HomeMy WebLinkAboutFile Documents.614 North St.0224.2018 (2).ARBK0224-2018-ARBK_BuildingComment
Subject: PlanCheck
Page Label: 6
Author: justinh
File Name: Arch Permit Set.pdf
This fireplace wall is pushing out
further than the original, the roof
plan should also be revised to
show this new fireplace
consistently. Provide fireplace
details showing compliance with
the installation instructions for
this gas log fireplace (chimney
termination, hearth extension,
clearance to combustibles, etc).
From what I can tell from the
elevations you do not meet the 2'
above any structure within 10'
requirement in the provided
installation instructions.
Arch Permit Set.pdf (3)
Subject: PlanCheck
Page Label: 11
Author: justinh
File Name: Arch Permit Set.pdf
Is the garage unconditioned? It
was not shown as such in the
original permit drawings but F5
shows it as such. If that is the
case then then F5 would need to
be insulated to R49 as a ceiling
since it is proposed to be altered
and F4 would need to be R38 if
it is being altered. This would
also move the thermal envelope
to be at W6 rather than W3.
Please verify whether this space
is conditioned and revise if
needed.
Subject: PlanCheck
Page Label: 14
Author: justinh
File Name: Arch Permit Set.pdf
This maximum opening needs to
be less than 4" so that it restricts
the passage of a 4" sphere,
please revise.
Subject: PlanCheck
Page Label: 3
Author: justinh
File Name: Structual Permit Set.pdf
Is the 4" slab completely
supported by non combustible
construction? The 2x8 ledger
note makes me question this.
Please clarify and revise if
needed.
Structual Permit Set.pdf (1)
115116
114 113
W-5
W-4W-4
3'-111/2"42'-11"
35/8"3'-77/8"51/2"27'-103/4"3'-41/8"9'-71/4"35/8"3'-01/2"35/8"9'-0"35/8"5'-63/8"2'-6"51/2"4'-71/2"51/2"2'-6"8'-9"1'-103/8"1'-91/2"4'-6"4'-6"2'-33/4"2'-33/4"35/8"15'-81/4"10'-103/8"1'-2"
T.O. PLY101'-0"
T.O. FF101'-2"
T.O. PLY100'-0" = 7890'-9"
T.O. FF100'-2"
T.O. PAVER101'-0"
CA-303
9
27
28
29
13
ISOKERN UNIT36" MAGNUM SERIESSETBACK LINEPATIO
UP
18 R @ 7" = 10'-6"LIVING ROOM107
2
A-302
3
B
A
1
1.09
1.07
"
MAIN LEVEL
This fireplace wall is pushing out further than
the original, the roof plan should also be
revised to show this new fireplace consistently.
Provide fireplace details showing compliance
with the installation instructions for this gas log
fireplace (chimney termination, hearthextension, clearance to combustibles, etc).
From what I can tell from the elevations you donot meet the 2' above any structure within 10'
requirement in the provided installationinstructions.
DINING105 GARAGE107
BEDROOM 3008
BEDROOM 6208
W-1
W-6
W-7
W-7
12A-503
9A-502
3A-502
8A-502
F-1
FF-1
F-4
R-1
W-3
F-4
F-6 F-5
F-2
8"9'-13/8"1'-05/8"8'-73/8"105/8"209
106 107
007B
EXISTING UPPER LEVELT.O. PLY 110'-6"
T.O. EXISTING RIDGE125'-8 1/2"
PROPOSED LOWER LEVEL
EXISTING UPPER LEVEL STEPT.O. PLY 109'-6"
EXISTING MAIN LEVELT.O. PLY 101'-0" = 7891'-9"10'-111/2"PROPOSED MAIN LEVELT.O. PLY 100'-0" = 7890'-9"
1.09
1.10
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
WILDLIFE-RESISTANT TRASH ENCLOSURE PER26.575.020.E.5.t
STANDING SEAM ROOF
SYNTHETIC SHINGLE
ROOF OVERHANG
LINE OF FOUNDATION BELOW
FALL PROTECTION PROVIDED PER R612.2
1/4" PER 1' SLOPE
GAS LANTERNS BEVOLO CONTEMPORARY SERIES
ASPHAULT SHINGLES TO BE REPLACED
BRICK TO MATCH PAVER TBD
LINE OF PROPOSED GRADE
2" CURB TYP.
