February 16, 2018
RE: Responses to Building Comments 1 sent by Justin Hahn February 16, 2018 re: 805
Bonita Drive. Permit # 0005.2018.ARBK
Responses;
Comment #1
We are proposing to replace all the siding on the unit. We intend to replace the air
infiltration barrier with a new one as well. An assembly detail with this information and what
is to remain / replaced is provided on sheet A1.06 detail 2. Existing flashing is to remain.
Comment #2
Safety glazing for the shower window has been noted on sheet A1.06 drawing.
Comment #3
We are not proposing new mechanical equipment with the proposed scope of work.
Existing mechanical equipment is to remain unchanged. Note 6 has been revied on sheet
A1.07
Comment #4
A note on sheet A1.08 has been added noting there is no proposed work on the upper level
lighting
Comment #5
Sheet A1.09 has been revised to note that replacement doors must have a max U value of
0.28
Please let me know if there is anything else I can provide.
All the best,
Ralph Dupps
R A L L Y D U P P S
I
I
I
I
I
I
I
a r c h I t e c t
02/21/2018
NEW WALK IN PANTRY
WITH SHELVING
BEDROOM
108
SHOWER
104
BENCHBATH
105
W/C
107
DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF ROOF ABV.DASHED LINEOF BEAM ABV.DASHED LINE
OF ROOF ABV.
NEW
DOOR
TILE
CPT.
TILE
CPT.STEPSTEP
LIVING
ROOM
101
KITCHEN
102
LAUNDRY
103
EXTERIOR
DECK
115
DECK
113
ON GRADE
DECK
114
GARAGE
110
MECHANICAL
111
CLOS.
ENTRY
HALL
109
GAS APPLIANCE
FIREPLACE
EXTERIOR
MECH.
112
STEP
NEW
30" RANGE
OVEN
EXISTING
SINK
NEW
24"
DW
NEW
DRYER
NEW
WASHING
MACHINE
NEW
FRONT DOOR
NEW TILE
FLOORING
NEW TILE
FLOORING
NEW SLIDING
DOORS
REPLACE EXISTING DECKING WITH
NEW COMPOSITE DECKING
REF. SHEET A1.07
NOTE 29
ADD ELECTRIC
BASEBOARD
HEAT
TRASH
STONE
HEARTH
NEW TILE
FLOORING
NEW TILE
FLOORING
NEW CARPET
NEW TILE
FLOORING
UP
STAIR
116 TILECPT.REF. DRAWING A1.06 FOR GENERAL PLAN NOTES
CLOSET
106
NEW
36" REF.
NEW TILE
FLOORING
01
02
01
03
SAFETY
GLASS
SAFETY
GLASS
SAFETY
GLASS
SUPERINSULATED ROOF ASSEMBLY ABOVE ENTRY HALL 109:
REPLACEMENT COMPOSITE EXTERIOR DECKING OVER
EXISTING W.P. ROOFING OVER
EXISTING ROOF SHEATHING AND FRAMING OVER
FULL CAVITY DEPTH CLOSED CELL
EXPANDING SPRAY FOAM INSULATION
OVER (CLASS II VAPOR RETARDER)
OVER 1HR FIRE RATED 5/8" TYPE X GWB
INSULATED WALL ASSEMBLY AT GARAGE 110:
NEW 5/8" TYPE X 1 HR FIRE RATED GWB OVER
6 MIL. POLY VAPOR BARR . OVER
EXISTING WOOD STUD FRAMING OVER
FULL CAVITY DEPTH CLOSED CELL FOAM INSULATION
NEW TILE
FLOORING
0303
04
05
06
5'-6"5'-9 3/4"2'-10 3/4"3 1/2"3'-0 3/4"
6'-3"2'-6"3 1/2"803 BONITA DRIVE
UNIT 2
805 BONITA DRIVE
UNIT 1
SCOPE OF WORK TO ADD FULL CAVITY DEPTH CLOSED
CELL FOAM INSULATION TO EXISTING FRAMING:
CO
CO
SD
SD
SD
REPLACE GLASS.
REF. SHEET A1.07
NOTES 26 AND 27
REPLACE EXTERIOR SIDING
REF. SHEET A1.07
NOTE 28 AND DETAIL 2/A1.06
REPLACE EXISTING
GLASS WITH SAFETY
GLAZING
TYPICAL EXTERIOR WALL REPAIR ASSEMBLY:
(N) 3/4" FINISH SIDING - REF. ELEVATIONS
- OVER (N) AIR INFILTRATION BARRIER
(DU PONT TYVEK OR SIM.) OVER
(E) 1/2" OSB PWD. SHEATHING OVER
(E) 2x6 WOOD STUD WALL OVER
(E) INSULATION -
IF EXISTING GWB IS TO BE REPLACED:
OVER (N) 6 MIL. POLY VAPOR BARRIER OVER
(N) 5/8" TYPE X GWB FOR 1HR FIRE
RATED CONST. - REF. INTERIORS
ALL EXISTING METAL FLASHING IN
GOOD CONDITION IS TO REMAIN.
