HomeMy WebLinkAboutFile Documents.614 North St.0224.2018 (2).ARBK0224-2018-ARBK_BuildingComment Subject: PlanCheck Page Label: 6 Author: justinh File Name: Arch Permit Set.pdf This fireplace wall is pushing out further than the original, the roof plan should also be revised to show this new fireplace consistently. Provide fireplace details showing compliance with the installation instructions for this gas log fireplace (chimney termination, hearth extension, clearance to combustibles, etc). From what I can tell from the elevations you do not meet the 2' above any structure within 10' requirement in the provided installation instructions. Arch Permit Set.pdf (3) Subject: PlanCheck Page Label: 11 Author: justinh File Name: Arch Permit Set.pdf Is the garage unconditioned? It was not shown as such in the original permit drawings but F5 shows it as such. If that is the case then then F5 would need to be insulated to R49 as a ceiling since it is proposed to be altered and F4 would need to be R38 if it is being altered. This would also move the thermal envelope to be at W6 rather than W3. Please verify whether this space is conditioned and revise if needed. Subject: PlanCheck Page Label: 14 Author: justinh File Name: Arch Permit Set.pdf This maximum opening needs to be less than 4" so that it restricts the passage of a 4" sphere, please revise. Subject: PlanCheck Page Label: 3 Author: justinh File Name: Structual Permit Set.pdf Is the 4" slab completely supported by non combustible construction? The 2x8 ledger note makes me question this. Please clarify and revise if needed. Structual Permit Set.pdf (1) 115116 114 113 W-5 W-4W-4 3'-111/2"42'-11" 35/8"3'-77/8"51/2"27'-103/4"3'-41/8"9'-71/4"35/8"3'-01/2"35/8"9'-0"35/8"5'-63/8"2'-6"51/2"4'-71/2"51/2"2'-6"8'-9"1'-103/8"1'-91/2"4'-6"4'-6"2'-33/4"2'-33/4"35/8"15'-81/4"10'-103/8"1'-2" T.O. PLY101'-0" T.O. FF101'-2" T.O. PLY100'-0" = 7890'-9" T.O. FF100'-2" T.O. PAVER101'-0" CA-303 9 27 28 29 13 ISOKERN UNIT36" MAGNUM SERIESSETBACK LINEPATIO UP 18 R @ 7" = 10'-6"LIVING ROOM107 2 A-302 3 B A 1 1.09 1.07 " MAIN LEVEL This fireplace wall is pushing out further than the original, the roof plan should also be revised to show this new fireplace consistently. Provide fireplace details showing compliance with the installation instructions for this gas log fireplace (chimney termination, hearthextension, clearance to combustibles, etc). From what I can tell from the elevations you donot meet the 2' above any structure within 10' requirement in the provided installationinstructions. DINING105 GARAGE107 BEDROOM 3008 BEDROOM 6208 W-1 W-6 W-7 W-7 12A-503 9A-502 3A-502 8A-502 F-1 FF-1 F-4 R-1 W-3 F-4 F-6 F-5 F-2 8"9'-13/8"1'-05/8"8'-73/8"105/8"209 106 107 007B EXISTING UPPER LEVELT.O. PLY 110'-6" T.O. EXISTING RIDGE125'-8 1/2" PROPOSED LOWER LEVEL EXISTING UPPER LEVEL STEPT.O. PLY 109'-6" EXISTING MAIN LEVELT.O. PLY 101'-0" = 7891'-9"10'-111/2"PROPOSED MAIN LEVELT.O. PLY 100'-0" = 7890'-9" 1.09 1.10 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 WILDLIFE-RESISTANT TRASH ENCLOSURE PER26.575.020.E.5.t STANDING SEAM ROOF SYNTHETIC SHINGLE ROOF OVERHANG LINE OF FOUNDATION BELOW FALL PROTECTION PROVIDED PER R612.2 1/4" PER 1' SLOPE GAS LANTERNS BEVOLO CONTEMPORARY