HomeMy WebLinkAboutFile Documents.805 Bonita Dr.0005.2018 (6).ARBK POB 3662 Aspen, CO 81612 Phone 720 481 7353 February 16, 2018 RE: Responses to Building Comments 1 sent by Justin Hahn February 16, 2018 re: 805 Bonita Drive. Permit # 0005.2018.ARBK Responses; Comment #1 We are proposing to replace all the siding on the unit. We intend to replace the air infiltration barrier with a new one as well. An assembly detail with this information and what is to remain / replaced is provided on sheet A1.06 detail 2. Existing flashing is to remain. Comment #2 Safety glazing for the shower window has been noted on sheet A1.06 drawing. Comment #3 We are not proposing new mechanical equipment with the proposed scope of work. Existing mechanical equipment is to remain unchanged. Note 6 has been revied on sheet A1.07 Comment #4 A note on sheet A1.08 has been added noting there is no proposed work on the upper level lighting Comment #5 Sheet A1.09 has been revised to note that replacement doors must have a max U value of 0.28 Please let me know if there is anything else I can provide. All the best, Ralph Dupps R A L L Y D U P P S I I I I I I I a r c h I t e c t 02/21/2018 NEW WALK IN PANTRY WITH SHELVING BEDROOM 108 SHOWER 104 BENCHBATH 105 W/C 107 DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF BEAM ABV.DASHED LINE OF ROOF ABV. NEW DOOR TILE CPT. TILE CPT.STEPSTEP LIVING ROOM 101 KITCHEN 102 LAUNDRY 103 EXTERIOR DECK 115 DECK 113 ON GRADE DECK 114 GARAGE 110 MECHANICAL 111 CLOS. ENTRY HALL 109 GAS APPLIANCE FIREPLACE EXTERIOR MECH. 112 STEP NEW 30" RANGE OVEN EXISTING SINK NEW 24" DW NEW DRYER NEW WASHING MACHINE NEW FRONT DOOR NEW TILE FLOORING NEW TILE FLOORING NEW SLIDING DOORS REPLACE EXISTING DECKING WITH NEW COMPOSITE DECKING REF. SHEET A1.07 NOTE 29 ADD ELECTRIC BASEBOARD HEAT TRASH STONE HEARTH NEW TILE FLOORING NEW TILE FLOORING NEW CARPET NEW TILE FLOORING UP STAIR 116 TILECPT.REF. DRAWING A1.06 FOR GENERAL PLAN NOTES CLOSET 106 NEW 36" REF. NEW TILE FLOORING 01 02 01 03 SAFETY GLASS SAFETY GLASS SAFETY GLASS SUPERINSULATED ROOF ASSEMBLY ABOVE ENTRY HALL 109: REPLACEMENT COMPOSITE EXTERIOR DECKING OVER EXISTING W.P. ROOFING OVER EXISTING ROOF SHEATHING AND FRAMING OVER FULL CAVITY DEPTH CLOSED CELL EXPANDING SPRAY FOAM INSULATION OVER (CLASS II VAPOR RETARDER) OVER 1HR FIRE RATED 5/8" TYPE X GWB INSULATED WALL ASSEMBLY AT GARAGE 110: NEW 5/8" TYPE X 1 HR FIRE RATED GWB OVER 6 MIL. POLY VAPOR BARR . OVER EXISTING WOOD STUD FRAMING OVER FULL CAVITY DEPTH CLOSED CELL FOAM INSULATION NEW TILE FLOORING 0303 04 05 06 5'-6"5'-9 3/4"2'-10 3/4"3 1/2"3'-0 3/4" 6'-3"2'-6"3 1/2"803 BONITA DRIVE UNIT 2 805 BONITA DRIVE UNIT 1 SCOPE OF WORK TO ADD FULL CAVITY DEPTH CLOSED CELL FOAM INSULATION TO EXISTING FRAMING: CO CO SD SD SD REPLACE GLASS. REF. SHEET A1.07 NOTES 26 AND 27 REPLACE EXTERIOR SIDING REF. SHEET A1.07 NOTE 28 AND DETAIL 2/A1.06 REPLACE