(N) = NEW
(E) = EXISTING TO REMAIN
INTERIOREXTERIOR
805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.06
PROPOSED PLAN
c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates:
NORTH
PROPOSED MAIN LEVEL PLAN 1
A1.06 1/4" = 1'-0"
NOTE: NO FLOOR AREA CHANGES ARE PROPOSED
REPLACEMENT SIDING ASSEMBLY2
A1.06 3" = 1'-0"
02/21/2018
02/21/2018
justinh
BEDROOM
201
OPEN TO BELOW
CLOSET
209
CLOSET
202
BATH
203
SHOWER
204
BENCH
CLOSET205CLOSET206BUILT IN CABINETOFFICE
207
EXTERIOR
UNCOVERED
DECK
210
HALL
208
DASHED LINE
OF CEILING ABV.DASHED LINEOF CEILING ABV.DN
STAIR
116
NEW COUNTER TOP
NEW TILE
NEW TILE IN SHOWER
NEW CARPET
NEW CARPET
NEW CARPET
CPT.
TILE
TILE
CPT.
NEW CARPET
NEW CARPET
803 BONITA DRIVE
UNIT 2
805 BONITA DRIVE
UNIT 1
REPLACE GLASS.
REF. SHEET A1.07
NOTES 26 AND 27
REPLACE EXISTING DECKING
WITH NEW COMPOSITE
DECKING. REF. SHEET A1.07
NOTE 29
REPLACE EXTERIOR SIDING
REF. SHEET A1.07
NOTE 28 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.07
PROPOSED PLAN
c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates:
NORTH
PROPOSED UPPER LEVEL PLAN 1
A1.07 1/4" = 1'-0"
NOTE: NO FLOOR AREA CHANGES ARE PROPOSED
GENERAL PLAN NOTES:
1. ALL DIMENSIONS SHOWN ARE TO BE VERIFIED IN FIELD. DO NOT SCALE DRAWINGS. GENERAL CONTRACTOR IS TO VERIFY ALL
PROPERTY LINES WITH SURVEYOR PRIOR TO CONSTRUCTION OF FOUNDATION - ALL SETBACKS SHOWN HERE ARE DERIVED FROM THE
SURVEYOR, WHICH IN TURN ESTABLISH THE BUILDING FOOTPRINT INCLUDING ANGLED PORTIONS OF THE BUILDING FOOTPRINT. IN
CASE OF DIMENSIONAL CONFLICT, PLEASE CONSULT ARCHITECT.
2. EXTERIOR OF LOWER LEVEL CONC WALLS (IF ANY) TO ALIGN WITH WOOD FRAMED WALLS ABOVE.
3. ALL WOOD STUD WALLS ARE TO BE EITHER 2x4 OR 2x6. REFER TO ARCH. DRAWINGS FOR WALL THICKNESS. ALL EXTERIOR AND LOAD
BEARING WALLS ARE TO BE 2x6.
4. VERIFY ALL DOOR AND WINDOW R.O. DIMENSIONS W/ DOOR AND WINDOW SCHEDULES
5. IF BASEMENT EXIST, ALL LOWER LEVEL EXTERIOR CONC. WALLS ARE TO BE 8" THICK PLUS 2" FOR FURRING STRIPS AND INSULATION
U.N.O.
6. ALL EXISTING MECHANICAL IS TO REMAIN UNCHANGED.
7. CITY BUILDING OFFICIAL SHALL DETERMINE IF SPRINKLER SYSTEM IS REQUIRED. IF REQUIRED, GEN CONTRACTOR SHALL BE
RESPONSIBLE FOR COMPLIANCE W/ CODE.
8. ALL FINISH MATERIALS ARE TO BE LOW TOXIC
9. ALL SHEATHING IS TO BE OSB AND / OR RECYCLED CONTENT SHEATHING SUCH AS THERMO-PLY OR EQUIVALENT - REF. STRUCTURAL
10. REF. CIVIL DRAWINGS FOR RIGHT OF WAY IMPROVEMENTS SUCH AS SIDEWALKS, CURB, GUTTER, AND OTHER IMPROVEMENTS.
11. REFER TO CIVIL ENGINEERING PLAN FOR ALL DRYWELL SIZES, LOCATIONS, AND CONFIGURATION. REF. CIVIL ENG. FOR ROUTING OF
ALL WATER FROM ROOF AND ALL OTHER SURFACE AREAS. REF. GRADING AND CIVIL DRAWINGS FOR LOCATION, CONFIGURATION AND
ALL OTHER INFORMATION PERTAINING TO DRAINING AND SURFACE SLOPES TO THESE DRAINS.
