HomeMy WebLinkAboutMaster Permit.623 S Monarch St.0005-2022-BREP (3) *scent Building Consulting, Inc. 872 Eveningsong Drive Castle Rock,Colorado 80104 Tel: 303-877-1119 August 20,2019 Aspen Mountain Townhomes c/o Mr. Marley Hodgson 623 South Monarch Street Aspen, Colorado 81611 Re: Report on Evaluation of Window Wall Assemblies Aspen Mountain Townhomes,Units A&C 623 South Monarch Street,Aspen, Colorado 81611 Ascent No.: 19033 Dear Mr. Hodgson: In accordance with our proposal dated July 9,2019,we have completed our initial evaluation of the water intrusion reported at south facing window wall assemblies at Units A and C at Aspen Mountain Townhomes located in Aspen, Colorado. The follow is a summary of our observations,opinions, and recommendations. Purpose and Scope of Building Envelope Consulting Services The purpose of our Building Envelope Consulting Services was to develop opinions on the general condition of south facing window wall assembly, to develop opinions regarding the likely source(s) for leakage through or around the window wall, and to develop a recommended repairs we believe would be appropriate. We performed the following services: We visited the site on June 24,2019 to perform our initial review as well as July 11,2019 to review and document with notes and photographs the readily visible portions of the south facing window wall assemblies of Units A and C,as well as portions of the roof flashings above these windows. We performed limited water spray testing on the south facing window wall assembly of Unit C on July 11, 2019. Finally, we accessed the roof from Unit A to observe the window extensions above the roof lines for both Units A and C on July 11,2019. No intrusive test cut examinations were performed; however, existing damages and loose interior trim did permit our observation of water intrusion and portions of the as-built construction of the window wall assembly. We also reviewed the following documents that you provided for our review: • "Aspen Mountain Townhomes Exterior Renovation" Structural Details dated March 31, 2015, denoted as a `Permit Revision' set and produced by KL&A,Inc. • "Aspen Mountain Townhomes Exterior Renovation" Architectural Details dated September 1, 2014, denoted as a '100%Design Development' set and produced by Willis Pember Architects. • "Aspen Mountain Townhomes Exterior Renovation"Architectural Details dated January 15,2015,denoted as a `Permit and Construction Set' and produced by Willis Pember Architects. • Invoice from Probuild to Silver Sage Building Company for the sale of Jeld-Wen Siteline aluminum clad windows for use at the Aspen Mountain Townhomes project dated June 30,2015. We also consulted with Manko Window Systems,Inc. for selection of a replacement window wall assembly as well as Chris Hendrickson of Hendrickson Construction to help develop an Opinion of Probable Construction Costs to replace the south facing window wall assemblies and associated flashings at Units A and C. Aspen Mountain Townhomes Mr.Marley Hodgson August 20,2019 Page 2 of 13 This scope was the limit of our building envelope consulting services. Project Summary The following is a summary of the project: • Aspen Mountain Townhomes is a three unit townhome building that was renovated approximately 5 years ago. The Architect of Record for the renovation was Willis Pember Architects. The general contractor was Silver Sage Builders,which we understand is no longer in business. • The installed windows were reportedly purchased through Pro Builders/Builders First Source. • Water leakage testing was performed by Hendrickson personnel on the windows; however, only very limited water intrusion was observed. • Water leakage appears to be primarily limited to conditions when high ambient temperature changes occur within a short period of time (potentially due to differential expansion and contraction of materials); however, some limited water leakage has occurred at other times. • The interface of the