HomeMy WebLinkAboutFile Documents.311 Park Ave.0319.2017 (2).ARBK BuildingCommentl Advanced+Glazing+Technology+Sheet.pdf(1) i ,VE Subject: PlanCheck --' The U value requirement is for=' °' Page Label: 2 q a�. ,•.. n.. ME Author:justinh the entire assembly, not just File Name: Advanced+Glazing+Technology+Sheet.pdf center of glass which is what this spec is showing. Provide documentation that the entire assembly will meet the required w U value. Architectural Permit Set.311 Park Ave.2017.12.pdf(19) p q', , Subject: PlanCheck '� — a Page Label: 9 You are marking multiple areas '- -- Author:justinh as exterior covered areas that =-:.---:it,' a IL' File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf are not actually covered in both . the existing and proposed gross g -._.- -.Z.°,7 :47 4.._.. ..sr__ b area plans. Revise your -° ------ °--° - drawings and tables to correctly show gross floor area as defined p p . °'' `.. p q, in the IRC/IBC. Provide total i �, gross in both the existingand 1r� proposed tables. Subject: PlanCheck Page Label: 19 Provide cutsheets on the glass flooring that shows compliance lir,williprIfii,� %\, Author:justinh with table R301.5 for loading File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf „'_o .._, requirements and a detail i i N 1 t _ showing how the assembly is to � be attached to the flooring • SE—, system. _o«w i® = - - Subject: PlanCheck Provide a detail for the new wall. W �wi =T �,-. Page Label: 19 Reference that detail in all ° } ^ Author:justinh l �,� o applicable areas for the main ��, File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf pp oa ,-- 11®./k,_- .0 and upper levels. Be sure to ��f l show a compliant air barrier. _ Detail or note how this air barrier ° °� ,b b will be tied into the existing _, w" construction and dissimilar �e,.�a .... materials such as at the foundation and roof. Subject: PlanCheck W-2 is an interior foundation wall - Page Label: 20 per your details. Provide the �'4 Author:justinh File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf proper reference and wall detail tl��l 1 for this location. b Subject: PlanCheck �——— g You appear to have a break in ,'n�l,�'ll Page Label: 23 the guard here that would allow °° -111 Author:justinh ere.n°t" a ---- _ the passage of a 4"sphere. s sea°a o .- File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf Please clarify what you are m _ II III: III a ��II III showing here,this does not °'°°°'mow '`i'A III appear to comply with the IEEE - =_ = requirements for a guard as EEi o��� � shown. = T- NI Subject: PlanCheck =_i_=_=__=_ =Mall Page Label: 23 Label these windows as you Ili Authorjustinh have others on the elevations. °ai oni11.111=1,- ..-..I File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf 4;1 Inl! :, _- Subject: PlanCheck Label all new windows and I,�� �I Page Label: 24 Iire « g doors on the elevations. Author:justinh II ��1 File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf IT iI° ): e.,ntol. 1 �1. 1h Subject: PlanCheck aiM �L. �II You appear to have a break in �II Page Label: 24 FAR,.appearto have a break intheguard Ili the guard here that would allow 1�=here that would allow the passage of a 4' —II I Author:justinh ;,sphare Peo:',,a ywhatyo°a,eehewing �■I I11 the passage of a 4"sphere. ��enrer "men00foragu°B assho n There File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf Iy requirements oraguaNasshown.There �9 Please clarify what you are rI i tar situation on the main level guartl II tlirectly below this location a w II. Rill I.�1 1.1 1-� .�, ,.,I ME showinghere,this does not I�I �I:I`_�I_ ;, appear tocomply with the 1i___= = M' requirements for a guard as = ==_!=ilk:= i � `,�_ shown. There is a similar I' ��pr situation on the main level guard directly below this location as well. Subject: PlanCheck o Revise or clarify why you are 11111k.._ Reme or clarify why Page Label: 25 showing a gap in the guard here. iiiii iiiike,you are showing a gap Author:justinh the guard here `\ File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf = . _' Ii"1111 II II�.III 11,.► III ---1 ____ Subject: PlanCheck Page Label: 28 Dimension the typical open riser --,o ;t `-. - Author:justinh to show that a 4"sphere cannot ® File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf pass through. Dimension the typical _open riser to show that a 4"sphere cannot pass through. kos � NvAtA eA. L I — Subject: PlanCheck i Page Label: 28 Clearly show in the enlarged i o Author:justinh detail and the enlarged plan view - File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf how the handrail terminates at the lower level landing and Clearly ahew,n„< upper level landing per rgeee<tail and Me 1 anlarg1°,1m<w - R311.7.8.2. rssw t6ane2il I t<rminar<satth<mwar level lantling antl upper level lantling Per R3^1118.2. - Subject: PlanCheck Page Label: 28 Your stair configuration does not ! work,the top riser at each level Author:justinh Ill '.4v, File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf is only 5.75", R311.7.5.1 only allows for 3/8"of variance in ^• ^� riser height. The handrail height at the top riser also does not only 5.75"1woynaxiveri5.omva s L comply with R311.7.8.1 as it s 6 18 exceeds the maximum height of 38". I I Subject: PlanCheck 1 This opening must not allow the Page Label: 28 „will, Ip Author:justinh passage of a 6"sphere, it does 4 ' File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf not as currently shown. Please revise. This opening must not allow the passage of A a 6"sphere,it does not as currently shown. Please revise. C, Subject: PlanCheck Is this a glass guard in-fill? If so, Page Label: 28 Author:justinh provide a spec on the glass Is this a glass guard File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf guard system that shows in-fill?If so,provide a - compliance with COA spec on the glass i guard system that 8.16.020(s)and table R301.5. shows compliance with COA 8.16.020(s)and I table R301.5. Subject: PlanCheck Page Label: 30 This does not meet prescriptive -, - Author:justinh insulation values nor is it R-21 File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf as you have it labeled. Revise to comply. OFTAI ,...,,' A-5 Subject: PlanCheck Page Label: 30 Provide documentation of class E,tt, Author:justinh a roof assembly(UL listing, ESR File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf report, etc.) Subject: PlanCheck Page Label: 32 Identify windows for emergency Identify windows for Author:justinh escape egress on the schedule. emergency escape File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf These windows need to be egress on the schedule. shown as operable on both the These windows need to schedule and elevations. be shown as operable on both the schedule and elevations. Subject: PlanCheck Page Label: 32 .55 is the maximum U value allowed for a residential skylight ICI Ell Ell justinh� �� File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf by R402.1.2 of the IECC. Please revise. — 10 111111 iglu DI a A-6 Subject: PlanCheck Page Label: 33 The door to the garage from the Author:justinh residence must comply with File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf R302.5.1. Specify the door material/fire rating and note the ®®M®® requirement for a self-closing device. �� DI DI I u ® = A-602 Special Inspection and Testing Agreement.311 Park Ave.2017.12.pdf(1) Subject: PlanCheck Page Label: 3 You are missing several . '°. Author:justinh signatures on the special aec,nh°. inspection form. File Name: Special Inspection and Testing Agreement.311 _.. Park Ave.2017.12.pdf