12. PROVIDE SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AS REQUIRED BY CODE - REF. ELECTRICAL PLAN
13. ALL GRID LINES ARE TO OUTSIDE FACE OF FRAMING UNLESS NOTED OTHERWISE.
14. PROVIDE RADON MITIGATION PER PASSIVE RADON SYSTEM USING DRAIN TILE LOOP AS DETAILED IN 2015 IRC - REF. ARCH. DETAILS
15. REF. ARCH. SITE PLAN FOR SNOWMELT AREAS. REF. MECHANICAL FOR REMP CALCULATIONS
16. SLOPE FINISH FLOOR FOR ALL FLOOR DRAINS AT 1/8" PER 12" MIN. SLOPE ALL DECKS, PORCHES, BALCONIES AND ALL OTHER
EXTERNAL OR EXPOSED FLOORS AT 1/8" PER 12" MINIMUM W. DIRECTION OF SLOPE AS SHOWN ON DRAWINGS
17. ALL T.O. FLOOR ELEVATIONS AT SLOPING AREAS ARE SHOWN AT THE HIGHEST POINT.
18. REF. ARCH. ROOF PLANS / BUILDING ELEVATIONS FOR ROOF GUTTER AND DOWNSPOUT LOCATIONS
19. CARBON MONOXIDE AND SMOKE DETECTOR LOCATIONS SHALL COMPLY PER ASPEN MUNICIPAL CODE CH 8.15. REF. FLOOR PLANS
20. TOILET AND BATH FIXTURE CLEARANCES AND SAFETY GLAZING SHALL COMPLY PER IRC R307.1, R308.4
21. SAFETY GLAZING SHALL COMPLY PER IRC R308.4
22. DOOR SWINGS AND FLOOR LEVELS SHALL COMPLY PER IRC R311
23. EXTERIOR LANDINGS, LANDING SURFACE SLOPE SHALL COMPLY PER IRC R311
24. STAIRS AND RAMPS, DIRECTION OF TRAVEL, HANDRAILS, MUST RETURN, GURADRAILS SHALL COMPLY PER IRC R311
25. DWELLING SEPARATION AND FIRE RATED ASSEMBLIES SHALL COMPLY PER IRC R301.3
26. TYPICAL THROUGHOUT UNIT 1: ALL FAILED WINDOW GLASS TO REPLACED WITH NEW TO FIT WITHIN EXISTING FRAME AND SASH
OPENINGS.
27. GLASS ONLY REPLACEMENT IS CONSIDERED A REPAIR UNDER R504 OF THE IECC AND DOES NOT HAVE A U VALUE REQUIREMENT.
28. ALL EXTERIOR SIDING TO BE REPLACED WITH NEW WEATHER RESISTANT PAINTED OR TREATED WOOD SIDING. VERIFY WOOD
SPECIES AND FINISH COLOR WITH OWNER AND GENERAL CONTRACTOR
29. ALL EXISTING DECKING THAT NEEDS REPLACEMENT WILL BE REPLACED WITH WEATHER RESISTANT COMPOSITE DECKING. REF.
OWNER AND GENERAL CONTRACTOR FOR SPECIFICATION.
02/21/2018
02/21/2018
justinh
ROOM #FIXT.
RESIDENTIAL LIGHTING SCHEDULE
#
MANUF.TYPE IC RATED
A
B
MODEL
NO
LAMP FIXTURE RATING
TBD TBD LED SLOPED CLG. RECESSED IC RATED CAN 12W LED 15 W
TBD TBD UNDER COUNTER LED STRIP LIGHTING INTERNAL LED 12 W PER FT.
C TBD NO35 WTBD6" X 36" FLUORESCENT SURFACE MOUNT T5 FLUORESCENT
QUANTITY
HIGH EFF.
