Page: 3
Checkmark: Unchecked
Author: jimp
File Name: 17.042C 614 W North Remodel - Permit
2017-10-02.pdf
Why are these walls shaded different than
the other walls?
FP Response: The shaded walls are existing to remain. All other foundation walls are being underpinned. REF: S2.002 and Z-101X.
17.042C 614 W North Remodel - Permit 2017-10-02.pdf (1)
Page: 1
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Please rewrite this.. The allowable FA is not
based on existing conditions but rather what
the code allows for. The allowable FA =
2,698.2
FP Response: The allowable floor area is based on existing conditions. The existing, nonconforming floor area is 2,793.05 SF. REF: Z-001.
Zoning Permit Set.614 W North St.2017.10.pdf (42)
Page: 1
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
15% of 2698.2 = 404.73
Page: 2
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
In the future, please include the RDS
Approval signed by a planner as well as
the stamped approved RDS drawings
FP Response: RDS Approval signed by a planner, and stamped, approved RDS drawings will be provided in the re-submittal. REF: Z-002.
Page: 4
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Page: 4
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
The mechanical engineer talked about an
exterior chiller unit. If so, please show it
on this drawing. if it is within the
setbacks, it needs to meet all of the
restrictions in 26.575.020.E.5, Allowed
Projections into Setbacks.
E
D
C
BW10X22(E) FLOOR PLY STEP - V.I.F.
REMOVE (E) CONC TONEW WINDOW WIDTH
(E) JOISTS - V.I.F.(E) JOISTS - V.I.F.
W8X10
NEW STL HDR - V.I.F.BM POCKET RE:2/S6.002 - TYP, V.I.F.CSWhy are these walls
shaded different thanthe other walls?
or Area
EET
Reference
26.710.040
Reference
Reference
Reference
Table 26.575.020-2
Existing Gross (Sq Ft)Existing Countable Floor Area (Sq Ft)Proposed Gross (Sq Ft)Proposed Countable Floor Area (Sq Ft)Reference1,249.75 164.05 1,645.75 98.58 Z-010X, Z-013
1,280.00 1,280.00 1,374.50 1,374.50 Z-011X, Z-014 Level)251.75 0.88 251.75 0.88 Z-011X, Z-014
1,373.00 1,334.75 1,372.00 1,304.50 Z-012X, Z-015
N/A
First 250 sq ft exempt
Next 251-500 sq ft to exlude 50% of area
15% of 4,080 allowable flor area per R-6
N/A
The allowable floor area of 2,779.67 is based on existing conditions. This is an existing, non-conforming floor area that is currently over the allowable floor area for thie current site of 2670 sq ft.
ments Reference
er R-6)6,000 sq ft 26.710.040
R-6)4,500 sq ft 26.710.040
Referenceh slopes 0%-20% (100% of parcel area to be
a)N/Ah slopes 20%-30% (50% of parcel area to be a)N/A
h slopes greater than 30% (0% of parcel area to be a)N/A
0
4065 sq ft
Please rewrite this.. The allowable FA is not based on existingconditions but rather what the code allows for. The allowableFA = 2,698.2
Existing Gross (Sq Ft)Existing Countable Floor Area (Sq Ft)Proposed Gross (Sq Ft)
1,249.75 164.05 1,645.75
1,280.00 1,280.00 1,374.50
251.75 0.88 251.75
1,373.00 1,334.75 1,372.00
81.00 0.00 161.00
4,235.50 2,779.68 4,805.00
N/A
First 250 sq ft exempt
Next 251-500 sq ft to exlude 50% of area
15% of 4,080 allowable flor area per R-6
N/A
area for thie current site of 2670 sq ft.
