HomeMy WebLinkAboutFile Documents.501 Dean St.0019-2022-BCOM (12) villevE 11/17/2022 44N0' d linzhid FORCOOMMLIANCE FIXED FENESTRATION tall g/ B001, B002, B003, & B004 CITY OF ASPEN Memorandum of Policy Building Codes From: Mike Metheny Date: May 10, 2018 Revised: Date: June 1, 2020 Subject: Fenestration U-factor Documentation The following are acceptable methods under the IECC to verify fenestration U- ► factors as part of the building thermal envelope: 0 w 1. NFRC certification, factory assembled: NFRC label applied to window assembly and verified at field inspection. Lu 2. NFRC certification, site assembled: provide an NFRC CPD number or certificate of authorization from an NFRC authorized inspection agency prior to permit approval. To document the chain of custody, project specific NFRC labels must be affixed to the units or a project specific NFRC label certificate must be provided prior to field inspection. 3. Provide a simulation or test by an NFRC-accredited lab in accordance with NFRC-100 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the simulation or test is required prior to field inspection. 4. Provide a calculation using 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3: "U-Factor (Overall Coefficient of Heat Transfer)" prior to permit approval. Calculation is required to be in the standard NFRC window size of 47.2"x 47.2". To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the calculation is required prior to field inspection. 5. Use default values from Table 4 U-Factors for Various Fenestration Products in 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the values is required prior to field inspection. 6. Use default values from IECC tables in chapter 3 of the residential and commercial sections. RECEIVED 10/31/2022 130 South Galena Street Aspen,CO 81611-1975 I P:970.920.5000 I F:970.920.5197 I cityofaspen.com ASPEN BUILDING DEPARTMENT J FIXED FENESTRATION B001, B002, B003, & B004 D � WE FENESTRATION PRODUCT RATING OVERALL RATING - i2ozz GfU �RaDlkicnfhid -Factor: 'CERTIFICATE (IP) (Btu/h•ft2•°F)SHGC: .30 Certificate Authorization VT: .53 Name: Company: Richard Middleton Eagle Glass GJ Signature: Date: ° i'ch-ardaVddTeton 10-28-2022 STIPULATES THAT THE MATERIALS LISTED ON THIS CERTIFICATE WERE INSTALLED ON THE PROJECT IDENTIFIED BELOW. PROJECT INFORMATION: The Residences at The Little Nell _ Street Address: 501 East Dean Street City: State: Zip: Aspen CO 81623 GLAZING CONTRACTOR/INSTALLER: Contact Person: Eaglite DBA Eagle Glass Keegan Simons Street Address: Phone Number: 2520 W Pinyon Ave 970-245-0399 City: State: Zip: Grand Junction CO 81505 GLAZING MATERIAL SUPPLIER: Contact Person: Manko Window Systems Sam Sloan Street Address: Phone Number: 1700 E 22nd Ave 720-326-3491 City: State: Zip: Aurora CO 80011 Glass and Spacer Type: Quanex Tri-Seal Center-of-glass(C.O.G.)U-factor: Center-of-glass(C.O.G.)SHGC: Center-of-glass(C.O.G.)VT .18 Btu/h•ft2•°F .33 .60 FRAMING MATERIAL SUPPLIER: Contact Person: Kawneer Cameron Hendrix Street Address: Phone Number: 4837 W 2400 S Suite 100 303-471-1848 City: State: Zip: Salt Lake City UT 84120 U-factor Matrix SHGC Matrix VT Matrix (BtU/h•ft2•°F) Product Line: z C.O.G. Overall C.O.G. Overall COG Overall 1620UT CURTAIN WALL SYSTEM - U-factor factor SHGC SHGC VT VT FIBERGLASS PP (TG) a LL 0.48 - 0.75 0.69 0.75 0.69 l 0.46 - 0.70 0.65 0.70 0.64 The overall ratings for U-factor and SHGC are based on a N w 0.44 - 0.65 0.60 0.65 0.59 size of 2000 mm x 2000 mm(78.75 in x 78.75 in)as a 0.42 - 0.60 0.56 0.60 0.55 required in NFRC 100. I- 0.40 - 0.55 0.51 0.55 0.50 0.38 - 0.50 0.46 0.50 0.46 Overall U-factors,Solar Heat Gain Coefficients(SHGC)and 0.36 - 0.45 0.42 0.45 0.41 Visible Transmittances(VT)listed in the matrix were 0.34 - 0.40 0.37 0.40 0.37 determined in accordance with NFRC 100 and NFRC 200 0.31 0.36 0.35 0.33 0.35 0.32 respectively by an NFRC accredited independent laboratory. 