File Documents.1300 Riverside Dr.0309.2017 (34).ARBK
RFI Response #2 — Sewage Ejector— Riverside Residence Page 1 ARCHITECTS RFI Response #2 - Sewage Ejector August 2,2018 Project: Riverside Residence From: Joseph Spears (S2 Architects) Issued To: Madigan&Company Copy: Below is the RFI Submitted by Koru: Hi Joseph—As we discussed,this project neglected to specify a sewer pumping vault. We have a suggestion figured out and would like to set it as below at about Grid B.5—1.75. Attached are the specifica- tions for the duplex pumps and control panel.The shop drawing for the vault will not be released until we order it. It is a 36"diameter fiberglass tube of a pre-planned fixed height with a system to cut in inflow and outflow as decided on site. At a minimum,we would like it to be 18'tall. This height would allow at the best case 85 gallons of storage(important in the case of power failure)..at the worst case(pumps were just about to start) there would only be about 40 gallons of storage before sewer backup. We can design the vault much deeper but the issue becomes excavating for it which would impact the bearing of the footer above on native soil. We tried to pick an area where there are no beam loads above and my expectation is that concrete wall could span this as a grade beam although the hole will of course be back- filled to provide some bearing. The overdig of course won't be fully 4.5'deep at the outer circle but will layback and be backfilled at least to that line. If you did need more or wider footer here,we can probably accommodate but would prefer to keep the bottom of the footer as currently shown,without any vertical steps due to water- proofing membrane. This general sketch below is what it will take to install an 18'tank. There is a trade off on specification—the deeper tank will dig more out of the footer bearing while providing more storage capacity. Less storage capacity will require less digging under the footer. The larger tank will of course cost more in materials and excavation. Please provide some guidance on the appropriate specification. We don't have much time to lose as this tank has to be set before footers can be formed and there is a lead time associated which requires ordering it this week. Response S2 Architects,AEC,and Albright&Associates: Please proceed with the double pump and 18'tall fiberglass basin. This basin will just pickup the lower level bathrooms. AEC has helped review and we feel 36"x 40"below the inlet is acceptable. Albright&Associates have reviewed the direction and would like to revise the footing as shown in the attached sketch C1.1. The exact location of the new pad footings can adjust slightly to avoid the disturbed soils,but if it gets too far from the centerline of the beam pockets let us know. Attached: Sump Ejector Pump/Controls /Calculations /Footing Sketch C1.1 gD [06/03/2019 J POBCOO GYrvIWkE 215 S.Nbnarch Suite G 102 Aspen,Colorado 81611 60em P 970.544.4856 Email joseph@s2architects.com 1 THIS SUBMITTAL HAS BEEN REVIEWED FOR CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. THIS REVIEW DOES M YE R S O NOT RELIEVE THE CONTRACTOR FROM HIS RESPONSIBILITY FOR:VERIFIED DIMENSIONS WHICH SHALL BE CONFIRMED AND CORRELATED AT THE JOB I SITE PRIOR TO FABRICATION AND INSTALLATION; FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION; COORDINATION OF HIS WORK WITH VR1 & VR2 SERIES THAT OF OTHER TRADES AND THE SATISFACTORY PERFORMANCE OF HIS WORK. NO EXCEPTIONS TAKEN 0 REVISE AND RESUBMIT Or 1 & 2 H P A U T 0 M AT ❑ MAKE CORRECTIONS 0 TED 0 REJECTED SUBMIT SPECIFIED ITEM _j DATE 8�2��$ BY i/�,�G"i/ URINDER PUMPS :a ARCHITECTS SHREDDING . 