EXISTING GLASS WITH SAFETY GLAZING TYPICAL EXTERIOR WALL REPAIR ASSEMBLY: (N) 3/4" FINISH SIDING - REF. ELEVATIONS - OVER (N) AIR INFILTRATION BARRIER (DU PONT TYVEK OR SIM.) OVER (E) 1/2" OSB PWD. SHEATHING OVER (E) 2x6 WOOD STUD WALL OVER (E) INSULATION - IF EXISTING GWB IS TO BE REPLACED: OVER (N) 6 MIL. POLY VAPOR BARRIER OVER (N) 5/8" TYPE X GWB FOR 1HR FIRE RATED CONST. - REF. INTERIORS ALL EXISTING METAL FLASHING IN GOOD CONDITION IS TO REMAIN. (N) = NEW (E) = EXISTING TO REMAIN INTERIOREXTERIOR 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.06 PROPOSED PLAN c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates: NORTH PROPOSED MAIN LEVEL PLAN 1 A1.06 1/4" = 1'-0" NOTE: NO FLOOR AREA CHANGES ARE PROPOSED REPLACEMENT SIDING ASSEMBLY2 A1.06 3" = 1'-0" 02/21/2018 02/21/2018 justinh BEDROOM 201 OPEN TO BELOW CLOSET 209 CLOSET 202 BATH 203 SHOWER 204 BENCH CLOSET205CLOSET206BUILT IN CABINETOFFICE 207 EXTERIOR UNCOVERED DECK 210 HALL 208 DASHED LINE OF CEILING ABV.DASHED LINEOF CEILING ABV.DN STAIR 116 NEW COUNTER TOP NEW TILE NEW TILE IN SHOWER NEW CARPET NEW CARPET NEW CARPET CPT. TILE TILE CPT. NEW CARPET NEW CARPET 803 BONITA DRIVE UNIT 2 805 BONITA DRIVE UNIT 1 REPLACE GLASS. REF. SHEET A1.07 NOTES 26 AND 27 REPLACE EXISTING DECKING WITH NEW COMPOSITE DECKING. REF. SHEET A1.07 NOTE 29 REPLACE EXTERIOR SIDING REF. SHEET A1.07 NOTE 28 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.07 PROPOSED PLAN c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates: NORTH PROPOSED UPPER LEVEL PLAN 1 A1.07 1/4" = 1'-0" NOTE: NO FLOOR AREA CHANGES ARE PROPOSED GENERAL PLAN NOTES: 1. ALL DIMENSIONS SHOWN ARE TO BE VERIFIED IN FIELD. DO NOT SCALE DRAWINGS. GENERAL CONTRACTOR IS TO VERIFY ALL PROPERTY LINES WITH SURVEYOR PRIOR TO CONSTRUCTION OF FOUNDATION - ALL SETBACKS SHOWN HERE ARE DERIVED FROM THE SURVEYOR, WHICH IN TURN ESTABLISH THE BUILDING FOOTPRINT INCLUDING ANGLED PORTIONS OF THE BUILDING FOOTPRINT. IN CASE OF DIMENSIONAL CONFLICT, PLEASE CONSULT ARCHITECT. 2. EXTERIOR OF LOWER LEVEL CONC WALLS (IF ANY) TO ALIGN WITH WOOD FRAMED WALLS ABOVE. 3. ALL WOOD STUD WALLS ARE TO BE EITHER 2x4 OR 2x6. REFER TO ARCH. DRAWINGS FOR WALL THICKNESS. ALL EXTERIOR AND LOAD BEARING WALLS ARE TO BE 2x6. 4. VERIFY ALL DOOR AND WINDOW R.O. DIMENSIONS W/ DOOR AND WINDOW SCHEDULES 5. IF BASEMENT EXIST, ALL LOWER LEVEL EXTERIOR CONC. WALLS ARE TO BE 8" THICK PLUS 2" FOR FURRING STRIPS AND INSULATION U.N.O. 6. ALL EXISTING MECHANICAL IS TO REMAIN UNCHANGED. 7. CITY BUILDING OFFICIAL SHALL DETERMINE IF SPRINKLER SYSTEM IS REQUIRED. IF REQUIRED, GEN CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLIANCE W/ CODE. 8. ALL FINISH MATERIALS ARE TO BE LOW TOXIC 9. ALL SHEATHING IS TO BE OSB AND / OR RECYCLED CONTENT SHEATHING SUCH AS THERMO-PLY OR EQUIVALENT - REF. STRUCTURAL 10. REF. CIVIL DRAWINGS FOR RIGHT OF WAY IMPROVEMENTS SUCH AS SIDEWALKS, CURB, GUTTER, AND OTHER IMPROVEMENTS. 