15% of 2698.2 = 404.73
DRAWING ISSUANCE INDEXID010203
NAMESCHEMATIC APPROVALDDRDS REVIEW
ISSUED DATE10/2/17, 11:34 AM10/2/17, 11:35 AM10/2/17, 12:02 PM
STEVENWILSON402127STATEOFCOLORADO
LICENSEDARCHITECT
COPYRIGHT
PROJECT NO:DRAWN BY:FORUM PHI LLC
DATE OF PUBLICATION
Z-002
RDS COMPLIANCE
10/3/17
RL/JM1712.00
Aspen CO 81611614 W NORTH ST
Aspen:715 West Main Street, #204Aspen, Colorado 81611
Basalt:104 Midland Ave, #202Basalt, CO 81612forumphi.comp: 970.279.4157f: 866.770.5585
273512112006
10/3/17
7/10/17, 5:00 PM 9/1/17, 10:00 AM
10/3/17, 9:30 AMPERMIT SUBMITTAL04
Residential Design Standards Administrative Compliance Review Applicant Checklist
Standard CompliesAlternative Compliance N/A Sheet #(s)/Notes
B.1.Articulation of Building Mass(Non-flexible)
B.2.Building Orientation(Flexible)B.3.Build-to Requirement(Flexible)
B.4.One Story Element(Flexible)
C.1.Garage Access(Non-flexible)
C.2.Garage Placement(Non-flexible)
C.3.Garage Dimensions(Flexible)
Instructions: Please fill out the checklist below, marking whether the proposed design complies with the applicable standard as written or is requesting Alternative Compliance (only permitted for Flexible standards). Also include the sheet #(s) demonstrating the applicable standard. If a standard does not apply, please mark N/A and include in the Notes section why it does not apply. If Alternative Compliance is requested for a Flexible standard, include in the Notes section how the proposed design meets the intent of the standard(s). Additional sheets/graphics may be attached.Disclaimer: This application is only valid for the attached design. If any element of the design subject to Residential Design Standards changes prior to or during building permit review, the applicant shall be required to apply for a new Administrative Compliance Review.
Address: Parcel ID: Zone District/PD:
Representative: Email: Phone:
Page 1 of 2
Z-003X, Z-003, Z-102: Not applicable, the existing garage is accessed from a private alley and access to the residence is to remain unchanged.
Z-003X, Z-003, Z-102: The existing garage is accessed from a private alley and access to the residence is to remain unchanged.
Z-003X, Z-003, Z-102: The existing garage is accessed from a private alley and access to the residence is to remain unchanged.
Z-003, Z-201: The front loggia is recessed at least six (6) feet from the front facade and has a width equivalent to at least 20% of the building's overall width. The loggia is open on two sides and is street facing.
Z-003X: Not applicable, the existing non-conforming footprint is not within 60% of the front yard setback line.
Z-003X, Z-003: Not applicable, the existing footprint is to be utilized.
Z-102X, Z-102: Not applicable, the existing structure has a non-conforming building depth of 59'-8". The proposed depth of residence is to remain unchanged.
4
4
4
4
444
(405) 314-5104R-6 rlee@forumphi.com273512112006Ryan Lee614 W NORTH ST
Standard CompliesAlternative Compliance N/A Sheet #(s)/Notes
C.4.Garage Door Design(Flexible)
D.1.Entry Connection(Non-flexible)
D.2.Door Height(Flexible)
D.3.Entry Porch(Flexible)
E.1.Principle Window(Flexible)
E.2.Window Placement(Flexible)
E.3.Nonorthogonal Window Limit(Flexible)
E.4.Lightwell/Stairwell Location(Flexible)
E.5.Materials(Flexible)
Residential Design Standards Administrative Compliance Review Applicant Checklist
Disclaimer: This application is only valid for the attached design. If any element of the design subject to Residential Design Standards changes prior to or during building permit review, the applicant shall be required to apply for a new Administrative Compliance Review.
Page 2 of 2
Z-201, Z-202, Z-203: The quality, details, and application of the proposed exterior materials are consistent on all sides of the building. 4
Z-003X, Z-003, Z-101, Z-102: Proposed lightwells are located behind the front most wall on the street facing facade. 4
Z-201: There are no non-orthogonal windows on the street-facing facade in this proposed design. 4
Z-201, Z-202, Z-203: No windows in this proposed design span more than one story vertically.4
Z-201: The proposed design has a group of windows on the front facade that when measured is greater than four (4) feet by four (4) feet. 4
Z-201: The front porch in this proposed design is no more than one-story in height. 4
Z-201: All doors facing the street in this proposed design are not taller than eight (8) feet. 44
4
Z-102, Z-201: The street facing entry door is not set back more than ten (10) feet from the principal facade.
Z-003, Z-203: The garage is a one-car garage with a single door.