215 S.Monarch St.Suite G-102 Aspen,CO 81611 phone: (970)544-4856 WASTEWATER 4 . ► • ^, ,, : /, CHALLENGES r." _a-+ 'ZI'' ' 11 tr f PATENT-PENDING AXIAL CUTTER TECHNOLOGY • EASY INSTALLATION 0 PERFORMANCE kiii,ii i .. . t �* N. )1., ic.gdllgjillIlIllCm. O.- - 'It .••••' . ' i 11 -.- • PENTAIR • y am`- &' )14:14i\ MYERS® VR1 & VR2 SERIES OUTPERFORMING AUTOMATIC GRINDER PUMPS 0 THE COMPETITION The new MYERS VR1 and VR2 grinders feature a 1HP Pump Curves patent pending axial cutter technology that easily 80 slices through solids and trash found in domestic . .-1 — Liberty PRG100 Zoeller 807 wastewater without roping or clogging.They 70 come with plenty of standard features to make 60 installation a breeze. 50 ,..ilii - = 30 z ,� ,. ,. 20 up to 18% • 10 more flow at 20' 0 0 10 20 30 40 50 60 70 (F Flow(gpm) 2HP Pump Curves 160 -VR2 Liberty LSG200 i ,Zoeller 820 140 a. 120 libliiiiik upto371 % .,100 w iI-. iii m 80 more flow at 100' = 60 401 20 The VR1 is an ideal upgrade for The VR2 is a rugged and 0 residential sewage pumps struggling economical solution for o 10 20 30 40 50 60 70 with trash and debris found in residential and pressure Flow(gpm) residential wastewater. sewage systems. *Based on internal test data and published competitive flow curves. PATENT- PENDING AXIAL Watch the video at www.femyers.com 411 CO CUTTER TECHNOLOGY Easily slices through solids and trash found ". SIM, in domestic wastewater i f I 1, l I without roping or clogging. POLY ROPE SHOPRAG — 1111Dlie TV I 1 + P E N TA I R SWIFFERS® MOP HEAD 1:41rilli — 7 IP At• A pi r. ft:r Nig -tier,: , ‘ Atik74libb' I FEATURES A. Wide Angle Float Switch F. Shaft Seals • Piggy-back cord for easy • Oil lubricated single carbon and maintenance ceramic faced seal provides motor protection ( 11/ B. Cable E System • Cable jacket ntry sealed by G. Impeller 116 compression fitting and individual wires sealed by compression grommet for • Semi-open impeller handles ground slurry without clogging or binding double seal protection against • Pump-out vanes help keep trash water ingress from seal and reduces pressure at seal face for longer life C. Oil-Filled Motor © • Maximizes heat dissipation H. Axial Cutter System and provides constant bearing • Easily slice through solids I lubrication for long life and trash commonly found in • High torque start/run capacitor domestic wastewater without I for single phase motors for roping or clogging . iil _ assured starting under heavy • Constructed of 440 SST hardened loads. to 57-60Rc for long life • Internal capacitors eliminate • Easily replaceable without •s need for control panel dismantling pump 0 D. Integrated Heat Sensor I. Volute Case • Protects motor from burnout • Cast iron, 1-1/4"vertical,flanged due to excessive heat from discharge(VR2) any overload condition. • 2"vertical discharge (VR1) � Automatically resets when TM motor has cooled 11111111 ' E. Shaft and Fasteners • Stainless steel for maximum corrosion resistance and long life b , d. i 0 r 1 il.1 1114 eii,......,, ® kil.ti, . Filatic...::: 0 .�:_ ,illillr Tom` ♦- i ii — . linFl , 1 --igi r. _ ., , . ., 1 ` - ` \ leitggirt t: ,, • L.s., - ,IIIIIIIIIIII,I6iip,, PERFORMANCE DATA AND DIMENSIONS Liters Per Minute 3450 RPM 160 0 38 76 114 151 189 227 [Dimensions in mm] 45 55T LIFTING HANDLE 140 VR1 _ - WITH PADDED GRIP VR2 40 8.36" 120 [212.31 4.46" v 35 II!