11. REFER TO CIVIL ENGINEERING PLAN FOR ALL DRYWELL SIZES, LOCATIONS, AND CONFIGURATION. REF. CIVIL ENG. FOR ROUTING OF ALL WATER FROM ROOF AND ALL OTHER SURFACE AREAS. REF. GRADING AND CIVIL DRAWINGS FOR LOCATION, CONFIGURATION AND ALL OTHER INFORMATION PERTAINING TO DRAINING AND SURFACE SLOPES TO THESE DRAINS. 12. PROVIDE SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AS REQUIRED BY CODE - REF. ELECTRICAL PLAN 13. ALL GRID LINES ARE TO OUTSIDE FACE OF FRAMING UNLESS NOTED OTHERWISE. 14. PROVIDE RADON MITIGATION PER PASSIVE RADON SYSTEM USING DRAIN TILE LOOP AS DETAILED IN 2015 IRC - REF. ARCH. DETAILS 15. REF. ARCH. SITE PLAN FOR SNOWMELT AREAS. REF. MECHANICAL FOR REMP CALCULATIONS 16. SLOPE FINISH FLOOR FOR ALL FLOOR DRAINS AT 1/8" PER 12" MIN. SLOPE ALL DECKS, PORCHES, BALCONIES AND ALL OTHER EXTERNAL OR EXPOSED FLOORS AT 1/8" PER 12" MINIMUM W. DIRECTION OF SLOPE AS SHOWN ON DRAWINGS 17. ALL T.O. FLOOR ELEVATIONS AT SLOPING AREAS ARE SHOWN AT THE HIGHEST POINT. 18. REF. ARCH. ROOF PLANS / BUILDING ELEVATIONS FOR ROOF GUTTER AND DOWNSPOUT LOCATIONS 19. CARBON MONOXIDE AND SMOKE DETECTOR LOCATIONS SHALL COMPLY PER ASPEN MUNICIPAL CODE CH 8.15. REF. FLOOR PLANS 20. TOILET AND BATH FIXTURE CLEARANCES AND SAFETY GLAZING SHALL COMPLY PER IRC R307.1, R308.4 21. SAFETY GLAZING SHALL COMPLY PER IRC R308.4 22. DOOR SWINGS AND FLOOR LEVELS SHALL COMPLY PER IRC R311 23. EXTERIOR LANDINGS, LANDING SURFACE SLOPE SHALL COMPLY PER IRC R311 24. STAIRS AND RAMPS, DIRECTION OF TRAVEL, HANDRAILS, MUST RETURN, GURADRAILS SHALL COMPLY PER IRC R311 25. DWELLING SEPARATION AND FIRE RATED ASSEMBLIES SHALL COMPLY PER IRC R301.3 26. TYPICAL THROUGHOUT UNIT 1: ALL FAILED WINDOW GLASS TO REPLACED WITH NEW TO FIT WITHIN EXISTING FRAME AND SASH OPENINGS. 27. GLASS ONLY REPLACEMENT IS CONSIDERED A REPAIR UNDER R504 OF THE IECC AND DOES NOT HAVE A U VALUE REQUIREMENT. 28. ALL EXTERIOR SIDING TO BE REPLACED WITH NEW WEATHER RESISTANT PAINTED OR TREATED WOOD SIDING. VERIFY WOOD SPECIES AND FINISH COLOR WITH OWNER AND GENERAL CONTRACTOR 29. ALL EXISTING DECKING THAT NEEDS REPLACEMENT WILL BE REPLACED WITH WEATHER RESISTANT COMPOSITE DECKING. REF. OWNER AND GENERAL CONTRACTOR FOR SPECIFICATION. 02/21/2018 02/21/2018 justinh ROOM #FIXT. RESIDENTIAL LIGHTING SCHEDULE # MANUF.TYPE IC RATED A B MODEL NO LAMP FIXTURE RATING TBD TBD LED SLOPED CLG. RECESSED IC RATED CAN 12W LED 15 W TBD TBD UNDER COUNTER LED STRIP LIGHTING INTERNAL LED 12 W PER FT. C TBD NO35 WTBD6" X 36" FLUORESCENT SURFACE MOUNT T5 FLUORESCENT QUANTITY HIGH EFF. QUANTITY OTHER SWITCH W/ DIMMER WHERE POSSIBLE AC PHONE / TV / CABLE / INTERNET / SATELLITE HOOKUP F JUNCTION BOX 3 WAY (OR MORE) SWITCH W/ DIMMER WHERE POSSIBLE EXHAUST FAN 220 SMOKE DETECTOR BY CODE OUTLET LOW VOLTAGE CABLE LIGHTING CO2 DETECTOR BY CODE F S J WALL MOUNTED LIGHT AIR CONDITIONING UNIT W/ EXT. COMPRESSOR