10/11/17
In the future, pleaseinclude the RDSApproval signed by aplanner as well asthe stampedapproved RDSdrawings
ONC1/2"27
28
9
29
ETBACK
7'-7"5'-0"
10'-0"
T.O.CONC99'-11 1/2"
40
27
28
9
29
3
57
7890
ALLEYREAR YARDSETBACK
PROPERTY LINE5' REAR SETBACK LINE10' REAR SETBACK LINEREAR YARDSETBACK
TRASH
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
WILDLIFE-RESISTANT T26.575.020.E.5.t
EXISTING HORIZONTAL
VERTICAL METAL SIDING
STANDING SEAM ROOF
SYNTHETIC SHINGLE
ROOF OVERHANG
LINE OF FOUNDATION B
FALL PROTECTION PRO
1/4" PER 1' SLOPE
GAS LANTERNS BEVOL
ASPHAULT SHINGLES T
BRICK TO MATCH PAVER
LINE OF PROPOSED GR
2" CURB TYP.
HOSE BIB
LADDER AND STEPS PE
1/2 POINT FROM EAVE T
1/3 POINT FROM EAVE T
RADON VENT PIPE
For this window well
to be in the setback,
it needs to be the
minimum necessary
for building codecompliance. this
would be no larger
than 3' x 6' since it
serves two bedrooms
- please revise.
The mechanical engineer talked
about an exterior chiller unit. If
so, please show it on this
drawing. if it is within the
setbacks, it needs to meet all of
the restrictions in
26.575.020.E.5, Allowed
Projections into Setbacks.
FP Response: The deck area exemption on Z-001 has been updated to show 15% of 2698.2 SF, which is the allowable floor area per R-6 zoning. REF: Z-001.
Page: 6
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FP Response: Chiller units have been added to the Proposed Site Plan, Z-003 & Z-202
7'-7"
FP Response: The window well is existing to remain. Dimension
has been revised to the original 7'-4 7/8" depth. REF: Z-003X,
Z-003, Z-101X & Z-101
For this window well to be in the setback,
it needs to be the minimum necessary for
building code compliance. this would be
no larger than 3' x 6' since it serves two
bedrooms - please revise.
FP Response: The window well is existing
to remain. REF: Z-003X, Z-003, Z-101X & Z-101
2/27/2018
Page: 7
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FP Response: The wall demolition diagrams only include calculations of exterior walls above grade. Demolition diagrams have been removed from the lower level. REF: Z-006, Z-007 and Z-008.
There is no reason to include wall
demolition drawings or calculations for the
sub-grade space, because demolition is
only above grade walls and roof.
Page: 8
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
There is a whole section of wall being cut
out here for the new chimney - revise
FP Response: All demolition calculations and graphics for diagram 13 have been updated to include correct demolition area. REF: Z-007 and Z-008.
Page: 8
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
There is a new door being cut in here -
revise
FP Response: All demolition calculations and graphics for diagram 9 have been updated to include correct demolition area. REF: Z-007 and Z-008.
Page: 8
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
This window is changing shape - revise
FP Response: All demolition calculations and graphics for diagram 13 have been
updated to include correct demolition area. REF: Z-007 and Z-008.
Page: 8
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
The bank of windows is changing shape
-revise
FP Response: All demolition calculations and graphics for diagram 2 have been updated to include correct demolition area. REF: Z-007 and Z-008.
Page: 8
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
A new opening is being cut in here.
FP Response: All demolition calculations and graphics for diagram 18 have been
updated to include correct demolition area. REF: Z-007 and Z-008.
Page: 10
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Show the top of the chimney as being
removed - revise
FP Response: The top of the chimney has been revised to show area being demolished. REF: Z-009.
