HomeMy WebLinkAboutFile Documents.330 Gillespie St.0003.2018 (15).ARBK A-Ot_Lochinvar Typical Specification 615-889-8900/Fax:615-547-1000 KHN-SPEC-01 www.Loch i nvar.com Typical Specification for Lochinvar® KNIGHTTM Heating Boiler Models 55,000—285,000 Btu/Hr The BOILER shall be a LOCHINVAR KNIGHT Model KHN 199 having a modulating input rating of Btu/Hr,an output of Btu/Hr and shall be operated on(Natural Gas)(L.P.Gas). The BOILER shall be capable of following performance: Model Turndown Minimum Input Maximum Input KHN055 6.7:1 8,200 55,000 KHN085 10:1 8,500 85,000 KHN110 10:1 11,100 110,000 KHN155 10:1 15,500 155,000 KHN199 10:1 19,999 199,999 KHN285 10:1 28,500 285,000 Maximum unit dimensions shall be: 19 inches Length, 16 inches Width and 43-1/2 inches Height. Maximum operating(wet)unit weight shall be no more than 205 pounds. The BOILER shall bear the ASME"H" stamp for 80 psi working pressure and shall be National Board listed. The BOILER shall have a fully welded, stainless steel, fire tube heat exchanger.There shall be no banding material, bolts,gaskets or"0"rings in the pressure vessel construction. The heat exchanger shall be designed for a single- pass water flow to limit the water side pressure drop. The condensate collection basin shall be constructed of welded stainless steel.The complete heat exchanger assembly shall carry a twelve(12)year limited warranty. The heat exchanger shall have a volume of water no less than: Model Water Content KHN055 2.3 gallons KHNO85 2.2 gallons KHN110 3.2 gallons KHN155 3.2 gallons KHN199 5.2 gallons KHN285 4.9 gallons The BOILER shall be certified and listed by C.S.A. International under the latest edition of the harmonized ANSI Z21.13 test standard for the U.S.and Canada. The BOILER shall operate at a minimum of 95%AFUE Efficiency as registered with AHRI. The BOILER shall be certified for indoor installation. The BOILER shall be constructed with a heavy gauge steel jacket assembly,primed and pre-painted on both sides. The combustion chamber shall be sealed and completely enclosed,independent of the outer jacket assembly,so that integrity of the outer jacket does not affect a proper seal.A burner/flame observation port shall be provided for observing the burner flame and combustion chamber. The burner shall be a premix design constructed of high temperature stainless steel with a woven Fecralloy outer covering to provide smooth operation at all modulating firing rates. The BOILER shall be supplied with a negative pressure regulation gas valve and be equipped with a pulse width modulation blower system to precisely control the fuel/air mixture to the burner.The BOILER shall operate in a safe condition with gas supply pressures as low as 4 inches of water column. The burner flame shall be ignited by direct spark ignition with flame monitoring via a flame sensor. The BOILER shall utilize a 24 VAC control circuit and components. The control system shall have a factory installed display for boiler set-up,boiler status,and boiler diagnostics.All components shall be easily accessed and serviceable from the front and top of the jacket.The BOILER shall be equipped with a temperature/pressure gauge; high limit temperature control with manual reset;ASME certified pressure relief valve set for 30 psi(standard); outlet water temperature sensor with a dual thermistor to verify accuracy; system supply water temperature sensor; outdoor air sensor,flue temperature sensor with dual thermistor to verify accuracy;low water cut off with manual reset,blocked drain switch and a condensate trap for the heat exchanger condensate drain. The BOILER shall feature the"SMART SYSTEMTM"control which is standard and factory installed with 128 x 128 resolution display,password security,outdoor air reset,pump delay with freeze protection,pump exercise,ramp delay featuring six steps,domestic hot water prioritization with limiting capabilities,USB drive for simple uploading of