CEILING FAN 220 VOLT OUTLET GFI / AFCI AND/OR WATERPROOF OUTLET PER 2014 NEC S3 SD W.P. LANDSCAPE WALL OR POLE MOUNTED LIGHT CO LIGHTING LEGEND SYMBOL AND DESCRIPTION CEILING MOUNTED FLUORESCENT CEILING MOUNTED SPEAKER WP CEILING MOUNTED WITH DIRECTIONAL TRIM WP CEILING MOUNTED RECESSED CAN W.P. LANDSCAPE GROUND SURFACE MOUNTED LIGHT UNDER CABINET LED STRIP LIGHTING TS SWITCH ON TIMER JAMB SWITCHJS FLOOR OUTLETF DIMMER SWITCHDS NO CEILING MOUNTED RECESSED CAN WITH WET LOCATION TRIM ADD NEW LIGHTS INTO EXISTING KITCHEN LIGHTING CIRCUIT NEW LOCATION FOR EXISTING REF. OUTLET BEDROOM 108 SHOWER 104 BATH 105 W/C 107 LIVING ROOM 101 KITCHEN 102 LAUNDRY 103 EXTERIOR DECK 115 GARAGE 110 MECHANICAL 111 CLOS. ENTRY HALL 109 GAS APPLIANCE FIREPLACE EXTERIOR MECH. 112 STAIR 116 CLOSET 106 S EXISTING BEDROOM SWITCH IN NEW LOCATION TO EXISTING LIGHTING S C A B B NEW ELECTRIC BASEBOARD HEAT - STUB INTO EXISTING 220V S D TBD TBD LED WALL SCONCE 12W LED 15 W NO GENERAL NOTES: ALL LIGHTING SHALL COMPLY WITH 2014 NEC, 2015 IECC, PROVIDE LIGHT REDUCTION CONTROLS PER 2015 IECC C405.2.2.2 ALL BULBS ARE TO BE 12W LED ONMIDIRECTIONAL BULBS, UNLESS NOTED OTHERWISE PLEASE NOTE THAT THERE IS NO LIGHTING PROPOSED WITHIN AN INSULATED EXTERIOR ROOF. THEREFORE IC RATED CANS ARE NOT REQUIRED. TOTAL PERCENTAGE HIGH EFFICIENCY PER 2015 IECC R404.1 :MIN 75% <100 % HIGH EFFICIENCY 0SUBTOTAL D S F B WP A A S CONNECT TO EXISTING LIGHTING IN LIVING RM. 101 A A A A D D WP WP WP WP EXISTING DUPLEX OUTLETS TO REMAIN ELECTRICAL PLAN NOTES 1. ELECTRICAL / HVAC PLAN IS SCHEMATIC IN NATURE. FINAL PLAN LAYOUT BY THE APPROPRIATE CONTRACTOR TO MEET ALL CURRENT CODES. 2. VERIFY ALL FIXTURE LOCATIONS AND PRODUCTS WITH OWNERS 3. SWITCHING SHOWN ARE SCHEMATIC, ELECTRICIAN TO REVIEW WITH OWNERS EXACT SWITCHING REQUIREMENTS AND LOCATIONS 4. INSTALL OUTLETS AS REQUIRED BY OWNERS AND ELECTRICAL CODE. LOCATIONS AND QUANTITIES SHOWN ARE SCHEMATIC 5. LIGHTING PLAN IS SCHEMATIC. REFER TO FLOOR PLANS FOR TV AND LOW VOLTAGE LOCATIONS. VERIFY REQUIREMENTS WITH OWNER AND A/V SPECIALIST FOR TV, DATA AND SOUND SYSTEMS LOCATION, POWER SOURCE AND ANYTHING ELSE REQUIRED FOR THEIR FUNCTION. 6. LOCATION AND QUANTITY OF SMOKE DETECTORS BY ELECTRICAL CONTRACTOR AND LOCAL BUILDING CODE. 7. LOCATION, TYPE AND QUANTITY OF ELECTRICAL OUTLETS BY ELECTRICAL CONTRACTOR AND LOCAL BUILDING CODE. 8. ELECTRICAL SUBCONTRACTOR SHALL PROVIDE SURGE PROTECTION IN ALL AREAS THAT REQUIRE PROTECTION 9. ALL EXISTING DUPLEX OUTLETS ARE TO REMAIN UNLESS NOTED OTHERWISE. B CO CO SD SD SD 101, 102, 104, 105, 107 7 102, 103 13 106 1 105, 107 3 24 803 BONITA DRIVE UNIT 2 805 BONITA DRIVE UNIT 1 NOTE: NO PROPOSED LIGHTING CHANGES TO UPPER LEVEL 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.08 LIGHTING PLAN c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates: NORTH PROPOSED MAIN LEVEL LIGHTING PLAN 1 A1.08 1/4" = 1'-0" 02/21/2018 