DRAWING ISSUANCE INDEX
ID010203
NAMESCHEMATIC APPROVALDDRDS REVIEW
ISSUED D10/2/17, 11:310/2/17, 11:310/2/17, 12:0
STEVENWILSON402127STATEOFCOLORADOLICENSEDARCHITECT
COPYRIGHT
PROJECT NO:DRAWN BY:FORUM PHI LLC
DATE OF PUBLICATION 10/3/17
RL/JM1712.00
Aspen CO 81611614 W NORTH ST
Aspen:715 West Main Street, #204Aspen, Colorado 81611Basalt:104 Midland Ave, #202Basalt, CO 81612
forumphi.comp: 970.279.4157f: 866.770.5585
273512112006
10/3/17
7/10/17, 5:0 9/1/17, 10:0
10/3/17, 9:3PERMIT SUBMITTAL04
1
PROPERTY LINE
SETBACK LINE
LINE YP.2 3 4 5 6
D D
C C
E E
B B
1.) EXISTING FRAMING & SHEATHING TO REMAIN AT AREASNOT SHOWN AS DEMOLISHED. TYPICAL.2.) ALL DIMENSIONS TO EXISTING WALLS TO BE VERIFIEDIN FIELD. TYPICAL.3.) EXISTING RIDGE HEIGHTS TO REMAIN.4.) ALL EXTERIOR MATERIALS TO REMAIN AND TO BE RE-FINISHED UNLESS NOTED OTHERWISE.5.) ALL EXISTING WINDOWS AND EXTERIOR DOORS TO BEREPLACED. VERIFY IN FILED PRIOR TO ALL SHOP DRAWINGAPPROVALS.6.) VERIFY ALL EXISTING & PROPOSED SPOT ELEVATIONSIN FIELD. PROJECT 100'-0" IS IN RELATION TO EXISTINGTOP OF PLYWOOD ON THE MAIN LEVEL.
GENERAL PLAN NOTES
EXISTING TO REMAIN
TO BE DEMOLISHED
NEW WALL
WALL LEGEND
14.00 sq ft14.00 sq ft
273.75 sq ft
10.25 sq ft3.50 sq ft23.50 sq ft
160.00 sq ft
343.25 sq ft
217.75 sq ft
40.75 sq ft
21.25 sq ft
10.00 sq ft 9.25 sq ft 9.25 sq ft 67.25 sq ft
4.00 sq ft
4.00 sq ft4.00 sq ft
21.25 sq ft
25.25 sq ft 8.50 sq ft
8.50 sq ft 13.75 sq ft
13.75 sq ft 8.50 sq ft
34.00 sq ft
14.00 sq ft
8.50 sq ft
8.50 sq ft
8.50 sq ft
8.50 sq ft
30.75 sq ft
352.50 sq ft
100.25 sq ft50.00 sq ft
311.00 sq ft
178.00 sq ft
115.75 sq ft
155.75 sq ft
116.25 sq ft
127.00 sq ft
52.25 sq ft
293.00 sq ft 86.75 sq ft
170.00 sq ft
55.50 sq ft
52.25 sq ft 110.25 sq ft
95.25 sq ft 95.25 sq ft
1 2 3 4 5 6 7 8
9 10 11 12 13 14 16 17 1815
26.75 sq ft
xisting Wall Demolition Calculations W NORTH ST
l Demolition
Wall Label Individual Wall Area (Sq Ft)Area Reduced for Fenestration(Sq Ft)Area of Wall to be Removed(Sq Ft)1 273.75 65.25 160.002352.50 54.75 0.003100.25 0.00 100.25450.00 0.00 50.005311.00 31.25 0.006293.75 18.50 0.007155.75 67.25 0.008217.75 12.00 30.759343.25 46.50 116.251052.25 0.00 52.2511127.00 0.00 127.001252.25 0.00 52.2513293.00 17.00 0.00
0 4'8'16'SCALE: 1/8" = 1'-0"DEMOLITION CALCULATIONS 1
There is no reason to include wall demolitiondrawings or calculations for the sub-gradespace, because demolition is only abovegrade walls and roof.
1 2 3
8.50 sq ft
8.50 sq ft
127.00 sq ft
52.25 sq ft
293.00 sq ft
52.25 sq ft 110.25 sq ft
10 11 12 13 14
26.75 sq ft
NS There is a whole
section of wall being
cut out here for the
new chimney - revise
25.25 sq ft
9
SCALE: 1/8" = 1'-0"
DEMOLITION CALCULATIONS
There is a new door
being cut in here -
revise
q ft
ft
ft 8.50 sq ft
127.00 sq ft
52.25 sq ft
293.00 sq ft
52.25 sq ft
10 11 12 13
ULATIONSThis window is
changing shape -
revise
40.75 sq ft
352.50 sq ft
100.25 sq ft 50.00 sq ft
3 4 5
The bank of windows
is changing shape -
revise
8.50 sq ft
34.00 sq ft
170.00 sq ft
55.50 sq ft
18
A new opening is
being cut in here.