HOSE BIB
LADDER AND STEPS PER IRC R310.2.3.1
1/2 POINT FROM EAVE TO RIDGE
1/3 POINT FROM EAVE TO RIDGE
RADON VENT PIPE
VENTILATION FLUE
WINDOW FALL PROTECTION WILL BEPROVIDED PER R312.2.1
BEVOLO CONTEMPORARY SERIES LIGHT FIXTURE
Is the garage unconditioned? It was not shown as such in theoriginal permit drawings but F5 shows it as such. If that is the
case then then F5 would need to be insulated to R49 as a ceiling
since it is proposed to be altered and F4 would need to be R38 ifit is being altered. This would also move the thermal envelope
to be at W6 rather than W3. Please verify whether this space isconditioned and revise if needed.
M
10'-21/8"10'-61/8"77/8"10'-01/4"4"4"2'-101/8"63/4"3'-23/8"3'-21/4"63/4"3"4"21/2"1'-01/8"7"11"
CLOSED STAIR
STEEL STRINGER
STEEL HANDRAIL(TYP)
HANDRAIL RETURN
HANDRAIL RETURN
WOOD TREAD (TYP)
FULL HEIGHT BASEMENT WALLAND SHELF AT WINDOW SILLTYP.TYP.STORAGE UNDERNEATHSTAIRCASE. ACCESS FROMTYP.MAXIMUM SPACINGOF GUARD
TYP.TYP.
TYP.TYP.This maximum
opening needs to be
less than 4" so that it
restricts the passage
of a 4" sphere, please
revise. W10X33W10X33BEDROOM 1
BATH 1
STORAGE
11 7/8" LVL LEDGER w/ (2)5/8" TITEN HD @ 16"o.c. -TYP U.N.O.
W8X18
2x8 LEDGER w/5/8" TITEN HD @16"o.c. - EMBED 4"SHADING INDICATES 4"CONC SLAB w/ #3 @12"o.c. EA WAY CTRDT.O. SLAB = 100'-0"MIT11.88 HGR TYP @ 2 -COORD BM ALIGNMENTFOR HGR PLACEMENT11 7/8" LVL11 7/8" LVL(2) 11 7/8" LVL
OVERFRAMET.O. PLY = 101'-0"1'-61/2"2S6.003 3S6.00
.O. STL =99'-9 3/4"STL SHIM & WELD BASEPLATE TO BM IN LIEU OF MAX(2) A.B. AS REQ'D - TYP @ 2
#3 HOOKED DOWELS @12"o.c. - EMBED 6" INEPOXY AT TOP OF WALLCOL ABVRE: 4/S6.0011 2 3 4
Is the 4" slab
completely supported
by non combustible
construction? The 2x8
ledger note makes me
question this. Please
clarify and revise if
needed.
FP Response: The garage will be conditioned
space. W3 will remain as the thermal envelope at
the garage. Reference A-501 for an updated F-5
assembly showing both spaces are conditioned.
Reference details 3 and 8 on Sheet A-502
showing the existing assemblies, W-3 and R-1 to
be insulated with spray foam. Section A on sheet
A-301 also shows correct assemblies at the
garage.
FP Response: The 4" slab is not supported by non
combustible construction. This slab is on grade,
additionally supported by the new basement wall
below and cantilevered for the hearth extension.
The 2x8 Ledger is to support the new wood
framing on the main level. Reference detail 1, on
A-403 which shows a section of this condition.
FP Response: A glass guard will now be installed
instead of the lattice system previously shown. A
specification sheet for the glass guard railing
system has been provided. This glass guard
complies with COA 8.16.020(s) and Table R301.5.
Reference sheet A-401 for updated stair drawings.
FP Response: The roof plan has been revised to
show the new fireplace correctly. Exterior walls of
the fireplace are canted, which decreases the
overall width of the termination at the chimney
cap. An enlarged fireplace plan and sectional
drawings have been provided on sheet A-403. The
revised Fireplace now meets the IRC clearance
requirement of Table R1001.1 (R)