windows to the roofing was previously evaluated by Mr. Rodney Turner of Orion Architectural Systems,Inc.,whom we understand had some flashing repairs made around the windows and the roof of Unit C;however,these were not successful in stopping water leakage into the residence. Observations and Opinions We observed that a `window wall assembly' that is two stories tall is installed on the south elevations of Units A and C(as well as Unit B which was not included within the scope of our services as requested by you). The window walls for each unit consist of a bottom row of four awning(project out)windows,with a row of four picture(fixed lite) windows above the awning windows. These bottom two rows of windows are installed vertically and are located on the first floor. A third row of four picture windows are installed on the second floor and are slightly tilted inward(see Photo 1 below). A simulated extension of these windows is installed above the roof line and is described later in this report. 4` it 111141 • es', Photo 1: South facing window wall assembly Unit C. Photo 2:Water damage @ 1st floor of Unit C windows We accessed the interiors of both Units A and C. Unit C exhibited the greatest amount of interior damages. The following is a summary of some of the interior water damages we observed: Unit C: • Separation of interior trim at a mullion and water stains on the wood frames of the windows (see Photo 2 above). Aspen Mountain Townhomes Alijr- Mr.Marley Hodgson August 20,2019 Page 3 of 13 • Damaged floor trim and water stains at the sill of the 2nd floor windows(see Photo 3 below). • Various water drip stains along the steel beam that runs between the first and second floor. Unit A: • Water stains and curled trim board at the sill of the 2nd floor windows(see Photo 4 below). • Peeling paint and water stains at jamb/head of the 1st floor windows(see Photo 5 below). f► c 1 1111tal lik svc...Tc - ir ................ 14 4" _ , - Photo 3:Water damage @ 2nd floor of Unit C windows Photo 4:Water damage @ 2nd floor of Unit A windows ��� •.. I e • i h. _1,- : : , . �. - j Imo'% 'V • s1 L 1, 44 ... II lir; VA I Photo 5:Water damage @ 1st floor of Unit A windows Photo 6:Horizontal mullion width over awnings. We measured the interior dimensions of various windows and the interior trim for the horizontal mullions was measured to be approximately 2-5/16" wide (see Photo 6 above) and the vertical mullion to be approximately 2- 5/16" wide (see Photo 7 below). This installation is consistent with dimensions associated with mulling without use of a structural support. Figures 1 and 2 below show the mulling options for Jeld-Wen Siteline aluminum clad wood windows for vertical and horizontal installation. The dimensions measured indicate mullions without the 1/4" structural support. The lack of a structural mullion was further evidenced in Unit C with separated trim board that shows that no structural support appears to be provided(see Photo 8 below). Due to the size of the window wall assembly, structurally supported mullions would have been needed and the as- built condition of the field-mulled windows is a significant contributing factor to the water intrusion into the unit and resultant damages. Aspen Mountain Townhomes Mr.Marley Hodgson i(C)Y August 20,2019 Page 4 of 13 • t r w `.4 ' iti:1 II , ,,7 . k ,I 4:41 „ , ' 4"*‘‘ . ISIIV:ell5K .1 ,� t' ( IP, .cam litik --.,-. ,... ,.ilrAt } { Photo 7:Vertical mullion width. Photo 8:Mullion without structural support. 6 1/8" 5 15/16" — 25/16" —I r.- 2 9/16" —I t I � implionsim Tproi J i pe 'H i P 11, 111) jiMilrlilifkrAiri° , ii% or Milli mil 1 -- , 0: 14 __ E i� �c Art �� a 'Di ', Operator / Operator — 1?4" Operator / Operator 1/4" Structural Mull Figure 1: Jeld-Wen Vertical Mullion Details(Non-Structural on Left, Structural on Right) Aspen Mountain Townhomes 011".." Mr.Marley Hodgson August 20,2019 Page 5 of 13 111 ['Ilk i14-7 /Mk I -{ loliairro • 2 5/16" i � � ' 2 9/16" 6 3/16" ---1---'-‘%-wr," 403.1d Acw__ Alai'c..i . i * will al OM-1 frr M - Stationary Direct Set Operator Operator 1/4" Structural Mull Figure 2: Jeld-Wen Horizontal Mullion Details(Non-Structural on Left, Structural on Right) The lower windows are projection out awning units (see Photo 9 below). The horizontal and vertical mullions are covered with a mullion cap (see Photo 10 below). .,, ." 