HomeMy WebLinkAboutFile Documents.311 Park Ave.0319.2017 (2).ARBK BuildingCommentl
Advanced+Glazing+Technology+Sheet.pdf(1)
i ,VE Subject: PlanCheck
--' The U value requirement is for=' °' Page Label: 2 q
a�. ,•.. n.. ME Author:justinh the entire assembly, not just
File Name: Advanced+Glazing+Technology+Sheet.pdf center of glass which is what this
spec is showing. Provide
documentation that the entire
assembly will meet the required
w
U value.
Architectural Permit Set.311 Park Ave.2017.12.pdf(19)
p q', , Subject: PlanCheck
'� — a Page Label: 9 You are marking multiple areas
'- -- Author:justinh as exterior covered areas that
=-:.---:it,' a IL' File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf are not actually covered in both
. the existing and proposed gross
g -._.- -.Z.°,7 :47 4.._.. ..sr__
b area plans. Revise your
-° ------ °--° - drawings and tables to correctly
show gross floor area as defined
p p . °'' `.. p q, in the IRC/IBC. Provide total
i �, gross in both the existingand
1r�
proposed tables.
Subject: PlanCheck
Page Label: 19 Provide cutsheets on the glass
flooring that shows compliance
lir,williprIfii,� %\, Author:justinh with table R301.5 for loading
File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf
„'_o .._, requirements and a detail
i i N 1 t
_ showing how the assembly is to
� be attached to the flooring
• SE—, system.
_o«w
i® =
- - Subject: PlanCheck
Provide a detail for the new wall.
W �wi =T �,-. Page Label: 19 Reference that detail in all
° } ^ Author:justinh
l �,� o applicable areas for the main
��, File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf pp
oa ,-- 11®./k,_- .0 and upper levels. Be sure to
��f l show a compliant air barrier.
_ Detail or note how this air barrier
° °� ,b b will be tied into the existing
_, w" construction and dissimilar
�e,.�a .... materials such as at the
foundation and roof.
Subject: PlanCheck W-2 is an interior foundation wall
- Page Label: 20 per your details. Provide the
�'4 Author:justinh
File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf proper reference and wall detail
tl��l 1 for this location.
b
Subject: PlanCheck
�——— g You appear to have a break in
,'n�l,�'ll Page Label: 23 the guard here that would allow
°° -111 Author:justinh
ere.n°t" a ---- _ the passage of a 4"sphere.
s sea°a o .- File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf
Please clarify what you are
m _ II III: III
a ��II III showing here,this does not
°'°°°'mow '`i'A III appear to comply with the
IEEE - =_ = requirements for a guard as
EEi o��� � shown.
= T- NI
Subject: PlanCheck
=_i_=_=__=_ =Mall Page Label: 23 Label these windows as you
Ili Authorjustinh have others on the elevations.
°ai oni11.111=1,- ..-..I File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf
4;1 Inl!
:,
_- Subject: PlanCheck Label all new windows and
I,�� �I Page Label: 24
Iire « g doors on the elevations.
Author:justinh
II ��1 File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf
IT iI° ):
e.,ntol. 1
�1.
1h Subject: PlanCheck
aiM �L. �II You appear to have a break in
�II Page Label: 24
FAR,.appearto have a break intheguard Ili the guard here that would allow
1�=here that would allow the passage of a 4' —II I Author:justinh
;,sphare Peo:',,a ywhatyo°a,eehewing �■I I11 the passage of a 4"sphere.
��enrer "men00foragu°B assho n There File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf
Iy requirements oraguaNasshown.There �9 Please clarify what you are
rI i tar situation on the main level guartl
II tlirectly below this location a w II.
Rill I.�1 1.1 1-�
.�, ,.,I ME showinghere,this does not
I�I �I:I`_�I_ ;, appear tocomply with the
1i___= = M' requirements for a guard as
= ==_!=ilk:=
i � `,�_ shown. There is a similar
I' ��pr situation on the main level guard
directly below this location as
well.
