HomeMy WebLinkAboutInspection.1034 E Cooper Ave.0008-2022-BREP (6) HealthSa f e NSPECTIO NS HealthSafe Inspections Inc 390 Apple Drive Basalt CO 81621 970-920-2100 Jim Baker CDPHE Asbestos Building Inspector#13437 Ben Baker CDPHE Asbestos Building Inspector#25863 ASBESTOS REPORT DATE 01/12/2022 CLIENT Wyll c/o Timberline Construction & Consultants, Inc. PROPERTY ADDRESS of INSPECTION Chateau Eau Claire#27, 1034 East Cooper Avenue,Aspen, Colorado 81611 ZS•_: ;fd • fat. 45w` s'. ATE A • C AIIN7LE RECEIVED 1 02/22/2022 ASPEN BUILDING DEPARTMENT CLIENT BACKGROUND & PLANS The Client,Wyll, is planning a renovation-remodel-demolition of the condominium floors, which will have impacts of disturbance, detachment, deconstruction, demolition, and disposal(5D) of wood flooring adhesive, which is a suspect asbestos containing materials (ACM). Prior to 5D, Wyll is required to have an asbestos inspection by a State of Colorado CDPHE certified asbestos inspector who will collect bulk samples of the suspect ACM and have those samples analyzed at a certified laboratory for asbestos content. Wyll hired HealthSafe Inspections, Inc. (hereinafter, HealthSafe) via Timberline Construction to perform a limited asbestos inspection for flooring materials in the condo. VISUAL INSPECTION & LABORATORY FINDINGS An inspection was conducted by Ben Baker of HealthSafe on Tuesday, January 11, 2022, with Eric Fisher of Timberline Construction present during the initial survey, inspection and sample collecting.All suspect ACM were identified by homogenous materials and sampled randomly respective to the scope of those materials slated for 5D. The suspect ACM collected and analyzed by EPA 600 Method PLM analysis are the following: 1. Wood Flooring Adhesive, a homogeneous miscellaneous material requiring a minimum of at least two samples [samples 1-2:ADH-1,2], collected from the entry coat closet floor in the center and the NE bedroom doorway, respectively. The PLM analytical estimated results: NONE DETECTED. A total of 2 suspect homogeneous ACM bulk samples were collected, and 2 samples were analyzed. The bulk samples were analyzed by EPA 600 PLM analytical methods by a NVLAP accredited laboratory in accordance with Colorado State Regulation 8 for the presence of asbestos mineral fibers. There is NO asbestos in both samples. See supporting Hayes Microbial Consulting, Inc. data report#22001117_1. HEALTHSAFE CONCLUSIONS • There is NO asbestos in any of the suspect building materials slated for 5D in this condo flooring replacement project.NO asbestos abatement will be required for any of the flooring building materials.All flooring waste and debris can be disposed of in any landfill which accepts normal, non-hazardous building waste. Sincerely Submitted, Ben Baker ge-frt, ga/62.2. RECEIVED 2 02/22/2022 ASPEN BUILDING DEPARTMENT NEW SPICE RACK IN UPPER CABNET C -w CARPET NEW ROLCUTSL - EI EXISTING PANTRY R - F CARRY NEW VINYL N B,g9iit FLOCKS IN-0 J I X: e BATHROON _ II !EA5\frOR / � ^. SSX30 /{�W VINYL EEXISTING OUTLET J II O / _ PER CODE L/ W NEW VINYL W a- I CMPE FLOORS 7 Z J m // V . :Xis o G 7 N O RECLIN'�- W .2 I • �—REFINISHEXISTING y� 2■ ■ b / SANEWill , i._. ■ ARP 1 U 3sX]s DATE:YBY, _ NEW BUILT IN �FIEW PORCELAIN =.W BUILT IN URROU RACE ISSUE SURROUND, ��^��^��rrrr TILEWPLL PORCELAIN TILE OPo FD O= SHEETTITLE: OPOSED FLOOR PLAN ID.01 RECEIVED 3 02/22/2022 ASPEN BUILDING DEPARTMENT COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY Regulation No. 8 Part B—Asbestos of the Colorado Department of Public Health and Environment(CDPHE),Air