parameters and a PC port connection for connection to a local computer for programming and trending. A secondary operating control that is field mounted outside or inside the appliance is not acceptable. The BOILER shall have alarm contacts for any failure,runtime contacts and data logging of runtime at given modulation rates, ignition attempts and ignition failures. The BOILER shall have a built-in"Cascade"with leader redundancy to sequence and rotate while maintaining modulation of up to eight boilers of different Btu inputs without utilization of an external controller. The internal"Cascade"function shall be capable of lead-lag,efficiency optimization,front- end loading,and rotation of lead boiler every 24 hours.The BOILER shall be capable of remote communication via optional CON-X-USTM Remote Connectivity with the capability of historical trending and sending text message or email alerts to notify the caretaker of a boiler alarm and remote programming of onboard boiler control.The control must have optional capability to communicate via Modbus protocol with a minimum of 46 readable points. The BOILER shall have an optional gateway device which will allow integration with LON or BacNet protocols. The"SMART SYSTEMTM"control shall increase fan speed to boost flame signal when a weak flame signal is detected during normal operation. A 0-10 VDC output signal shall control a variable speed boiler pump to keep a fixed Delta T across the boiler regardless of the modulation rate. The BOILER shall have the capability to receive a 0-10 VDC input signal from a variable speed system pump to anticipate changes in system heat load in order to prevent flow related issues such as erratic temperature cycling. The BOILER shall be equipped with two terminal strips for electrical connection. A low voltage connection board with 46 connection points for safety and operating controls,i.e.,Alarm Contacts,Runtime Contacts,Low Water Cut Off,Louver Proving Switch,Tank Thermostat,Domestic Hot Water Building Recirculation Pump Contacts, Domestic Hot Water Building Recirculation Temperature Sensor Contacts,Remote Enable/Disable, System Supply Temperature Sensor,Outdoor Temperature Sensor,Tank Temperature Sensor,Modbus Building Management System Signal and Cascade Control Circuit. A high voltage terminal strip shall be provided for Supply voltage. Supply voltage shall be 120 volt/60 hertz/single phase on all models.The high voltage terminal strip plus integral relays are provided for independent pump control of the System pump,the Boiler pump and the Domestic Hot Water pump. The BOILER shall be installed and vented with a(select one): (a)Direct Vent system with horizontal sidewall termination of both the exhaust vent and combustion air. The flue shall be Category IV approved material constructed of PVC,CPVC,Polypropylene or Stainless Steel. A separate pipe shall supply combustion air directly to the boiler from the outside. The boiler's total combined air intake length shall not exceed 100 equivalent feet. The boiler's total combined exhaust venting length shall not exceed 100 equivalent feet. (b)Direct Vent system with vertical roof top termination of both the exhaust vent and combustion air. The flue shall be Category IV approved material constructed of PVC,CPVC,Polypropylene or Stainless Steel. A separate pipe shall supply combustion air directly to the boiler from the outside. The boiler's total combined air intake length shall not exceed 100 equivalent feet. The boiler's total combined exhaust venting length shall not exceed 100 equivalent feet. The air inlet must terminate on the rooftop with the exhaust. RECEIVED 01/09/2018 ASPEN BUILDING DEPARTMENT (c)Vent system with Vertical rooftop Exhaust and Horizontal sidewall Air Intake with the combustion air intake in a different pressure zone. The flue shall be Category IV approved material constructed of PVC, CPVC,Polypropylene or Stainless Steel. A separate pipe shall