1 .tj 7� d. I I /l. 114111111111 Photo 9:Lower awning(project out)windows. Photo 10: Horizontal/vertical mullion caps. A mullion cap also covers the horizontal transition between the first floor vertical picture windows and the second floor sloped windows (see Photo 11 below). We observed that silicone sealant appeared to be smeared over the transition between the vertical and horizontal mullions at the base of the second floor picture windows as an apparent attempt at a `repair' (see Photo 12 below). This sealant joint repair has not been effective as demonstrated in the failed water testing of the area as described later in this report. Aspen Mountain Townhomes Air' Mr.Marley Hodgson August 20,2019 Pa:e6of13 il f I ` 11,11r1._ r } i •4 s r � Photo 11:Mullion @ vertical to sloped windows. Photo 12: Silicone sealant`repairs' @ Photo 11. I METAL FLASHING I Willis Pember Architects originally specified an aluminum allit I, 1 . -SEE DETAIListorefront window assembly to be installed, which wouldIl I NEW METAL CAP . k, 1 FLASHING(TYP.) I have been more appropriate for this project. We understand l�; / _ _ ` �T that contractor, Silver Sage Building Company (SSBC), 1 - imaii I substituted aluminum clad wood windows for the storefront , window assembly without review or approval from the •••r� E j Architect. The Architect's drawings from the Permit and 1 I Construction Set are shown in Figure 3 to the right and j 1 ' j Figure 4 below. SYS EM TO MSLOPED TCHING i —-— iii\ EXISTING(TYP.) I i 0 EXISTING GLAZING . _� 'o SYSTEM TO BE ;p REMOVED I `� 4 NEW 2x6 SIDEWALLS i TO MATCH EXISTING ro W.4 12"MIN.R-31.5 . PRE-FINISHED SLOPED SPRAY FOAM INS.& I GLAZING SYSTEM PRODEMA VERTICAL , SIDING BENT STEEL PLATE W. — HSS4x4x1/4 WIND GIRT-SEEi STRUCTURAL I 24 li I r I c,3 - I I ; 1---1 ,,V- n UPPER LEVEL S r•I I \ U -! io9.,, '' . 110 2„ Jail i SEALANT CAULK&SHIM SPACE(TYP.; REPLACE EXISTING I WINDOWS TO 31/6" 1 3/6" MATCH EXISTING I PRE-FINISHED ALUMINUM (TYP.) . MI WINDOW SYSTEM I NEW DOOR& GLAZING BY UNIT C Figure 4: Aluminum Storefront Window Detailed I I . 3llA601 "' '' NEW,�- - - L r Figure 3: Aluminum Storefront Wall Assembly Aspen Mountain Townhomes ()Sr' Mr.Marley Hodgson August 20,2019 Page 7 of 13 Figure 5 below shows a receipt reported for this project that indicates that Jeld-Wen Siteline aluminum clad windows were purchased and used on the project. We confirmed use of these windows by branding on the windows themselves indicating they were Jeld-Wen windows, as well as the dimension and overall manufacture of the windows that match the literature obtained from Jeld-Wen's website. ik2 PRQSuild 38005 HIGHWAY 82 SP ORDER INN. 560673 PRcauild ASPEN. CO 81611 DATE 6/30/2015 2:12 PM 1 (970) 925-4262 i F S.O. P08 0801-00565548-00 SILVER SAGE BUILDING COMPANY LLC H SILVER SAGE BUILDING COMPANY LLC ASPEN MOUNTAIN TOUNHOMES P 62l S MONARCH ST 623 S MONARCH ST ASPEN, CO e1611-2957 0 ASPEN, CO 81611-2957 ( ORD: DAVID DORR ACCOUNT 83 4-008 55300-008 64LUNO 801 SHInNO 801 Mi.I 30S MARIO ESPINOZA OIIA 565548 cum BTomI 8TO82 MASON 409 8R TAN FRS14ON'T ONOER ►O_ DUE DATE: 7/10/2015 INV TERMS: CHARGE OUT 10TH _ ,n�• LOCH AIY VNR DESOFOPT,ON WIT MONO= l DAVID DORR 379-7110 JYLD-WEN 4 4EA SPC169413 77X124-1/2 SITLN CASEMENT CLAD 4EA 2726.76 10,907.04 7 1 LEA SPC169442 77X124-1/2 SITU) CASEMENT CLAD lEA 2726.76 2.726.76 7 1 LEA 5PC169443 39X124-1/2 STLN DIRECT SET CLA lEA 1393.80 1,393.80 T 2 2EA 5PC169444 77X101 STLN CASEM T CHESNT CLA 2EA 2507.39 5,014.78 T 2 2EA 9PC169445 77X137-1/2 STLN CASt4NT CHSNT C 2EA 2984.65 5,969.30 T 1 IRA SPC169446 77X101 STIlI CASNKtiT CHESNT CLA lEA 2507.39 2,507.39 