Subject: PlanCheck
o Revise or clarify why you are
11111k.._ Reme or clarify why Page Label: 25 showing a gap in the guard here.
iiiii iiiike,you are showing a gap Author:justinh
the guard here
`\ File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf
= . _'
Ii"1111 II
II�.III 11,.►
III ---1 ____
Subject: PlanCheck
Page Label: 28 Dimension the typical open riser
--,o ;t `-. - Author:justinh to show that a 4"sphere cannot
® File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf pass through.
Dimension the typical
_open riser to show that
a 4"sphere cannot
pass through.
kos
� NvAtA eA. L I — Subject: PlanCheck
i Page Label: 28 Clearly show in the enlarged
i o Author:justinh detail and the enlarged plan view
- File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf how the handrail terminates at
the lower level landing and
Clearly ahew,n„< upper level landing per
rgeee<tail and Me
1 anlarg1°,1m<w - R311.7.8.2.
rssw t6ane2il
I t<rminar<satth<mwar
level lantling antl
upper level lantling Per
R3^1118.2.
- Subject: PlanCheck
Page Label: 28 Your stair configuration does not
! work,the top riser at each level
Author:justinh
Ill '.4v,
File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf is only 5.75", R311.7.5.1 only
allows for 3/8"of variance in
^• ^� riser height. The handrail height
at the top riser also does not
only 5.75"1woynaxiveri5.omva s
L comply with R311.7.8.1 as it
s 6 18 exceeds the maximum height of
38".
I
I Subject: PlanCheck
1 This opening must not allow the
Page Label: 28
„will,
Ip Author:justinh passage of a 6"sphere, it does
4 ' File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf not as currently shown. Please
revise.
This opening must not
allow the passage of
A a 6"sphere,it does
not as currently
shown. Please revise.
C,
Subject: PlanCheck Is this a glass guard in-fill? If so,
Page Label: 28
Author:justinh provide a spec on the glass
Is this a glass guard
File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf guard system that shows
in-fill?If so,provide a - compliance with COA
spec on the glass i
guard system that 8.16.020(s)and table R301.5.
shows compliance with
COA 8.16.020(s)and I
table R301.5.
Subject: PlanCheck
Page Label: 30 This does not meet prescriptive
-, - Author:justinh insulation values nor is it R-21
File Name:Architectural Permit Set.311 Park Ave.2017.12.pdf as you have it labeled. Revise
to comply.
OFTAI
,...,,' A-5
Subject: PlanCheck
Page Label: 30 Provide documentation of class
E,tt, Author:justinh a roof assembly(UL listing, ESR
File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf report, etc.)
Subject: PlanCheck
Page Label: 32 Identify windows for emergency
Identify windows for Author:justinh escape egress on the schedule.
emergency escape File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf These windows need to be
egress on the schedule. shown as operable on both the
These windows need to schedule and elevations.
be shown as operable
on both the schedule
and elevations.
Subject: PlanCheck
Page Label: 32 .55 is the maximum U value
allowed for a residential skylight
ICI Ell Ell
justinh� �� File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf by R402.1.2 of the IECC.
Please revise.
— 10 111111
iglu DI a
A-6
Subject: PlanCheck
Page Label: 33 The door to the garage from the
Author:justinh residence must comply with
File Name: Architectural Permit Set.311 Park Ave.2017.12.pdf R302.5.1. Specify the door
material/fire rating and note the
®®M®® requirement for a self-closing
device.
�� DI DI I u ® =
A-602
Special Inspection and Testing Agreement.311 Park Ave.2017.12.pdf(1)
Subject: PlanCheck
Page Label: 3 You are missing several
. '°. Author:justinh signatures on the special
aec,nh°. inspection form.
File Name: Special Inspection and Testing Agreement.311
_.. Park Ave.2017.12.pdf