supply combustion air directly to the boiler from the outside in a different pressure zone from that of the exhaust vent. The boiler's total combined air intake length shall not exceed 100 equivalent feet. The boiler's total combined exhaust venting length shall not exceed 100 equivalent feet. (d)Vertical rooftop or Horizontal sidewall exhaust with the combustion air drawn from the equipment room. The flue shall be Category IV approved material constructed of PVC,CPVC,Polypropylene or Stainless Steel. The boiler's total exhaust venting length shall not exceed 100 equivalent feet. Combustion air drawn from the equipment room shall be supplied with properly sized combustion and ventilation air openings based on NFPA requirements. The BOILER shall have an independent laboratory rating for Oxides of Nitrogen(NOX)to meet the requirements of South Coast Air Quality Management District in Southern California and the requirements of Texas Commission on Environmental Quality. The manufacturer shall verify proper operation of the burner,all controls and the integrity of the heat exchanger by connection to water and venting for a factory fire test prior to shipping. The BOILER shall operate at altitudes up to 4,500 feet above sea level without additional parts or adjustments. The BOILER shall be certified for operation at elevations of 4,500 feet,and above,by a 3' party organization. The BOILER shall be suitable for use with polypropylene glycol up to a 50%concentration. The de-rate associated with the glycol will vary per glycol manufacturer. STANDARD CONSTRUCTION The BOILER shall be constructed in accordance with the following code requirements as standard equipment. Manufacturing of special models to meet the below code requirements is not acceptable. California Code(Except KHN285) Massachusetts Code Kentucky Code CRN Approval in Canada Note: Due to the large disparity in CSD-1 interpretation from state to state,please confirm to the factory all controls required in your jurisdiction. 11/15—Printed in U.S.A. RECEIVED 01/09/2018 ASPEN BUILDING DEPARTMENT KNIGHT®BOILER DIMENSIONS AND SPECIFICATIONS* : AIR INLET A ` WATER OUTLET �1�-� LUE `I! 1 • II GAS CONNECTIONIIP -Madam 2-3/4" :,.:i it T--� t • 43-3/8" 2-7/8" '-%" r p i HIGH-VOLTAGE B ELECTRICAL I'y� • CONNECTIONS IS • • M D ® LOW-VOLTAGE ELECTRICAL F Men 19" O CONNECTIONS I_ G • ❑o 0.1i WATER INLET C CONDENSATE 16" - DRAIN I 55 — 1/4"-1-1/4" ADJUSTABLE J ci o l E — f 1 KNIGHT BOILER AM/9.etin tt' DIMENSIONS AND SPECIFICATIONS Input MBH Net Heating AHRI Model Capacity Rating Gas Water Air Vent Shipping Number Min Max AFUE% MBH MBH A B C D E F G H I J Connect. Connect. Inlet Size Weight KHNO55 8.3 55 95 51 44 6" 8-3/8" 11-1/8" 10-1/2" 13-1/4" 37-1/2" 32-5/8" 32-1/4" 13-1/4" 3-3/8" 1/2" 1" 2" 2" 160 KHN085 8.5 85 95 79 69 6" 8-3/8" 11-1/8" 10-1/2" 13-1/4" 37-1/2" 32-5/8" 32-1/4" 13-1/4" 3-3/8" 1/2" 1" 2" 2" 165 KHN110 11 110 95 102 89 7-3/8" 9-3/4" 11-1/8" 10-5/8" 14-5/8" 37-3/4" 33" 32-1/2" 14" 4-5/8" 1/2" 1" 3" 3" 170 6H8155 15.5 155 95 144 125 7-3/8" 9-3/4" 11-1/8" 10-5/8" 14-5/8" 37-3/4" 33" 32-1/2" 14" 4-5/8" 1/2" 1" 3" 3" 175 88N199 19.9 199.9 95 185 161 7-1/2" 10-1/2" 11-1/8" 11-5/8" 15-3/8" 38" 33" 32-3/4" 14" 4-5/8" 1/2" 1-1/4" 3' 3" 195 KHN285 28.5 285 95 264 229 7-1/2" 10-1/2" 11-1/8" 11-5/8" 15-3/8" 38" 33" 32-3/4" 14" 4-5/8" 1/2" 1-1/4" 3" 3" 205 *Information subject to change without notice.Change"N"to"L"for LP gas models. *The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15.*Lochinvar should be consulted before selecting a boiler for installations having unusual piping and pickup requirements,such as intermittent system operation,extensive piping systems,etc.