T 1 lEA SPC169448 39X101 STLN CLAD CASMNP CHESNT lEA 1271.58 1,271.58 T 11 11EA 5PC169453 60X60 STIli CLAD RECTANGLE FRAM IlEA 200.00 2.200.00 7 1 LEA 5PC169454 18'1[50' COIL STOCK CHESNTBRNZV lEA 18a.80 184.80 7 TELL BRIAN WHEN IN DAVID DORR SILVER SAGE Prgoci Nam): Contract Number — Ca t Code: 'S j (r G 3- S Approved By. rAte: Figure 5: Sales receipt indicating Jeld-Wen Siteline aluminum clad wood windows purchased. It should be noted that the maximum allowable height by Jeld-Wen for these windows is 84"as shown in Figure 6 below. As a result of using excessively size windows and a window type that did not match the performance characteristics of the window assembly originally specified by the Architect, the as-built window wall assembly has failed and resulted in water intrusion and damages to the building. Aspen Mountain Townhomes OP.- Mr.Marley Hodgson August 20,2019 Page 8 of 13 FA1 JJ &WWDON CLAD-WOOD WINDOW AWNING MIN-MAX SIZING - STATIONARY 84" 12"L „ . , 18" 1 F 84" 1 Minimum Configuration Maximum Configuration Stationary Width 18" 20" 24" 28" 30" 32" 36" 42" 48" 54" 60" 66" 72" 84" Stationary Height 12" 18" 20" 24" 28" 30" 36" 42" 48" 54" 60" 64" 66" 72" 78" j 84" I Figure 6: Maximum allowable sizes for fixed(stationary)windows. Aspen Mountain Townhomes Alisr- Mr.Marley Hodgson August 20,2019 Page 9 of 13 We completed our evaluation of the water leakage adjacent to the balconies by performing extensive water testing on the balcony of Unit 407. Water testing can be challenging to identify particular sources for water leakage; however,water testing was performed in a methodical and sequential manner that would help identify sources for water leakage. This generally includes testing locations from low to high, as well as testing the least likely source for water leakage, and then those with the highest likelihood for leakage. It is also common for there to be more than one source for leakage. To that end,water testing was conducted with a water hose and a spray nozzle in the following manner at the balcony of Unit 407 (also see Figure 1 below for locations for water spray testing): • Water spray testing was first conducted at the sill of the windows at the transition with the balcony to the right (west) of a brick veneer wall for approximately 5 minutes (see yellow highlight in Figure 1 below). No water intrusion to the interior of the unit was observed within that time. • Water spray testing was then conducted on the aluminum storefront window on the lowest window pane, gaskets, and aluminum framing for approximately 5 minutes(see orange highlight in Figure 1 below). No water intrusion to the interior of the unit was observed within that time. • Water spray testing was then conducted at the base of the brick veneer wall just above the balcony for approximately 5 minutes(see light green highlight in Figure 1 below). No water intrusion to the interior of the unit was observed within that time. • Water spray testing was then conducted on the brick veneer higher up the wall for approximately 5 minutes (see darker green highlight in Figure 1 below). No water intrusion to the interior of the unit was observed within that time. • Water spray testing was then conducted on the aluminum storefront window and portions of the brick veneer above the first horizontal mullion for the window. After approximately 5 minutes of water testing, water was observed at the level of the carpet on the interior(see Photo 17 below). 