Loading...
HomeMy WebLinkAboutFile Documents.971 Ute Ave. (2)0084-2017-ARBK_BuildingComments_1 Page: A-103 File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf Subject: PlanCheck Author: nickt Color: If new range hood exhausts greater than 400cfm, interlocked makeup air will be required. 2015 IMC 505.2. 2017.04.06_971 Ute Ave._Permit Set.pdf (5) Page: A-105 File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf Subject: PlanCheck Author: nickt Color: Provide an exhaust fan in the master bath area containing the bathtub and shower. Page: D-101 File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf Subject: PlanCheck Author: nickt Color: The walls and ceiling separating the ADU bath and kitchen from the rest of the house must be 1 hour fire rated with an STC rating of at least 50. You will likely be disturbing the existing drywall. Provide listed assemblies to be used to replace the drywall if more than 32sqft is disturbed. Page: G0.00 File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf Subject: PlanCheck Author: nickt Color: Provide an asbestos inspection report including the narrative, lab data, and inspector's certifications. Page: G0.00 File Name: 2017.04.06_971 Ute Ave._Permit Set.pdf Subject: PlanCheck Author: nickt Color: This project was submitted after April 10, 2017, putting it on the 2015 codes. Revise to make all codes be 2015 except for the 2014 NEC. DWDW KITCHEN 308 WOOD LIVING 303 WOOD DN CLOSET 305 WOOD NEW POCKET DOOR SKYLIGHT ABOVE BUILT IN EXISTING STAIR TO REMAIN WASHER E KITCHEN APPLIANCES "4'-0 9/32"10'-8"7'-1"4'-3 1/2""If new range hood exhausts greater than 400cfm, interlocked makeup air will be required. 2015 IMC 505.2. F MSTR BATH 201 MASTER BED 202 Provide an exhaust fan in the master bath area containing the bathtub and shower. C E FD 41'-0" 16'-3"14'-0"2'-10"4'-2" BED 101 CARPET ADU BED 103 CARPET ADU BATH 102 STONE ADU KITCHEN 104 STONE CLOSET113CARPET ADU CLOSET 105 CARPET BATH 111 MEDIA ROOM 107 CARPETOOM ET ADU STAIR106CONCRETE UP REF BUILT IN D CABINETS REPLACE EXISTING FIXTURES AND CABINETS AREAS OF WORK The walls and ceilingseparating the ADUbath and kitchen fromthe rest of the house must be 1 hour firerated with an STC rating of at least 50.You will likely be disturbing the existingdrywall. Provide listed assemblies to be usedto replace the drywall ifmore than 32sqft isdisturbed. Provide an asbestos inspection report including the narrative, lab data, and inspector's certifications. CIVIL ENGINEER: -CONTACT:-- A.F.F. PROJECT ADDRESS: PARCEL ID: FIRE SPRINKLER SYSTEM INSTALLED: APPLICABLE CODES:·2009 IRC (International Residential Code) Chapters 1-10·2009 IRC appendixes:·Manufactured homes, F: Radon, J: Existing Buildings & Structures, H:Patio Covers, K: Sound Transmission. ·2009 IPC (International Plumbing Code) ·2009 IMC (International Mechanical Code)·2009 IFGC (International Fuel Gas Code)·2009 IECC (International Energy Conservation Code) - Prescriptive Path ·2009 IFC (International Fire Code) ·2014 NEC (National Electrical Code) 971 Ute Aveune, Aspen CO 81611 273718295029 NO R-15 3,682.79 sq ft EXISTING, 3,682.79 sq ft PROPOSED (NO CHANGE) Residential Front - 25', Side and Rear - 10' ZONING: F.A.R. PERMITTED USE: SETBACKS: PROJECT DIR CONTACT: Ryan Doremus STRUCTURAL ENGINEER: LANDSCAPE DESIGN: OWNER/CLIENT: ARCHITECT: Aspen, CO 81611 Thunderbowl Architects 300 Spring St. Suite 201 Ajax Holdings PROJECT STATISTICS TYPE: OCCUPANCY: OVERALL PROJECT HEIGHT AND AREA: PROJECT SUMMARY: Type V - Non-rated Type R-3 Maximum Height N/A - Area N/A INTERIOR REMODEL OF EXISTING BATHROOMS AND UPDATING KITCHEN CABINETRY AND PLUMBING FIXTURES. --CONTACT:- CONTRACTOR ENOTES DIMENSION ENOTES DIMENSION R DENOTES FINISH -CONTACT:-- Kaegebein Fine HomebuildingCONTACT: Nate Kaegebein- -- MECHANICAL DESIGN: -- CONTACT: - CONTACT: Ryan Doremus (Thunderbowl Architects) Aspen, CO 81611300 Spring St. Suite 201 This project was submitted after April 10, 2017, putting it on the 2015 codes. Revise to make all codes be 2015 except for the 2014 NEC. A-103 NOW HAS A NEW NOTE REFLECTING EXISTING HOOD AND RANGE TO REMAIN A-105 NOW HAS A NEW FAN LOCATED IN THE MAIN BATHROOM AREA G0.00 NOW HAS A UPDATED APPLICABLE CODES TO REFLECT THE 2015 CODE ADOPTION INCLUDED IS THE ASBESTOS CERTIFICATE SEE NOTE ON D-101, AND ATTACHED LISTED WALL ASSEMBLY City of Aspen Received 6/26/17 Building Department