HomeMy WebLinkAboutFile Documents.108 Midland Ave.0264.2017 (8).ARBK ��eU1LC/�C aecM f�6Ea Architectural Engineering Consultants, Inc. Mechanical, Electrical, & Lighting Design Services An Office with LEEDTM Accredited Professionals June 27, 2017 Philippe-Antoine Beauregard Poss Architecture & Planning 605 East Main Street, Aspen, CO 81611 Re: 108 Midland Avenue, Sandler Residence Dear Philippe, This document is intended to show compliance of the new construction of the residence located at 108 Midland Avenue, Aspen in Pitkin County, Colorado with the 2015 International Energy Conservation Code (2015 IECC). We propose to use a prescriptive approach per sections 402.1-402.3 and 403.2.1 of the 2015 IECC. I have also included the inspection checklist from the 2015 IECC Rescheck program for your use. Project The project at 108 Midland Avenue is the new construction of a residence with a floor area of approximately 6,555 sf. The heat load calculations are performed using the Carrier Hourly Analysis Program and provides a more detailed and accurate load than Manual J. A dewpoint calculation is not included in these permit documents, as the roof assembly meets the requirements of section R806.5 of the 2015 IRC. Building Envelope The following table lists the mandatory minimum insulation and fenestration requirements for the project climate zone (7). All new assemblies will meet the following requirements. Fenestration Skylight Ceiling Wood frame Mass Wall Floor Basement Slab Crawl Wall U-factor U-factor R-value wall R-value R-Value (i) R-value wall R-value R-value R-value Code 0.28 (1) 0.55(1) 49 20+5 19/21 38 (2) 15/19 (3) 10 (4) 15/19 (5) Min Notes: 1) Fenestration SHGC requirements do not apply in climate zone (7) 2) Or insulation sufficient to fill the framing cavity, R-19 minimum 3) R-15 continuous insulation on the interior or exterior or R-19 cavity insulation on the interior of the basement wall. Can be satisfied with R-13 cavity plus R-5 continuous. 4) 4 ft deep and R-15 edge insulation for heated slabs 5) R-15 continuous insulation or R-19 cavity insulation. Sincerely, David Denio, PE 40801 US Hwy 6 &24, Suite 214, Eagle-Vail, CO 81620 Post Office Box 8489,Avon, CO'$16 0 j fir" phone: 970-748-8520 email: stannaec-vail.com web: www.aec-vail.com 10/16/2017 ASPEN BUILDING DEPARTMENT MANUAL J DESIGN CONDITIONS WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 81 °F INDOOR TEMPERATURE 70 °F INDOOR TEMPERATURE 75 °F TOTAL HEAT LOSS 122,500 BTU/HR SENSIBLE HEAT GAIN 218,300 BTU/HR LATENT HEAT GAIN 5,600 BTU/HR TOTAL HEAT GAIN 223,900 BTU/HR PO REG/ST. lliregrA '; • Ili N •' • SS��NAL E ,••' ,,,,,,,,,,, RECEIVED 10/16/2017 ASPEN BUILDING DEPARTMENT aec Architectural Engineering Consultants, Inc. Mechanical,Electrical,&Lighting Design Services An Office with LEEDTM Accredited Professionals Warm Roof Assembly Worksheet Project: Sandler Residence AEC Project Number: 17017 Date: 6/27/2017 Calculated By: Bryan Urban Thermal Resistance of Assembly-Typical Roof Thickness Component R-Value Outside air Layer 0.17 Varies Water-proof Membrane 0.2 5/8" Plywood 0.77 6" Tapered Rigid Insulation 12.5 5/8" Plywood 0.77 6" Spray Foam Insulation 37.5 5/8" Gypsum Board 0.56 Inside Air Layer 0.65 Rew 51.91 Rt.! 53.12 Re,a R Value of the Exterior Sheating Rtotai R Value of the Total Roof Assembly Tin Interior Temperature(70°) Tout Exterior Temperature(Assuming-20.0°) Tinterface Temperature at the Rigid/Batt Insulation Interface Tinterface Re,n / Rtotal * (Tin - Tout) + Tout Tinterface 51.91 53.12 70 -20 -20 Tinterface 67.9°F Dewpoint at 30%Relative Humidity 37.2°F Dewpoint at 35%Relative Humidity 41.1°F The temperature of the foam/batt insulation interface is 67.9°F. Therefore,the resulting dew point of 41.1°F would occur in the exterior impermeable insulation,which verifies compliance. RECEIVED 10/16/2017 ASPEN BUILDING DEPARTMENT Zone Sizing Summary for All Rooms Project Name: 17017 Sandler Residence 10/13/2017 Prepared by:AEC 09:19AM Air System Information Air System Name All Rooms Number of zones 1 Equipment Class UNDEF Floor Area 6706.0 ft2 Air System Type SZCAV Location Eagle,Colorado Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Calculation Months Jan to Dec Space CFM Individual peak space loads Sizing Data Calculated Zone Sizing Data Maximum Design Minimum I Time Maximum Zone Cooling Air Air of Heating Floor Sensible Flow Flow Peak Load Area Zone Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft2) CFM/ft2 Zone 1 214.1 21458 21458 Jul 1700 121.2 6706.0 3.20 Zone Terminal Sizing Data No Zone Terminal Sizing Data required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name/ Sensible of Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft2) CFM/ft2 Zone 1 001 Media/Game 1 9.8 Jul 1500 963 3.7 654.0 1.47 002 Bar 1 2.9 Jul 1600 289 2.4 171.0 1.69 003 Vest 1 0.7 Jul 1700 66 0.9 36.0 1.83 004 Mechanical 1 2.1 Jul 1500 207 0.7 164.0 1.26 005 Powder 1 0.8 Jul 1500 76 0.4 60.0 1.26 006 Laundry 1 1.3 Jul 1500 129 0.4 102.0 1.26 007 Bedroom#3 1 4.3 Jul 1500 419 2.0 273.0 1.53 008 Bath#3 1 1.3 Jul 1500 131 1.2 100.0 1.31 010 Bedroom#4 1 4.1 Jul 1500 401 3.4 240.0 1.67 011 Bath#4 1 2.1 Jul 1800 205 1.2 123.0 1.66 014 Hall 1 0.4 Jul 1500 41 0.1 33.0 1.26 015 Massage 1 1.8 Jul 1500 176 0.5 113.0 1.56 016 Bedroom#5 1 4.1 Aug 1500 403 2.2 258.0 1.56 017 Bath#5 1 3.5 Jul 1500 346 3.0 258.0 1.34 019 Stair 1 1.1 Jul 1500 104 0.3 82.0 1.26 020 Hall 1 0.3 Jul 1500 25 0.1 20.0 1.26 021 Hall 1 0.5 Jul 1500 47 0.2 37.0 1.26 100 Entry 1 7.9 Jul 1700 776 3.4 193.0 4.02 101 Hall 1 2.6 Jul 1500 256 0.8 204.0 1.25 102 Stair 1 16.1 Jul 1400 1577 13.7 135.0 11.68 103 Mudroom 1 2.9 Jul 1500 280 1.6 162.0 1.73 105 Garage 1 9.6 Jul 1700 947 5.6 320.0 2.96 106 Closet 1 0.6 Jul 1200 56 0.4 37.0 1.50 107 R's Office 1 2.2 Jul 1000 218 1.6 85.0 2.56 108 Guest Master 1 11.7 Jul 1700 1153 4.9 288.0 4.00 109 Guest Bath 1 2.2 Jul 1700 218 1.3 81.0 2.69 111 G.Closet 1 0.4 Jul 1500 40 0.1 32.0 1.25 112 Hall 1 2.8 Jul 1000 274 1.5 102.0 2.69 113 Master Bedroom 1 13.8 Jul 1700 1354 7.3 274.0 4.94 114 Master Bath 1 9.3 Jul 1700 910 4.2 192.0 7 115 R's WC 1 0.2 Jul 1500 24 0.1 19.0 R 5 E AVi� r.A 116 M Shower 1 0.5 Jul 1500 45 0.2 33.0 .37 117 M's W.C. 1 1.9 Aug 1600 188 0.9 22.0 1�$. 