5 additional minutes of water testing was performed to aid in our observation of avenues for water intrusion. Water was also observed running down the interior side of aluminum framing,just below the horizontal mullion for the aluminum storefront window(see Photo 18 below). Leakage appeared to occur at the transition between the horizontal mullion and vertical framing at a failed sealant joint. • Water spray testing was then conducted at the base of the aluminum storefront window just left (east) of the brick veneer wall for approximately 10 minutes (see blue highlight in Figure 1 below). No water intrusion to the interior of the unit was observed within this time. • Water spray testing was finally conducted at the exterior door threshold for approximately 1 minute (see purple highlight in Figure 1 below). Water was observed at the existing opening cut in the laminated wood flooring(see Photo 20 below). Aspen Mountain Townhomes ni..... Mr.Marley Hodgson August 20,2019 Page 10 of 13 I N i I lit I REPLACE EXISTING _ WINDOWS (TYP.) I II r7 I ow jimil- I 1 1 1 1 1 I _ Figure 1: Locations of water spray testing of south window wall assembly of Unit C. Aspen Mountain Townhomes niir.' Mr.Marley Hodgson August 20,2019 Pa.e 11 of 13 i 0 • , - I , 1 Photo 13: Water leakage during spray testing 1st floor. Photo 14:Water leakage during spray testing 2'floor. Faux window extensions are installed above the aluminum clad wood windows at the roof level (see Photo 15 below). The window extension appear to be supported by light gauge steel I beams(see Photo 16 below). It further appears that the glazing consists of tempered glass inserted into `U' channels' (see Photo 17 below). T t. , r�i..:-.;:_.:::4:: t VAT �:, lall Ili I . " JY Ill ' i ilk . ' . . 4:12, •• -4 Photo 15: Faux `window extension' above roof line. Photo 16: Steel support for`window extension'. tiii, tgg . » -„ EMI • ,EL: -1111111111111111 ...c.- --' .0'iLZ \ mill Photo 17:Tempered glass installed in `U' channel. Photo 18: Sealant failure @ steel supports&roof. Aspen Mountain Townhomes Air' Mr.Marley Hodgson August 20,2019 Page 12 of 13 he steel supports penetrate the single ply roof membrane and a sealant has been applied around the base of the support but is failing and is a likely source for leakage into the roof or above the roof assembly(see Photo 18 above). A metal drip cap flashing appears to be installed between the edge of the roof that extends over the top of the aluminum clad wood windows below (see Photo 19 below). The end of the cap flashing is heavily caulked and likely indicates improper flashing at the transition with the adjacent wall. 1111111040 ir AM 4.11 Photo 19:Cap flashing over 2'floor window unit. Photo 20:End of cap flashing heavily caulked. Based upon these findings, it is our professional opinion that improper windows and flashings were installed at the south facing window walls and that the installation itself was deficient as well. To stop water leakage into the units, the window walls will need to be replaced in their entirety. An aluminum curtain wall or storefront window assembly should be installed as a replacement that complies with the window manufacturer's requirements and local Code. This includes the window extensions above the roof level. While a preliminary scope of repair work has been provided, additional design services will be required to further evaluate as-built conditions with intrusive test cut examinations at wall and roof flashing conditions as well as to develop the flashing and window installation details required for the project. Recommendations and Opinion of Probable Construction Costs(OPCC) The following recommendations are intended to give a general sense of the repairs or replacements we are recommending and are not intended for bid or for construction. Based upon future intrusive examinations planned to be performed to better understand existing conditions, some of the recommendations may be altered; however, the basic scope of work will be similar to that noted below. The recommended scope of work to Units A and C includes,but is not limited to,the following: • Removal of the existing south facing Jeld-Wen aluminum clad window wall assembly. • Removal of the existing south facing window wall extension above the roof line. • Carefully remove adjacent wood siding,store,and reinstalled after new windows are installed and properly flashed. • Install Manko 250 XPT thermally broken aluminum curtain wall window assembly for fixed lites (picture