3 4
O
P
Show the top of the
chimney as being
removed - revise
2/27/2018
Page: 10
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
As shown on the roof plans, much of the
eaves are being shortened - revise
FP Response: All roof sheathing, structure, heights, and overhangs are existing to remain. Verify in field. REF: General Roof Notes on Z-009.
Page: 11
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
16?
FP Response: Graphic label has
been updated from 19 to 16. REF: Z-010X.
Page: 11
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
15?
FP Response: Graphic label has been updated from 18 to 15. REF: Z-010X.
Page: 11
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
14?
FP Response: Graphic label has been updated from 17 to 14. REF:
Z-010X.
Page: 13
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Less than 15% of allowable and therefore
exempt.
FP Response: Existing Floor Area Calculations have been revised to exempt all deck SF under 15% of allowable SF. REF: Z-011X.
Page: 14
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdfFP Response: Subgrade wall diagrams 1-8 have been revised to show any exposed wall area above grade, excluding floor structure, per 26.575.020.D.8. Floor Area calculations have been revised to reflect exposure. REF: Z-010-X and Z-013.
As per 26.575.020.D.8, Subgrade Areas,
the diagrams above are supposed to
show exposed wall above natural or
finished grade. Looking at the exposed
wall diagrams in the existing FA drawings,
as well as the existing elevations, there
should be exposed wall along the tops of
many of these subgrade walls.
Page: 14
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
This does not match the structural
drawings. Please make the two drawings
match.
FP Response: Structural drawings have been updated to match proposed walls in the lower level. REF: Z-013 and S2.001.
DRAWING ISSUANCE IND
ID0102
03
NAMESCHEMATIC APPROVALDD
RDS REVIEW
IS11
10
STEVENWILSON402127STATEOFCOLORADLICENSEDARCHITEC
COPYRIGHT
PROJECT NO:DRAWN BY:FORUM P
DATE OF PUBLICATION 10/3/17
RL/JM1712.00
Aspen CO 81611614 W NORTH
Aspen:715 West Main Street, #Aspen, Colorado 816
Basalt:104 Midland Ave, #20Basalt, CO 81612
forumphi.comp: 970.279.4157f: 866.770.5585
273512112006
10/3/17
7
PERMIT SUBMITTAL04
1 2 3 4 5 6
EXISTING TO REMAIN
TO BE DEMOLISHED
NEW ROOF
16.25 sq ft
18.75 sq ft
4.75 sq ft
4.75 sq ft
29.75 sq ft
24.50 sq ft
19.50 sq ft 233.50 sq ft
218.25 sq ft
15.25 sq ft
15.25 sq ft
254.75 sq ft 430.25 sq ft
370.50 sq ft
78.25 sq ft
194.50 sq ft
36.50 sq ft
233.50 sq ft
15.25 sq ft
15.25 sq ft
9.25 sq ft
19.50 sq ft
6.75 sq ft
1.50 sq ft
A
B
C
D
E F
G
H
I
J
K
O
L
M
N
P
Q R
S
T
U
V
1.) EXISTING FRAMING & SHEATHING TO REMAIN AT AREASNOT SHOWN AS DEMOLISHED. TYPICAL.
2.) ALL DIMENSIONS TO EXISTING WALLS TO BE VERIFIEDIN FIELD. TYPICAL.
3.) EXISTING RIDGE HEIGHTS TO REMAIN.4.) ALL EXTERIOR MATERIALS TO REMAIN AND TO BE RE-FINISHED UNLESS NOTED OTHERWISE.5.) ALL EXISTING WINDOWS AND EXTERIOR DOORS TO BEREPLACED. VERIFY IN FILED PRIOR TO ALL SHOP DRAWINGAPPROVALS.6.) VERIFY ALL EXISTING & PROPOSED SPOT ELEVATIONSIN FIELD. PROJECT 100'-0" IS IN RELATION TO EXISTINGTOP OF PLYWOOD ON THE MAIN LEVEL.