0.30 0.36 0.30 0.28 0.30 0.27 ACCREDITED INDEPENDENT LABORATORY: 0.28 0.34 0.25 0.24 0.25 0.23 Intertek Building & Construction 0.26 0.32 0.20 0.19 0.20 0.18 0.24 0.30 0.15 0.14 0.15 0.14 Reference Test Report# J7573.01-116-46 0.22 0.28 0.10 0.10 0.10 0.09 Reference Simulation Report# J7572.05-116-45 0.20 0.26 0.05 0.05 0.05 0.05 0.18 0.25 Air Leakage less than or equal to 0.06 cfm/ft2 Directions: Fill out form completely. Determine the Overall Rating 0.16 0.23 at a test pressure of 1.57 psf when tested in for this project by using the C.O.G U-Factor(winter-ti O 0.14 0.21 accordance with(check one): SHGC,COG VT from Table 1 and looking up the tfr II I 1 ED AAMA/WDMA/CSA 101/I.S.2/A440 from Table 2. Indicate the Overall Rating in the s u:,- -- 0.12 0.19 X ASTM E283 Linear interpolation is permitted. 0.10 0.18 NFRC 400 10/31/2022 AUGUST,2021 COCD212C EC 95516-030 ‘,J1 t BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & 6004 rNO N•RESIDENTIAL FENESTRATIO NCALCULATIO NREPO RT / BID REPO RT 7/2022 9) ACCO (DING TO NFRC CMAPRO CEDURES-NFRC STANDARD SIZE. tCOIRIANCE linzhid NO 1E: This is NO Tan NFRC Label Certificate. This document can NO The used in place of a NFRC Label Certificate and can be used only for Bid and Design Purposes. f ( Project Information/Number: BR-KAW-18751 Bid Report G eierated By: K awneer Company Inc. ProjectName: Residences at Little Nell i Project Address: 501 East Dean Street �1 Project City: Aspen State: CO /ZIP code: 81611 Specifying Company Name: Kawneer Com peny Inc. Specifying Authority Contact Person: S G ieg B M cKenna pecifying Corn pany Phone: 770-840-6433 Frame Corn ponent Uploaded By: Approved Entity Frame Corn ponent Status: Approved Spacer Corn ponent Uploaded By: Approved Entity Spacer Corn ponent Status: Approved PRO WCT LISTING : ,<< , 1 Performance at NFRC Standard Size ID Name Framing Ref I G azing Ref S pacer Ref U SHG C VT Btu/h•ft2•F - - P-KAW- 1620UT System FA-KAW- G AG N-25366 S A-NFC-7183 0.28 0.30 0.53 116437 1 FG FP Triple 145508 G I SG SN68 (#2)Clr, Air,C1r,Air,IS20 (#6)Clr, Warm (Ne> Edge Spacer _ P-KAW- 350 Door Pair, FA-KAW- G AG N-25325 S A-NFC-7183 0.66 0.23 0.37 116440 SG SN68 (#2) 145349 Clr, Air, IS20 (#4) Clr, Warm Edge Spacer Copy FRAM E G LAZING AND SPACER ASSEM BLIES: G LAZING LISTING : G lazing Ref S upplier ID D escription G A0 N-25325 G ardian 1 /4" SunG Lard SN68 (#2) Clr, 1/2"Air, 1/4" IS20 (#4) Clr G AG N-25366 G ardian 1 /4" SunG Lard SN68 (#2) Clr, 1/2"Air, 1/4" Clr, 1/2"Air, 1/4" IS20 (#6) Clr SPACER LISTING : Spacer Ref S upplier ID D escription SA-NFC-7183 N e FRC G neric Warm Edge Spacer Non M NFRC Path I, G cup 4 FRAM FIG LISTING : Framing Ref S upplier ID D escription FA-KAW-145349 K awneer Company Inc. L-KAW-1720 350 Non Therm al Door Pair 10/31/2 02 2 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 FRAM NG LISTING : rillegrni 17/2o22 IV Framing Ref S upplier ID D escription , FORCOOtbACMOCE 1inlzhid FA-KAW-145508 K awneer Company Inc. ' L-KAW-6438 1620UT System 1 FG FP Triple G tize1 q. �, O _ 0 O -. ..,..., , O \vie ck) \:. oip / (74 0 O, o (c::: 0 ":::::„7 +CI RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 ramisuiaill I I} GUARDIAN PERFORMANCE ni9�� 9)CALCULATOR linzhid Residences at Little Nell Visible Light Solar Energy Thermal Properties Glass 1 & Glass 2& Transmitta Transmitta Reflectanc Solar Heat Make-up Name Reflectance U-Value Coating Coating nce nce a Gain Coefficient Visible(s %) p %out %in Solar(T %) p %out (SHGC) Winter Night Summer Day v v Pv e e (Btu/hrft2.F) (Btu/hrftz F) SunGuard ®SN 68 (North Guardian