02/21/2018 justinh DOOR / WDW. SCHEDULE 1/4" = 1'-0" 1 A1.09 01 (EXTERIOR, SINGLE) PREMANUFACTURED EXTERIOR GLASS DOOR VERIFY SIZE W/ MFG. REF. PLANS FOR OPERATIONVERIFY 6'-8"VERIFY 3'-0"6'-8"02 (INTERIOR, SINGLE) FLAT SOLID CORE REF. PLANS FOR OPERATION 2'-8" DOOR SCHEDULE 6'-8"03 (INTERIOR, SINGLE) FLAT SOLID CORE REF. PLANS FOR OPERATION 2'-6" SAFETY GLASS 6'-8"04 (INTERIOR, DOUBLE) FLAT SOLID CORE BY PASS DOOR REF. PLANS FOR OPERATION 2'-6"2'-6" DOOR AND WINDOW SCHEDULE GENERAL NOTES: 1. NEW DOOR HARDWARE TO BE BRUSHED NICKEL BALDWIN OR EQUAL 2. INTERIOR DOORS ARE TO BE FLAT PANEL W/ A SOLID CORE OF MDF OR EQUIVALENT - REF. INTERIORS 3. INTERIOR DOORS ARE TO BE PRE HUNG W/ INTEGRAL HEAD & JAMB OF (4) 1/4 STOCK 4. ALL OPENINGS AND UNIT SIZES ARE TO BE VERIFIED IN FIELD BY CONTRACTOR IN ORDER TO INSURE PROPER FIT IN EXISTING, MODIFIED, OR NEW OPENINGS. 5. ALL WINDOW R.O. AND UNIT OPENINGS SHOWN ON THIS SCHEDULE ARE TO BE VERIFIED BY GENERAL CONTACTOR WITH MANUFACTURER AND COORDINATED WITH ALL SUBCONTRACTORS IN THE FIELD. 6. ALL MECHANICAL ROOM DOORS ARE TO BE 1 HR FIRE RATED WITH SELF CLOSING HARDWARE. 7. ALL WINDOW / DOOR EXTERIOR GLASS IS TO BE LOW E SQUARED, ARGON FILLED, & TEMPERED GLASS AS REQUIRED BY BUILDING CODE, ENERGY CODE 8. BEFORE ORDERING, THE GENERAL CONTRACTOR SHALL VERIFY ALL MODEL #'S, FRAME SIZE, AND MULLED WINDOW ASSEMBLIES WITH ARCHITECT AND WINDOW REP. THE GENERAL CONTRACTOR SHALL CONSULT WITH ARCHITECT SHOULD DISCREPANCIES OCCUR. ALL WINDOW R.O. AND UNIT OPENINGS ARE TO BE VERIFIED IN FIELD BY AFTER FRAMING IS COMPLETE AND PRIOR TO PLACING DOOR AND WINDOW ORDERS TO INSURE PROPER FIT IN EXISTING, MODIFIED, OR NEW OPENINGS. 9. ALL DOOR AND WINDOW OPERATION, MULLION AND MUNTIN PATTERS ARE TO BE COORDINATED WITH ARCHITECTURAL BUILDING ELEVATIONS. THESE ARE TO BE COORDINATED BY GENERAL CONTRACTOR WITH ARCHITECT AND WINDOW REP. ALL WINDOW ELEVATIONS SHOWN ARE MEASURED FROM INTERIOR FINISH FLOOR LEVELS TO THE BOTTOM OF THE WINDOW ROUGH OPENING 10. WINDOW AND DOOR FRAMES ARE TO INCLUDE O.E.M. NAILING STRIPS. 11. USE METAL FLASHING AT BOTH DOOR & WINDOW HEAD & JAMB LOCATIONS. USE BUILDING WRAP AIR INFILTRATION BARRIER AROUND WALLS OF ENTIRE STRUCTURE, WITH TAPED JOINTS. 6" PAST ROUGH OPENING, USE WATERPROOF TAPE AROUND WINDOW AND DOOR JAMBS AS A AIR INFILTRATION BARRIER. USE BUILDING WRAP AS BASE LAYER FOR DRAINAGE PLANE. SHINGLE BUILDING WRAP OVER RUBBER HEAD SILL TO ENSURE WATER IS KICKED OUT AWAY FROM HEADER. INSTALL METAL FLASHING PAN AT WINDOW SILLS OVER BUILDING WRAP AND FLASHING TAPE ON TOP OF BUILDING WRAP. 12. USE STANDARD DENSITY CLOSED CELL EXPANDING POLYURETHANE FOAM INSULATION TO PLUG GAPS BETWEEN THE FRAME AND WALL ROUGH OPENINGS AROUND ALL DOOR AND WINDOWS. 13. ALL WINDOW R.O. AND UNIT OPENINGS SHOWN ON THIS SCHEDULE ARE TO BE VERIFIED BY GENERAL CONTRACTOR WITH MANUFACTURER AND COORDINATED WITH ALL SUBCONTRACTORS IN THE FIELD. 