��( --[113.3]i ' 100 awl- 7timi E 30 c �` 12 80 25 = :9 ;4 18.01" `- 2"N PT [457.51 �\�� 15 Discharge ®�� 40 [50.81 15.51" 10 'a :/ [393.9] 20 I VR1 5,_ .lam OI '�-�`- 1IN 1 0 0 10 20 30 40 50 60 riv,-- 378" Gallons Per Minute [960] Refer to factory for VR2 applications below dotted line. _ 5.00" 3.90" Product Capabilities [127] [99.11 Capacities To: VR1 49 gpm 185 1pm VR2 I VR2 33 gpm 125 1pm Heads To: VR1 57 ft. 18.6 m VR2 138 ft. 42.1 m I4.00" Liquids Handling domestic raw sewage Intermittent Liquid Temp. up to 140°F up to 60°C [101.6] 11 . Winding Insulation Temp. 311F 155°C 2.84" [72.1] o (Class F) Motor Electrical Data 3450 rpm,60 Hz,1 ph iv 5.77" 115V(VR1),230V(VR1 and VR2) [146.61 Std.Third Party Approvals CSA 17.41 �296 ql Acceptable pH Range 6-9 [442.21 C\ o�A Specific Gravity .9-1.1 ��O Viscosity28-35 SSU �.. Discharge(Flange Dial VR1 2 in. 50.8 mm / � VR2 1-1/4 in. 31.75 mm 7.13" 8.72" I [181.2] Min.Sump Diameter [221.5] i�� c_�; VR1 24 in. 61.0 mm VR2 Simplex 24 in. 61.0 cm VR2 Duplex 36 in. 91.4 cm Electrical Data Construction Materials Model Engineering Cord HP Voltage Phase Hz Amps Length Discharge Switch Weight Motor Housing,Seal Housing, Cast Iron,Class 30, Cord Cap and Volute Case ASTM A48 VRS10A-11 28172D000 1 115 1 60 13 20 2" Auto 70 VRS10M-11 28172D001 1 115 1 60 13 20 2" Manual 70 Semi-Open Impeller VR1=thermoplastic VRS10A-21 28172D002 1 230 1 60 7 20 2" Auto 70 VR2=stainless steel VRS1OM-21 28172D003 1 230 1 60 7 20 2" Manual 70 Power Cord SJOOW Mechanical Seals: VRS20A-21 1 28200D000 1 2 230 1 1 60 1 15 20 1-1/4" 1 Auto 1 95 Standard Carbon and Ceramic VRS20M-21 28200D010 2 230 1 60 15 20 1-1/4" Manual 95 Pump,Motor Shaft 416 SST Fasteners 300 Series SST Cutting Mechanism 440 SST 58-60 Rockwell ►►� PENTAIR C4® 1101 MYERS PARKWAY,ASHLAND,OH 44805 WWW.FEMYERS.COM PH:419-289-1144 Because we are continuously improving our products and services,Pentair reserves the right to change specifications without prior notice. ©2016 Pentair plc.All Rights Reserved. M-02-4070(10/19/161 7r Y fC r: : - "ram r - Ilk. 7 -) .- 1 ge ,.� - til‘ .• �? - - ` .11. u k• iii,. .: '' PUMP CONTROL PANELS . ....._._.__. - -,. .:_ ., : . . ,X .. . ., .-7' �, —ate„ ,f .+ _ - Il - .... .. \ 1 1,... /.0,111:. ILL iI W i C -.., Ai, 111,4 /al ,, - 1 elr .: II ... )1k - 1 lj w.vs )� ,; l. z �: r,1\i ... , o,. —:11. :r ... �a I� +e ) 'I....;17 1111 •+' • i Iit , ` MADE IN THE USA ,...., is (/'')* _, _ ,_ ..._ .. . lit BY r ...AN P C 1,,,,„e,,„,,, ... , _- .,,,_ ,44,, , , ._., ._, ,..„...._ W ‘0 I •... ,. , . , \ , i - - CON/fairCal to %(ou-az1, ?All_ Setat o to -! -I EMI® Standard Molded Sub-Door (Dead front) The RK Series control panel has increased user safety through the use of a non-conductive molded polycarbonate inner door. This provides Space Savings and Convenient Operator Controls while isolating the 1 user from energized components. Patent# 7,151,459 B1 MI 'M I 1" .._te:�: 1 ii 11` ...it,.? 1: lam. Touch Here IIAr i/f to Silence I -_= 'ha Jr Audible ! ' ('. I Ii . I Audible Alarm Circuitry Inside Sub-Door RK panels come standard with an On the inside of the audible piezo alarm (95 db +/-) and sub-door RK Panels have the exclusive side mounted "Touch to quick disconnect circuit Silence" pad. With this feature the boards for easy replacement user is able to silence the audible by and troubleshooting, spare simply touching the decal on the side fuses for alarm and control - - s) of the enclosure. This eliminates fuse replacement, and a -fie v rubber boots that can leak and custom RK Series " m ">,7 switches that fail due to moisture screwdriver to ease servicing. . / while maintaining the integrity of the •> enclosure. Patent# 7,075,443 B1 " ,0 2m ,,r, ii l Non-Conductive Back Panel Standard Lockable RK Panels come standard with an injection Standard Circuit Breakers molded back panel providing a raised Latches RK panels come standard with platform for mounting circuit breakers, a High quality stainless steel control & motor circuit breakers heavy duty paralled ground lug, housing lockable latches come standard for accessible through the sub door. for contactors (rated at 25 FLA) and safe and secure operation indoors (Can be