America) Clear on Triple Pane Guardian Glass 60 15 19 28 35 0.33 0.184 0.180 Clear (North Glass America) (North America) Calculation Standard:NFRC 2010 Sriple Pane Outdoors Guardian Clear Glass(North America) #1 GLASS 1 Thickness=1/4"(6mm) #2 SunGuard®SN 68(North America) GAP 1 100%Air,1/2"(12.7mm) Guardian Clear Glass(North America) #3 GLASS 2 Thickness=1/4"(6mm) #4 GAP 2 100%Air,1/2"(12.7mm) Guardian Clear Glass(North America) #5 GLASS 3 Thickness=1/4"(6mm) #6 SunGuard®IS 20 Interior Surface LE(North America) Total Unit(Nominal)=1 3/4 in Slope=90° Window Height=1 meter Estimated Nominal Glazing Weight:8.62 lb/ft2 Indoors IS 20 must be heat-treated for all applications and uses. Important Notes Calculations and terms in this report are based on NFRC 2010.The performance values shown above represent nominal values for the center of glass with no spacer system or framing. Laminated products: The Performance Calculator allows the user to model a wide variety of laminated glass makeups using different float glass substrates, coatings and interlayer material, including those makeups where the coating faces the interlayer. It is the user's responsibility to assess whether the laminated glass makeup meets relevant regional standards and complies with applicable laminated glass safety regulations. In addition,when the laminated glass makeup includes a coating facing the interlayer material,there may be a loss of therm insulation performance and a color change compared to non-embedded coated class. C � D Non-specular products(translucent or diffuse): The performance measurement for non-specular(translucent or diffuse) materials such as translucent interla*VnI 2022 etched glass surface, or surface with ceramic frit is limited by the current experimental technologies. Since measurements ASPEN BUILDING DE315ARI1T FIXED FENESTRATION B001, B002, B003, & B004 IEVAIEWE GEnTIZIE, PERFORMANCE 11/17/2022 CALCULATOR R � linzhid capture physically only a part of the resulting radiation, calculated performance results provided herein and based on such measurements are not compliant with any standard (including EN 410)and may only be used as a general reference. Actual values may vary significantly based upon exact fabrication process, as well as type,thickness and color of used non-specular material. Please note that the Thermal Stress Guideline is only a general guide to the thermal safety of a glazing, and it is not a replacement for detailed thermal stress analysis. Explanation of Terms Visible Light Transmittance(Tv,%) is the percentage of incident light in the wavelength range of 380 nm to 780 nm that is transmitted by the glass. Ultraviolet(UV)Transmittance(Tuv, %) is the percentage of the incident solar radiation transmitted by the glazing in the 300 nm to 380 nm range. Solar Energy Direct Transmittance(Te, %) is the percentage of incident solar energy in the wavelength range of 300 nm to 2500 nm that is directly transmitted by the glass. Visible Light Reflectance Outdoors/Indoor(Rv out/in, %) is the percentage of incident visible light directly reflected by the glass. Solar Direct Reflectance Outdoors/Indoors(Re out/in, %) is the percentage of incident solar energy directly reflected by the glass. Solar Energy Absorptance(Ae, %) is the percentage of the sun's energy that is absorbed by glass. U-Value is the glazing parameter that characterizes the heat transfer through the central part of the glazing, i.e.without edge effects, and expresses the steady-state density of heat transfer rate per temperature difference between the environmental temperatures on each side. US Standard units are Btu/hr•ft2•F and SI / Metric units are W/m2 K. Relative Heat Gain (RHG) is the total net heat gain to the indoors