HomeMy WebLinkAboutFile Documents.845 Meadows Rd.0048.2018 (18).ACBKAspen Meadows Reception Renovation + Pavilion Addition
Drawing set revisions post permit issuance
4/12/2018
GENERAL NOTES:
1. Surprises upon demolition of existing conditions since the building was constructed in 1958.
2. Most existing roof drain lines and plumbing lines were either clogged or disintegrated. We had
to become creative to fix the issues after demolition.
a. Existing roof drainage needed to be revised to route back to existing drywell.
3. Minor lighting revisions as it did not work with existing concrete structure and actual MEP
routing.
CIVIL:
1. GENERAL NOTE: This updated set has already been submitted to Mike Horvath on 3/22/2018
2. Additional downspout at existing terrace / catwalk to new pit.
3. Three revised lower level terrace drain locations
4. East curved wall location confirmation
5. Arrival court landing / stair / access bridge location confirmation
ARCHITECTURAL:
· Sheet A0.02
a. Revised or added sheets clouded
· Sheet Egress 1
a. Revised egress path
· Sheet Egress 2
a. Revised egress path
· Sheet A2.00, A2.01 and A2.02
a. Plumbing wall revisions between 005 and 006.
b. Mechanical 007 was not big enough for mechanical equipment designed. Revised.
c. Rated wall clarification in Boiler 009, Electrical 001 and Communication 002
d. Top of slab number verification
e. West wall in locker rooms 005 + 006. Water infiltration. Revised detail 3/A6.06.1
· Sheet A2.10, A2.11 and A2.12
a. Clarify rated walls at Stair 02 and Storage 116-A
b. Clarify rated walls at Mechanical 111
c. Existing Dining Area Fireplace storage millwork under existing fireplace
d. No insulation or waterproofing shown after demolition of wall on Gridline D. Revised
detail / assembly.
e. Added non-latching / locking doors at Dining 104.
· Sheet A2.20, A2.21 and A2.22
a. Revised Men Restroom 213 (Toilet and urinal)
b. Revised Women Restroom 209 (Toilet)
c. Exterior terrace guardrail clarification
d. Dimensional clarification for Shaw
· Sheet A2.30, A2.31 and A2.32
a. All roof drain locations
· Sheet A3
· Sheet A5.01 and A5.02
a. Interior soffit clarification
· Sheet A6.01
a. W4 Assembly revised to NON-1 HOUR.
· Sheet A6.06.1
a. Additional details per field conditions
· Sheet A6.09
a. Interior soffit clarification
· Sheet A6.09.1
a. Accordion wall replacement between 104 and 105.
· Sheet A6.30, A6.31, and A6.32
a. Elevator details
· Sheet A6.40
a. Curved wall details
STRUCTURAL:
· Sheet S0.00
o Added or revised sheets as bubbled
· Sheet S1.00
o Outdoor Grill Concrete Counter structure
· Sheet S2.00, S2.01 and S2.02
o Removed support line at Grid A.5 per existing conditions.
o Removed footing and column at Grid X.A.5
· Sheet S2.10, S2.11 and S2.12
o Combined and revised footing at Grid B.6
o Added pan deck at Grid A.5 and 2
· Sheet S2.20, S2.21 and S2.22
o Reinforce existing and add screening
o Reinforce storage roof
o Revised existing floor elevation heights and associated new steel
o Revised framing per existing conditions
· Sheet S2.30, S2.31
o Revisions for attachment of existing catwalk to be reused and guardrail.