ordered w/o circuit elevated terminal strip for installer friendly or outdoors. breakers). field wiring. Patent# 7,151,459 B1 2 Cs/Co,tfi-o/s www, ,f/tcoffefidPaite�s com - 1 to Durable NEMA 4X Enclosure I I The enclosure is manufactured from durable polycarbonate material "' El and is UL Listed NEMA Type 4X rating as accepted by industry I standards. It is intended for indoor or outdoor use and provides jimil_ typical 4X protection against corrosion, windblown dust and rain, ® splashing and hose directed water while remaining undamaged by I the formation of ice on the enclosure. In addition the door of the enclosure has the useful and unique ability to be removed simply by l'Junsnapping from the hinges to allow better access for installation �' and service. The RK enclosure is available in Black or Gray and includes mounting feet. Also available with an optional clear door. Selica 11 .. 57,k /00 1 , urn -ttl- j !'I I I ME U ENTER i ..';. ..r �, •��� SET • ...se..... CHANGE 1 Tr.ems. Am •...., 1 Digital Display Center With Future Expansion in mind, every RK Panel has a Removable © - Expansion Board Face Plate to add features like: Elapsed Time o Meter(s), Cycle Counter(s), Liquid Level Display in Inches, Time Dosing Fields, and many more. (See page 7 for more details) (i Jl a User Safe Fuses Each RK Panel has separate Alarm & Control Fuses Standard with Fuse Fail Indicator Lights prominently located on the Sub-Door for Simple Troubleshooting. ATEST / Hand Run Buttons Alarm Light ® SILENCE RK panels include push-to-run (HAND) pushbuttons for the motor starters output and a push-to-test (TEST) A top mounted high intensity pushbutton for the alarm output accessible on the sub- flashing red light with RK's variable door. The push-to-run (HAND) pushbuttons toggle their flashing modes that is programmed • HAND respective outputs off and on each time pushed under to indicate the specific alarm fault normal operation. However, to protect the pumps should comes standard. This enables the sump go below pump off level, the HAND service personnel to recognize pushbuttons revert to momentary contact and must be specific faults before actually going held down to maintain its respective output on. This is a • to the site. HAND safety feature that keeps the pumps from running dry. www, /e/(Coirtio/Pa,reds,cola 2vv, CS7 Co, o/' 3 • sew é,4t .06\ The RK Series is an innovative approach to today's pump control - ^ ° system requirements with standard r -1 features unmatched by most Ht' ,9 i I standard sub-door and raised 1-- = r-+— i � backpanel the RK Series offers a 1. , revolutionary design for housing 1 common control panel features such as b. ! S.u, circuit breakers, start components, o contactors and a terminal strip. While r -e , _. ` others ask you for more dollars to 1•4# ^o cover"options", the RK Series provides many of the most requested items as standard equipment. Some of these --- _f standard features include: lockable latches, a flashing red alarm light with .. an electronic horn, the innovative touch to silence pad, and a control circuit board all in a NEMA 4X enclosure. In Sub-Door Control Center addition to unsurpassed standard Alarm Circuit features, RK offers an exclusive control Control Circuit • circuit board. Convenientlylocated on Power Light POWER Power Light CONTROL ® the Sub-Door the float indication lights 0 ALARM allow the user to see the status of each ; se44 float and flashes should a float fail. Available in simplex and duplex single phase to three phase these innovative High Level Light n /� controllers are certain to revolutionize FLOAT er CS'/G$�rtro4 INDICATION Test/Silence the industry. Lag Pump On Light HIGH Pushbutton LEVEL 0 Typical Simplex Float Installation