HomeMy WebLinkAboutFile Documents.34 Westview Dr.0056.2018 (16).ARBK FLAMEOUT FIRE PROTECTION,Inc.
P O. Box 56
Snowmass.C()81654
Phone(970)927-4933
Fax(970)927-3817
March 7,2018
S2 Architects
215 S. Monarch St. Ste.G-102
Aspen,CO 81611
OWNER: Westview, LLC.
101 S Mill St.#200
Aspen,CO 81611
RE: New Construction: Koval Residence
34 Westview Dr.
Aspen,CO 81611
Attn: Meghan Nemechek
It is my recommendation that a 2"water service(piping) be installed into each building to adequately supply
the required pressure and gallons per minute(gpm)for the new fire sprinkler system as well to meet the
secondary domestic use. My recommendation is based on current water flow information supplied by Aspen
Fire District and preliminary hydraulic fire sprinkler calculations. We assume a residential fire hazard per
NFPA 13D and applicable code per the IFC. Smaller water supply piping will be inadequate for this project.
Also my recommendation is to install 2" K Copper underground piping.
**DISCLAIMER**: The above statement is to establish water source pipe sizing only. In no way should this
be used solely to determine any fire sprinkler design or to be used for any approvals for
fire sprinkler system design
Best Regards,
Spencer Boothe
President
Flame Out Fire Protection,Inc.
RECE VEt%
03/22/2018
ASPEN
BUILDING DEPARTMENT