windows)or Equal. See attached data sheet. • Install Manko 4527i thermally broken aluminum project-out awning window at the bottom of the window wall assembly or Equal. See attached data sheet. • Install new roof curb and new flashings to facilitate extension of the window wall assembly above the roof level. Aspen Mountain Townhomes Alisr- Mr.Marley Hodgson August 20,2019 Page 13 of 13 • Reflash windows to existing wall assemblies. In addition,the new window wall assembly and associated wall and roof flashings should be designed by a building envelope consultant. We have included our estimated fees for these services in the opinion of probable construction costs below. An Opinion of Probable Construction Cost (OPCC) for the repair work we recommend in this report has been prepared in today's dollars. The OPCC is not a bid, nor is it intended to be a guaranteed maximum cost for the recommended repairs. The OPCC is only intended to give the Association a reasonable amount that the repair work recommended might cost. All OPCC dollar amounts are in today's dollars, and no calculations for inflation have been incorporated into the amounts shown. Scope OPCC Remove existing windows and extension above roof. Remove, store and reinstall wood $50,000 siding adjacent window walls. Install new window flashings,roof curb,and roof flashings. Install new Manko 250 XPT and 4527i thermally broken aluminum curtain wall and $48,000 storefront window assemblies (or Equal). Subtotal $98,000 Contingency of 15% $9,800 Building envelope consultant fees for design. $4,000 Grand Total $111,800 Please let us know if there are any questions. This concludes our report and our services at this time. Sincerely, Ascent Building Consulting,Inc. Steve R. Bunn,RRC,RRO President NIANIKC) p0 WINDOW SYSTEMS INC. www.mankowindows.com 2SOxpt With energy performance at the forefront of every project design conversation, Manko Window Systems has developed one of its newest curtain wall series, the 25oxpt. With its 2 1/2" face profile and polyamide thermal nose, this two sided or fully captured high performance system gives you the versatility to meet any energy code. The 25oxpt comes with an option for single pane (25oxpt-1), dual pane (25oxpt-2), or triple pane (25oxpt-3) glazing coupled with a backmember depth ranging from 2 1/2" - 8". Suited well for low to mid-rise applications, the 25oxpt is compliant with AAMA air, water, and structural testing and NFRC too, 200, and 50o certifications. When your project calls for a high performance curtain wall system that is fabrication and installation friendly, look no further, Manko's 25oxpt can meet the requirements. / 7 /� A . 1 ' PUS S �, At ,` ' . t p ,IC 4 NMI � p 4 1 ■ El t III It 74 1 ' i ;01-,,,'--- ' i F Multiple face cap&back member depths _ ,t; %`, �/4ii, .125 (3mm)wall thickness Window vent options, including Manko's t 3116 1 314 glazing cavity iwoo series zero sightline window U = Subframe accommodates storefront doors Full range of anodized &AAMA 2605 1— Compatible with Manko's thermal doors painted finishes with dual finish capability Take-out&hinged sash venetian blinds Blast capability asp Specify our Products in 5 Integral venetian &pleated blind options 0 as i n k-e 11 8" 6 3/4" L.. Glass Type go 5 1/2" • •-Value 4" Clear SN 68#2/Clear 0.34 0.30 0.34 60 2 1/2" Clear SNX 62/27#2/Clear o.33 0.29 0.25 61 1 i 0 ! �ti - - Clear SB 6o#2/Clear o.33 0.29 0.36 6o - 1 I I I I I I I I j .17,1 ���Clear SB 7oXL#2/Clear o.33 0.29 0.25 61 cN I I I I a C-- Clear SN 68#2/IS-2o#4 0.29 0.26 0.33 51 Clear SNX 62/27#2/IS-2o#4 0.28 0.25 0.24 51 4 5/8" 6 1/8" 7 5/8" 8 7/8" I '• 'M 10 1/8" Iill 17.5mm polyamide thermal strut Certified Compliant 250xpt-2 • ASTM E z83-Air • ASTM E 331 -Water 2.7° 111° 19.5° 27.9°I 36.3"I 44.7°I 53.0°I 61.4°I 698° • ASTM E 330-Structural miriIIIiri • NFRC too- U-Factor 250xpt- 3 • NFRC200-SHGC&VT • NFRC 500 &AAMA 15o3 35.5mm polyamide thermal strut Condensation Resistance 8„ 1lii . ,.1 6 3/4" 1/2" A - 2 1/2" System Performance Valuliii 1 Glass Type Air Argon ] .I' _/^ iI ----fii===1t===fi--7I--71 U-Value U-Value SHGC CR V e I I I I Clear/SN 68#3/Clear 0.25 0.22 0.37 71 ee of N dN 1 1I 11 I II II Clear/SNX 62/27#3/Clear 0.24 0.21 0.31 71 L °' r 1 1 _______i__ =___i_l___Lf -_I-i__-J Clear/SN 68#3/SN 68#5 0.20 0.17 0.33 77 Clear/SNX 62/27#3/SNX _ 5 3/8" 62/27#5 o.19 o.16 o.27 77 6 7/8" SN 68#2/SN 68#4/ 8 3/8" 0.18 o.16 o.26 68 IS-2o#6 9 5/8" SNX 62/27#z/SNX 62/27 o.18 o.15 o.18 69 10 7/8" #4/I52o#6 - _ 11%#11k1NIKC:1 0 0 WINDOW SYSTEMS INC. www.mankowindows.com 4527 . 