14. OPERABLE WINDOW ACCESSORIES TO INCLUDE ALL HARDWARE AND CRANK EXTENSIONS AS NEEDED PER ELEVATIONS AND PER CODE AS REQUIRED FOR EGRESS. 15. REFER TO EXTERIOR BUILDING ELEVATIONS FOR MULLED WINDOW COMBINATIONS - TYP. 16. WINDOW ENEGY PERFORMANCE TO MEET REQUIREMENTS AS SPECIFIED BY ENERGY CALCULATIONS. 17. REFER TO EXTERIOR BUILDING ELEVATIONS AND FLOOR PLANS FOR ALL DOOR AND WINDOW QUANTITIES, SWINGS, OPERATION, MULLION AND MUNTIN PATTERNS, AND HANDING 18. ALL SHOWER DOORS ARE TO BE TEMPERED GLASS AS REQUIRED BY CODE. ALL HINGES AND FITTINGS ARE TO BE BRUSHED NICKEL OR EQUIVALENT, EUROPEAN STYLE HARDWARE, AND ABLE TO SWING IN BOTH DIRECTIONS FROM THE JAMB. 19. PLEASE REFER TO PLANS AND / OR THIS WINDOW SCHEDULE FOR EGRESS WINDOWS. ALL EGRESS WINDOWS ARE TO BE SIZED PER IRC. ALL WINDOWS LOCATED WITHIN LIGHT WELLS FOR THE LOWER LEVEL ARE TO MEET IRC FOR EGRESS, LIGHT AND VENTILATION 20. POCKET DOORS ARE TO USE 2X4 FRAMING EACH SIDE OF DOOR PASSAGE WAY ON FLAT. FRAMING SHALL BE ENGINEERED WOOD OR STEEL. DOORS TO INCLUDE TRACKING HARDWARE WITH GLIDE ROLLER BEARINGS AND SHALL BE ABLE TO BECOME ENTIRELY RECESSED WITHIN WALL CAVITY POCKET. 21. POCKET AND BY PASS DOOR BID TO INCLUDE FLUSH OR RECESSED DOOR HARDWARE AND POCKET DOOR JAMB MOUNTED DOOR PULL. 22. PROVIDE PRIVACY LOCK FOR ALL INTERIOR DOORS AT BEDROOMS AND BATHROOMS. 5'-0" 05 (EXTERIOR, DOUBLE) PREMANUFACTURED EXTERIOR GLASS DOOR VERIFY SIZE W/ MFG. REF. PLANS FOR OPERATIONVERIFY 6'-8"VERIFY 5'-0" SAFETY GLASS SAFETY GLASS WINDOW SCHEDULE NO NEW WINDOW FRAMES OR WINDOW SASHES ARE PROPOSED. ONLY FOGGED GLAZING IS PROPOSED TO BE REPLACED WITH NEW GLASS TO FIT WITHIN THE EXISTING SASH AND FRAME GLASS ONLY REPLACEMENTS ARE EXEMPT FROM U VALUE REQUIREMENTS PER IECC R504.2 06 (INTERIOR, SINGLE) TEMPERED GLASS SHOWER DOOR W/ TEMPERED GLASS PANELS VERIFY W/ INTERIORS REF. PLANS FOR OPERATION FOR DOOR PROVIDE EUROPEAN HARDWARE FINISH TBD 2'-6"7'-0"VERIFYV.I.F.VERIFY LINE OF FINISH FLOOR EXT. DOOR AND WINDOW U FACTOR: ALL REPLACEMENT DOORS = 0.28 MIN ENERGY CODE INTERIOR REMODEL GENERAL NOTES: 1. ENERGY EFFICIENCY U VALUES PER 2015 IECC TABLE R402.1.2 FOR CLIMATE ZONE 7 2. SKYLIGHT GLASS FOR UNITS LOCATED OVER HEATED AREAS IS TO BE DOUBLE PANE LOW E LAMINATED GLASS WITH ELECTRONICALLY OPERATED BLIND 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.09 DOOR AND WINDOW SCHEDULE c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates: 02/21/2018 02/21/2018 justinh 0005.2018.ARBK_BuildingComment1 Subject: PlanCheck Page Label: A1.06 PROPOSED PLAN Author: justinh File Name: 805 BONITA ARCHITECTURAL.pdf Are you proposing to reside the entire unit or just the one location on each level that you've noted? If the entire unit is being resided please provide a detail for the siding assembly showing what existing components are to remain (insulation/sheathing, etc) and a compliant weather/air barrier and flashing. 