Lead Pump On Light LAG TEST! L PUMP ON ALARM SILENCE Pumps Off Light LEAD PUMP 2 Alarm Light C (10) US PUMP ON RUN HAND Hand Run PUMPS 0 PUMP 1 Pushbuttons OFF RUN PUMPS mJuii HAND Flange 4 10 4 (unction I Pump Run Lights SPECIFICATIONS Pump �_• I;" Available in Simplex& Duplex Duplex Includes alternator& lagpumptime delayPower Cord P P p card Enclosure Dimensions 12"X 10"X 6" f Stainless Steel Overall Dimensions 14.5"X 12"X 7.5" Inlet Mounting Bracket Enclosure Nema 4X with Molded Mounting Feet 'MEL Alarm Piezo 95 db with"Touch to Silence"circuitry Float Status Lights Displayed on Sub-Door Discharge Flashing Red Alarm Beacon Provides 360°Visual Display Weight 10.8 lbs. 25 amp"DP" Heavy Duty Definite Purpose Contactors -High Level Alarm Non-Conductive Injection Molded Sub-Door Blown Fuse Status LightsUL 508A Listed —Pump On Includes 20' Mechanical Floats (3 for simplex, 4 for Duplex) ui, j ►° —Pump Off Maximum 2 HP- (12 FLA) 3 Year Limited Warranty, Floats Patents (# 7,075,443 B1) (# 7,151,459 B1) 4 C /C z o/' www, ,f/(C 1 o/Pa,re%s Qom' • iir 711)91e444)4e eariedil=11 Using our proprietary pressure bell, these ground breaking liquid level - -- - systems allow the user to change all settings and adjustments outside of confined space with no electrical level I a'i - _ _ system components in wet areas, no cords to tangle or adjust, no mercury, no mechanical switches to fail, no 9 — probes to corrode, and no venting • a0 ' ` _ , i _ required. The pressure bell is non- I .' � electric and transmits a pressure only r ,�s�c r signal to the controller. No voltage r j o = from the level-sensing device enters �� A- _ the wet well. As the water level rises �' in the basin, pressure is created in the III I I 11 .. — pressure bell sending an air pressure �! I �;, only signal to the controller. In fact, installation of the pressure bell is as - simple as mounting the bell and connecting it to the control panel Sub-Door Control Center using the provided 1% poly tubing (50ft Control Circuit • Alarm Circuit comes standard). Through the use of Power Light POWERONTRDL Power Light a control circuit board conveniently located on the Sub-Door, this system ALARM allows the user to adjust all settings at precise levels in inches by simply turning a knob. Amazingly, these Adjustable High Rikelteed systems are priced comparable to Level Alarm standard float systems! Adjustable Lag 12° 24" ss lit C`S'/C°ati°k Test/Silence Pump "Cut-In" Dial HIGH (3"; �„ Pushbutton LEVEL Adjustable Lead 12" 24° 36., ..l Typical Simplex PAC Installation Pump "Cut-In" Dial PUMP ON 48' ALARM f.9 • SILENCE 12" 24 36„ Alarm Light 11 Adjustable Pumps LEAD PUMP 2 PUMP ON ° 48' HAND "Cut-BUY" Dial `� RUN C US \,15° 26" 37• Hand Run PUMPS PUMP 1 HAND Pushbuttons OFF 4" 48 RUN + Conduit 4 I Flange SPECIFICATIONS Pump Run Lights Boxtion Available in Simplex& Duplex Duplex Includes alternator& lag pump time delay Pump Pressure Tubing Enclosure Dimensions 12"X 10"X 6" cord • Overall Dimensions 14.5"X 12"X 7.5" ■ Stainless Steel Inlet Mounting Bracket Enclosure Nema 4X with Molded Mounting Feet 1Alarm Piezo 95 db with"Touch to Silence"circuitry • Battery Back-Up 9 VDC for alarm horn n' Extension Tube Flashing Red Alarm Beacon Provides 360°Visual Display Discharge Weight 10.8 lbs. 25 amp"DP" Heavy Duty Definite Purpose Contactors Non-Conductive Injection Molded Sub-Door 41 III ii Blown Fuse Status Lights UL 508A Listed iiLti Pressure Bell Includes Pressure Bell &50'of Tubing w/Rolling Diaphragm Maximum 2 HP- (12 FLA) _ , ew •3 Year Limited Warranty Patents (# 7,075,443 B1) (# 7,151,459 B1) (# 6,595,051 B1) vvrvav, f/(Ooeiv/Pa tes,comr CY/Co/rtwo&s 5 L J J SSe R° 1zied 5 s • if For those who don't need all the _ features of the standard RK Series, the "' "E" Series provides a feature packed 1 P 7 y •._1 control for price sensitive markets. 