0 4'8'16'SCALE: 1/8" = 1'-0"
ROOF DEMOLITION
As shown on the roofplans, much of theeaves are beingshortened - revise
EXEMPT - OPEN TO BELOW
EXEMPT - FRONT PORCH
1'-77/8"5'-51/4"8'-33/8"8'-33/8"13.75 sq ft 45.00 sq ft
1918
4'8'16'
16?6'-10"8'-33/13.75 sq ft 45.00 sq ft
1918
0 4'8'
15?
41'-7"7'-6344.25 sq ft
17
102.25 sq ft
1'-0"
G SUBGRADE CALCULATIONS
14?
1,334.75
2,779.67
0.00
81.00
81.00
Less than 15% of
allowable and
therefore exempt.
20.75 sq ft
42.75 sq ft
20.75 sq ft
32'-11/4"27'-7"2'-3"
25'-11"18'-8"11'-11"8'-33/8"9'-101/4"41'-7"8'-33/8"8'-33/8"8'-33/8"8'-33/8"8'-33/8"8'-33/8"8'-33/8"265.75 sq ft
81.50 sq ft
98.75 sq ft
154.50 sq ft214.50 sq ft
18.75 sq ft
344.25 sq ft
228.50 sq ft
1 2
7
654
3
8
COUNTABLE
FAR LEGEND
DECK
GARAGE
EXEMPT - OP
EXEMPT - FR
1.) EXISTING FRAMINGNOT SHOWN AS DEMOL
2.) ALL DIMENSIONS TOIN FIELD. TYPICAL.
3.) EXISTING RIDGE HE
4.) ALL EXTERIOR MATEFINISHED UNLESS NOT
5.) ALL EXISTING WINDREPLACED. VERIFY IN FAPPROVALS.
6.) VERIFY ALL EXISTININ FIELD. PROJECT 100TOP OF PLYWOOD ON T
GENERAL PLA
0 4'8'16'SCALE: 1/8" = 1'-0"PROPOSED SUBGRADE CALCULATIONS
As per 26.575.020.D.8, Subgrade Areas, the
diagrams above are supposed to show exposedwall above natural or finished grade. Looking atthe exposed wall diagrams in the existing FAdrawings, as well as the existing elevations,there should be exposed wall along the tops ofmany of these subgrade walls.
1,645.75 sq
2 3
C
A
1 18PROPERTY LINESETBACK LINEB
@50%
SCALE: 1/8" = 1'-0"
PROPOSED LOWER LEVEL FLOOR AREA
This does not match
the structural
drawings. Pleasemake the two
drawings match.
2/27/2018
Page: 20
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-1 1/2"
FP Response: All roof sheathing, rafters, and overhangs are existing to
remain. Heights are to remain unchanged. All dimensions to be
verified in field. REF: General Roof Notes on Z-104X.
Page: 20
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-1 1/2"
FP Response: All roof sheathing, rafters, and overhangs are existing to
remain. Heights are to remain unchanged. All dimensions to be
verified in field. REF: General Roof Notes on Z-104X.
Page: 20
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-1 1/2"
FP Response: All roof sheathing, rafters, and overhangs are existing to
remain. Heights are to remain unchanged. All dimensions to be
verified in field. REF: General Roof Notes on Z-104X.
Page: 20
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-1 1/2"
FP Response: All roof sheathing, rafters, and overhangs are existing to
remain. Heights are to remain unchanged. All dimensions to be
verified in field. REF: General Roof Notes on Z-104X.
Page: 22
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
22'-5 1/4"
Page: 22
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdfFP Response: Subgrade wall diagrams 1-8 have been revised to show any exposed wall area above grade, excluding floor structure, per 26.575.020.D.8. Floor Area calculations have been revised to reflect exposure. REF: Z-013.
As per 26.575.020.D.8, Sub-grade Areas,
Sub-grade walls are to be measured
outward. Therefore, when projecting the
inside of the sub-grade walls out, if any
portion of that wall would be exposed,
then that exposure should be shown on
the sub-grade wall diagrams.