o Showing height of mechanical equipment + screening
o Mechanical Heights and Screening location being processed by City Council
· Sheet A3.01, A3.02, A3.03
o Showing heights on screening
o Screening location and heights being processed by City Council
· Sheet S5.1
o Added insulation to existing foundation (Detail 7 / S5.1)
· Sheet S5.4
o Wall to Pan Deck Connection revision (Detail 7/S5.4)
· Sheet S5.6
o Concrete T to Concrete Pan Deck (Detail 12 / S5.6)
· Sheet S5.7
o Revised detail
· Sheet S5.8
o Revised detail
MECHANICAL:
· Sheet M1.01:
o Added electric resistance baseboards, and ventilation air hot water coil at Meadows
Banquet Kitchen Offices
o Revised EA, OA, S, and R louver and grille specs
o Revised pump specs and configuration
o Changed Staff Break Rm from supply fan, to exhaust fan
o Changed from in-line EF at Pavilion to ceiling units
o Added “Future” ceiling cassettes to Pavilion basement
o Rooftop kitchen equipment changes for spatial rearrangement (15’ setback, and height
limitations)
o Removed hydronic in-floor radiant heating from basement zones, and added existing
zone for Plato’s Dining
o Added mixing valves, and updated specifications
o Updated expansion tank and air/dirt separator specifications
· Sheet M1.02:
o FC-4, 5 - add cooling
o FC-10, 11 - Future planning for Pavilion
o Add a DHW recirculation zone, and reconfigure DHW piping configuration
o Redundant HW and CW piping configurations
o Meadows Banquet Kitchen hood height detail
· Sheet M2.00, M2.01, M2.02:
o Moved A/V racks to alternate locations, along with FC-2 (change spec)
o Move EA ducting and louver location, add CFM, change size
o Modify AHU ducting to work with existing structure
o Move OA ducting and louver locations, reduce CFM, changes sizes
o Changed Staff Break Rm from supply fan, to exhaust fan
o Delete basement radiant heating zones
o Add electric resistance heat to basement Pavilion stairwell
o Added fire damper note at Mech Rm wall penetration of EA duct
· Sheet M2.10, M2.11, M2.12:
o Meadows Banquet Kitchen MAU ducting and diffuser configuration change, to work
with existing structure
o Move KH-6, and change EA duct routing/size
o Add HWC-1 at OA vent for Offices
o Change FC-9 spec for A/V rack cooling and office heating
o Change AHU-4 equipment and ducting configuration to work with existing structure
· Sheet M2.20, M2.21, M2.22:
o Rearrange Banquet roof equipment locations, per 15’ setback requirements
Changed equipment specifications to meet clearance requirements
o Revise Plato’s Kitchen MAU ducting and diffuser configuration to work with structure
and kitchen layout
o Change KH-9 hood EA collar connection, duct routing/size change
o AHU-6 orientation and ducting configuration change to better work in space
o Moved FC-2 to A/V Rack location; changed unit spec
o Moved FC-8 in Lounge to work with Bar configuration, and change spec (not ducted)
o Delete EA duct chase and exterior custom louver at Pavilion
· Sheet M2.30, M2.31:
o Change rooftop equipment configuration, locations, and equipment specs to work with
15’ setback and duct routing
o Change AHU-5 location, specification, duct routing, and RA grille configuration
ELECTRICAL:
· Sheet E1.00:
o Sheet List includes addition of E1.04: Electrical Schedules
o Sheet List includes additions of E3.00 through E3.22: Lighting design
o Sheet List includes additions of E4.00 through E4.22: Emergency Lighting design
o Updated Lighting symbol to match background format
· Sheet E1.01:
o Revised One-Line Diagram per site coordination and panel locations
o Service size increased from 1000A at 208V/120, 3Ø to 1200A at 208V/120, 3Ø
o Main Distribution Panel, MDP, reconfigured to accommodate additional sub-panel and
large motor load distribution previously occurring at House Panel, HP
o Addition of sub panel, S1, to accommodate new and existing site loads and site lighting
loads
o Updated elevator electrical design requirements per provided manufacturer cut sheets
o Associated feeders, grounding schematic, and short circuit calculations updated per
changes above.
· Sheet E1.02:
o Panel MK:
Added supplementary 30kW booster heater to dishwasher; revised associated
circuiting
Revised KEF electrical requirements; revised associated circuiting
Added Captive Air exhaust hoods and provided circuiting
Revised gas island cooking from junction box supply to manufacturer built-in
sub-panel for gas cooking loads and controls; revised associated circuiting
Added heated soak tank system and provided associated circuiting
o Panel PK:
Revised panel rating from 150A at 208/120V, 3Ø to 200A 208/120V, 3Ø per
changes below:
Revised dishwasher electrical requirements for built-in booster heater supply
Revised KEF electrical requirements
Added Captive Air exhaust hood
Added several undercounted refrigerators and freezers
Added heated soak tank system
o Panel HP
Revised panel rating from 600A at 208/120V, 3Ø to 200A 208/120V, 3Ø per
changes below:
Relocated sub feeds for panels P0, P1, P2, M1 and passenger elevators EL-1, EL-