1Like the standard RK Series, the "E" --Jlc_l: Series comes standard with a NEMA I 4X enclosure and poly molded inner door to isolate users from line voltage. This provides safety unmatched by our —.I,r 1 Is competitors in an agressively priced simplex panel. The "E" Series also • S„., _ uses the proprietary "Touch to Silence" Ra, pad that is standard on all RK pump "" ••-- • 1 controllers along with power, alarm, el and pump run LEDs. The H-O-A switch is an industry standard toggle ° switch and an Alarm test button with auto reset and alarm fuse is also standard. To keep this panel at a competitive price the "E" Series does not have the float status lights that Sub-Door Control Center come on the standard RK float panel. Although this series does not provide Control Board as many extras it will still accept an RK Power Light / DDC module to provide Elapsed Time POWER 0 `S'el and Cycle Counting with a plug in `� Alarm Light module. See page 7 for more information about the DDC module. 8 CS/Cortro Test/Silence Blown Fuse SIMPLEX FLOAT CONTROL - ' Pushbutton Indicator EST/ Typical Simplex Float Installation ALARM SILENCE Pump Run l FUSE HAND-OFF-AUTOS Light C ® U$ 1I User Safe Hand-Off- Fuse c n,i��it Auto Switch Flange i - C •� Iunction SPECIFICATIONS Pump APower Available in Simplex OnlyCord p �,f Stainless Steel Enclosure Dimensions 12"X 10"X 6" Inlet Mounting Bracket Overall Dimensions 14.5"X 12"X 7.5" Enclosure Nema 4X with Molded Mounting Feet Alarm Piezo 95 db with "Touch to Silence"circuitry Discharge Flashing Red Alarm Beacon Provides 360°Visual Display Weight 10.8 lbs. 25 amp"DP" Heavy Duty Definite Purpose Contactors Non-Conductive Injection Molded Sub-Door II JIIIII -High Level Alarm Blown Fuse Status Light UL 508A Listed ►' -Pump On Includes two 20' Mechanical Floats �° —Pnt» Off Maximum 2 HP- (12 FLA) p 3 Year Limited Warranty kill It Floats Patents (# 7,075,443 B1) (# 7,151,459 B1) 6 C /C z oes www, f/(cofft"o/&aye%s CON U ENTEMENR I SET E CHANGE • Digital Display Center (DDC) o = k.:1 1_i 1 rl FI F. . SET CHANGE Typical RK Series Panel Illustrating j • - Display Location on Sub-Door T .. Digital Interface Board (DIB) Display Features: The RK Series Displays are available factory installed or as an accessory that can be easily field installed. Installing either display is as simple as removing the factory installed removable face plate and inserting the new or upgraded display from the back side of the sub-door. Once installed, the displays enable viewing of panel information such as Elapsed Run Time Meters and Cycle Counters for each pump. Pressure Activated panels also display the current liquid level depth in inches. Incorporating a timed dosing display transforms a basic level control panel into a programmable time dose panel. Timed dosing provides capabilities such as: Pump Run Time, Pump Off Time, Override Pump Run Time, Override Pump Off Time, and more (Time Dosing functionality varies between the DDC & DIB). The RK Series Displays are constantly being improved with new features. Please consult the factory or website periodically for the most up to date available features. The RK Series displays are currently available in two versions -the Digital Display Center (DDC), and the Digital Interface Board (DIB). The DDC display utilizes a (4) four character LED display screen while the DIB incorporates a two line 16 character display screen providing a more complete read out for the user. DDC Features: Additional DIB Features: • 4 Character LED Display • 32 Character LCD Display • Works with PAC or Float Panels • High Level Counter • Simplex or