6/2 01•� Hourly Analysis Program v4.50 v / EU 2 BUILDING DEPARTMENT Zone Sizing Summary for All Rooms Project Name: 17017 Sandler Residence 10/13/2017 Prepared by:AEC 09:19AM Cooling Time Air Heating Floor Zone Name/ Sensible of Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft2) CFM/ft2 118 R's Closet 1 0.6 Jul 1500 60 0.2 48.0 1.25 119 M's Closet/Office 1 2.9 Jul 1600 286 2.2 175.0 1.63 201 Living Room 1 22.6 Jul 1700 2218 12.1 416.0 5.33 202 Dining Room 1 11.9 Sep 1600 1172 7.4 91.0 12.88 203 Bar 1 4.5 Jul 1500 439 2.5 274.0 1.60 204 TV Nook 1 12.9 Jul 1700 1272 9.0 248.0 5.13 205 Powder 1 1.3 Jul 1400 128 1.0 40.0 3.21 206 Kitchen 1 23.5 Aug 1400 2309 5.5 340.0 6.79 207 Nook 1 10.0 Jul 1700 987 8.0 97.0 10.17 208 Pantry 1 1.0 Aug 1500 101 1.2 49.0 2.06 209 Hall 1 1.5 Jul 1500 143 1.9 25.0 5.72 RECEIVED 10/16/2017 Hourly Analysis Program v4.50 ASPEN 2 BUILDING DEPARTMENT REScheck Software VersionChecklist 4.6.2 Li Energy Code: 2015 IECC Requirements: 0.0% were addressed directly in the REScheck software Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section Plans Verified Field Verified # Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions & Req.ID 103.1, Construction drawings and EComplies 103.2, documentation demonstrate ❑Does Not 403.7 energy code compliance for [PR3]1 lighting and mechanical systems. ENot Observable ,0 Systems serving multiple ❑Not Applicable dwelling units must demonstrate compliance with the IECC Commercial Provisions. 302.1, Heating and cooling equipment is Heating: Heating: '❑Complies 403.7 sized per ACCA Manual S based Btu/hr Btu/hr ❑Does Not [PR2]z on loads calculated per ACCA Cooling: Cooling: Manual J or other methods ENot Observable Btu/hr Btu/hr approved by the code official. ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) RECEIVED Project Title: Report dzito/I2$0/2.017 Data filename: Untitled.rck Page 1 of 5 ASPEN BUILDING DEPARTMENT Section # Foundation Inspection Complies? Comments/Assumptions & Req.ID 403.9 :Snow-and ice-melting system controls 11=1Complies [F012]2 installed. ❑Does Not J ['Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J RECEIVED Project Title: Report dzit0/312$O,R .O17 Data filename: Untitled.rck Page 2 of 5 ASPEN BUILDING DEPARTMENT Section Plans Verified Field Verified # Framing /Rough-In Inspection Value Value Complies? Comments/Assumptions & Req.ID 403.2.1 Supply and return ducts in attics '❑Complies [FR12]1 insulated >= R-8 where duct is ❑Does Not 1e >= 3 inches in diameter and >= ['Not Observable R-6 where < 3 inches. Supply and return ducts in other portions of ❑Not Applicable the building insulated >= R-6 for diameter>= 3 inches and R-4.2 for< 3 inches in diameter. 403.3.3.5 ;Building cavities are not used as ❑Complies [FR15]3 iducts or plenums. ❑Does Not ❑Not Observable ❑Not Applicable 403.4 :HVAC piping conveying fluids R- R- ❑Complies [FR17]2 above 105 °F or chilled fluids ❑Does Not 4./, below 55 °F are insulated to >_R- 3 ❑Not Observable 1 ❑Not Applicable 403.4.1 :Protection of insulation on HVAC ❑Complies [FR24]1 piping. ❑Does Not d ; ❑Not Observable ❑Not Applicable 403.5.3 Hot water pipes are insulated to R- R- ❑Complies [FR18]2 >_R-3. ❑Does Not 0. ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J RECEIVED Project Title: Report d10/1260/H17 Data filename: Untitled.rck Page 3 of 5 ASPEN BUILDING DEPARTMENT Section Plans Verified Field Verified # Final Inspection Provisions Value Value Complies? Comments/Assumptions & Req.ID 403.2.3 :Duct tightness test result of<=4 cfm/100 cfm/100 '❑Complies [F14]1 cfm/100 ft2 across the system or ft2 ft2 ❑Does Not i<=3 cfm/100 ft2 without air ENot Observable j handler @ 25 Pa. For rough-in :tests, verification may need to ENot Applicable ,occur during Framing Inspection. 403.3.2 Ducts are pressure tested to cfm/100 cfm/100 ❑Complies [F127]1 determine air leakage with : ft2 ft2 ❑Does Not either: Rough-in test:Total leakage measured with a ❑Not Observable pressure differential of 0.1 inch ❑Not Applicable w.g. across the system including the manufacturer's air handler enclosure if installed at time of test. Postconstruction test:Total leakage measured with a pressure differential of 0.1 inch :w.g. across the entire system :including the manufacturer's air handler enclosure. 403.3.2.1 :Air handler leakage designated ❑Complies [F124]1 :by manufacturer at<=2%of ❑Does Not ;design airflow. ❑Not Observable ❑Not Applicable 403.1.1 :Programmable thermostats EComplies [F19]2 installed for control of primary ❑Does Not 41 heating and cooling systems and initially set by manufacturer to ❑Not Observable code specifications. ❑Not Applicable i 403.1.2 :Heat pump thermostat installed ❑Complies [FI10]2 on heat pumps. ❑Does Not : ❑Not Observable ❑Not Applicable 403.5.1 :Circulating service hot water ❑Complies [F111]2 11111 systems have automatic or ❑Does Not accessible manual controls. [Not Observable : ❑Not Applicable 403.6.1 :All mechanical ventilation system '❑Complies [F125]2 fans not part of tested and listed ❑Does Not II HVAC equipment meet efficacy and air flow limits. ❑Not Observable i❑Not Applicable 403.2 'Hot water boilers supplying heat '❑Complies [F126]2 through one-or two-pipe heating ❑Does Not systems have outdoor setback control to lower boiler water ❑Not Observable :temperature based on outdoor ❑Not Applicable temperature. 403.5.1.1 'Heated water circulation systems ❑Complies [F128]2 have a circulation pump.The EDoes Not system return pipe is a dedicated return pipe or a cold water supply ENot Observable pipe. Gravity and thermos- ENot Applicable syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Ail 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J GINNED Project Title: Report d10/1260/H17 Data filename: Untitled.rck Page 4 of 5 ASPEN BUILDING DEPARTMENT Section Plans Verified Field Verified # Final Inspection Provisions Value Value Complies? Comments/Assumptions & Req.ID 403.5.1.2 ;Electric heat trace systems '❑Complies [F129]z icomply with IEEE 515.1 or UL ❑Does Not 515. Controls automatically adjust the energy input to the ['Not Observable heat tracing to maintain the ❑Not Applicable desired water temperature in the piping.1403.5. Water distribution systems that ❑Complies [F130]� have recirculation pumps that ❑Does Not pump water from a heated water supply pipe back to the heated [Not Observable water source through a cold ❑Not Applicable water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104°F. 403.5.4 Drain water heat recovery units ❑Complies [F131]2 tested in accordance with CSA ❑Does Not B55.1. Potable water-side pressure loss of drain water heat ❑Not Observable recovery units < 3 psi for ❑Not Applicable individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. 