805 BONITA ARCHITECTURAL.pdf (5) Subject: PlanCheck Page Label: A1.06 PROPOSED PLAN Author: justinh File Name: 805 BONITA ARCHITECTURAL.pdf Because of this new shower this window is now required to be safety glazed. Please note this on the plan. Subject: PlanCheck Page Label: A1.07 PROPOSED PLAN Author: justinh File Name: 805 BONITA ARCHITECTURAL.pdf Are you proposing any new exterior mechanical equipment with this permit? If so please show it as I will need to verify compliant location for zoning's review. Subject: PlanCheck Page Label: A1.08 LIGHTING PLAN Author: justinh File Name: 805 BONITA ARCHITECTURAL.pdf Please verify that no lighting work is proposed for the upper level as no RCP was submitted for that level. If that is the case please specifically note that on this RCP. Subject: PlanCheck Page Label: A1.09 DOOR AND WINDOW SCHEDULE Author: justinh File Name: 805 BONITA ARCHITECTURAL.pdf All replacement exterior doors shall have a max U value of .28. Note the requirement or provide a cutsheet on the door. REPLACE EXTERIOR SIDING REF. SHEET A1.07 NOTE 28 PROP Are you proposing to reside the entire unit or just the one location on each level that you've noted? If the entire unit is being resided please provide a detail for the siding assembly showing what existing components are to remain (insulation/sheathing, etc) and a compliant weather/air barrier and flashing. NEW WALK IN PANTRY WITH SHELVING BENCHDASHED LINEOF ROOF ABV.NEW SHING CHINE Because of this new shower this window is now required to be safety glazed. Please note this on the plan. GENERAL PLAN NOTES: 1. ALL DIMENSIONS SHOWN ARE TO BE VERIFIED IN FIELD. DO NOT SCALE DRAWINGS. GENERAL CONTRACTOR IS TO VERIFY ALLPROPERTY LINES WITH SURVEYOR PRIOR TO CONSTRUCTION OF FOUNDATION - ALL SETBACKS SHOWN HERE ARE DERIVED FROM THESURVEYOR, WHICH IN TURN ESTABLISH THE BUILDING FOOTPRINT INCLUDING ANGLED PORTIONS OF THE BUILDING FOOTPRINT. INCASE OF DIMENSIONAL CONFLICT, PLEASE CONSULT ARCHITECT.2. EXTERIOR OF LOWER LEVEL CONC WALLS (IF ANY) TO ALIGN WITH WOOD FRAMED WALLS ABOVE.3. ALL WOOD STUD WALLS ARE TO BE EITHER 2x4 OR 2x6. REFER TO ARCH. DRAWINGS FOR WALL THICKNESS. ALL EXTERIOR AND LOAD BEARING WALLS ARE TO BE 2x6.4. VERIFY ALL DOOR AND WINDOW R.O. DIMENSIONS W/ DOOR AND WINDOW SCHEDULES5. IF BASEMENT EXIST, ALL LOWER LEVEL EXTERIOR CONC. WALLS ARE TO BE 8" THICK PLUS 2" FOR FURRING STRIPS AND INSULATIONU.N.O. 6. EXACT SPECIFICATIONS AND LOCATIONS OF ALL MECH. EQUIPMENT ARE TO BE DETERMINED BY MECHANICAL ENGINEER AND MECH.SUB CONTRACTOR. REF. MECHANICAL DRAWINGS7. CITY BUILDING OFFICIAL SHALL DETERMINE IF SPRINKLER SYSTEM IS REQUIRED. IF REQUIRED, GEN CONTRACTOR SHALL BERESPONSIBLE FOR COMPLIANCE W/ CODE.8. ALL FINISH MATERIALS ARE TO BE LOW TOXIC9. ALL SHEATHING IS TO BE OSB AND / OR RECYCLED CONTENT SHEATHING SUCH AS THERMO-PLY OR EQUIVALENT - REF. STRUCTURAL10. REF. CIVIL DRAWINGS FOR RIGHT OF WAY IMPROVEMENTS SUCH AS SIDEWALKS, CURB, GUTTER, AND OTHER IMPROVEMENTS.11. REFER TO CIVIL ENGINEERING PLAN FOR ALL DRYWELL SIZES, LOCATIONS, AND CONFIGURATION. REF. CIVIL ENG. FOR ROUTING OFALL WATER FROM ROOF AND ALL OTHER SURFACE AREAS. REF. GRADING AND CIVIL DRAWINGS FOR LOCATION, CONFIGURATION ANDALL OTHER INFORMATION PERTAINING TO DRAINING AND SURFACE SLOPES TO THESE DRAINS.12. PROVIDE SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AS REQUIRED BY CODE - REF. ELECTRICAL PLAN 13. ALL GRID LINES ARE TO OUTSIDE FACE OF FRAMING UNLESS NOTED OTHERWISE.14. PROVIDE RADON MITIGATION PER PASSIVE RADON SYSTEM USING DRAIN TILE LOOP AS DETAILED IN 2015 IRC - REF. ARCH. DETAILS15. REF. ARCH. SITE PLAN FOR SNOWMELT AREAS. REF. MECHANICAL FOR REMP CALCULATIONS16. SLOPE FINISH FLOOR FOR ALL FLOOR DRAINS AT 1/8" PER 12" MIN. SLOPE ALL DECKS, PORCHES, BALCONIES AND ALL OTHEREXTERNAL OR EXPOSED FLOORS AT 1/8" PER 12" MINIMUM W. DIRECTION OF SLOPE AS SHOWN ON DRAWINGS17. ALL T.O. FLOOR ELEVATIONS AT SLOPING AREAS ARE SHOWN AT THE HIGHEST POINT.18. REF. ARCH. ROOF PLANS / BUILDING ELEVATIONS FOR ROOF GUTTER AND DOWNSPOUT LOCATIONS19. CARBON MONOXIDE AND SMOKE DETECTOR LOCATIONS SHALL COMPLY PER ASPEN MUNICIPAL CODE CH 8.15. REF. FLOOR PLANS20. TOILET AND BATH FIXTURE CLEARANCES AND SAFETY GLAZING SHALL COMPLY PER IRC R307.1, R308.421. SAFETY GLAZING SHALL COMPLY PER IRC R308.422. DOOR SWINGS AND FLOOR LEVELS SHALL COMPLY PER IRC R311 23. EXTERIOR LANDINGS, LANDING SURFACE SLOPE SHALL COMPLY PER IRC R31124. STAIRS AND RAMPS, DIRECTION OF TRAVEL, HANDRAILS, MUST RETURN, GURADRAILS SHALL COMPLY PER IRC R31125. DWELLING SEPARATION AND FIRE RATED ASSEMBLIES SHALL COMPLY PER IRC R301.326. TYPICAL THROUGHOUT UNIT 1: ALL FAILED WINDOW GLASS TO REPLACED WITH NEW TO FIT WITHIN EXISTING FRAME AND SASHOPENINGS.27. GLASS ONLY REPLACEMENT IS CONSIDERED A REPAIR UNDER R504 OF THE IECC AND DOES NOT HAVE A U VALUE REQUIREMENT.28. ALL EXTERIOR SIDING TO BE REPLACED WITH NEW WEATHER RESISTANT PAINTED OR TREATED WOOD SIDING. VERIFY WOODSPECIES AND FINISH COLOR WITH OWNER AND GENERAL CONTRACTOR29. ALL EXISTING DECKING THAT NEEDS REPLACEMENT WILL BE REPLACED WITH WEATHER RESISTANT COMPOSITE DECKING. REF.OWNER AND GENERAL CONTRACTOR FOR SPECIFICATION. Are you proposing any new exteriormechanical equipmentwith this permit? If so please show it as I willneed to verifycompliant location for zoning's review. Please verify that no lighting work is proposed for the upper level as no RCP was submitted for that level. If that is the case please specifically note that on this RCP. FY 6'-8"VERIFY 3'-0"6'-8"2'-8" OR SCHEDULE 6'-8"2'-6" SAFETY 6'-8"2'-6"2'-6" 5'-0"FY 6'-8"VERIFY 5'-0" SAFETY GLASS SAFETY GLASS All replacement exterior doors shall have a max U value of .28. Note the requirement or provide a cutsheet on the door. 02/21/2018