Duplex Panels • More Advanced Time Dosing • Elapsed Time Meter(s) • On-Screen Alarm Annunciation • Cycle Counter(s) • Pump Failure Alarm (Duplex Panels) • Lead Pump Selector (Duplex Panels) •Alarm History (last 3 alarms) • Liquid Level Read Out (PAC Panels) • On-Screen Level Setpoint Read Out (PAC Panels) • Low Level Alarm Option • Three Auxiliary 120V AC Inputs Gf'6e/a', f/(co/(t o/Page/.cox CY/coefidel 7 About CSI Controls . .. A major strength of our product line is the custom control panel. CSI manufactures alarms and controls that are unsurpassed in design, workmanship, and overall quality. From our manufacturing facility in Ashland, Ohio, we manufacture virtually any control panel imaginable. However, we pride ourselves on continually offering innovative products to the wastewater industry. Our engineering team is constantly developing new products to revolutionize the industry and the RK Series is no exception to this ongoing task. This series is like nothing ever seen in the wastewater industry. Through the use of molded polycarbonate and proprietary technology RK offers the most user friendly, safest, best designed, and most complete panel for the money in today's market. Bill Chandler, President What Customers are Saying About CSI "We have worked with several panel shops over the years and CSI has offered the best service and quality we have found. They have worked hard to help us obtain business which is good for both parties. Thanks CSI" Jim Hicks, Hughes Supply "The innovative new products that CSI continues to develop, like the Pressure Activated Controls, keep my company ahead of my competition. CSI provides training and technical support for their products, which helps my sales and service personnel as well as our customers. It is good to work with a company that is an industry leader." Bob Tilton, Williamson Electric Warranty Chandler Systems Inc., warrants to the original consumer that its products shall be free from defects in material or workmanship for 3 years after the date of purchase for the entire RK product line, and will repair or replace any units with such defects. Warranty is void if units are improperly applied, improperly installed, if it has been disassembled, modified, abused or tampered with. Chandler Systems Inc. is not liable for damages from lightning or severe weather. All items replaced under this warranty must be returned to CSI, or such place as designated by CSI. 11%, -Nali„„ok „lots . i Chandler.Systems III I . 4 CSI Controls 220 Ohio Street • Ashland, Ohio 44805 800-363-5842 • 419-281-5767 • fax: 419-289-2535 csi@zoominternet.net•www.chandlersystemsinc.com RKCatalog 0407 Sewer Pumping Calculations Bottom of Footer — 7988.48 FF Lower Level 7990.04 3/" FF — 1-1/2" Gyprcrete — 4" slab Bottom of 4" slab 7989.52 Bottom of 2" Foam -7989.35 Top of Pipe @ Tub Bath 2 -7989.35 Invert of 4" pipe at Tub 2 -7989.02 73' Run to lift station — 1'6-1/4" fall Maximum Height of invert into lift station -7987.50 Lower for potential error about 5" Design Height of inlet invert into lift station 7987.1' Outflow 7998.75 (Ground level here 8002 which gives — 3' of cover over outflow pipe.) 11 2-9 1/2'LVL W/HUC410 W/ • DEN 14.1/4'0 x 1 3/4"SIMPSON TITEN SCREWS @ EA.END Edge of pathway to above. Lid to be J? contained in planter cb and exposed -Do permanently. _W iox33 — JJ 36" diameter pumping toNI4 ,,1,y ,G1 MI 199 9 3/41 vault.. BO Vault 4.5' `V_ -,•• ` ViJf.3 I 4T.PLY below bottom of F4,s Imo footer. Line of expected overdig for sewer x T.PLY 2-4• vault.~ ` • /8 ' b I l l I I • U 11I HATCH INDI DROPPE r o 1®' I AM I v,•1 'I N 1 FLOOR FO R " u' 43 BEAM '. 311\‘° I t< '' POCKET ��Sti. *F` I - - - ii — I W10x 31 n 1 CAI 99'.II1/4 1 ( 99.9 o '�A %', z - .. 1