404.1 :75%of lamps in permanent ❑Complies [F16]1 :fixtures or 75%of permanent ❑Does Not ;fixtures have high efficacy lamps. :Does not apply to low-voltage ❑Not Observable lighting. LINot Applicable 404.1.1 :Fuel gas lighting systems have ❑Complies [F123]3 no continuous pilot light. ❑Does Not di ❑Not Observable ❑Not Applicable 303.3 :Manufacturer manuals for ❑Complies [F118]3 mechanical and water heating ❑Does Not El systems have been provided. ❑Not Observable ❑Not Applicable — Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) J RE(,, lEt Project Title: Report dIviiiirpii5 17 Data filename: Untitled.rck Page 5 of 5 ASPEN BUILDING DEPARTMENT HIGH EFFICIENCY BOILERS / 7TM --__ JI F.."'" 4 IRE TUBE BOIL TM S MA R T - S YS T E M : , r, , CON.X.US® REMOTE CONNECT CAPABLE CASCADING SEQUENCER LOCH-N-LINK® USB DRIVE SETUP 5 INPUTS FROM 399,999 TO 850,000 BTU/HR UP TO 10:1 TURNDOWN RATIO COMMON VENT AND PVC DIRECT-VENTING 98% � ( :1 \\ •J CERTIFIED... FLOW RATES FROM 10 TO 150 GPM THERMAL EFFICIENCY* *See back page for efficiency by model SMALL 6.2 SQ. FT. FOOTPRINT 4 PUMP CONTROL WIRELESS OUTDOOR SENSOR CAPABLE hilt DESIGNED*ENGINEERED*ASS' D 1 i)IC-IC e I US 1 � ��4kiii 411 HIGH EFFICIENCY BOILERS&WATER HEATERS LOChinvart'cm 6/2 ASPEN - - BUILDING DEPARTMENT iii ..If* TIM .. .._.. FIRE TUBE BOILER THE NEW 98% STANDARD Lochinvar re-defined the fire-tube boiler category with its I<NIGHT®Wall-Mount and CREST® lines. For residential and light commercial applications, the FTXL'""adds models from 399,999 to 850,000 Btu/hr, and takes Lochinvar's fire-tube technology to the next level. FTXL offers best-in-class AHRI Thermal Efficiency and footprints, plus remote connectivity that puts the SMART SYSTEM'" control at your fingertips, anywhere! • l..E:. BS REDUCE INSTALLATION COST WITH '' 7t•-� • VARIABLE FLOW TECHNOLOGY �' .. MICROMETALFIBER BURNER . . FTXL can operate over a wide range of flow rates*with very low pressure drop. DELIVERS HEAT TO THE This permits installation of a"full flow"(variable primary)system eliminating the COMBUSTION CHAMBER time and materials cost of primary/secondary piping,and pumps needed to maintain flow in a water-tube boiler.Variable flow also makes FTXL more flexible • at handling frequent fluctuations in the system flow rate. BAFFLES DIRECTTHE i , i[ *see back page for minimum and maximum flow rates by model. FLOW OF WATER FOR OPTIMAL HEAT TRANSFER SMOOTH-RUNNING, MODULATING COMBUSTION FTXL boilers have a top-mounted,micrometal fiber burner,with a blower/gas WATER ENTERS THE BOTTOM 1�1 AND TRAVERSES UP valve assembly that drives heat energy downward,through stainless steel fire AROUNDAND f FIREi. tubes,with exhaust venting through the bottom of the unit.With up to 10:1 TUBES J modulation turndown,the burner automatically changes its firing rate as building heat loads vary.An FTX500 fires at its maximum 500,000 Btu/hr rateDOWNWARD I when heat load is highest,then gradually"turns down"to as low as 10% DO BASES DFLOW OF FLUE • - 1. i, I (50,000 Btu/hr)as load decreases.A modulating system runs smoothly and TRANSFER HEAT l i efficiently,without frequent on/off cycling. WITHIN FIRETUBES • ' 1, . 1. i • MINIMUM SUPPLY PRESSURE, INSTALLER-FRIENDLY ' FTXL operates with supply gas pressure as low as 4 inches water column. Negative Regulation draws gas into a pre-mix combustion system,instead of relying on utility pressure through the gas valve. The result is steady operation in low gas pressure systems or when peak demand occurs on gas supply. Automatic fan speed control fine-tunes the correct fuel/air ratio entering the burner,providing superior combustion throughout the entire operating range. CON X US® r. INTRODUCING BOILER PLANT CONTROL, FROM ANYWHERE. qLUihrar FTXL features the next generation of Lochinvar's all-in-on SMART SYSTEM operating control with a re-designed multi-co or 2 ..J interface.SMART SYSTEM provides outstanding functionality,and • .` :,.._ .... ) be integrated directly into a Building Automation System via ModBu^ and other communications protocols.And now,the CON•X•US mobile t .. .... , , communication platform allows SMART SYSTEM to go where no other irboiler has gone before.' I ® SMARTSYSTEMM 6 CON•X•US provides the ability to monitor and manage multiple FTXL 1 boiler plants without ever stepping into the mechanical room. CON•X•US will send alerts via text or e-mail notifying of changes in system status, and anytime,from anywhere,a user can check system status and re-program any boiler function.Once downloaded,the free CON•X•US _ mobile application allows for remote access to all SMART SYSTEM functions using any Internet-capable device. ,: - I iL LceNimwr 13457M t 11D7l�017 69 Iti, - l J ,t1. t'1..r.T h ♦ f — 11111r— If ANDROID APP ON • Google play / Download on the tCON-X-US control boa,d solo separately. IIIApp Store See backcover for a complete list of SMART SYSTEM features. HOW 98%TRANSLATES 3 -Year Fuel Savings INTO FTXL SAVINGS $14,000 Even when compared to other S12,000 SAVES$12,400 condensing boilers,the FTXL fire-tube S10,000 combustion system will produce S8,000 significant fuel cost savings.Here are three comparisons,based on building $6,000 load of approximately 19,000 therms/ $4,000 year,at a cost of$1.09 per therm of S2,000 natural gas. SO EFFICIENCY 85% 87% 94% FTXL 98% Fuel savings is based on a heating load of 19,000 therms per year being supplied by an 82%efficient boiler at the DOE National average for natural gas of$1.09. OW ENHANCED MULTI-COLOR WIRELESS LCD INTERFACE lockout OUTDOOR SENSOR Easy to install,greatly reduces time LOCKOUT th and materials cost for running maintenance SYSTEM} DHW TANK sensor wire from standard outdoor 41% A 1 A DHW CIRZZC(� temperature sensor to boiler normal MAR12:170PM C control.Approximate range 2,000 VCTGM(C\ DHW TANK* SW LOCH-N-LINK®EASY USB 55%6 "T` DHW CIRCA feet line-of-sight. Nw = REQUIRED l FLASH PROGRAMMING SYSTEM* DHW TANK* SING & HTG. RESET BOILER() DHW CIRCO i7 Use a USB drive to name,store and SYSTEM: 130°F TANK: 124°F(130) easily manage multiple existing OUTDOOOR: 139°FINLE TEEN SHDN proven parameter sets.Quickly upload OUTLET: 165'F(165) DHW RECIRC 127'F them via the front panel port into the FTXL boiler,reducing installation and MENU •LSETPOINT SHDN programming time by up to 30 minutes per boiler. i - ,, . .VED , -..