File Documents.815 Roaring Fork Rd.0084.2017 (2).ARBK
0085-2017-ARBK_BuildingComments_1 815 ROARING FORK_PERMIT SET_2017.04.05.pdf(16) Page:A-101 File Name: 815 ROARING FORK_PERMIT Show the location of the SET_2017.04.05.pdf electrical panel. Must comply Subject: PlanCheck with 2014 NEC 110.26 Show the location of the electrical Author: nickt panel.Must comply with 2014 , ON SHEET A-102, ELECTRICAL NEC 110.26 Color: • PANEL LOCATION IS IN THE GARAGE, NOTED PER 2014 NEC 110.26 REQUIREMENTS Page:A-101 File Name: 815 ROARING FORK_PERMIT It appears there are two washers SET_2017.04.05.pdf and two dryers(2 W/Ds). If two Subject: PlanCheck dryers, provide makeup air to the �® a Author: nickt laundry room. 2015 IMC 504.6 :.,: m...,.. Color: ■ .. I s O % ON SHEET A-105, A FAN IS NOW ri ill T ii 1ilOgli ' SHOWN IN THE LAUNDRY A li ^�! - — t ®' ROOM, NOTING REQUIRED MAKEUP AIR, PER CODE 2015 IMC 504.6 City of Aspen Received 7/17/17 Building Department LL Page:A-101 Provide information on existing • File Name: 815 ROARING FORK_PERMIT z SET 2017.04.05.pdf to remain mechanical equipment �W•• m•w•••, — and systems: J ""— Subject: Mech for existing but total gut Author: nickt -Fuel type, combustion air Color: • -Where new openings occur in proximity to existing exhausts, EXISTING MECHANICAL flues, and vent outlets; cc SYSTEMS TO REMAIN, NOT dimension the distances from ADDED TO SHEET A-101 the new openings. For all new equipment and systems, provide drawings prepared by a licensed mechanical engineer or licensed mechanical contractor showing: -Basic one-line schematic drawing of the HVAC system -Show all new intake, exhaust, flue, and vent outlets with dimensions to openings and property lines. -Equipment layout with access, working space, and clearances -Equipment schedule -Description of all systems and sequence of operation -Winter/summer indoor and outdoor design temperatures listed on the plan. Must fit within the following parameters: --Winter indoor temp may not be above 72 deg F (2015 IECC R302.1) --Winter indoor temp may not be below 68 deg F (2015 IRC R303.8) --Summer indoor temp may not be below 75 deg F (2015 IECC R302.1) --Summer outdoor design temp: 82 deg F(Ordinance 40, 2016) --Winter outdoor design temp: -15 deg F (Ordinance 40, 2016) -Kitchen Hood CFMs and interlocked makeup air if over 400cfm -Dryer duct length, CFMs and makeup air as required by 2015 IMC 504.6 -Radiant floor locations -Balanced whole house mechanical ventilation system per 2015 IRC R303.1 ex1 and Ordinance 40, 2016. Provide calculations used to determine the ventilation in accordance with Ord 40, 2016. City of Aspen Received 7/17/17 Building Department Page:A-104 File Name: 815 ROARING FORK_PERMIT Identify where the air barrier is Identify where the air barrier is SET_2017.04.05.pdf (interior or exterior). If interior, (interior or exterior).If interior, Subject: PlanCheck NOTE ADDED TO SHEETS provide air barrier continuity provide air barrier continuity J REQUIRING AIR BARRIER details at all locations where it details at all locations where it Author: nickt will be disturbed,complying with COlor: ■ CONTINUITY AT NEW WALL will be disturbed, complying with 2015 IECC rbed, 402.4.1.1. LOCATIONS. SEE SHEETS A-101, 2015 IECC table R402.4.1.1. Most likely this house relied on drywall or spray foam for the air A-102,A-103 Most likely this house relied on barrier.(Ordinance 40,2016) NEW ROOF AND WALL drywall or spray foam for the air ASSEMBLIES ADDED TO SHOW AIR barrier. (Ordinance 40, 2016) BARRIER CONTINUITY SEE SHEET A-601 DETAILS 10& 12 MN 11:. Page:A 104 Provide snow stops at the new m ;riinimm I13, File Name: 815 ROARING FORK_PERMIT � � NA SET 2017.04.05.pdf dormer roof which sheds over o °i." M Subject: PlanCheck the deck below(Ordinance 40, © - - i ` Author: nickt 2016). I Color: ■ J aa SNOW STOPS ADDED TO SHEET A-103 &A-104. Page:A-104 File Name: 815 ROARING FORK_PERMIT Provide a window and door SET_2017.04.05.pdf schedule. Note the U factor(max Subject: PlanCheck 0.28)and which require safety Provide a window and door schedule.Note glazing and fall protection. the U factor(max 0.28)and which require Author: nickt safetyglazingandfall protection. (Ordinance 40, 2016&2015 IRC &O 3i12n2c)e40,2016&20eciisn 308.4 Color: ■ R308.4&R312.2) DOOR AND WINDOW TAGS ADDED TO ELEVATION SHEETS, NOTE ADDED TO ELEV DRAWINGS STATING MAX U-VALUE (0.28) I Page:A-104 < File Name: 815 ROARING FORK_PERMIT Detail the new chimney SET_2017.04.05.pdf construction. a -■ -►om di Subject: PlanCheck NEW CHIMNEY CONSTRUCTION EM mommig nnmmmmm Author: nickt DETAILED ON SHEET A-402 _:i!III111111liillliiiiiiiillll Color: • • _■IIIIIII'!II! 1111IIVIIIIII o _=IIIL iiiiimiiiI II III Page:A-104 MnnIGi€€nm €nn�iununn€!