QUANTITY
OTHER
SWITCH W/ DIMMER WHERE POSSIBLE
AC
PHONE / TV / CABLE / INTERNET / SATELLITE HOOKUP
F
JUNCTION BOX
3 WAY (OR MORE) SWITCH W/ DIMMER WHERE POSSIBLE
EXHAUST FAN
220
SMOKE DETECTOR BY CODE
OUTLET
LOW VOLTAGE CABLE LIGHTING
CO2 DETECTOR BY CODE
F
S
J
WALL MOUNTED LIGHT
AIR CONDITIONING UNIT W/ EXT. COMPRESSOR
CEILING FAN
220 VOLT OUTLET
GFI / AFCI AND/OR WATERPROOF OUTLET PER 2014 NEC
S3
SD
W.P. LANDSCAPE WALL OR POLE MOUNTED LIGHT
CO
LIGHTING LEGEND
SYMBOL AND DESCRIPTION
CEILING MOUNTED FLUORESCENT
CEILING MOUNTED SPEAKER
WP
CEILING MOUNTED WITH DIRECTIONAL TRIM
WP
CEILING MOUNTED RECESSED CAN
W.P. LANDSCAPE GROUND SURFACE MOUNTED LIGHT
UNDER CABINET LED STRIP LIGHTING
TS SWITCH ON TIMER
JAMB SWITCHJS
FLOOR OUTLETF
DIMMER SWITCHDS
NO
CEILING MOUNTED RECESSED CAN WITH WET LOCATION TRIM
ADD NEW LIGHTS INTO
EXISTING KITCHEN
LIGHTING CIRCUIT
NEW LOCATION FOR
EXISTING
REF. OUTLET
BEDROOM
108
SHOWER
104
BATH
105
W/C
107
LIVING
ROOM
101
KITCHEN
102
LAUNDRY
103
EXTERIOR
DECK
115
GARAGE
110
MECHANICAL
111
CLOS.
ENTRY
HALL
109
GAS APPLIANCE
FIREPLACE
EXTERIOR
MECH.
112
STAIR
116
CLOSET
106
S
EXISTING BEDROOM
SWITCH IN NEW
LOCATION
TO EXISTING
LIGHTING
S
C
A
B
B
NEW ELECTRIC
BASEBOARD
HEAT - STUB INTO
EXISTING 220V
S
D TBD TBD LED WALL SCONCE 12W LED 15 W NO
GENERAL NOTES:
ALL LIGHTING SHALL COMPLY WITH 2014 NEC, 2015 IECC,
PROVIDE LIGHT REDUCTION CONTROLS PER 2015 IECC C405.2.2.2
ALL BULBS ARE TO BE 12W LED ONMIDIRECTIONAL BULBS, UNLESS NOTED OTHERWISE
PLEASE NOTE THAT THERE IS NO LIGHTING PROPOSED WITHIN AN INSULATED EXTERIOR ROOF. THEREFORE IC RATED CANS ARE NOT REQUIRED.
TOTAL PERCENTAGE HIGH EFFICIENCY PER 2015 IECC R404.1 :MIN 75% <100 % HIGH EFFICIENCY
0SUBTOTAL
D
S
F B
WP A
A
S
CONNECT
TO EXISTING
LIGHTING IN
LIVING RM. 101
A A A
A
D
D
WP
WP
WP
WP
EXISTING DUPLEX
OUTLETS TO REMAIN
ELECTRICAL PLAN NOTES
1. ELECTRICAL / HVAC PLAN IS SCHEMATIC IN NATURE. FINAL PLAN
LAYOUT BY THE APPROPRIATE CONTRACTOR TO MEET ALL CURRENT
CODES.
2. VERIFY ALL FIXTURE LOCATIONS AND PRODUCTS WITH OWNERS
3. SWITCHING SHOWN ARE SCHEMATIC, ELECTRICIAN TO REVIEW
WITH OWNERS EXACT SWITCHING REQUIREMENTS AND LOCATIONS
4. INSTALL OUTLETS AS REQUIRED BY OWNERS AND ELECTRICAL
CODE. LOCATIONS AND QUANTITIES SHOWN ARE SCHEMATIC
5. LIGHTING PLAN IS SCHEMATIC. REFER TO FLOOR PLANS FOR TV
AND LOW VOLTAGE LOCATIONS. VERIFY REQUIREMENTS WITH OWNER
AND A/V SPECIALIST FOR TV, DATA AND SOUND SYSTEMS LOCATION,
POWER SOURCE AND ANYTHING ELSE REQUIRED FOR THEIR
FUNCTION.
6. LOCATION AND QUANTITY OF SMOKE DETECTORS BY ELECTRICAL
CONTRACTOR AND LOCAL BUILDING CODE.
7. LOCATION, TYPE AND QUANTITY OF ELECTRICAL OUTLETS BY
ELECTRICAL CONTRACTOR AND LOCAL BUILDING CODE.
8. ELECTRICAL SUBCONTRACTOR SHALL PROVIDE SURGE
PROTECTION IN ALL AREAS THAT REQUIRE PROTECTION
9. ALL EXISTING DUPLEX OUTLETS ARE TO REMAIN UNLESS NOTED
OTHERWISE.
B
CO
CO
SD
SD
SD
101, 102, 104, 105, 107 7
102, 103 13
106 1
105, 107 3
24
803 BONITA DRIVE
UNIT 2
805 BONITA DRIVE
UNIT 1
NOTE: NO PROPOSED LIGHTING CHANGES TO UPPER LEVEL 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.08
LIGHTING PLAN
c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates:
NORTH
PROPOSED MAIN LEVEL LIGHTING PLAN 1
A1.08 1/4" = 1'-0"
02/21/2018
02/21/2018
justinh
DOOR / WDW. SCHEDULE
1/4" = 1'-0"
1
A1.09
01
(EXTERIOR, SINGLE)
PREMANUFACTURED
EXTERIOR GLASS DOOR
VERIFY SIZE W/ MFG.