Quality Control Commission requires a State-certified Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos containing materials (ACM) or suspect asbestos containing building materials (ACBM) prior to their disturbance, removal or demolition and disposal. The suspect materials shall be analyzed by a NVLAP accredited laboratory by polarized light microscopy(PLM) using EPA 600 analytical method.A material which is estimated to contain more than 1% asbestos is classified as ACM/ACBM and regulated by the State and Federal governments.Any friable (able to crush or reduce to powder by finger pressure) asbestos with trace amounts of asbestos fibers or less than 1%must be point-counted using EPA 400 analytical method to prove that it is indeed less than 1%; if not, it must be classified as ACM/ACBM and shall be treated as a State and Federal regulated material.Any friable asbestos containing material (greater than 1% asbestos concentration) or ACM/ACBM that could be rendered friable during its removal or demolition and disposal shall require an asbestos abatement by a certified asbestos abatement contractor to remove and dispose of the material(s). A Colorado State (CDPHE) issued asbestos abatement permit is required for the following trigger levels of ACM/ACBM: 1. Residential buildings of four or fewer units--if more than 32 square feet of any surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing materials/textures, acoustic sprays,joint compounds,plaster, etc.), 50 feet of asbestos covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is going to be disturbed, removed or disposed of, an asbestos abatement permit is required. 2. Residential complexes with more than four residential units, public access areas to a residential building, commercial and retail buildings, public and civic buildings, industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet or more than 35 cubic feet(NESHAP) or 55-gallon drum(CDPHE) of suspect ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement permit is required under NESHAP and by the CDPHE. See note below on OSHA. The regulations require an absolute minimum of 3 samples (EPA suggests 9)per homogenous suspect surfacing and TSI materials and an absolute minimum of 2 samples of homogenous miscellaneous materials or any number of"samples sufficient to determine whether a material is ACM" (Reg8.IV.D.3). More samples are required based on surface area or volume. These are minimums; the asbestos building inspector has the field responsibility to determine homogenous materials and the number of samples to collect per material; more than the minimum number of samples may be necessary at the discretion of the inspector.An assessment of friability and functional space conditions of the materials are also the inspector's field responsibilities. RECEIVED 4 02/22/2022 ASPEN BUILDING DEPARTMENT OSHA compliance is required for all employers and employees no matter the quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or friable surfacing materials, and therefore it does not matter what the quantity or State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for asbestos prior to their disturbance, removal and disposal for worker protection and safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134 Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos hazards. Note: County or City regulations may be more stringent. RECEIVED 5 02/22/2022 ASPEN BUILDING DEPARTMENT 4 HAYES MICROBIAL CONSULTING #22001 1 17 Analysis Report prepared for We would like to thank you