Page: 23
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FIELD.1'-1 1/2"1'-1 1/2"1'-1 1/2"1'-1 1/2"22'-5 1/4"
EXISTING GRADE
SCALE: 1/4" = 1'-0"EXISTING WEST ELEVATION
As per 26.575.020.D.8, Sub-grade Areas, Sub-grade walls are to bemeasured outward. Therefore, when projecting the inside of the sub-gradewalls out, if any portion of that wall would be exposed, then that exposureshould be shown on the sub-grade wall diagrams.
EXISTING GRADESETBAC 25'-0"25'-0"
FP Response: Existing ridge heights to remain
unchanged except for the extension above the master bedroom. Roof plans, heights over
topography, and all elevations have been updated to show the 25'-0" height limit. REF:
Z-005, Z-104, Z-201, Z-202 and Z-203.
2/27/2018
Page: 25
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
The exception for Overhangs projecting
into the setback is 1'-6". This overhang is
1'-11". I understand that part of this is
probably gutters, which are also allowed
to project into the setback, but
exemptions cannot be combined.
Therefore the total projection cannot be
more than 1'6" - revise.
Page: 26
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-11 1/16"
FP Response: The proposed remodel no
longer includes a gutter along the new roof projection on the South side of the
development. The projection is now 1'-4" into the setback. REF: Z-005.
Page: 27
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-3 1/2"
FP Response: All roof sheathing, rafters, and overhangs are existing to
remain. Heights are to remain unchanged. All dimensions to be
verified in field. REF: Z-104X, Z-104, & Z-204
Page: 27
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
0'-9 1/2"
FP Response: All roof sheathing,
rafters, and overhangs are existing to remain. Heights are to remain
unchanged. All dimensions to be verified in field. REF: Z-104X, Z-104,
& Z-204
Page: 27
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
0'-9 1/2"
FP Response: All roof sheathing,
rafters, and overhangs are existing to remain. Heights are to remain
unchanged. All dimensions to be verified in field. REF: Z-104X, Z-104,
& Z-204
Page: 27
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
0'-9 5/8"
FP Response: All roof sheathing,
rafters, and overhangs are existing to remain. Heights are to remain
unchanged. All dimensions to be verified in field. REF: Z-104X, Z-104,
& Z-204
LINE OF ROOFABOVE LINEABO
1024'-2"3'-77/8"
51/2"3'-81/2"51/2"3'-23/8"51/2"1'-11"1'-91/2"3'-2"E
D
This post placement
does not match your
structurals. please
verify that the post
will be outside of the
setback.
1Z-201
6'-10"-41/2"51/2"8'-8"2'-111/2"E
D
The exception for Overhangs projecting
into the setback is 1'-6". This overhang is
1'-11". I understand that part of this is
probably gutters, which are also allowed to
project into the setback, but exemptions
cannot be combined. Therefore the total
projection cannot be more than 1'6" -
revise.
1'-1
1
1
/
1
6
"1'-3 1/2"0'-9 1/2"0'-9 1/2"0'-9 5/8"This post placement does not match your
structurals. please verify that the post will be
outside of the setback.
FP Response: Structural drawings have been updated to show correct post placement. REF:
S2.002 and Z-102.
Page: 26
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FP Response: The proposed remodel no longer includes a gutter along the new roof projection on the South side of
the development. The projection is now 1'-4" into the setback. REF: Z-005.
2/27/2018
Page: 28
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
25'-0"
FP Response: Existing ridge heights to remain unchanged except for the extension above the master bedroom. Roof plans, heights over topography, and all elevations have been updated to show the 25'-0" height limit. REF: Z-005, Z-104, Z-201, Z-202, Z-203 & Z-204.
Page: 28
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Page: 29
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
On all of your elevations I believe that these
two lines are reversed.
FP Response: Setback and Property Lines have been corrected on all existing and proposed elevations and sections. REF: Z-201X, Z-202X, Z-203X, Z-201, Z-202, andZ-203.
It appears that the proposed patio will be
more than 6" above the grade. Either
show how this patio is no more than 6"
above grade, or reduce the height of the
patio.