SERIES ASPHAULT SHINGLES TO BE REPLACED BRICK TO MATCH PAVER TBD LINE OF PROPOSED GRADE 2" CURB TYP. HOSE BIB LADDER AND STEPS PER IRC R310.2.3.1 1/2 POINT FROM EAVE TO RIDGE 1/3 POINT FROM EAVE TO RIDGE RADON VENT PIPE VENTILATION FLUE WINDOW FALL PROTECTION WILL BEPROVIDED PER R312.2.1 BEVOLO CONTEMPORARY SERIES LIGHT FIXTURE Is the garage unconditioned? It was not shown as such in theoriginal permit drawings but F5 shows it as such. If that is the case then then F5 would need to be insulated to R49 as a ceiling since it is proposed to be altered and F4 would need to be R38 ifit is being altered. This would also move the thermal envelope to be at W6 rather than W3. Please verify whether this space isconditioned and revise if needed. M 10'-21/8"10'-61/8"77/8"10'-01/4"4"4"2'-101/8"63/4"3'-23/8"3'-21/4"63/4"3"4"21/2"1'-01/8"7"11" CLOSED STAIR STEEL STRINGER STEEL HANDRAIL(TYP) HANDRAIL RETURN HANDRAIL RETURN WOOD TREAD (TYP) FULL HEIGHT BASEMENT WALLAND SHELF AT WINDOW SILLTYP.TYP.STORAGE UNDERNEATHSTAIRCASE. ACCESS FROMTYP.MAXIMUM SPACINGOF GUARD TYP.TYP. TYP.TYP.This maximum opening needs to be less than 4" so that it restricts the passage of a 4" sphere, please revise. W10X33W10X33BEDROOM 1 BATH 1 STORAGE 11 7/8" LVL LEDGER w/ (2)5/8" TITEN HD @ 16"o.c. -TYP U.N.O. W8X18 2x8 LEDGER w/5/8" TITEN HD @16"o.c. - EMBED 4"SHADING INDICATES 4"CONC SLAB w/ #3 @12"o.c. EA WAY CTRDT.O. SLAB = 100'-0"MIT11.88 HGR TYP @ 2 -COORD BM ALIGNMENTFOR HGR PLACEMENT11 7/8" LVL11 7/8" LVL(2) 11 7/8" LVL OVERFRAMET.O. PLY = 101'-0"1'-61/2"2S6.003 3S6.00 .O. STL =99'-9 3/4"STL SHIM & WELD BASEPLATE TO BM IN LIEU OF MAX(2) A.B. AS REQ'D - TYP @ 2 #3 HOOKED DOWELS @12"o.c. - EMBED 6" INEPOXY AT TOP OF WALLCOL ABVRE: 4/S6.0011 2 3 4 Is the 4" slab completely supported by non combustible construction? The 2x8 ledger note makes me question this. Please clarify and revise if needed. FP Response: The garage will be conditioned space. W3 will remain as the thermal envelope at the garage. Reference A-501 for an updated F-5 assembly showing both spaces are conditioned. Reference details 3 and 8 on Sheet A-502 showing the existing assemblies, W-3 and R-1 to be insulated with spray foam. Section A on sheet A-301 also shows correct assemblies at the garage. FP Response: The 4" slab is not supported by non combustible construction. This slab is on grade, additionally supported by the new basement wall below and cantilevered for the hearth extension. The 2x8 Ledger is to support the new wood framing on the main level. Reference detail 1, on A-403 which shows a section of this condition. FP Response: A glass guard will now be installed instead of the lattice system previously shown. A specification sheet for the glass guard railing system has been provided. This glass guard complies with COA 8.16.020(s) and Table R301.5. Reference sheet A-401 for updated stair drawings. FP Response: The roof plan has been revised to show the new fireplace correctly. Exterior walls of the fireplace are canted, which decreases the overall width of the termination at the chimney cap. An enlarged fireplace plan and sectional drawings have been provided on sheet A-403. The revised Fireplace now meets the IRC clearance requirement of Table R1001.1 (R)