 10.00 HSPF, Required Efficiency = 9.02 HSPF
Cooling Mode: Capacity = 1 kBtu/h,
Proposed Efficiency = 16.00 SEER, Required Efficiency: 15.40 SEER
Fan System: None
1 SPLIT SYSTEM 1 (Single Zone):
Split System Heat Pump
Heating Mode: Capacity = 1 kBtu/h,
Proposed Efficiency = 10.00 HSPF, Required Efficiency = 9.02 HSPF
Cooling Mode: Capacity = 1 kBtu/h,
Proposed Efficiency = 16.00 SEER, Required Efficiency: 15.40 SEER
Fan System: None
1 SPLIT SYSTEM (Single Zone):
Electric Storage Water Heater, Capacity: 30 gallons w/ Circulation Pump
Proposed Efficiency: 19.30 SL, %/h (if > 12 kW), Required Efficiency: 1.20 SL, %/h (if > 12 kW)
1 Water Heater 1:
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
142 ofPage02/24/2021
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.4.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
143 ofPage
Earl G. Wong, Jr - Senior Mechanical Engineer 12-16-2020
02/24/2021
Inspection Checklist
Requirements: 100.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.4.3
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
144 ofPage02/24/2021
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
145 ofPage02/24/2021
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.1,
C404.6.2
[PL3]1
Automatic time switches installed to
automatically switch off the
recirculating hot-water system or heat
trace.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
146 ofPage02/24/2021
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Water distribution system that pumps
water from a heated-water supply
pipe back to the heated-water source
through a cold-water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold-water piping to
104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
147 ofPage02/24/2021
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
148 ofPage02/24/2021
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.2.12
.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.12
.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.13
[ME71]2
Unenclosed spaces that are heated
use only radiant heat.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
149 ofPage02/24/2021
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.8
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9
[ME60]2
HVAC ducts and plenums insulated.
Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9
[ME10]2
Ducts and plenums sealed based on
static pressure and location.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.9.
1.3
[ME11]3
Ductwork operating >3 in. water
column requires air leakage testing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.2.
3.2.2
[ME122]3
Open- or closed circuit cooling towers
have a separate heat exchanger to
isolate the cooling tower from the
heat pump loop, and heat loss is
controlled by shutting down the
circulation pump on the cooling tower
loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.2.
3.2.2
[ME122]3
Open- or closed circuit cooling towers
have a separate heat exchanger to
isolate the cooling tower from the
heat pump loop, and heat loss is
controlled by shutting down the
circulation pump on the cooling tower
loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
1410 ofPage02/24/2021
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.4.4.
6
[ME110]3
Multiple zone VAV systems with DDC
of individual zone boxes have static
pressure setpoint reset controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
1411 ofPage02/24/2021
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
1412 ofPage02/24/2021
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.3
[FI11]3
Heat traps installed on supply and
discharge piping of non-circulating
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.4
[FI25]2
All piping insulated in accordance with
section details and Table C403.2.10.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.6.1
[FI12]3
Controls are installed that limit the
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
1413 ofPage02/24/2021
Project Title:
Data filename:
CHASE MAIN AND MONARCH
\\US1279-
F01\workgroup\2227\active\222769128\architecture\drawing\mechanical\schedules\COMCHECK\C
HASE ASPEN.cck
12/16/20Report date:
1414 ofPage02/24/2021