- , ..,,,.....,.... ..."0,_•• . . IF--;110////1/////////////////////////1" - 10/16/2017 ASPEN BUILDING DEPARTMENT �lJ - _ PEACE OF MIND, WHEN a ,.: • IT MATTERS MOST 1 2 3 4 5 6 I, Up to eight FTXL boilers can be sequenced using a In an Efficiency Optimized system,all boilers fire 2-wire daisy-chain connection.Cascade and modulate simultaneously at the same BTU/hr sequencing can be programmed for"Lead-Lag"or input rates,maximizing thermal efficiency. "Efficiency Optimized"operation. If the lead boiler is turned off for maintenance, With Lead-Lag operation,one lead boiler Cascade Redundancy automatically shifts the lead L' !'4 modulates to capacity on demand.As load role to the second sequenced boiler.Peace of mind increases,the system then cascades to additional comes from knowing the system will still function ro lag boilers in sequence.The first-on role shifts with no downtime until the original lead boiler is I daily,distributing equal runtimes to each unit. back online. 1 till . 111 i A r._ THE SMALLEST FOOTPRINT, EASY TO INSTALL&SERVICE FTXL can be installed with zero clearance on the left and right,and the boiler's installed footprint is just 6.2 sq.ft. All water,gas and vent connections are in the back of the unit.A hinged top opens for easy access to components and the front panel is easily removed using no tools. y 1 OPTIONS, FLEXIBLE VENTING ‘Iiii ' 1 FTXL offers 6 venting options,and e�; e � e,,,/ permits direct-vent air intake and *��/ exhaust runs up to 100 equivalent feet,using PVC,CPVC,polypropylene Room Air Vertical Room Air Sidewall Direct Vent or stainless steel pipe.Plus multiple units can be common-vented to �,, `I 7 I reduce time and materials costs. Ii es I r/ Common Vent Direct-Vent Vertical Vertical w/Sidewall Air TO LEARN MORE, LOG ON TO WWW.FTXLBOILER.C�I:A 1'i ).°.1 FTXL"'BOILER DIMENSIONS AND SPECIFICATIONS* E D Air Inlet Electrical Connections 2-1/2" AL likr11111 a..-gl ---— — : "r_...1C/1(1 li 1).-1 if I--cl,/ \ ® Q . A Ill Gas Connection / F B 65 1/2" 53.1/2" G Water Outlet 40" 1 i Water Inlet 4a ' \Flue Connection 26-1/4" ® —II yH III 9 3/4" -- " 26-1/4" 1:..._. f 2.1/2" Condensate Connection - A 22-1/2 FTXL BOILER ^' OERTifi(iT DIMENSIONS AND SPECIFICATIONS Input Gross NET AHRI HEX Model Min Max Thermal Output Rating Turn Flow(GPM) Water Water Vent Air Gas Shipping Number MBH MBH Efficiency MBH MBH down Min Max Volume A B C D E F G H Conn. Size Intake Conn. Wt.(lbs.) FTX400(N,L) 40.0 399.9 98.0% 392 341 10:1 10 105 13 30-1/2" 27-1/2" 10-1/4" 17" 23-1/4" 46-1/4" 39-1/2" 10-3/4" 2" 4" 4" I" 435 FIX5001N,L) 50.0 500.0 97.7% 489 425 10:1 15 105 12 30-1/2" 27-1/2" 10-1/4" 17" 23-1/4" 46-1/4" 39-1/2" 10-3/4" 2" 4" 4" 1" 460 FIX600(N,L) 85.0 600.0 97.5% 585 509 7:1 15 105 12 30-1/2" 27-1/2" 10-1/4" 17" 23-1/4" 46-1/4" 39-1/2" 10-3/4" 2" 4" 4" 1" 470 F1X7251N,L) 103.5 725.0 97.2% 705 613 7:1 20 150 17 33" 28-1/2" 10-1/2" 17-1/2" 23-1/2" 48-1/2" 41-1/4" 11" 2-1/2" 6" 4" 1" 510 F1X850(N,L) 121.5 850.0 97.0% 825 717 7:1 25 150 16 33" 28-1/2" 10-1/2" 17-1/2" 23-1/2" 48-1/2" 41-1/4" 11" 2-1/2" 6" 4" 1" 535 *Information subject to change without notice Dimensions are in inches. Select"N"or"L"for Natural or LP gas."The Net AHRI Water Ratings shown are based on a piping and pickup allowancof 1.15.*Lochinvar should be consulted before selecting a boiler for installations having unusual piping and pickup requirements,such as intermittent system operation,extensive piping systems,etc.*The ratings have been determined under the provisions governing forced draft burners. SMART SYSTEM FEATURES )Low-Voltage Terminal Strip >Vertical and Horizontal Direct Vent Building Recirculation Pump Start/Stop Direct Vent up to 100 feet >Smart System Digital Operating Control Proving Switch Contacts PVC,CPVC,Polypropylene or AL29-4C Multi-Color Graphic LCD Display w/Navigation Dial Flow Switch Contacts Factory Supplied Sidewall Vent Termination >Loch-N-Link®USB Thumb Drive Port for Easy Alarm Contacts >Smart System Control Programming Runtime Contacts >Other Features >Cascading Sequencer with Built-in Redundancy 3 Space Heat Thermostat Contacts On/Off Switch Selectable Cascade Type: Tank Thermostat Contacts Adjustable High Limit with Manual Reset Lead Lag/Efficiency Optimization System Sensor Contacts Automatic Reset High Limit Multiple Size-Boilers Tank Sensor Contacts Manual Reset Low Water Cutoff Front-End Loading - Cascade Contacts Flue Temperature Sensor • >3 Reset Temperatures Inputs w/Independent Outdoor 0-10 VDC BMS Contacts Low Air Pressure Switch Reset Curves for Each • - 0-10 VDC Boiler Rate Output Contacts Temperature and Pressure Gauge Outdoor Sensor - 0-1.0 VDC Boiler Pump Speed Contacts Condensate Trap >Four-Pump Control 0-10 VDC System Pump Speed Contacts Zero Service Clearances System Pump with Parameter for Continuous Operation ModBus Contacts 10-Year Limited Warranty(See Warranty) Boiler Pump with-Variable-Speed Control - - >Time Clock Custom Maintenance Reminder with Contact Info • Domestic Hot Water Boiler Pump >Data Logging Password Security Domestic Hot Water Recirculation Pump Control Ignition Attempts Customizable Freeze Protection Parameters with Sensor •- . .- • Last 10 Lockouts • >Building Management System Integration Space Heat Run Hours OPTIONAL EQUIPMENT - . 0-10 VDC Input to Control Modulation or Setpoint - Domestic Hot Water Run Hours CON•X-US®Remote Connectivity 0-.10 VDC Input from Variable-Speed System Pum• p - TANDARD FEATURES Motorized Isolation Valve S - 0-10 VDC Modulation Rate-Output Signal Wireless Outdoor Temperature Sensor - • 0-10 VDC Enable/Disable Signal - >97%-98%Thermal Efficiency Multi-Temperature Loop Control >-Programmable System Efficiency Optimizers >Modulating Burner with up to 10:1 Turndown Variable-Speed Boiler Circulator . Space Heating Night Setback Direct Spark Ignition Constant-Speed Boiler Circulator DHW.Night Setback • Low NOx Operation. ModBus Communication • Anti-Cycling � . Alarm Bell Y y Seated Combustion O - Condensate Neutralization Kit .Ramp Delay Low Gas Pressure Operation .Boost Time and Temperature Concentric Vent Kit(FT)(400-FTX600) >Stainless Steel Fire-lirbe Heat Exchanger BMS Gateway to BACnet or LonWorks>High-VoltageTerminal5trip. ASME-Certified;"H"Stamped 120 VAC/60 Hertz/1 Phase High and Low Gas Pressure Switches w/Manual Reset Pump Contacts for 3 Pumps 160 psi Working Pressure (FTX500-FTX850) - - • 50 psi Relief Valve >Firing Controls Combustion Analyzer Test Port M9-Standard Construction Fully Welded Design M13-CSD-1/FM/GE Gap(FTX500-FTX850) r Lochinvar,LLC .