REF. PLANS FOR
OPERATIONVERIFY 6'-8"VERIFY
3'-0"6'-8"02
(INTERIOR, SINGLE)
FLAT SOLID CORE
REF. PLANS FOR
OPERATION
2'-8"
DOOR SCHEDULE
6'-8"03
(INTERIOR, SINGLE)
FLAT SOLID CORE
REF. PLANS FOR
OPERATION
2'-6"
SAFETY
GLASS 6'-8"04
(INTERIOR, DOUBLE)
FLAT SOLID CORE
BY PASS DOOR
REF. PLANS FOR
OPERATION
2'-6"2'-6"
DOOR AND WINDOW SCHEDULE GENERAL NOTES:
1. NEW DOOR HARDWARE TO BE BRUSHED NICKEL BALDWIN OR EQUAL
2. INTERIOR DOORS ARE TO BE FLAT PANEL W/ A SOLID CORE OF MDF OR EQUIVALENT - REF. INTERIORS
3. INTERIOR DOORS ARE TO BE PRE HUNG W/ INTEGRAL HEAD & JAMB OF (4) 1/4 STOCK
4. ALL OPENINGS AND UNIT SIZES ARE TO BE VERIFIED IN FIELD BY CONTRACTOR IN ORDER
TO INSURE PROPER FIT IN EXISTING, MODIFIED, OR NEW OPENINGS.
5. ALL WINDOW R.O. AND UNIT OPENINGS SHOWN ON THIS SCHEDULE ARE TO BE
VERIFIED BY GENERAL CONTACTOR WITH MANUFACTURER AND COORDINATED
WITH ALL SUBCONTRACTORS IN THE FIELD.
6. ALL MECHANICAL ROOM DOORS ARE TO BE 1 HR FIRE RATED WITH SELF CLOSING HARDWARE.
7. ALL WINDOW / DOOR EXTERIOR GLASS IS TO BE LOW E SQUARED, ARGON FILLED, & TEMPERED GLASS AS
REQUIRED BY BUILDING CODE, ENERGY CODE
8. BEFORE ORDERING, THE GENERAL CONTRACTOR SHALL VERIFY ALL MODEL #'S, FRAME SIZE, AND MULLED
WINDOW ASSEMBLIES WITH ARCHITECT AND WINDOW REP. THE GENERAL CONTRACTOR SHALL CONSULT WITH
ARCHITECT SHOULD DISCREPANCIES OCCUR. ALL WINDOW R.O. AND UNIT OPENINGS ARE TO BE VERIFIED IN
FIELD BY AFTER FRAMING IS COMPLETE AND PRIOR TO PLACING DOOR AND WINDOW ORDERS TO INSURE
PROPER FIT IN EXISTING, MODIFIED, OR NEW OPENINGS.
9. ALL DOOR AND WINDOW OPERATION, MULLION AND MUNTIN PATTERS ARE TO BE COORDINATED WITH
ARCHITECTURAL BUILDING ELEVATIONS. THESE ARE TO BE COORDINATED BY GENERAL CONTRACTOR WITH
ARCHITECT AND WINDOW REP. ALL WINDOW ELEVATIONS SHOWN ARE MEASURED FROM INTERIOR FINISH
FLOOR LEVELS TO THE BOTTOM OF THE WINDOW ROUGH OPENING
10. WINDOW AND DOOR FRAMES ARE TO INCLUDE O.E.M. NAILING STRIPS.
11. USE METAL FLASHING AT BOTH DOOR & WINDOW HEAD & JAMB LOCATIONS. USE BUILDING WRAP AIR
INFILTRATION BARRIER AROUND WALLS OF ENTIRE STRUCTURE, WITH TAPED JOINTS. 6" PAST ROUGH
OPENING, USE WATERPROOF TAPE AROUND WINDOW AND DOOR JAMBS AS A AIR INFILTRATION BARRIER. USE
BUILDING WRAP AS BASE LAYER FOR DRAINAGE PLANE. SHINGLE BUILDING WRAP OVER RUBBER HEAD SILL TO
ENSURE WATER IS KICKED OUT AWAY FROM HEADER. INSTALL METAL FLASHING PAN AT WINDOW SILLS OVER
BUILDING WRAP AND FLASHING TAPE ON TOP OF BUILDING WRAP.
