Loading...
HomeMy WebLinkAboutFile Documents.110 Coach Rd.0079.2018 (24).ARBK Air System Sizing Summary for DGQ Project Name: 18003-DBX 7 10/19/2018 Prepared by: RADER ENGINEERING INC. 01:38PM Air System Information Air System Name DGQ Number of zones 1 Equipment Class UNDEF Floor Area 653.0 ft2 Air System Type SZCAV Location Eagle,Colorado Sizing Calculation Information Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates Sizing Data Calculated Space CFM Sizing Individual peak space loads Central Cooling Coil Sizing Data Total coil load 1.3 Tons Load occurs at Aug 1400 Total coil load 15.6 MBH OA DB/WB 88.9/64.7 °F Sensible coil load 13.4 MBH Entering DB/WB 73.1 /58.5 °F Coil CFM at Aug 1400 754 CFM Leaving DB/WB 51.2/49.8 °F Max block CFM 754 CFM Coil ADP 48.8 °F Sum of peak zone CFM 754 CFM Bypass Factor 0.100 Sensible heat ratio 0.859 Resulting RH 46 CFM/Ton 581.7 Design supply temp. 50.0 °F ft2/Ton 503.6 Zone T-stat Check 1 of 1 OK BTU/(hr•ft2) 23.8 Max zone temperature deviation 0.0 °F Water flow @ 10.0°F rise 3.11 gpm Central Heating Coil Sizing Data Max coil load 14.6 MBH Load occurs at Des Htg Coil CFM at Des Htg 754 CFM BTU/(hr•ft2) 22.3 Max coil CFM 754 CFM Ent. DB/Lvg DB 68.6/92.5 °F Water flow @ 20.0°F drop 1.46 gpm Humidifier Sizing Data Max steam flow at Des Htg 0.59 lb/hr Air mass flow 2540.49 lb/hr Airflow Rate 754 CFM Moisture gain .00023 lb/lb Supply Fan Sizing Data Actual max CFM 754 CFM Fan motor BHP 0.15 BHP Standard CFM 565 CFM Fan motor kW 0.12 kW Actual max CFM/ft2 1.16 CFM/ft2 Fan static 0.75 in wg Outdoor Ventilation Air Data Design airflow CFM 0 CFM CFM/person 0.00 CFM/person CFM/ft2 0.00 CFM/ft2 O j OO L/C6.� �1 1 .•. co 10/19/18!�\ Iy 39 ? • I J I9p . / P .• k, 40 I AN • cr RECEIVED 10/30/2018 Hourly Analysis Program 5.11 pASREcit,i2 BUILDING DEPARTMENT Zone Sizing Summary for DGQ Project Name: 18003-DBX 7 10/19/2018 Prepared by: RADER ENGINEERING INC. 01:38PM Air System Information Air System Name DGQ Number of zones 1 Equipment Class _UNDEF Floor Area _653.0 ft2 Air System Type SZCAV Location Eagle,Colorado Sizing Calculation Information Calculation Months __ Jan to Dec Zone CFM Sizing Sum of space airflow rates Sizing Data .Calculated Space CFM Sizing Individual peak space loads Zone Terminal Sizing Data Reheat Zone Zone Design Minimum Reheat Coil Htg Unit Htg Unit Mixing Supply Supply Coil Water Coil Water Box Fan Airflow Airflow Zone Load gpm Load gpm Airflow Zone Name (CFM) (CFM) CFM/ft2 (MBH) @ 20.0°F (MBH) @ 20.0°F (CFM) DGQ 754 754 1.16 0.0 0.00 0.0 0.00 0 Zone Peak Sensible Loads Zone Zone I Zone I Cooling Time of , Heating Floor ISensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (ft2) DGQ 13.4 Aug 1400 15.4 653.0 Space Loads and Airflows Time of Cooling Peak Air Heating Floor Zone Name/ Sensible Sensible Flow Load Area Space Space Name Mult. (MBH) Load (CFM) (MBH) (ft2) CFM/ft2 DGQ DGQ-01 Flex Room 1 10.5 Aug 1400 591 12.3 286.0 2.07 DGQ-02 Sitting 1 1.3 Jul 1500 76 1.3 181.0 0.42 DGQ-03 Bedroom 1 1.0 Jul 1500 58 1.3 125.0 0.46 DGQ-04 Bath 1 0.5 Jul 1500 29 0.5 61.0 0.48 RECEIVED 10/30/2018 Hourly Analysis Program 5.11 piNSE412 BUILDING DEPARTMENT