��I Gs' �p 0 300 Maddox Simpson Parkway >� /� L �IAA�I`I■iciE�/�cY Lebanon,Tennessee 37090 LO N� ® �^ �� 615.889-89D0,[F:615.547.1000.... to" Mil r 1511t- - HIGH EFFICIENCY BOILERS&WATER HEATERS Ban 1:1 LOchinw.com— • -• - FTXE-01 (Reprint.5/16) - --. • 10M PUP-©Lochinvar;LLC 12/16-Printed in-U.S.A. �� � -. - -- U.S.- . - '-iPhoneand iPod touch are trademarks of Apple Inc:,registered in the an [tiercou�nfr- - -----. - Android andGoogie are trademarks of Google Inc.,registeredjpft{gp ..a n d other cowmiec App Store.is a service mark of Apple Inc.Google Play lfa�ntGMotle lr TMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-1 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH20 LAH003A 230/60/1 1.85 Horizontal Unit Model Number: LAH003A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 47.8 in 22.4 in 34.8 in 359.3 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 2.8 ft2 354.6 ft/min 0.61 inH20 Mean Pressure Drop (1) 18 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 3.0 ft2 333.3 ft/min 16.0 in 27.0 in 0.16 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.125 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 19505 14960 80.0 67.0 61.6 60.6 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 54.8 4.5 7.5 1.7 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 3.0 ft2 333.3 ft/min 16.0 in 27.0 in 0.08 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location .875 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 16751 70.0 130.0 90.9 109.1 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 1.7 0.3 0.6 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 9 in x 9 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 1 HP Open Drip 70 0% 230/60/1 7.3 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK25 1VP34 1 A31 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 1000 1.85 1846 0.72 1190 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 72 71 62 63 67 62 63 Discharge 76 71 72 69 71 66 60 Radiated 71 59 57 53 55 47 38 Internal Pressure Drop Calculation Water Heating Coil: 0.08 inH2O Cooling Coil: 0.16 inH2O Filter: 0.61 inH2O Total Internal Pressure Drop: 0.85 inH2O AHRI Certification AIM CERTIFIED.. r^ All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-2 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH20 LAH003A 230/60/1 2.04 Horizontal Unit Model Number: LAH003A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 47.8 in 22.4 in 34.8 in 362.3 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 2.8 ft2 464.5 ft/min 0.65 inH20 Mean Pressure Drop (1) 18 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 3.0 ft2 436.7 ft/min 16.0 in 27.0 in 0.26 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.125 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 22568 18412 80.0 67.0 62.7 61.4 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 54.3 5.5 9.4 2.1 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 3.0 ft2 436.7 ft/min 16.0 in 27.0 in 0.13 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location .875 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 20001 70.0 130.0 88.8 111.2 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 2.2 0.6 0.9 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 9 in x 9 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 1.5 HP Open Drip 74 0% 230/60/1 10.0 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK26 1VL4OL 1 AX32 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 1310 2.04 1970 1.07 1560 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 75 74 65 66 70 65 66 Discharge 79 74 75 72 74 69 63 Radiated 74 62 60 56 58 50 41 Internal Pressure Drop Calculation Water Heating Coil: 0.13 inH2O Cooling Coil: 0.26 inH2O Filter: 0.65 inH2O Total Internal Pressure Drop: 1.04 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-3 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH20 LAHOO2A 230/60/1 1.91 Horizontal Unit Model Number: LAHOO2A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 47.8 in 20.5 in 28.5 in 255.9 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 2.6 ft2 303.0 ft/min 0.59 inH20 Mean Pressure Drop (1) 16 in x 25 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 2.0 ft2 392.2 ft/min 14.0 in 21.0 in 0.21 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location .875 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 14546 11488 80.0 67.0 62.1 61.0 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 54.4 3.5 5.8 1.5 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 2.0 ft2 392.2 ft/min 14.0 in 21.0 in 0.10 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location .875 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 12650 70.0 130.0 89.7 110.3 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 1.4 0.2 0.6 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 7 in x 7 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 1 HP Open Drip 70 0% 230/60/1 7.3 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK23 1VL4OL 1 A29 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 800 1.91 2591 0.64 1455 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 74 80 70 68 72 69 72 Discharge 81 79 77 72 76 72 71 Radiated 76 67 62 56 60 53 49 Internal Pressure Drop Calculation Water Heating Coil: 0.10 inH2O Cooling Coil: 0.21 inH2O Filter: 0.59 inH2O Total Internal Pressure Drop: 0.91 inH2O AHRI Certification AIM CERTIFIED.. r^ All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-4 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH2O LAHOO5A 230/60/1 1.40 Horizontal Unit Model Number: LAH005A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 58.9 in 28.4 in 56.5 in 562.5 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 7.6 ft2 355.7 ft/min 0.61 inH20 Mean Pressure Drop (2) 24 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 7.3 ft2 368.3 ft/min 22.0 in 48.0 in 0.19 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 45524 37836 80.0 67.0 62.7 61.5 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 53.6 12.0 6.2 1.7 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 7.3 ft2 368.3 ft/min 22.0 in 48.0 in 0.10 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 