€€veer€€�€€€ File Name: 815 ROARING FORK_PERMIT Detail the new dormer Illlltillg IIIII hIIOrI11ENp1r11 n.... — IIII€ I IIIII�� II11� II construction including materials, MVO i€s_: ����� ����������€ t,���€€ SET_2017.04.05.pdf 'limn II IIIIII Ili I° Subject: PlanCheck thermal envelope R values and oI =��11.:IllIII��lhl Ell J continuity, air barrier details and -____ Author: nickt ii I� Color: ■ continuity(which will be j ..- j inspected),waterproofing, and • flashing. - ---- NEW DORMER CONSTRUCTION UPDATED. SEE SHEETS A-403 &A-601 City of Aspen Received 7/17/17 Building Department Page:A-104 File Name: 815 ROARING FORK_PERMIT Provide sheet A-301 Provide sheet A-301 SET_2017.04.05.pdf Subject: PlanCheck SECTION NOTE DELETED. NEW Author: nickt WALL SECTION @ NEW c Color: ■ DORMER ADDED TO DRAWING alSET. SEE SHEET A-402 ROGtRERECIED o�axw Page:A 105 Lighting must meet 2015 IECC File Name: 815 ROARING FORK_PERMIT SET_2017.04.05.pdf requirements, including 75%of � __ Subject: PlanCheck lamps in permanently installed Author: nickt fixtures must be high efficacy. IEGEND "ran Color: •■ Revise RCPs. tZr° ® � � NOTE ON RCP SHEETS a _ UPDATED WITH 2015 IECC REQUIREMENTS. SEE SHEETS A-105, A-106, A-107 Page:A-201 File Name: 815 ROARING FORK_PERMIT The filled spaces where windows SET_2017.04.05.pdf are removed and any exposed Subject: PlanCheck framing cavities in the thermal Thefilletl spaces where wintlows are removetl entl Author: nickt envelope must be filled with any exposed framing cavflies In the thermal envelope must be flletl vMhinsulation.(20151ECC Color: ■ insulation. (2015 IE CC R5°"." R503.1.11 NOTE ADDED TO SHEETS REQUIRING GAPS TO BE FILLED WITH INSULATION. SEE SHEETS A-101, A-102, A-103 Page:A-401 File Name: 815 ROARING FORK PERMIT Stair guards are missing infill. If .. — glass, it must be safety glazed. ' SET_2017.04.05.pdf Subject PlanCheck Revise stair details to : Author: nickt demonstrate guards and — ICI- -- Color: ■ handrails complying with code. 2015 IRC R308, Ordinance 40, 2016. ■E_- i11.lR _ STAIR GUARDS AND SAFETY '- r GLAZING NOTE ADDED TO SHEET A-401 sr sc. Page:A 601 Provide the insulation schedule Provide the insulation File Name: 815 ROARING FORK PERMIT e hetlmle SET_2017.04.05.pdf Subject: PlanCheck NO INSULATION SCHEDULE. Author: nickt INSULATION SPECS. ADDED TO SG� EX. Color: ■ ASSEMBLY NOTES. SEE SHEET ,. A-601 wD00 SmnVG PtR FIEYA'WNS City of Aspen Received 7/17/17 Building Department Page:A-601 File Name: 815 ROARING FORK_PERMIT Provide documentation that the °� SET 2017.04.05.pdf roof assembly is Class A. This is '' Subject: Class A Roof typically either an ESR or UL ' ' report. Revise you roof detail to matchmi iiiim.. ___ ... .._ ,..---'""-- --- —*SW_y .: p Author: nickt Color: • the report. (Ordinance 40, 2016) ITZMY ROOF ASSEMBLY UPDATED TO SHOW"CLASS A" RATING. SEE r°y, �7!°° SHEET A-601 DETAIL 12 Page: G-001 File Name: 815 ROARING FORK_PERMIT Provide an asbestos test report SET_2017.04.05.pdf including: Subject: PlanCheck -Inspector narrative -Inspector certification Provide an asbestos test report including: Author: nickt p -Inspector narrative -Laboratory data -Inspector certification Color: • -Laboratory data ASBESTOS REPORT ADDED TO 8.5X11 FOLDER TM Page: G-001 m File Name: 815 ROARING FORK_PERMIT This permit came in after April LS PROJECTscvsg➢CS SET_2017.04.05.pdf 10, 2017; putting it on the 2015 - — --••—" =- Subject: PlanCheck codes. Revise as necessary. Still ' ®' -° on 2014 NEC. EF.o_ ._.... ____` Author: nickt .., Color: • SHEET G-000 REVISED TO °.°••- SHOW 2015 CODES City of Aspen Received 7/17/17 Building Department