HomeMy WebLinkAboutFile Documents.905 Chatfield Rd.0012-2020-BCHO0012-2020-BCOM_BuildingComment1
Subject: PlanCheck
Page: A-123_ENLARGED UPPER LEVEL FLOOR PLAN
Author: justinh
Color:
File Name: 0_ARCH_CHANGE ORDER 2.pdf
Update the door and window
schedules and your ResCheck
to reflect these changes to
fenestration and wall square
footages.
0_ARCH_CHANGE ORDER 2.pdf (3)
Subject: PlanCheck
Page: A-204_EXTERIOR ELEVATIONS
Author: justinh
Color:
File Name: 0_ARCH_CHANGE ORDER 2.pdf
Call out this new glass guard on
the main level floor plans (both
enlarged and overall).
Subject: PlanCheck
Page: A-438 3_INTERIOR ELEVATIONS -HALL / DEN /
POWDER
Author: justinh
Color:
File Name: 0_ARCH_CHANGE ORDER 2.pdf
You do not appear to be
providing the required 15" from
centerline of the fixture to the
adjacent wall (IPC 405.3) per my
measurements. Revise to
comply or add a dimension to
this enlarged detail so there is
no confusion.
A-202 1
OFFICE200WOODWOOD
GUEST BDRM 1201CARPETCARPET
A-4003
DRESSING ROOM
201.A
203.C
GUEST BDRM 2203CARPETCARPET
GUEST BATH 2204TILETILE
1A-303
1A-304
3A-322
1A-322
1A-321
Y1
W7
W6
W7
W7
W7
W4
W4
W4
W7
201.C
GUEST BATH 1202TILETILE
204.A
Y222'-9"
203.A
DN
202.A
W4
W4 W8
A-446A
A-4471
RD
RD
A-445A
1/4" /12"W4
W4
W4
W4
W6 168.00°192.00°
STONE PANEL WALL WITH CAPSTONE
HIGH WINDOWS
W7
W7
W7
W7
W8
A-201
1
5 1/2"6 1/2"
4'-11"5 1/2"11'-10 1/2"
5 1/2"
5'-6"
5 1/2"1'-8 1/2"3 1/2"
16'-2 1/8"9 1/4"
12'-8"5 1/2"2'-11 1/2"
6 1/2"
5 1/2"
3 1/2"
4'-8 1/2"5 1/2"
4'-0 1/2"5 1/2"3"
1/4"/12"
INSWING DOOR ADDED TO WINDOW
REMOVAL OF DECKS1
19 STEPS @ 7 1/2" RISE
201.B
X
V
203.B
STEEL GUARDRAIL FOR JULIET BALCONY.3' ABOVE FINISH
3
INSWING DOOR ADDED TO WINDOW
UPPER LEVEL -ENLARGED FLOOR PLAN -C 1
Update the door andwindow schedules andyour ResCheck toreflect these changesto fenestration andwall square footages.
2A-301V1 V2
FF
RR
ZONE DISTRICT HEIGHT LIMIT PER 26.575.020.F.2.aZONE R15: 26.710.070.D.7 = 25'-0"EL. 'A' T.O. SH
SEE SHEET A-
EL. 'B' T.O. SHEATING = 7842'-3 1/2"
SEE SHEET A-007
FIREPLACE TERMINATION,RE: A-420
MECH GRILL, RE: MECH
TEMPERED, LAMINATED GLASS GUARDRAIL
FACE MOUNTED TO FASCIA.3' -0" ABOVE FINISH FLOOR
3 EE
3
3'-0"Call out this new glassguard on the mainlevel floor plans (bothenlarged and overall).
A-438
1
103
CARPETCARPET
PWDR
102
TILETILE 3
24
A-438
5
COAT CLOSET
CPT-01
TL-01 PF-26
PF-02
PF-10PF-12 PF-11
HIDDEN CLEATS, FINISH MT-01
1/2" = 1'-0"
101/102/103 -ENLARGED -
HALL/DEN/POWDER A" = 1'-0"
UTH 1
" = 1'-0"
ACE 10
You do not appear to
be providing the
required 15" from
centerline of the fixtureto the adjacent wall
(IPC 405.3) per my
measurements.
Revise to comply or
add a dimension tothis enlarged detail so
there is no confusion.
Subject: PlanCheck
Page: 2
Author: justinh
Color:
File Name: cs 77 lr.pdf
Verify that the new proposed
windows and doors will be
NFRC stickered at inspection so
that we can verify the U values
claimed on the ResCheck (this
applies to all windows installed
on this project). This spec
seems to reference various
European standards so I
question whether they will have
NFRC labels. The following are
acceptable methods under the
2015 IECC to verify fenestration
U-factors as part of the building
thermal envelope. If not
providing NFRC labels for all
exterior doors and windows
(option 1), clarify how you will
document compliant U values:
1.NFRC certification; label
applied to window assembly and
verified at field inspection.
2.Default values from 2015 IECC
tables C303.1.3(1) C303.1.3(2),
R303.1.3(1), and R303.1.3(2).
3.Default values from Table 4
U-Factors for Various
Fenestration Products in 2013
ASHRAE Fundamentals
Handbook chapter 15, pg. 15.3.
To document the chain of
custody, a certificate, affidavit or
other evidence from the
manufacturer confirming
compliance with the above
method is required.
4.Calculation methods in 2013
ASHRAE Fundamentals
Handbook chapter 15, pg. 15.3:
“U-Factor (Overall Coefficient of
Heat Transfer)”. A calculation is
required for the standard NFRC
window size of 47.2” x 47.2”. To
document the chain of custody,
a certificate, affidavit or other
evidence from the manufacturer
confirming compliance with the
above calculation is required.