39863 70.0 130.0 88.2 111.8 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 4.6 0.2 0.6 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 12 in x 12 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 2 HP Open Drip 74 0% 230/60/1 10.0 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK49 1VL44 1 A41 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 2700 1.40 1197 1.38 1862 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 78 72 70 71 69 68 66 Discharge 80 78 80 78 75 73 66 Radiated 75 66 65 62 59 54 44 Internal Pressure Drop Calculation Water Heating Coil: 0.10 inH2O Cooling Coil: 0.19 inH2O Filter: 0.61 inH2O Total Internal Pressure Drop: 0.90 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-5 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH2O LAH003A 230/60/1 1.97 Horizontal Unit Model Number: LAH003A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 47.8 in 22.4 in 34.8 in 359.3 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 2.8 ft2 429.1 ft/min 0.64 inH20 Mean Pressure Drop (1) 18 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 3.0 ft2 403.3 ft/min 16.0 in 27.0 in 0.22 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.125 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 22077 17484 80.0 67.0 62.2 61.0 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 54.1 5.5 9.4 2.1 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 3.0 ft2 403.3 ft/min 16.0 in 27.0 in 0.11 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location .875 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 19045 70.0 130.0 89.4 110.6 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 2.1 0.5 0.8 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 9 in x 9 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 1 HP Open Drip 70 0% 230/60/1 7.3 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK26 1VL4OL 1 A32 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 1210 1.97 1931 0.95 1440 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 74 73 65 65 69 64 65 Discharge 78 74 74 71 73 68 62 Radiated 73 61 59 55 57 49 40 Internal Pressure Drop Calculation Water Heating Coil: 0.11 inH2O Cooling Coil: 0.22 inH2O Filter: 0.64 inH2O Total Internal Pressure Drop: 0.97 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-6 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH20 LAHOO5A 230/60/1 2.07 Horizontal Unit Model Number: LAH005A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 54.7 in 28.4 in 42.5 in 479.5 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 6.3 ft2 397.5 ft/min 0.63 inH20 Mean Pressure Drop (2) 20 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 5.2 ft2 481.7 ft/min 22.0 in 34.0 in 0.30 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 41155 34137 80.0 67.0 63.0 61.6 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 54.0 10.4 14.5 2.9 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 5.2 ft2 481.7 ft/min 22.0 in 34.0 in 0.15 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location .875 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 32805 70.0 130.0 86.3 113.7 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 4.2 0.3 0.6 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 10 in x 10 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 2 HP Open Drip 74 0% 230/60/1 10.0 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK28 1VL4OL 1 AX34 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 2500 2.07 1802 1.96 2427 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 80 76 74 76 78 73 67 Discharge 83 81 82 82 84 78 73 Radiated 78 69 67 66 68 59 51 Internal Pressure Drop Calculation Water Heating Coil: 0.15 inH2O Cooling Coil: 0.30 inH2O Filter: 0.63 inH2O Total Internal Pressure Drop: 1.07 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT 4/26/2017 Enviro-Tec-Selection Summary I tI ENVIRO-TEC Project Name: Sandler Residence Ship Cycle: Standard Shipment Line#: 1 Tag: FC-7 Selection Method:Fixed ESP/Nominal Airflow Elevation:8000 ft Selection Date:4/26/2017 1:31:29 PM Printed Date:4/26/2017 5:24:56 PM ET Coil Version:7.05b Notes:This field is for user purposes only and will not transfer to the order form. General Mfg Filter Model Unit Unit Airflow OA ESP Motor Motor FuIl F an Load MCA MSCP Fan Fan V/P/Hz Motor Weight* FilterType APd Size Capacity (cfm) (cfm) (in.wc) (Hp) RPM Amps Watts Qty Speed (lb) (in.wc) Enviro-Tec HPP 06 Standard 281 0 0.5 1/6 1075 I 1 1.25 15 233 1 208/1/60 High 130 Throwaway 0.01 *Weight does not include accessories. Hiah 0.70-Med ... 4 I I ) 1 I 1 1 0.50-N Low ----__-_---::7-,---User Selection r ' y 0.40- - • - . : 4 77 II .c 0.30- - I t : It 0.20- t 0.10- • • — 0.00 ' r r r r 0 100 200 300 400 500 600 cfm Fan selection and performance is shown at elevation of 8000 ft Chilled Water Coil EAT LAT Total Sensible EWT/LWT Fluid Fluid Fluid Air PD Coil Coil No. Conn. Tube Pct Fluid DBIWB DBIWB Capacity Capacity (deg.F) Flow pD(ft.) Velocity (in.wc) Rows FPI Circuits Size Dia. Glycol Type (deg.F) (deg.F) (Btuh) (Btuh) (gpm) (fps) (in.) 58.3/ I Water w/ 75/63 55.4 5565 3735 45/54.9 1.40 4.83 1.4 0.08 6 12 4 7/8" 3/8 50 Propylene Glycol Hot Water Coil Sensible Fluid Fluid Fluid r— Tube EAT DB LAT DB Capacity EWT/LWT Flow PD Velocity Air PD Coil Coil No. Conn. Dia. Pct Fluid (deg.F) (deg.F) (Btuh) (deg.F) (gpm) (ft.) (fps) (in.wc) Rows FPI Circuits I Size (in.) Glycol Type Water w/ 70 105.4 7925 130/110 0.70 0.87 1.1 0.03 2 12 2 5/8" 3/8 30 Propylene Glycol Sound Data at High Fan Speed Band , 2 3 4 5 6 7 I 8 Frequency 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Total 68 63 58 57 52 46 42 I • Unit data is certified in accordance with AHRI-440. • HPP Sound data supplied for casing radiated,ducted supply,and ducted return.Total sound power level data based on Horizontal Concealed Plenum Return Model with fan CFM at corresponding motor tap with 115/1/60 volt PSC motor,4 row coil,1"throwaway filter,unit standard insulation,0.25"external static pressure and standard rated internal pressure losses. • Unit pressure drop and CFM based upon dry coil as required byAHRI-440. • Scheduled motor information is for Hi Speed. • The coil selection has been made at Standard conditions. • Outside Airflow is a user input value for scheduling purposes. RECEIVED 10/16/2017 http://www.enviro-tec.com/selection/fcu.asp?action=print_selection&lineitem i d=3019077&sound=sel ect&N