for trusting Hayes Microbial for your analytical needs! We received 2 samples by FedEx in good condition for this project on January 12th, 2022. HealthSafe The results in this analysis pertain only to this job, collected on the stated date, and should not be used Inspections in the interpretation of any other job. This report may not be duplicated, except in full,without the written consent of Hayes Microbial Consulting, LLC.. 390 Apple Drive This laboratory bears no responsibility for sample collection activities, analytical method limitations,or Basalt, CO 81621 your use of the test results. Interpretation and use of test results are your responsibility. Any reference to Phone: (970) 920-2100 health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or consequential damages arising out of the use of these test results. Wyll Residence Chateau Au Claire #27 1034 E Cooper Ave 44( n *„..e4_,.... Aspen, CO, 81611 Collected: January11, 2022 Steve Hayes,BSMT(ASCP) Laboratory Director Received: January 12, 2022 Hayes Microbial Consulting,LLC. Reported: January 12, 2022 ��-0ED STA0T1 J s / AL'bo,,o \ w 1DPH 1 tia +T G� \ Connecticut Department 4C pROjE of tkot Health RECEIVE EPA Laboratory ID: VA01419 Lab ID: #188863 DPH License: #PH-0198 02/22/2022 Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 3 ASPEN BUILDING DEPARTMENT Ben Baker #22001 117 HealthSafe Inspections Wyll Residence 390 Apple Drive Chateau Au Claire #27 Basalt,CO 81621 1034 E Cooper Ave Asbestos PLM Bulk (970) 920-2100 Aspen,CO, 81611 EPA 600/R-93,M-4/82-020 # Sample Material Description Non-Asbestos Fibers Asbestos Fibers 1 ADH-1 Granular/Gray None Detected Adhesive/Yellow None Detected 2 ADH-2 Adhesive/Yellow None Detected Collected:Jan 11,2022 Received: Jan 12,2022 Reported: Jan 12,2022 RECEIVED HAY E S Project Analyst: l, Date: Reviewed By: 3e/2 2 2 0 2 2 Renaldo Drakes, O1 12 2022 Geepha Jacob, 01 /- 12-2022 0ASMICROBIAL CONSULTING 3005 East Boundary errace, uite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILDING D�ERTMEtJ�T Ben Baker #22001117 HealthSafe Inspections Wyll Residence 390 Apple Drive Chateau Au Claire #27 Basalt,CO 81621 1034 E Cooper Ave Asbestos Analysis Information (970) 920-2100 Aspen,CO, 81611 Analysis Details All samples were received in acceptable condition unless otherwise noted on the report.This report must not be used by the client to claim product certification, approval,or endorsement by AIHA,NIST,NVLAP,NY ELAP,or any agency.The results relate only to the items tested. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines. PLM Analysis All Polarized Light Microscopy(PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM. Materials with interfering matrix,low asbestos content,or small fiber size may require additional analysis via TEM Analysis. TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content. Definitions 'None Detected'-Below the detected reporting limit of 1%unless point counting is performed,then the detected reporting limit is .25%. New York ELAP Per NY ELAP198.6(NOB),TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing. Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those samples.The original report provided to Hayes Microbial Consulting is available upon request. RECEIVED H AY E S 02/22/2022 MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com ASPASPal 3 of 3 BUILDING DEPARTMENT • HeallthSafe Inspections SHIP: FEDEX - ENV PO ASBESTOS l- J 390 Apple Drive DATE: 61 1z 2022 —= MICROBIAL CONSULTING Basalt, CO 81621 8136 1033 2242 Job Number: Job Name: Wy // Aosr'd's e 11111111111111111111111111111111 22001117 Collector g of �,� f �� ,,,} eAr, 4 o (/G,i f t4 I healthsafeinspections@grnail 13 /3 /� Mobile: 970-920-2100 Email: 1 J3`1 L Coy'Ic.el Avc Date Collected: vl / I// %^)- ! 