5.U-ratings by an
NFRC–accredited lab in
accordance with NFRC-100. To
document the chain of custody,
verification labels affixed to the
units by an accredited
independent inspection agency
or a certificate, affidavit or other
evidence from the manufacturer
confirming compliance with the
above simulation or testing.
cs 77 lr.pdf (1)
TECHNICAL CHARACTERISTICS
Style variants FUNCTIONAL RENAISSANCE HIDDEN VENT
Min. visible width inward opening window Frame 51 mm 51 mm 76 mmVent33 mm 33 mm not visible
Min. visible width outward opening window Frame 17.5 mm --Vent 76 mm --
Min. visible width inward opening flush door Frame 68 mm --Vent 76 mm --
Min. visible width outward opening flush door Frame 42 mm --
Vent 102 mm --Min. visible width T-profile 76 mm 76 mm 126 mm
Overall system depth window Frame 68 mm 77 mm 68 mmVent77 mm 86 mm 72.5 mmRebate height 25 mm 25 mm 18.5 mmGlass thickness up to 53 mm up to 53 mm up to 48 mmGlazing method dry glazing with EPDM or neutral silicones
Thermal insulation 32 mm omega and/or hollow chamber –shaped fibreglass reinforced polyamide stripsHigh Insulation variant (HI)Available Available Not Available
High Insulation Plus variant (HI+)Available Not Available Not Available
PERFORMANCESENERGYThermal insulation (1)EN ISO 10077-2 Uf-value down to 1.2 W/m²K depending on the frame/vent combination and the glass thickness.COMFORTAcoustic performance (2) EN ISO 140-3; EN ISO 717-1 Rw (C; Ctr) = 36 (-1; -4) dB / 42 (-2; -4) dB, depending on glazing type
Air tightness, max. test pressure (3)EN 1026; EN 12207 1 (150 Pa)2 (300 Pa)3 (600 Pa)4 (600 Pa)Water tightness (4)EN 1027; EN 12208 1A(0 Pa)2A(50 Pa)3A(100 Pa)4A(150 Pa)5A(200 Pa)6A(250 Pa)7A(300 Pa)8A(450 Pa)9A(600 Pa)E900(900 Pa)Wind load resistance, max. test pressure (5)EN 12211; EN 12210
1(400 Pa)2(800 Pa)3(1200 Pa)4(1600 Pa)5(2000 Pa)Exxx(> 2000 Pa)
Wind load resistance to frame deflection (5)EN 12211; EN 12210 A(≤ 1/150)B(≤ 1/200)C(≤ 1/300)
SAFETYBurglar resistance (6)EN 1627-1630 RC 1 RC 2 RC 3
Fire resistance (7)- EN 13501-2, EN 1364-1, EN 1634-1
- NEN 6069
EI 30EI 60, EI 45EW 30
This table shows possible classes and values of performances. The values indicated in red are the ones relevant to this system.(1) The Uf-value measures the heat flow. The lower the Uf-value, the better the thermal insulation of the frame.(2) The sound reduction index (Rw) measures the capacity of the sound reduction performance of the frame.(3) The air tightness test measures the volume of air that would pass through a closed window at a certain air pressure.(4) The water tightness testing involves applying a uniform water spray at increasing air pressure until water penetrates the window.(5) The wind load resistance is a measure of the profile’s structural strength and is tested by applying increasing levels of air pressure to simulate the wind force. There are up to five levels of wind resistance (1 to 5) and three deflection classes (A,B,C). The higher the number, the better the performance.(6) The burglar resistance is tested by statistical and dynamic loads, as well as by simulated attempts to break in using specified tools.(7) The performance is defined by directly exposing the construction to fire in order to determine the stability, thermal insulation and radiation insulation over a certain amount of time.(8) The bullet resistance of the window or door is evaluated for different classes of weapons and ammunition: hand guns, (automatic) rifles and shot guns.REYNAERS ALUMINIUM NV/SA • www.reynaers.com • info@reynaers.com 06/2017 – 0H0.08C2.00 – Publisher Responsible at Law: E. Fonteyne, Oude Liersebaan 266, B-2570 Duffel
Bullet resistance (8)EN 1522 FB 1 FB 2 FB 3 FB 4 FB 5 FB 6FSGKalashnikov
Verify that the new proposed windows and doors will be NFRC stickered at inspection so thatwe can verify the U values claimed on the ResCheck (this applies to all windows installed onthis project). This spec seems to reference various European standards so I questionwhether they will have NFRC labels. The following are acceptable methods under the 2015IECC to verify fenestration U-factors as part of the building thermal envelope. If notproviding NFRC labels for all exterior doors and windows (option 1), clarify how you willdocument compliant U values:
1.NFRC certification; label applied to window assembly and verified at field inspection.2.Default values from 2015 IECC tables C303.1.3(1) C303.1.3(2), R303.1.3(1), andR303.1.3(2).3.Default values from Table 4 U-Factors for Various Fenestration Products in 2013 ASHRAEFundamentals Handbook chapter 15, pg. 15.3. To document the chain of custody, acertificate, affidavit or other evidence from the manufacturer confirming compliance with theabove method is required.4.Calculation methods in 2013 ASHRAE Fundamentals Handbook chapter 15, pg. 15.3:“U-Factor (Overall Coefficient of Heat Transfer)”. A calculation is required for the standardNFRC window size of 47.2” x 47.2”. To document the chain of custody, a certificate, affidavitor other evidence from the manufacturer confirming compliance with the above calculation isrequired.5.U-ratings by an NFRC–accredited lab in accordance with NFRC-100. To document thechain of custody, verification labels affixed to the units by an accredited independentinspection agency or a certificate, affidavit or other evidence from the manufacturerconfirming compliance with the above simulation or testing.