1 FIXED • CASEMENT • PROJECT IN/OUT • GO Manko's 4527i series was specifically designed to provide an efficient, economical window to an industry seeking thermally enhanced products. The 4527i is a member of a family of projected windows utilizing the same exterior die profile with interchangeable thermal struts depths and interior dies to create six different frame depths. Specifically, the 4527i uses a 24mm I III polyamide crimped in place structural thermal barrier to create a 4 1/2" overall window with a 2 314" vent. This specific strut provides superior frame performance and can be used in conjunction with dual or triple pane insulated glass. Main frame , ..% f construction is mortise and tenon joinery with dual integral screw ./ ,.4_ 11 races. Operable sash uses mechanically joined, angle reinforced, y ',:.'' mitered corner construction. The 4527i is tested to , `�- AAMA Architectural Class (AW) specifications, and Features: carries NFRC too, 200, 400, and 50o certifications. 4 1/2" overall frame depth, 2 314"vent depth 1/4"to 2" glazing options F Preglazed at factory for added quality control .r,` " Exterior grids available (beveled, cove, OG) = _ _ Interior surface applied & between glass muntins , .: 0 ;-;:.-..-: 17 _ 4 available _ {� \� �w =_- 4 Ad Hermetically sealed, hinged sash, and take-out sash tt �` `_ blinds available \ ...................................................... 'iai _ ` - ` '� s Panning systems &interior snap trims available/1_____ rr,� = g Y p ` Es: 4__ -' 1 �' Receptor systems available w/optional starter sill � Custom profiles &configurations available _ Full range of anodized &painted finishes, including dual finish capability AAMA Structural Performance NFRC Thermal Performance AAMA Air Design Structural COG U-Value(NFRC 100) Type Performance Infiltration Water g Overload Rating @ 6.24 psf Pressure Pressure U-Value Fixed Projected Casement Fixed AW-PG100-F <_ .1 cfm/ft2 12.0 psf 100 psf 150 psf 0.38 0.44 0.54 0.53 Projected AW-PG80-AP <_ .1 cfm/ft2 12.0 psf 80 psf 120 psf 0.35 0.42 0.52 0.51 Casement AW-PG80-AP <_ .1 cfm/ft2 12.0 psf 80 psf 120 psf 0.32 0.40 0.50 0.49 Sizing Capabilities (Frame Size) 0.29 0.37 0.48 0.47 Width Height Max 0.26 0.35 0.47 0.46 Type Min Max Min Max FT2 0.23 0.32 0.45 0.44 Fixed 12" 100" 12" 100" <_ 36 0.20 0.30 0.43 0.43 Projected w/ 15" 60" 16" 41" <_ 16 All values shown are calculated with Manko standard TriSeal cam handle insulated units. Verify performance numbers with test Projected w/ cam handle 15" 60" 16" 60" 20 Glazing Infill Options Glazing 1/4" 1/2" 7/8" 1" 1 1/4" 1 1/2" 2" Projected w/ 22" 60" 20" 60" <_ 20 rotary handle Infill 0 0 0 S 0* 0 0 Casement w/ 16" 36" 16" 41" <_ 10 Hinged/Take- single cam handle S S Out Sash Casement w/ 16" 36" 16" 60" <_ 15 dual cam handle Grid Option 0 S 0 Casement w/ 18" 36" 18" 60" <_ 12 *Hermetically sealed blinds are available, rotary operator but will limit glass options and between glass muntins Hardware Options 4 Bar Auxiliary Single Dual Pole Access Butt Limit Cam Lift Type Hinge Friction Arm Arm Ring Control Hinges Device Handle Lock w/Friction Device Roto Roto Cam Custodial Projected S 0 0 *0 *S 0 0 *0 Casement 0 S 0 0 S 0 S S=Standard Hardware 0= Optional Hardware *Lift locks are standard with roto operators, and whenever vents exceed 42"tall when using cam handles ��J271-GO BEVELED COVE SMALL LARGE SMALL LARGE GRID ii400 4.4114. lx.., PROFILES