45,P,, 0) "d/G/; ! Note: (t; G,,, , i',� hiker- i1pa��^ :,, - ,,,-, Analysis Type ��Analysis Methods � • Tumaround Times • r PLM Bulk EPA 600 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day Point Count 400 Point,1 000 Point 3 Hour Same Day 1 Day, 2 Day 3 Day 5 Day Vermiculite CARB 435 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day TEM Air EPA AHERA,NIOSH 7402 - Same Day 1 Day 2 Day 3 Day 5 Day Bulk Chatfield - Same Day 1 Day 2 Day 3 Day 5 Day • Wipe ASTM D6480-05 - Same Day 1 Day 2 Day 1 Day 5 Day Microvac ASTM D5755-09 - Same Day 1 Day 2 Day 3 Day 5 Day s P CM Air ���' NIOSH 7400 ` �YM1�� yy Same Day 1 Day 2 Day 3 Day 5 Day # 1 Group Number Sample Name J Analysis Type Turnaround Volume/Area�I Slop (+) 1 .1 i)t1 q F i._4-? 5. 2 _ 4AN • a PL/11 5,4Mi 04L' 3 4 5 6 7 8 • 10 11 12 13 14 15 16 17 d Released by: /e" / Y �W .y E L)) Y ��� ,�/lam Date: o// 1/ i2. Received B : .r� Date 1 r /17 e . ? 2 Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F.tvlidlothian,VA.231124 022 (SO4)562-3435 contacfCliayesmicrol�ial.com Form:20,Rev. , cl 1 Chain of Custody ASPEN BUILDING DEPARTMENT r "�1��r. 1 f" k�'�� '._' oI�h�Y� � ( Y,� �2�2.1{a�; ''� )k�� ?b �,1�4� (D)f+z TI{I .)l' r �1;.4{i f� �'11 ei. � ) ��1,.�'i'„ .•v� ' f Sr 1 r,'d,N"'"1�. ,���1�'1'�'n r )i.(f ;4,�)a e`�4F�' .1.,�SU / 11.0 i. o o. rt4 , Fsyst 00 .„ 0,!IT.,. } .,,ok. {t 71'0,i, 6f V. { v. s 1 till V. t��ii t0;;; - ' •' }epS�''1,''{. I ''re :ies'n.t•;p tY ;. }'1 4s, t , :L,+h C. '•':t r„,ftl'}/'1• .. o ;,Y�1: :� !best aeon it : ;1A„� f a� V t. 1•= 3rr ,• M art' °.,......�� r. � 1 � t :eII f s 1t•4'r t, =�obi♦ .f s �'d. ' x i V���.:, t . o d 4 ` z e4..: x, °'t��d�;..; t . old .:; t (.. I -,.;r 7_ ,^ L e q4t. v, L ,p 1.41 > .L ._ . J. • .L e. 014, •L.. _ L Vil * - 1 .,l ,1,i 1,,,7,,,,t,V;;,v,t,,,,,,1,,r,:,,,I,t,r,t,i,,t I,;t,t r,t,l,t,l,t,,,,P',1,I, ,,, V.,1,1,1,1 v,tt„ ;,,t,t,1,1,,l,l,t ,t,r t,1,1,t;,,S., ,t r{,,,,,I,I t,1,r 1,4 t 1 , t,{ ,1,,t,I,1,V,t,t"I,,,t,t. ,t,t,r,t° I -,$s �� C�tO c�‘!....,it's,::.'..Z:.1.:, tip./ 4ry+� O ,F R L iD. e , �J876 ;:::::';71/ � , ' r1 Colorado Department ` , z of Public Health , and Environment =s �: ♦ I 'D;... a: ASBESTOS CONSULTING FIRM ' ';ti.. � This certifies that -Ear HealthSafe Inspections, Inc. =, !�, _-1 D. s• l dr � " Registration No. AC 18234 .4,1 R. y r j% . fi has met the registration requirements of 25-7-507, C.R.S. and the Air Quality Control :i-7 \S% j.j. Commission Regulation No.8,Part B,and is hereby authorized to perform asbestos consulting activities as required under Regulation No 8, Part B, in the state of Colorado. '- ° . 07 _ Issued: April 12,2021 r Expires: May 14,2022 i.___ rSi ,�. C; ...,.„ ,,,,,, di ) , ---{t,I t r t$IIn1`L:yt"'I'0 1 7 7 .1 t•qn 7,i1,.,7 7'1 1 t't, I} I I ;t" gi-I;l I1,t t t I t/J I,tt)t I?1$' I.{1 I I I'I`t'1 t t I",1'tt I 7 I II 6'.IA t A l l'1 It t V.I'I t rP •A.t l t u i t i - i-. y,y� -�1 i) — .a .� xJT `xi! Ts •:tido< 5 T ,^ ..sT. .�,%,,,, . T :' T Wu L 'I _ -r 11 1 1 1 11 I I _ ., „'P�rt ;� � ,; �, ` ' x s '� ' , e, ` `0, ti � ` P e w, ; '`:',. r J .a; I d� #. } (! 4! i"•};,'2 iis•I r'sl r ' r _ ' . >s r t v 'r si, li` tr ...; ti.• d d 4"t{1'>'s Ifl is •:. .. ,+}r s. ;i slrr t l , K' S l e ,tr ''i;it't}.�°� r }, rrI ,,Ir,,�. .Av 1,1 ,� •.1 ASSA Nr AS � av A. 1� 1r: i .:'. �.:.y.• t,� A. i � A I',�, I ♦`e .