oCache=0%2E3849874 ASPEN 1/ BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-8 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH2O LAHOO7A 230/60/1 1.43 Horizontal Unit Model Number: LAHOO7A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 58.9 in 28.4 in 56.5 in 565.5 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 7.6 ft2 375.5 ft/min 0.62 inH20 Mean Pressure Drop (2) 24 in x 24 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 7.3 ft2 388.8 ft/min 22.0 in 48.0 in 0.21 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 49366 40380 80.0 67.0 62.6 61.3 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 52.5 15.0 8.0 2.1 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 7.3 ft2 388.8 ft/min 22.0 in 48.0 in 0.11 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 41173 70.0 130.0 87.8 112.2 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Propylene Glycol 30.0 4.9 0.3 0.7 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 12 in x 12 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 1.5 HP Open Drip 74 0% 230/60/1 10.0 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number AK44 1VL4OL 1 A40 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 2850 1.43 1211 1.49 1966 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 78 72 70 71 70 68 66 Discharge 80 79 80 78 75 73 67 Radiated 75 67 65 62 59 54 45 Internal Pressure Drop Calculation Water Heating Coil: 0.11 inH2O Cooling Coil: 0.21 inH2O Filter: 0.62 inH2O Total Internal Pressure Drop: 0.93 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Destiny® Air Handler ' DAIKIN Job Information Technical Data Sheet Job Name Sandler Residence Date 4/26/2017 111111111111 Submitted By David Denio Software Version 05.80 Unit Tag FC-9 Unit Overview Model Number Voltage Airflow Static Pressure Unit Configuration V/Hz/Phase CEM External Total inH20 inH2O LAH010A 208/60/3 1.59 Horizontal Unit Model Number: LAH010A Type: Indoor Air Handler Configuration Horizontal construction: Double-wall construction with foam injected insulation Approval: AHRI, ETL,CETL& MEA Physical Unit Length Height Width Weight 58.9 in 32.5 in 63.0 in 682.0 lb Unit Construction Outer Panel Inner Liner Insulation Frame Access Removable panels Galvanized Steel Galvanized steel 1 inch Expanded Foam 1 inch Aluminum access;Side filter and fan Filter Type Face Area Filter Face Velocity Air Pressure Drop Air Pressure Drop Type (Quantity)Height x Width x Depth Pleated(MERV 8) 10.0 ft2 462.3 ft/min 0.65 inH20 Mean Pressure Drop (3) 20 in x 25 in x 2 in RECEIVED 10/16/2017 Page 1 of 3 www.DaikinApplied.com BUILDING DEPARTMENT Destiny® Air Handler VDAIKIN Chilled Water Cooling Coil Physical Fins per Inch Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 4 9.8 ft2 471.8 ft/min 26.0 in 54.0 in 0.29 inH20 Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized steel casing Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Drain Pan Material Connection Secondary Connection Microbial resistant coated galvanized 1 in ID MPT 1/2 in ID MPT Performance Capacity Air Temperature Total Sensible Entering Leaving Btu/hr Btu/hr Dry Bulb Wet Bulb Dry Bulb Wet Bulb °F °F °F °F 68893 60639 80.0 67.0 63.8 62.1 Fluid Type Glycol Entering Leaving Flow Rate Pressure Drop Velocity Concentration Temperature Temperature gpm ft H2O ft/min Propylene 50.0 45.0 53.1 19.3 9.9 2.3 Glycol Heat Coil Physical Fins per Inch Number of Rows Face Area Face Velocity Fin Height Fin Length Air Pressure Drop 12 2 9.8 ft2 471.8 ft/min 26.0 in 54.0 in 0.15 inH2O Material Fin Tube Header Casing .0060 in Aluminum .013 in Copper Copper Galvanized Connection Size Type Location 1.625 in OD Copper Sweat Drive Side Performance Total Capacity Temperature Btu/hr Entering Leaving Air Dry Bulb Fluid Air Dry Bulb Fluid °F °F °F °F 70555 70.0 130.0 88.9 111.1 Fluid Type Glycol Concentration Flow Rate Pressure Drop Velocity gpm ft H2O ft/min Ethylene Glycol 30.0 8.0 0.5 1.0 RECEIVED 10/16/2017 Page 2 of 3 www.DaikiAAp{�Ji&d.com BUILDING DEPARTMENT Destiny® Air Handler VDA/KIN Supply Fan Fan Type Class Wheel Diameter Orientation Vibration Isolation Forward Curved Class 1 12 in x 12 in Top Horizontal CCW Rubber in Shear Rotation Motor Horsepower Type Efficiency Voltage Full Load Current Drive Side VFD 5 HP Open Drip 89 5% 208/60/3 15.7 A Left Hand 60 Hz Proof V/Hz/Phase Drive Package Data Sheaves Belts Fan Motor Quantity Part Number BK57 1VP50L 1 BX44 Note: Daikin Applied reserves the right to provide a different but equivalent drive package Performance Air Flow Total Static Pressure Fan Speed Brake Horsepower Outlet Velocity Altitude CFM inH2O RPM HP ft/min ft 4600 1.59 1382 3.50 3172 8000 Sound Sound Power(db) Frequency 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Inlet 88 82 80 81 80 78 76 Discharge 90 89 90 88 85 83 77 Radiated 85 77 75 72 69 64 55 Internal Pressure Drop Calculation Water Heating Coil: 0.15 inH2O Cooling Coil: 0.29 inH2O Filter: 0.65 inH2O Total Internal Pressure Drop: 1.09 inH2O AHRI Certification NMI CERTIFIED- -----, All equipment is rated and certified in accordance with AHRI 430. Notes RECEIVED 10/16/2017 Page 3 of 3 www.DaikipA(�pJi&d.com BUILDING DEPARTMENT Multi TM • M H WW-36-H -1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 36,000 BTUH RECEIVED RelQ/16/2017 ASPEN BUILDING DEPARTMENT Multi aqua Chilled Water Air Conditioning Systems HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 36,000 BTUH Multiaqua Model Number: MHWW-36-H-1 Part 1-General 1.01 System Description Multiaqua Chilled Water Fan Coils are manufactured with high impact molded polymers. 1.02 Quality Assurance A. Certified in accordance with U.L. Standard 95,latest version (U.S.A.) B. Manufactured in a facility registered to ISO 9002,Manufacturing Quality Standard. C. Fully load tested at the factory. D. Damage resistant packaging. 1.03 Delivery,Storage and Handling A. Packaged and readied for shipment from the factory. B. Controls shall be capable of withstanding 150°F storage temperatures in the control compartment. C. Stored and handled per manufacturer's recommendations. Part 2-Product 2.01 Equipment A. General: 1. Unit shall be a factory assembled and tested chilled and hot water fan coil. 2. Shall be assembled with high quality. 3. Contained with the unit shall be all factory wiring,piping,associated controls and special accessories required prior to start up. B. Unit Cabinet: 1. Composed of high impact polymers. 