12. USE STANDARD DENSITY CLOSED CELL EXPANDING POLYURETHANE FOAM INSULATION TO PLUG GAPS
BETWEEN THE FRAME AND WALL ROUGH OPENINGS AROUND ALL DOOR AND WINDOWS.
13. ALL WINDOW R.O. AND UNIT OPENINGS SHOWN ON THIS SCHEDULE ARE TO BE
VERIFIED BY GENERAL CONTRACTOR WITH MANUFACTURER AND COORDINATED
WITH ALL SUBCONTRACTORS IN THE FIELD.
14. OPERABLE WINDOW ACCESSORIES TO INCLUDE ALL HARDWARE AND CRANK
EXTENSIONS AS NEEDED PER ELEVATIONS AND PER CODE AS REQUIRED FOR EGRESS.
15. REFER TO EXTERIOR BUILDING ELEVATIONS FOR MULLED WINDOW COMBINATIONS - TYP.
16. WINDOW ENEGY PERFORMANCE TO MEET REQUIREMENTS AS SPECIFIED BY ENERGY CALCULATIONS.
17. REFER TO EXTERIOR BUILDING ELEVATIONS AND FLOOR PLANS FOR ALL DOOR AND WINDOW QUANTITIES,
SWINGS, OPERATION, MULLION AND MUNTIN PATTERNS, AND HANDING
18. ALL SHOWER DOORS ARE TO BE TEMPERED GLASS AS REQUIRED BY CODE. ALL HINGES AND FITTINGS ARE
TO BE BRUSHED NICKEL OR EQUIVALENT, EUROPEAN STYLE HARDWARE, AND ABLE TO SWING IN BOTH
DIRECTIONS FROM THE JAMB.
19. PLEASE REFER TO PLANS AND / OR THIS WINDOW SCHEDULE FOR EGRESS WINDOWS. ALL EGRESS
WINDOWS ARE TO BE SIZED PER IRC. ALL WINDOWS LOCATED WITHIN LIGHT WELLS FOR THE LOWER LEVEL
ARE TO MEET IRC FOR EGRESS, LIGHT AND VENTILATION
20. POCKET DOORS ARE TO USE 2X4 FRAMING EACH SIDE OF DOOR PASSAGE WAY ON FLAT. FRAMING SHALL
BE ENGINEERED WOOD OR STEEL. DOORS TO INCLUDE TRACKING HARDWARE WITH GLIDE ROLLER BEARINGS
AND SHALL BE ABLE TO BECOME ENTIRELY RECESSED WITHIN WALL CAVITY POCKET.
21. POCKET AND BY PASS DOOR BID TO INCLUDE FLUSH OR RECESSED DOOR HARDWARE AND POCKET DOOR
JAMB MOUNTED DOOR PULL.
22. PROVIDE PRIVACY LOCK FOR ALL INTERIOR DOORS AT BEDROOMS AND BATHROOMS.
5'-0"
05
(EXTERIOR, DOUBLE)
PREMANUFACTURED
EXTERIOR GLASS DOOR
VERIFY SIZE W/ MFG.
REF. PLANS FOR
OPERATIONVERIFY 6'-8"VERIFY
5'-0"
SAFETY
GLASS
SAFETY
GLASS
WINDOW SCHEDULE
NO NEW WINDOW FRAMES OR WINDOW SASHES ARE PROPOSED. ONLY FOGGED GLAZING IS PROPOSED TO BE
REPLACED WITH NEW GLASS TO FIT WITHIN THE EXISTING SASH AND FRAME
GLASS ONLY REPLACEMENTS ARE EXEMPT FROM U VALUE REQUIREMENTS PER IECC R504.2
06
(INTERIOR, SINGLE)
TEMPERED GLASS
SHOWER DOOR W/
TEMPERED GLASS PANELS
VERIFY W/ INTERIORS
REF. PLANS FOR
OPERATION
FOR DOOR PROVIDE
EUROPEAN HARDWARE
FINISH TBD
2'-6"7'-0"VERIFYV.I.F.VERIFY
LINE OF FINISH
FLOOR
EXT. DOOR AND WINDOW U FACTOR:
ALL REPLACEMENT DOORS = 0.28
MIN
ENERGY CODE INTERIOR REMODEL
GENERAL NOTES:
1. ENERGY EFFICIENCY U VALUES
PER 2015 IECC TABLE R402.1.2 FOR
CLIMATE ZONE 7
2. SKYLIGHT GLASS FOR UNITS
LOCATED OVER HEATED AREAS IS
TO BE DOUBLE PANE LOW E
LAMINATED GLASS WITH
ELECTRONICALLY OPERATED BLIND 805 BONITA DRIVE REMODELWEST ASPEN LOT: 23 FILING 1, 1/2 INTERESTASPEN, CO 81611PARCEL ID# 2735 1220 9023A1.09
DOOR AND WINDOW
SCHEDULE
c 2017 RALLY DUPPS ARCHITECT - THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF CONSORTIUM ARCHITECTS. NO PART OF THIS INFORMATION MAY BE USED OR COPIED WITHOUT THE PRIOR WRITTEN PERMISSION OF CONSORTIUM ARCHITECTS. CONSORTIUM ARCHITECTS SHALL RETAIN ALL COMMON LAW STATUTORY AND ALL OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. ALL RIGHTS RESERVEDIssue Dates:
02/21/2018
02/21/2018
justinh
0005.2018.ARBK_BuildingComment1
Subject: PlanCheck
Page Label: A1.06 PROPOSED PLAN
Author: justinh
File Name: 805 BONITA ARCHITECTURAL.pdf
Are you proposing to reside the
entire unit or just the one
location on each level that
you've noted? If the entire unit is
being resided please provide a
detail for the siding assembly
showing what existing
components are to remain
(insulation/sheathing, etc) and a
compliant weather/air barrier and
flashing.