*The ratings have been determined under the provisions governing forced draft burners. SMART SYSTEM"'FEATURES STANDARD FEATURES >Smart System Digital Operating Control >Access to BMS Settings through Graphic LCD Display >ENERGY STAR Most Efficient Product Multi-Color Graphic LCD Display w/Navigation Dial, >High-Voltage Terminal Strip >95%DOE AFUE Efficiency Soft Keys and Loch-N-Link®USB programming 120 VAC/60 Hertz/1 Phase Power Supply >Modulating Burner with up to 1o:1 Turndown >Three Boiler Setpoint Temperature Inputs Three Sets of Pump Contacts Direct Spark Ignition Plus Domestic Hot Water Prioritization >Low-Voltage Terminal Strip Low NOx Operation >Built-in Cascading Sequencer for up to 8 Boilers, DHW Recirculation Pump Start/Stop >ASME Stainless Steel Heat Exchanger with Cascade Redundancy 24 VAC Device Relay 30 PSI ASME Relief Valve Multiple Size Boiler Cascade Proving Switch Contacts >Vertical&Horizontal Direct Vent Lead Lag Flow Switch Contacts PVC,CPVC,Polypropylene or SS Venting up to 100 feet Efficiency Optimization Alarm on Any Failure Contacts >Smart System Control Front End Loading Capability Runtime Contacts >Condensate Trap >Outdoor Reset Control with Outdoor Air Sensor DHW Thermostat Contacts Programmable for Three Reset Temperature Inputs 3 Space Heat Thermostat Contacts >Other Features >Programmable System EfficiencyOptimizers System Sensor Contacts Automatic Reset High Limit gTa Y P Adjustable High Limit w/Manual Reset SH Night Setback DHW Tank Sensor Contacts Boiler Circulating Pump DHW Night Setback Outdoor Air Sensor Contacts Zero Clearances to Combustible Materials Anti-Cycling Cascade Contacts y g 0-10 VDC BMS External Control Contact 12-Year Limited Warranty(See Warranty for Details) Outdoor Air Reset Curve 5-Year Limited Parts Warranty Ramp Delay 0-10 VDC Boiler Rate Output Contacts Modulation Factor Control 0-10 VDC Variable Speed System Pump Signal Input OPTIONAL EQUIPMENT Boost Temperature&Time 0-10 VDC Signal to Control Variable Speed Boiler Pump Modbus Contacts CON.X.US®Remote Connectivity >Four Pump Control Modbus Communication System Pump with Parameter for Continuous Operation >Time Clock BACnet MSTP Boiler Pump with Variable Speed Control >Data Logging Flow Switch Domestic Hot Water Pump Hours Running,Space Heating Low-Water Cutoff w/Manual Reset&Test Domestic Hot Water Recirculation Hours Running,Domestic Hot Water Alarm Bell >Domestic Hot Water Prioritization Ignition Attempts Concentric Vent Kit DHW tank piped with priority in the boiler loop Last 10 Lockouts Condensate Neutralization Kit DHW tank piped as a zone in the system with the pumps >Maintenance Reminder BMS Gateway to LON or BACnet IP controlled by the SMART SYSTEM Custom Maintenance Reminder with Multi-Temperature Loop Control DHW Modulation Limiting Contractor Contact Information Sidewall Vent Termination Separately Adjustable Space Heat/DHW Switching Times Installer Ability to De-activate Service Reminder Wireless Outdoor Sensor >Building Management System Integration >Low-Water Flow Safety Control&Indication LP Gas Conversion Kit 0-10 VDC Input to Control Modulation or Setpoint )Password Security >Firing Codes 0-10 VDC Modulation Rate Output >Customizable Freeze Protection Parameters M9 Standard Construction 0-10 VDC Input to Enable/Disable Call for Heat M7 California Code i ;;, Lochinvar,LLC ■ r ` ` ,•' 300 Maddox Simpson Parkwayllik—I ♦♦ fi n 1'lit Lebanon,Tennessee 37090 LOW 7.)J 1 P:615.889.8900/F:615.547.1000 (fluENCY BOILERS&WATER HEATERS 19©®0 Lochinvar.com CERTIFIED® L KHN-02 (Reprint KHN-o2 3/17) ©Lochinvar,LLC- ASB-5M 6/17-Printed in U.S.A. iPhone and iPod touch are trademarks of Apple Inc.,registered in the U.S.and other countries. Android and Google are trademarks of Google Inc.,registered in the U.S.and other countries. App Store is a service mark of Apple Inc.Google Play is a service mark of Google Inc. HIGH EFFICIENCY RESIDENTIAL BOILERS ARE FIRE TUBE BOILER Ar Mow, I � rmingr °cl" ,SMART A CON.X.US® REMOTE CONNECT CAPABLE LOCH-N-LINK® USB DRIVE SETUP 3 SETPOINTS WITH OUTDOOR RESET CURVES DHW RECIRCULATION PUMP CONTROL FLOOR-STANDING FIRE TUBE DESIGN 6 MODELS: 55,000 — 285,000 BTU/HR JE CER 4'(r F 9C% (A n' TIFIED./UP TO 10:1 TURNDOWN RATIO ( 