2. Shall be internally insulated to ensure quiet operation. C. Fan Motors: 1. Shall be 208/230-1-50/60 VAC. 2. Fan motors shall be three speed,direct drive,and PSC type. 3. Totally enclosed. 4. Internal overload protected. 5. Unit shall contain a swing motor to modulate the discharge air. D. Blower Wheels: 1. Blower wheels are dynamically balanced. E. Water Coil: 1. Manufactured with water coils containing 3/8"copper tubing mechanically bonded to aluminum fins. 2. Coils shall be factory tested to 300 psig. 3. Maximum inlet water temperature 160 F. F. Drain Pan: 1. All drain pans shall be molded with high impact polymers. 2. The exterior of all drain pans shall be insulated with closed cell insulation to prevent condensation. 3. Pans shall contain flexible drain tubing that is accessible from the back of the unit. G. Filters: 1. Unit shall contain washable filters. RECEIVED These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. 10/16/2 017 2 ASPEN BUILDING DEPARTMENT MUD&aqua Chilled Water Air Conditioning Systems Part 3-Controls and Safeties 3.01 Controls A. Fan coils shall be completely factory wired and tested. B. Controls shall include a circuit board,room sensor,indoor coil thermistor,transformer and wireless remote. C. Controls shall be capable of incorporating an optional hard-wired thermostat. 3.02 Safeties: A. Fan coil shall contain a non reusable fuse on the secondary voltage side of the transformer. Part 4-Operating Characteristics: 4.01 Electrical Requirements A. Unit shall be supplied with a three prong male primary electrical power cord. B. Electrical power supply shall be rated to withstand 120°F operating ambient temperatures. Part 5-Definitions: 5.01 Abbreviations A. CFM=Cubic Feet per Minute B. DB=Dry Bulb Temperature C. EWT=Entering Water Temperature D. GPM=US Gallons Per Minute E. MBH=BTU X 1000 F. SC=Sensible Cooling G. TC=Total Cooling=Sensible+Latent H. WB=Wet Bulb Temperature I. WPD=Water Pressure Drop in feet of head J. dB=Decibel Level K. m=Meter L. In=Inches M.FPI=Fins per Inch N. OD=Outside Diameter O. ID=Inside Diameter P. MCA=Minimum Circuit Amps Q. MOP=Maximum Over current Protection R. LBS=Pounds U.S. 5.02 Measurements A.All measurements with regard to length,width,and height shall be in inches. RECEIVED These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. 10/16/2 017 3 ASPEN BUILDING DEPARTMENT MU�ttia Chilled Water Air Conditioning Systems MHWW-36-H-1 Product Specifications Physical Data Cooling Copper Water Water Model Number Height Length (in) Depth (in) Weight Rows Diameter Inlet Outlet Drain (in) (Ibs) FPI (in) (in) (in) (in) MHWW-36-H-1 14.25 56.50 8.37 50.50 3-18 3/8 3/4 3/4 3/4 Electrical Data Fuse or HACR High Volts/ Fan Full Load Circuit Breaker Per Model Number Speed Phase/ Circuit Motor Ampacity CFM Hertz HP MCA MOP MHWW-36-H-1 850 0 1/12 0.42 .53 5 co 00 O N RECEIVED 10/16/2017 These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. ASPEN 4 BUILDING DEPARTMENT Ivlllltua. Chilled Water Air Conditioning Systems MHWW-36-H-1 Chilled Water Performance Data MHWW-36-H-1 COOLING CAPACITIES CFM ET GPM ENTERING AIR TEMPERATURE (°F) (°F) 80°D.B./67°W.B. TC 37523 8.0 SC 25156 WPD 17.9 TC 38146 8.5 SC 25427 850* 42 WPD 20.0 TC 38711 9.0 SC 25687 WPD 22.3 TC 39207 9.5 SC 25916 WPD 24.7 *High Speed MHWW-36-H-1 COOLING CAPACITIES CFM EWT GPM ENTERING AIR TEMPERATURE (°F) ( F) 80°D.B./67°W.B. TC 33331 8.0 SC 23304 WPD 17.8 TC 33960 8.5 SC 23585 850* 45 WPD 19.9 TC 34428 9.0 SC 23798 WPD 22.2 TC 34975 9.5 SC 24085 WPD 24.5 *High Speed Recommended minimum flow rate for this unit at > 2fps is 3.5 gpm Recommended maximum flow rate for this unit at < 6fps is 9.5 gpm RECEIVED 10/16/2017 These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. ASPEN 5 BUILDING DEPARTMENT MUltitaqua Chilled Water Air Conditioning Systems MHWW-36-H-1 Hot Water Performance Data This heating performance data is at dry bulb temperature indicated/wet bulb temperature not considered MHWW-36-H-1 HEATING CAPACITIES ENTERING CFM GPM WPD ENTERING WATER TEMPERATURE(°F) AIR (°F) 90° 100° 110° 120° 130° 140° 150° 160° 8.0 16.6 30234 37876 45545 53235 60914 68662 76392 84131 50 850 8.5 18.6 30427 38114 45827 53560 61309 69070 76842 84622 9.0 20.7 30599 38326 46078 53848 61634 69433 77241 85057 9.5 22.9 30753 38516 46302 54106 61926 69757 77598 85446 MHWW-36-H-1 HEATING CAPACITIES ENTERING CFM GPM WPD ENTERING WATER TEMPERATURE(°F) AIR (°F) 90° 100° 110° 120° 130° 140° 150° 160° 8.0 16.6 22700 30324 37977 45652 53345 61054 68774 76504 60 850 8.5 18.6 22843 30513 38210 45929 53665 61416 69178 76949 9.0 20.7 22971 30682 38418 46175 53949 61737 69836 77343 9.5 22.8 23086 30832 38603 46395 54203 62024 69855 77695 MHWW-36-H-1 HEATING CAPACITIES ENTERING CFM GPM WPD ENTERING WATER TEMPERATURE(°F) AIR (°F) 90° 100° 110° 120° 130° 140° 150° 160° 8.0 16.5 15159 22767 30404 38065 45746 53443 61154 68875 70 850 8.5 18.5 15254 22907 30589 38294 46019 53759 61511 69274 9.0 20.6 15338 23033 30754 38498 46261 54038 61828 69627 9.5 22.8 15414 23145 30902 38681 46477 54288 62111 69943 MHWW-36-H-1 HEATING CAPACITIES ENTERING CFM GPM WPD ENTERING WATER TEMPERATURE(°F) AIR (°F) 90° 100° 110° 120° 130° 140° 150° 160° 8.0 16.5 7612 15203 22824 30472 38140 45827 53527 61239 80 850 8.5 18.5 7659 15295 22962 30654 38367 46096 53839 61592 9.0 20.6 7700 15378 23085 30816 38567 46335 54115 61906 9.5 22.7 7737 15452 23195 30961 38747 46548 54361 62185 Heating at ANSI/AHRI 440 with addendum 1,6.3.2 Table 1 as follows ENTERING AIR GPM ENTERING WATER TEMPERATURE TEMPERATURE 140°F 8.0 53967 70°F DB/60°F WB 8.5 54293 9.0 54581 9.5 54839 RECEIVED 10/16/2017 These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. ASPEN BUILDING DEPARTMENT MU�ti��t�a Chilled Water Air Conditioning Systems MHWW-36-H-1 Sound Data _ MODEL# MHWW-36-H-1 Fan Speed dB @ 1 m H 43 M 42 L 40 RECEIVED 10/16/2017 These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. ASPEN BUILDING DEPARTMENT Mulaqtla Chilled Water Air Conditioning Systems `. .....) MHWW-36-H-1 Dimensional Drawing CD 1 K C y w o0 o, m . c = r a o f 0D o v co t bp �I 0 • - 0 c 0 j c 3 cpD 41. m m Ian a) -o — N m � � � c = 0 OCT 3Xm1 CD w 0 f I n NNo W C- _ DOn. 2 m v 5. N ` to cn m C31 00 RECEIVED 10/16/2017 These specifications are subject to change without notice. Check www.multiaqua.com for the latest information. ASPEN BUILDING DEPARTMENT