805 BONITA ARCHITECTURAL.pdf (5)
Subject: PlanCheck
Page Label: A1.06 PROPOSED PLAN
Author: justinh
File Name: 805 BONITA ARCHITECTURAL.pdf
Because of this new shower this
window is now required to be
safety glazed. Please note this
on the plan.
Subject: PlanCheck
Page Label: A1.07 PROPOSED PLAN
Author: justinh
File Name: 805 BONITA ARCHITECTURAL.pdf
Are you proposing any new
exterior mechanical equipment
with this permit? If so please
show it as I will need to verify
compliant location for zoning's
review.
Subject: PlanCheck
Page Label: A1.08 LIGHTING PLAN
Author: justinh
File Name: 805 BONITA ARCHITECTURAL.pdf
Please verify that no lighting
work is proposed for the upper
level as no RCP was submitted
for that level. If that is the case
please specifically note that on
this RCP.
Subject: PlanCheck
Page Label: A1.09 DOOR AND WINDOW SCHEDULE
Author: justinh
File Name: 805 BONITA ARCHITECTURAL.pdf
All replacement exterior doors
shall have a max
U value of .28. Note the
requirement or provide a
cutsheet on the door.
REPLACE EXTERIOR SIDING
REF. SHEET A1.07
NOTE 28
PROP
Are you proposing to reside the entire unit or
just the one location on each level that
you've noted? If the entire unit is being
resided please provide a detail for the siding
assembly showing what existing
components are to remain
(insulation/sheathing, etc) and a compliant
weather/air barrier and flashing.
NEW WALK IN PANTRY
WITH SHELVING
BENCHDASHED LINEOF ROOF ABV.NEW
SHING
CHINE
Because of this new
shower this window is
now required to be
safety glazed. Please
note this on the plan.
GENERAL PLAN NOTES:
1. ALL DIMENSIONS SHOWN ARE TO BE VERIFIED IN FIELD. DO NOT SCALE DRAWINGS. GENERAL CONTRACTOR IS TO VERIFY ALLPROPERTY LINES WITH SURVEYOR PRIOR TO CONSTRUCTION OF FOUNDATION - ALL SETBACKS SHOWN HERE ARE DERIVED FROM THESURVEYOR, WHICH IN TURN ESTABLISH THE BUILDING FOOTPRINT INCLUDING ANGLED PORTIONS OF THE BUILDING FOOTPRINT. INCASE OF DIMENSIONAL CONFLICT, PLEASE CONSULT ARCHITECT.2. EXTERIOR OF LOWER LEVEL CONC WALLS (IF ANY) TO ALIGN WITH WOOD FRAMED WALLS ABOVE.3. ALL WOOD STUD WALLS ARE TO BE EITHER 2x4 OR 2x6. REFER TO ARCH. DRAWINGS FOR WALL THICKNESS. ALL EXTERIOR AND LOAD
BEARING WALLS ARE TO BE 2x6.4. VERIFY ALL DOOR AND WINDOW R.O. DIMENSIONS W/ DOOR AND WINDOW SCHEDULES5. IF BASEMENT EXIST, ALL LOWER LEVEL EXTERIOR CONC. WALLS ARE TO BE 8" THICK PLUS 2" FOR FURRING STRIPS AND INSULATIONU.N.O.