There seem to be several height
challenges here. based on what you are
showing as grade, 25' seems to be much
lower than what you are showing. Please
either revise proposed grade or lower the
maximum height line. This new roof
element over the brand new projection on
the front of the house has a different roof
line than the rest of the gable, and
therefore has a different 1/3 point. Please
show both 1/3 points(the main gable and
this smaller projecting gable)
Page: 30
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
1'-2 3/8"
FP Response: Graphics have been updated to show existing grade around the proposed
patio. The patio is less than 6" above any existing and proposed grade. REF: Z-203.
Page: 30
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
14
32
7
9
18
2
2
5
61
60
61
2
9'-0"8'-6"1'-0"107108
29
26
28
10
58
60
10
6060
EXISTING MAIN LEVELT.O. PLY 100'-0" = 7891'-9"
EXISTING UPPER LEVELT.O. PLY 109'-6"
T.O. EXISTING RIDGE127'-0"
EXISTING UPPER LEVEL STEPT.O. PLY 108'-6"2'-3 3/8"SGSG 12'-7 1/4"2'-7 5/8"T.O. EXISTING RIDGE124'-8 7/8"
T.O. EXISTING RIDGE122'-1 1/4"
003004 25'-0"-0"8'-6"1'-0"115
205206 201202
10
14
32
7 117101102
9
13
6
5
4
18
7 7
29
27
58
29
27
58
61
61
60
61
28 28
EXISTT.O. PLY
EXISTIN
T.O.
EXISTING UPP12'-7 1/4"2'-3 3/8"SGSG
SGSG
SGSGSGSG 2'-7 5/8"T.O.
T.O.25'-0"2 1
18
61
T.O. EXISTING RIDG127'-2'-3 3/8"2'-7 5/8"T.O. EXISTING RIDG124'-8 7PROPERTY LINESETBACK LINEOn all of yourelevations I believethat these two linesare reversed.
It appears that the
proposed patio will
be more than 6"
above the grade.
Either show how this
patio is no more than
6" above grade, or
reduce the height of
the patio.
1 2 3
113114
212
10
13
26
9
18
56
29
58
28PROPERTY LINESETBACK LINESG
SG SG
001
There seem to be several heightchallenges here. based on what you areshowing as grade, 25' seems to be muchlower than what you are showing. Please
either revise proposed grade or lower themaximum height line. This new roofelement over the brand new projection onthe front of the house has a different roofline than the rest of the gable, andtherefore has a different 1/3 point. Pleaseshow both 1/3 points(the main gable andthis smaller projecting gable)1'-2 3/8"113114
212
10
13
9
18
56
29
58
28
SG
SG SG
00125'-0"Page: 30
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FP Response: The 25'-0" height restriction has been revised
to be precisely 25'-0" above existing grade. A 1/3 Point has been added to both planes of the new projecting roof. All 1/3
and 1/2 Points from roof eave to ridge are below the 25'-0" height restriction. REF: Keynote 18 on Z-201, Z-202, Z-203,
and Z-204.
Page: 30
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
FP Response: Graphics have been updated to show existing
grade around the proposed patio. The patio is less than 6" above any existing and proposed grade. REF: Z-203.
25'-0"
FP Response: Existing ridge heights to remain
unchanged except for the extension above the master bedroom. Roof plans, heights over
topography, and all elevations have been updated to show the 25'-0" height limit. REF:
Z-005, Z-104, Z-201, Z-202, Z-203 & Z-204.
25'-0"
FP Response: Existing ridge heights to remain
unchanged except for the extension above the master bedroom. Roof plans, heights over
topography, and all elevations have been updated to show the 25'-0" height limit. REF:
Z-005, Z-104, Z-201, Z-202 and Z-203.2/27/2018
Page: 31
Checkmark: Unchecked
Author: jimp
File Name: Zoning Permit Set.614 W North St.2017.10.pdf
Provide a 1/3 point for either side of this
projecting gable
FP Response: A 1/3 Point has been added to both planes of the new projecting roof. All 1/3 and 1/2 Points from roof eave to ridge are below the 25'-0" height restriction. REF: Graphic labels B and D on Z-204.
54.9723°
20.1832°PROPERTY LINESETBACK LINE78917892
28'-0"
B
A
C
12:12
12:12
12:12
12:12 12:12
23
23
RIDGE
1/3 POINT
1/3 POINT
1/2 POINT
C
B
A
D
Provide a 1/3 pointfor either side of thisprojecting gable
2/27/2018