7 ,' AFUE EFFICIENCY DIRECT-VENT FLEXIBILITY TO 100 FEET oTs"' r1 :st Efficient t017 DESIGNED { ENGINEEREDASSEMBL O -yam LeC� TK EA.. Laiel ► v , HIGH EFFICIENCY BOILERS&WATER HEATERS Lochinvor.ccre V - \ ro c� FIRE TUBE BOILER it t MONEY-SAVING 95% EFFICIENCY AND EASIER THAN EVER TO INSTALL The l<NIGHT®floor-standing fire tube-boiler features reduced installation . ) footprint for flexibility in boiler placement. Plus, all connections are on the top and left side, so KNIGHT is an easy drop-in replacement for older, less efficient boilers. Six models offer inputs from 55,000 to 285,000 Btu/hr. - t USE EXISTING PIPING TO REDUCE COSTS The KNIGHT fire tube boiler operates with low pressure drop.The design incorporates a small volume of water in the heat exchanger.This allows the boiler to be installed in a primary/secondary or a full-flow piped system.There is no need to change the piping to accommodate the boiler.The boiler adapts to i the system.This flexibility allows for a faster, more cost-effective boiler upgrade. 1 III 10:1 TURNDOWN RATIO OPTIMIZES PERFORMANCE Modulation turndown up to 10:1 means the firing rate automatically changes as the heat load varies.A KHN110 KNIGHT boiler fires at its maximum 110,000 Btu/hr rate when load is highest,then "turns down"to as low as 10% (11,000 Btu/hr) as load decreases.A modulating boiler runs smoothly 'I and efficiently,without frequent on/off cycling. SAFE, RELIABLE NEG/REG TECHNOLOGY . : KNIGHT boilers can operate with low gas supply pressure.Negative Regulation Ii , uses a pre-mix gas system instead of relying on utility pressure through the gas valve.The result is steady operation in low gas pressure systems or when gas s demand is highest.Automatic fan control fine-tunes the air/fuel ratio, Vier' providing superior combustion throughout the operating range. SUPERIOR DIRECT-VENTING FLEXIBILITY KNIGHT boilers can be installed with direct-vent air intake and exhaust runs up to 100 equivalent feet, using PVC, CPVC, polypropylene or AL29-4C stainless steel vent pipe. III r `// Venting Options ' ,0I > Direct Vent Vertical I�I> Vertical w/Sidewall Air .,> Concentric Direct Vent Sidewall � > Direct Vent Sidewall 0 'fft1' > Alternate lb ` `4 Concentric 'd' '''> 01 18 r•l Vertical �rS) Consult Installation&Operations manual o f o for complete KNIGHT venting information. CON* US® REMOTE CONNECT BOILER CONTROL, • FROM ANYWHERE. From wherever you are,the CON.X.US®option lets you use any Internet-capable device to link up with the SMART SYSTEM—on an unlimited number of KNIGHT®boilers. > Do regular CON•X•US > Adjust setpoints,domestic > Status alerts via text or checks for all your KNIGHT hot water, reset curves, e-mail let you know when customers, and let them pump delays and more, a KNIGHT boiler needs know you're monitoring using the CON.X.US attention. their boiler's performance. interactive display. i., With CON-X-US,you're always in touch and in control. ANDROID APPON / Download on the Optional CON•X•US control board is sold separately. i Google play 111 App Store S MART SYSTEM THE ULTIMATE IN BOILER CONTROL & MONITORING The industry's most advanced boiler control system now includes the CON.X.US® Remote Connect option and LOCH-N-LINK® Flash Programming feature. See back cover for a complete list of SMART SYSTEM—functions and features. COLOR-CODED LCD DISPLAY mice 4r44 t t Uw_Faait Blue Screen Normal system operation mill.* tow To** 6v.tv4, au TRaf ► Yellow Screen Maintenance due shows Wki. ALO am Cr!G, so mPO `ICI fo ,, installer name&number ` F �7N6 6.A6. &46 '►105 IOC 1".F1 ; Red Screen Lockout mode •r... Vs Ttra i.T cm. -s.•I .`uffl =.(.t ar 1 a -- .*-rt OOMAR T�. 9MART� •JMAR 0 0 0 A?i0QI tsitir gills— E C E WER LOCH-N-LINK® EASY USB FLASH PROGRAMMING Use a USB drive to name,store and easily manage multiple proven parameter sets. Ti Quickly upload them via the front panel port, reducing installation and programming time. ASPEN BUILDING DEPARTMENT