i• File Name: 3-A-101 Basement Floor Plan.pdf How is the dryer vented?Are
Subject: PlanCheck you using an existing duct? If
not, how will you route it and
Author: nickt
Color: ■ where is the termination?
11 Page: 1
_ i These plans are too small to
- —, __ File Name: 3-A-101 Basement Floor Plan.pdf
tom# --, Subject: PlanCheck print at a legible scale. Provide
"' full size digital drawings.
Author: nickt
Color: •
9e� RECEIVE
11/15/201
Wel
Page: 1 Water closet must have 15"from
File Name: 3-A-101 Basement Floor Plan.pdf
Subject: PlanCheck centerline to each opposing wall
Author: nickt for a total of 30"of clearance.
� v,- Color: ■_
• Page: 1 Provide more information on the
File Name: 3-A-101 Basement Floor Plan.pdf
1- Subject: PlanCheck new mechanical room under the
Author: nickt stairs. What equipment is being
Color: • installed?What is the fuel type?
Sealed combustion or is
`„"v combustion air required? If so,
how is it provided? Drawings
depict a vent going to the
common interior stair;what is
this? How are you venting the
equipment? Provide access to
the equipment; clean up the
drawing to clearly show the room
size and door.
4-A-102 Main Level Floorplan.pdf(3)
7% Page: 1
File Name: 4-A-102 Main Level Floorplan.pdf Clean up the notes that overlay
Subject: PlanCheck eachother on the main plan
-; I south of the stair.
i Author: nickt
_— _ Color: •
Pgid
RECEIVED
01/10/2018
ASPEN
BUILDING DEPARTMENT
Page: 1 Guard must be 42" high. (2015
File Name: 4-A-102 Main Level Floorplan.pdf
Subject: PlanCheck IBC 1015.3)
Author: nickt
Color: ■
Ku I[
Page: 1
' Provide the dimensions of the
1 File Name: 4-A-102 Main Level Floorplan.pdf
Subject: PlanCheck new egress window. Must
-- _ Author: nickt comply with 2015 IBC 1030.
" I! Color: ■
I _-
MEW
6- structural 16070 Thompson 2017-10-11.pdf(4)
Page: DETAIL SHEET Reivse S531 to specifically
File Name: 6-structural 16070 Thompson 2017-10-11.pdf
Subject: PlanCheck itemize each item that needs
Author: nickt special inspection and whether it
Color: • should be inspected periodically
• or continuousl .
.Nagesemer—
MI6= IBC 01 R IS D PE IA INSP C 10
TO AISC REQUIREMENTS. SKPE TO
NAM
FOLLOW IT R VISED DI-ECTION
MEM
Page: FOUNDATION PLAN
File Name: 6-structural 16070 Thompson 2017-10-11.pdf Distance from finish floor to
Subject: PlanCheck bottom of window opening may
Author: nickt
not exceed 44". S111 shows 43"
C•I • from floor to concrete sill,which
will not provide enough space for
HI . CoM E 1`N•T C EA-. KPE 0-1 -1 F•UN*A O framing and window and still
®_-37— PLAN S111 AND DETAIL 7/S531 BOTH SHOW CONCRETE acheive 44". Detail 7/S531
WALL SILL AT ELEVATION 95'-1 3/4"AND CONCRETE SLAB ` shows a different floor elevation.
ELEVATION 91'-10 3/4". THIS IS A 39"HEIGHT, LEAVING 5 Revise and coordinate. (2015
AVA LA:LE TO INI H. NI R VIS ON H R. IBC 1030.3)
➢OMPSON Page: FOUNDATION PLAN
File Name: 6-structural 16070 Thompson 2017-10-11.pdf Structural drawings must be
Subject: PlanCheck stamped and signed by the
.a,� aA�.�o..•
Author: nickt engineer.
:�" Color: •
„?, 6010 SEE ATTACHED,STAMPED E
FOUNDATION
PLAN
sill
RECEIVED
01/10/2018
ASPEN
BUILDING DEPARTMENT
Page: FOUNDATION PLAN Provide and detail connection of
J,® File Name: 6-structural 16070 Thompson 2017-10-11.pdf
_.e Subject: PlanCheck window well to foundation wall.
tg
LAuthor: nickt
T � Color: •
-WDETAIL 7/S531 HAS N T TO IN ICATE T EL ELL
••-
PRODUCT TO BE A PRE-FABRICATED COMPONENT.
CONNECTION TO FOUNDATION IS NOTED TO FOLLOW
MANUFACTURERS RECOMMENDATIONS. IF NEEDED,
SKPE WILL COORDINATE A RECOMMENDED FASTENING
SY TE F LL WINGSUF<iMITTAL,OF CCCJCT PF CIF ICATI .
window specs 2.pdf(1) J• ��� ��•
Page: 1 The Sierra Pacific Window
File Name: window specs 2.pdf schedule does not identify which
Subject: PlanCheck
Author: nickt window the window well one is.
Color: •
window specs CW-2436.pdf(1)
Page: 1
File Name: window specs CW-2436.pdf The"Window Well Experts"
INEEM
Subject: PlanCheck window does not meet minimum
Author: nickt egress window size
Color: • requirements. (Minimum 24"
wide, 20"high, 5.7sqft clear
opening)(2015 IBC 1030).
RECEIVED
01/10/2018
ASPEN
BUILDING DEPARTMENT