• 'fl b v'. c�li S 1 4 .Fp .il' Vrr tS - Ncrt'S'� -r S:l� iA e''' Ir ,o -, b..!lit��rr�� -. � �Z :X i . ' WI W A i 1e 77'' :,,_ f . --- Al 0.' 11 ,8"ir 1pbo.. s:1) BUILDING DEPARTMENT ii1;/ �,:i�N\•/1•'.mr../ 1pi,/'yizJ rrTiV 4v 1 ��/* Y i;;It1 . i1.••1•/i. viilp�� �. Iii;.� .ivi1r;:3� � i�i 1Py : � �i;;R :t. �i //jij"r .� f11//{i0):. �\ ff////I/i�i. q0:4/14►00r'r•.kll�gi1t1dei;,,,,:i\1� ►1;,o,i �n.41,10.41, �.t ,.0,fN1i0*,, *,,,11►►411•,;b,,`\\ /:3' .,:i•1lrilft.A�� 11,►N►0:,;:ii,,I,,q11 t.1.►r,11:1,,,i,,,,, 1r•./►�0,,;fik \1,1 ,,,..../I �/// 14...p/ iviAJ ..-. a4f,,er^\- ,i,ti.I ,/r Jyfk .ldj jh \_ii.•oii �L.:JtlI yl.♦M;,.'tQ liPri �ri� „ 't a \ .\ rgirr^\ , ,b,r,; /oo f✓� N ` viiir�^k \ ' •, ii/AkN\ l� h/ipri,�!iti- +- lZi:. - � ¢/ i:. ✓�> \ r ; ; r _Ik 1. ._��__ __"� .ymiiiiu1f Yl((IUll iiii1 U , I "I!1N� Iti S Ui UU! N L UN IH V NgIN V .. .�_\ •.: V.v Vv♦vV♦V. -'.V ♦. ♦`. ♦v1'V.I.v/ _♦ ...v� �iV..v•. ..r,.vv•.vv v V• ♦vV.V♦v♦vV1 /,,3�.:•..�r-_" -. •1 iftWi::Z......!.....;;..1)) 4,'-',::,,'-'-.•**Pt 1:::01217,:',11b4 ��jii1, '�i * * - l Z\\�- Colorado Department ig♦`` :• ..• -- - tip ' ' w of Public Health %tit-:. and Environment tm. >= r;>s>,, 0.:. =kV ASBESTOS 0 :. "Ilk g, CERTIFICATION (; , 44,....::: y) .; ��»fir,;.. Jc:r -_* IA t1C:' /si,,�-..,-s.A � - This certifies that s' ' Benjamin L Baker .• ,� ..:.A...„.::::::.,:-.,..: ,) t� - 14 "" 4 Certification No.: 25863 t"(fa`r� = /' �"''` has met the requirements of 25-7-507, C.R.S. and Air Quality Control . • �`\ain:'.i;l y,� : ✓ ,tlG_. _ , Commission Regulation No. 8, Part B, and is hereby certified by the t� ?:= •:; �� state of Colorado in the following discipline: tic_ ,, �• 4. >> Building Inspector* r = ; -41,...,-,..„..,*,,,: , 00 (R(1.17:is r.... _,:07:1::.4:,0 4W. Issued: August 19 2021 . Expires: September 25, 2022 ,�� iz h tCC F; :5� -_*: .•.fir: .�,::; j)) C,,..? �'(( „a� "I%�:`�"' *This certificate is valid only with the possession ofaOC-�`�_'•:�".��,�: �,�..L ) current Division-approved training coarse certification , %,11,1. •�.� <,.,. -7)) in the discipline specified above. %•. Authorized I Representative (( %t:74;y:4 • - ♦ramice �L- ��-•..•� �-� ?5`, ).O� I . ...rna.A.n.P..n ♦dP•i.�� t."4".4. ".n •I..•14a^. 'n r ♦ ♦ IRf nit r Ill.( • .r < , ,Wf1101}�linn tMMl l�l}FfiNnii �(nNN }fM{ �, tl } a11� l tf �4,. . \�`. .\�✓✓I :,;\N.�\�rrI `\�\.�\ rJr/ ;;.\�1\ J r f;;;,�\�\\ ✓4 ...;,;\NY\ r/�s \\ _ \� / \� ' LLB,r�Y i I/:�t'10...��.� i I! '� ,...�.r.'Jr/!'(Y%;!,,�.h\�Irr//(:i ..�.•�✓I/(.....,,„\�.\\�/!!/! , �,��\ ✓%L�;�tll:;��.y\�,�r�:Ti"','�t;;,.,�i1�r�ij�S.'r�=��. . ..• lii,e,P':.Sri♦y,y. Iiii 1:,:ii ,�.�\V/I/, ,y��.;IVII\� // .::'�•i,1 t I/, . ♦, .\�//, 1i \ /; .f;gi .�\a ,°'t.•r„\.\Vr n. • .ice����.y..�/>'i/I'11,11..y�.�/ ,r i�'r1N 1'.`�\\ l�o i�t'.1N�h'��,\��// .i�1�1.1'1�..1..,,\ //{,,,r�ii�:/♦�/,i1i�:(�.\�V/,/.i/lei:g��l ��f�t�\ /�/.�I�y':r♦�1.��';,..�\VI�I�i,♦"N.II.�r�l,�\\V/��-r�.i0•� $.3.yiNir��\\.t�//p1...1.►11h�\\1.�rl/l�l../441q��\��elii /��...1.1.�y�\\4�,/III�I.������\.���j�\w�;i,/I/I�r..�y�1h.� r!%/,ljl..♦ ih`'1\ '�/�//r11��.l��yq�p,f4ll 4,; V�kil./or/�Ip'1>•:�i �11/11,';,'\`'i%///%i11/�11�11�111;,`.�i11jl�II{1,�1�11�11ii�:`�i%///�//11�/1111�I�,1�:"'1j1/111.11�i1i��:`�i%/jl�l{{1,/1111����. •d/�/�1{{j�1�111.l\�hr�'�`//.!%IIII�11�Ii��`hw:.7.�/ I�r1.rt1�/11,gw-'iiI/I�lii;i!:�:Ir .'i.�,1j1/11Qet �osvIINIIiip ���.11111111� p' r<<•1111�111j�0 i....�1111i:' i0j//1/1111idp• iij//1111111:10 tti11/1j111psh . 1111�111•iIn• ro w1/1��.' .�1�:• :4• i}�• .���.10 ' 1��i�i l 4 4: • •�i�i�1�1�1 i 1 •tto./IA' ;4\ af•t61.01.11 �f46.ttsPi•^ •I�i t4./4•• ASPS BUILDING DEPARTMENT