Page: A 5.0 DETAILS
File Name: 0072-2018-ARBK Building Comments Set
181115.pdf
Subject: PlanCheck
Author: nickt
Color:
The drywall must be continuous
behind the baseboard for the
continuity of the fire rated
assembly.
0072-2018-ARBK Building Comments Set 181115.pdf (3)
Page: A 5.1 FIREPLACE DETAILS
File Name: 0072-2018-ARBK Building Comments Set
181115.pdf
Subject: PlanCheck
Author: nickt
Color:
Field verification will be required
for the existing hearth extension
during demo.
Page: A 6.0 SCHEDULES
File Name: 0072-2018-ARBK Building Comments Set
181115.pdf
Subject: PlanCheck
Author: nickt
Color:
Windows 11 and 27 must also
be safety glazed due to their
proximity to doors. 2015 IRC
R308.4.
INTERIOR
5/8" 5 1
2x FRAMING WITHMINERAL FIBER INSULATION
NOTE:
XISTING 2x FRAMING TO REMAIN
IF NO DEMOLITION REQUIRED,
RE: FLOOR PLANS
GWB IN UNIT 2 TO REMAIN
BASEBOARD
RESILIENT CHANNELS 16" O.C.ATTACHED AT RIGHT ANGLES
TO ONE SIDE OF WOOD STUDS
WITH ONE LAYER 5/8" GWB
APPLIED AT RIGHT ANGLES TO
CHANNELS. CAULK OR TAPE
SEAMS
SIM. GA FILE
NO WP 3242ON A1.3 & A1.4
SCA3TY
0 3''6''9''SCALE: 3" = 1'-0"
TYPICAL PARTITION WALL- STC
The drywall must be
continuous behind the
baseboard for the
continuity of the fire
rated assembly.
Scale: AS NOTED
ISSUE
SCHEMATIC DESIGN
PERMIT SET
VE SET
ZONING COMMENT
BUILDING COMMEN
PERMIT RESUBMITTA
BUILDING COMMENCOSTANZ950 CEMETEASPEN1" ACTUALIF THE ABOVE DIMENSION DONOT MEASURE ONE INCH (1"EXACTLY, THIS DRAWING WILHAVE BEEN ENLARGED ORREDUCED, AFFECTING ALLLABELED SCALES.
A 5.1
11/16/2018
FIREPLACE
DETAILS
DATE
1/24/18
4/2/18
7/30/18
8/14/18
9/27/18
10/05/18
11/15/18
6" 4"1'-11"T.O. LOWER LEVEL F.F.
LIVING ROOM FIREPLACE SECTION
EL. + RE: FLOOR PLAN
EXISTING CMU TO REMAIN
EXISTING WOOD BURNING FIREPLACETO REMAIN
ADD STEEL FRAME GLASS DOORSON FIREPLACE
REPLACE STONE HEARTH VENEERAT SAME ELEVATION. EXIST'GSTRUCTURE TO REMAIN
PIPE; WRAP WITH DECORATIVE STEEL.MAINTAIN REQUIRED CLEARANCES
REPLACE FIREPLACE VENEER
STEEL ANGLE HEADER
NEW STONE CAP ABOVE TOP WITH
RTH
ACE
AGE
0 6'' 1'2'SCALE: 1" = 1'-0"3 FIREPLACE
1'2'
Field verification willbe required for theexisting hearthextension duringdemo.
ISSUE
SCHEMATIC DES
PERMIT SETVE SETZONING COMMBUILDING COMM
PERMIT RESUBM
BUILDING COMMCOSTANZA REMODEL950 CEMETERY LANE, UNIT 1ASPEN, CO 81611ALL DESIGNS, IDEAS ARRANGEMEPLANS INDICATED BY THESE DRAND SPECIFICATIONS ARE THE PAND COPYRIGHT OF KIM RAARCHITECTS, INC. AND SHALL NEUSED ON ANY OTHER WORK USED BY ANY OTHER PERSON FUSE WHATSOEVER WITHOUT PERMISSION. WRITTEN DIMSHALL TAKE PRECEDENCE OVERDIMENSIONS AND SHALL BE VERTHE SITE. ANY DIMEDISCREPANCY SHALL BE BROUTHE ATTENTION OF THE ARCHITECTO COMMENCEMENT OF WORK.
DATE
1/24/18 KIM RAYMOND ARCHITECTS, INC.| 300 E. HYMAN AVENUE, SUITE 100 |4/2/187/30/188/14/189/27/18
10/05/18
11/15/18
W27
W28
W29
W31
W32
W33
W34
W35
W36
W37
4'-1 1/2"×8'-3/4"
4'×2'-4 3/4"
4'×1'-5 1/2"
4'×1'-5 1/2"
5'-3 1/4"×1'-5 1/2"
5'-3 1/4"×1'-5 1/2"
4'-10 1/4"×1'-5 1/2"
4'-10 1/2"×1'-5 1/2"
4'×1'-5 1/2"
4'×1'-5 1/2"
3'-6"
3'-6"
3'-6"
3'-6"
3'-6"
3'-6"
3'-6"
50.00"
48.50"
48.50"
48.50"
63.75"
63.75"
58.75"
59.00"
48.50"
48.50"
Window Schedule
ID TAG
W02
W03
W05
W06
W11
W12
W13
W14
W15
W16
W17
W18
W19
W20
W21
View from Opening Side Nominal W x H Size
4'-6"×4'-6"
4'-6"×4'-6"
5'×5'
5'×5'
4'×6'-4 1/4"
5'×2'
2'-6"×5'
2'-6"×5'
5'×5'
2'×5'
2'×5'
2'×3'-2"
5'-9"×2'
5'-9"×2'
2'-6"×5'-6"
Sill Height
3'-7"
3'-7"
3'-4"
1'-9 1/4"
5'-7 3/4"
2'-0"
2'-0"
2'-0"
3'-8"
3'-6"
SquareFootage
54.50"
54.50"
60.50"
60.50"
48.50"
60.50"
30.50"
30.50"
60.50"
24.50"
24.50"
24.50"
69.50"
69.50"
30.50"
Comments
Window Schedule
ID TAG View from Opening Side Nominal W x H Size Sill Height SquareFootage Comments
1'-6"×6'-8"
3'×6'-8"
3'×6'-8"
3'×6'-8"
2'×8'
2'×8'
2'-6"×8'
2'×8'
2'-6"×8'
10.00
20.00
20.00
20.00
16.00
16.00
20.00
16.00
20.00
Door Schedule
View from Opening Side Nominal Wx H Size Door SF
SAFETYGLAZINGREQUIRED
SAFETYGLAZINGREQUIRED
NOTE: WINDOWS AND EXTERIOR DOORS MUST PROVIDE A MAXIMUM U-VALUEOF 0.32, PER RESCheck SPECIFICATIONS IN REPORT DATED 9/24/18 ANDSUBMITTED AS DOCUMENTATION FOR THE BUILDING PERMIT APPLICATION
Windows 11 and 27must also be safetyglazed due to theirproximity to doors.2015 IRC R308.4.
Please see revised detail, which indicates a second,continuous layer of 5/8" Type "X" gyp bd on the wallscommon to Unit 2.
Please see revised Section, which calls for field verificationof existing hearth extension and that the extensionis to remain as built.
Please see revised Window Schedule, which indicatessafety glazing for windows 11 and 27.
12/27/2018