6. EXACT SPECIFICATIONS AND LOCATIONS OF ALL MECH. EQUIPMENT ARE TO BE DETERMINED BY MECHANICAL ENGINEER AND MECH.SUB CONTRACTOR. REF. MECHANICAL DRAWINGS7. CITY BUILDING OFFICIAL SHALL DETERMINE IF SPRINKLER SYSTEM IS REQUIRED. IF REQUIRED, GEN CONTRACTOR SHALL BERESPONSIBLE FOR COMPLIANCE W/ CODE.8. ALL FINISH MATERIALS ARE TO BE LOW TOXIC9. ALL SHEATHING IS TO BE OSB AND / OR RECYCLED CONTENT SHEATHING SUCH AS THERMO-PLY OR EQUIVALENT - REF. STRUCTURAL10. REF. CIVIL DRAWINGS FOR RIGHT OF WAY IMPROVEMENTS SUCH AS SIDEWALKS, CURB, GUTTER, AND OTHER IMPROVEMENTS.11. REFER TO CIVIL ENGINEERING PLAN FOR ALL DRYWELL SIZES, LOCATIONS, AND CONFIGURATION. REF. CIVIL ENG. FOR ROUTING OFALL WATER FROM ROOF AND ALL OTHER SURFACE AREAS. REF. GRADING AND CIVIL DRAWINGS FOR LOCATION, CONFIGURATION ANDALL OTHER INFORMATION PERTAINING TO DRAINING AND SURFACE SLOPES TO THESE DRAINS.12. PROVIDE SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS AS REQUIRED BY CODE - REF. ELECTRICAL PLAN
13. ALL GRID LINES ARE TO OUTSIDE FACE OF FRAMING UNLESS NOTED OTHERWISE.14. PROVIDE RADON MITIGATION PER PASSIVE RADON SYSTEM USING DRAIN TILE LOOP AS DETAILED IN 2015 IRC - REF. ARCH. DETAILS15. REF. ARCH. SITE PLAN FOR SNOWMELT AREAS. REF. MECHANICAL FOR REMP CALCULATIONS16. SLOPE FINISH FLOOR FOR ALL FLOOR DRAINS AT 1/8" PER 12" MIN. SLOPE ALL DECKS, PORCHES, BALCONIES AND ALL OTHEREXTERNAL OR EXPOSED FLOORS AT 1/8" PER 12" MINIMUM W. DIRECTION OF SLOPE AS SHOWN ON DRAWINGS17. ALL T.O. FLOOR ELEVATIONS AT SLOPING AREAS ARE SHOWN AT THE HIGHEST POINT.18. REF. ARCH. ROOF PLANS / BUILDING ELEVATIONS FOR ROOF GUTTER AND DOWNSPOUT LOCATIONS19. CARBON MONOXIDE AND SMOKE DETECTOR LOCATIONS SHALL COMPLY PER ASPEN MUNICIPAL CODE CH 8.15. REF. FLOOR PLANS20. TOILET AND BATH FIXTURE CLEARANCES AND SAFETY GLAZING SHALL COMPLY PER IRC R307.1, R308.421. SAFETY GLAZING SHALL COMPLY PER IRC R308.422. DOOR SWINGS AND FLOOR LEVELS SHALL COMPLY PER IRC R311
23. EXTERIOR LANDINGS, LANDING SURFACE SLOPE SHALL COMPLY PER IRC R31124. STAIRS AND RAMPS, DIRECTION OF TRAVEL, HANDRAILS, MUST RETURN, GURADRAILS SHALL COMPLY PER IRC R31125. DWELLING SEPARATION AND FIRE RATED ASSEMBLIES SHALL COMPLY PER IRC R301.326. TYPICAL THROUGHOUT UNIT 1: ALL FAILED WINDOW GLASS TO REPLACED WITH NEW TO FIT WITHIN EXISTING FRAME AND SASHOPENINGS.27. GLASS ONLY REPLACEMENT IS CONSIDERED A REPAIR UNDER R504 OF THE IECC AND DOES NOT HAVE A U VALUE REQUIREMENT.28. ALL EXTERIOR SIDING TO BE REPLACED WITH NEW WEATHER RESISTANT PAINTED OR TREATED WOOD SIDING. VERIFY WOODSPECIES AND FINISH COLOR WITH OWNER AND GENERAL CONTRACTOR29. ALL EXISTING DECKING THAT NEEDS REPLACEMENT WILL BE REPLACED WITH WEATHER RESISTANT COMPOSITE DECKING. REF.OWNER AND GENERAL CONTRACTOR FOR SPECIFICATION.
Are you proposing any
new exteriormechanical equipmentwith this permit? If so
please show it as I willneed to verifycompliant location for
zoning's review.
Please verify that no lighting
work is proposed for the
upper level as no RCP was
submitted for that level. If
that is the case please
specifically note that on this
RCP. FY 6'-8"VERIFY
3'-0"6'-8"2'-8"
OR SCHEDULE
6'-8"2'-6"
SAFETY 6'-8"2'-6"2'-6"
5'-0"FY 6'-8"VERIFY
5'-0"
SAFETY
GLASS
SAFETY
GLASS
All replacement
exterior doors shall
have a max
U value of .28. Note
the requirement or
provide a cutsheet on
the door.
02/21/2018