2 to MDP
Added sub feed for new panel S1
Relocated AV equipment feed to Panel P2
Revised heat tape distribution
Added elevator sump pumps
Added various mechanical pumps and exhaust fans
o Panel M1
Revised panel rating from 150A at 208/120V, 3Ø to 200A 208/120V, 3Ø per
changes below:
Added electrical requirements for walk-in coolers CU-1 and CU-2 evaporators
and associated fans
Added electrical requirements for walk-in coolers CU-3 and CU-4 condensers,
evaporators, and associated fans
Redistributed heat tape loads to other sub panels
· Sheet E103:
o Panel P0:
Added electric resistance heater, EH-2
Added fan coils FC-1, FC-10, FC-11
Added sump pump, SP-2, and lift station, LS-1
Added motorized shades for lower level pavilion
o Panel P1:
Added fan coils FC-5 (with supplementary electric resistance heating), FC-6 (with
supplementary electric resistance heating), and FC-9
Added ventilator, SF-1
Added electric resistance heater EH-1
Added electric resistance buffet warmers At Meadow’s Dining
o Panel P2:
Increased panel rating from 100A at 208/120V, 3Ø to 150A 208/120V, 3Ø per
changes below:
Revised and added various small appliance loads associated with Hefner Lounge
bar
Added air handler AHU-5 and fan coils FC-2, FC-7 and FC-8
Added existing motorized shade loads at Plato’s Dining
o Panel S1 added:
Added existing irrigation controls and water feature pump
Added existing and new exterior lighting loads
Distributed heat tape loads from Panel HP
o Updated Kitchen Appliance Schedules per panel changes noted above
· Sheet E104:
o Updated Mechanical Equipment Schedule per panel changes noted above
· Sheet E2.00, E2.01, E2.02:
o Rearranged distribution panel locations in Electrical Room per site coordination
o Added CU-x indoor units and circuited
o Re-circuited elevators and associated sump pumps
o Added electric resistance heat to basement pavilion stairwell
o Added civil site storm sump pump and plumbing lift station; circuited pumps
o Added ceiling cassette fan coil units throughout
o Revised receptacle circuiting throughout
· Sheet E2.10, E2.11, E2.12:
o Added indoor evaporation units for coolers; circuited units
o Added ceiling cassette fan coil units throughout
o Revised receptacle circuiting throughout
o Moved Panel M1, added Banquet suite panel
o Revised Meadows Dining receptacle circuiting
o Revised Meadows Kitchen equipment layout and circuiting requirements
o Added electric heat to FC-5, 6; revised circuiting
o Added receptacles to Pavilion; Provided junction boxes at Pavilion for motorized shades
· Sheet E2.20, E2.21, E2.22, E2.30, E2.31:
o Added outdoor condensing units for coolers; circuited units
o Added receptacle circuiting at Plato’s Dining for shade motors; switching and circuiting
o Revised Roof equipment layout and specs; revised circuiting
o Revised Lounge Bar layout, equipment loads and circuiting
o Revised Plato's Kitchen equipment layout and circuiting requirements
o Moved FC-8 per Mechanical plans; updated circuiting
o Provided junction boxes for Pavilion sky lighting shade motors
o Added heat trace receptacles, line routing, and circuiting
· Sheet E3.00 through E4.22:
o Provided lighting layout and controls throughout
o Provided emergency lighting layout and additional remote battery supplies throughout
o Provided exit sign locations throughout, coordinated fire panel and annunciator panel
locations
PLUMBING:
· Sheet P1.00:
o Update Water Service size and equipment specs, based on fire suppression design,
plumbing fixture selections, and available meter connection sizes
o Provide a Heated Water Supply Piping Detail
· Sheet P2.00, P2.01, P2.02:
o Add water service floor sink (FS-3)
o Reroute drain to hall slab, and around coolers
o Add FS-1 @ AHU-2 room
o Move sanitary force main from Pavilion tie-in location to work with existing structure
o Add SP-2 civil site sump pump/basin at Pavilion Mech Rm
· Sheet P2.10, P2.11, P2.12:
o Banquet Kitchen grease drain routing to work with existing structure and coolers
Add a couple drains (PCU’s, hood wash-down, etc.)
Move TS-1 trench drain due to structural conflict
Add solids interceptor for food grinder drain routing to grease interceptor
o Add drain stack from Lounge Bar above, and vent configuration at Barnhardt Dining
· Sheet P2.20, P2.21, P2.22:
o Plato’s Kitchen grease drain routing to work with existing structure and coolers
Add/Move a couple drains (PCU’s, hood wash-down, etc.)
Move TS-1 trench drain due to structural conflict
Add solids interceptor for food grinder drain routing to grease interceptor
o Move Women’s Bathroom WC-1’s to North wall; update W&V config.
o Lounge Bar drain routing and stack location
· Sheet P2.30, P2.31:
o Move PCU-2 and VTR locations
· General Piping Sheet Changes:
o Final routing per Contractors per field coordination
o Updated sizes per REG plans
o Change from domestic Manifold distribution to Branch method. Branch sizing per
Contractor
· Updated W&V Isometric diagram per changes listed above