due to both the air-to-air thermal conductance and the solar heat gain. US Standard units are Btu/hr.ft2 and SI/Metric units are W/m2. Shading Coefficient(sc) is Solar Factor divided by 0.87. It is a measure of the solar heat gain referenced to 3 mm clear glass which has the designated value of 1.00. Solar Heat Gain Coefficient(SHGC) is the sum of the solar direct transmittance and the secondary heat transfer factor of the glazing towards the inside,the latter resulting from heat transfer by convection and longwave IR-radiation of that part of the incident solar radiation which has been absorbed by the glazing. Light-to-Solar Gain (LSG) is the ratio of visible light gain to solar gain. LSG =(Visible Transmittance)/(SHGC) Color Rendering Index in transmission, D65(Ra) is the change in color of an object as a result of the light being transmitted by the glass. Weighted Sound Reduction Index(Rw) is a single-number quantity which characterizes the airborne sound insulation of a material or building element over a range of frequencies. Sound Transmission Class(STC) is a single-number quantity which characterizes the airborne sound insulation of a material or building element over a range of frequencies. Disclaimer This performance analysis is provided for the limited purpose of assisting the user in evaluating the performance of the glass products identified on this report. Spectral data for products manufactured by Guardian reflect nominal values derived from typical production samples or CE Initial Type Testing and subject to variations due to manufacturing and calculation tolerances. Spectral data for products not manufactured by Guardian were derived from the LBNL International Glazing Database and have not been independently verified by Guardian. Guardian recommends a full-size mock-up be approved. I, The values provided herein are generated according to established engineering practices and applicable calculations sari arma . , Many factors may affect glazing characteristics, including glass size, building orientation, shading,wind speed,type`of - installation, production process and others.The applicability and results of the analysis are directly related to sor jr�p tsar l any changes in actual conditions can have a significant effect on the results. It is the responsibility of the users-le�tj�c� I to ensure that the intended application is appropriate and complies with all relevant laws, regulations, standards, codes of ASPEN BUILDING DEf15Ar?Itfk1T FIXED FENESTRATION B001, B002, B003, & B004 € �} G GUARDIAN PERFORMANCE 11/17/2022 9) CALCULATOR FORCOUWAWLANCE linzhid practices, processing guidelines and other requirements. Guardian makes no guarantee that any glazing modeled herein is available from Guardian or any other manufacturer.The user has the responsibility to check with the manufacturer regarding availability of any glass type or make-up. While Guardian has made a good faith effort to verify the reliability of the tools used for this analysis,they may contain unknown programming errors that could result in inaccurate results.The user assumes all risk relating to the results provided and is solely responsible for selection of appropriate products for user's application. Guardian makes no express or implied warranty of any kind with respect to the tools used by Guardian and this analysis.There are no warranties of merchantability, non-infringement or fitness for a particular purpose with respect to the tools used by Guardian and this analysis and no warranty shall be implied by operation of law or otherwise.The only warranties applicable to Guardian products are those separately provided in writing for each product. In no event shall Guardian be liable for direct, indirect, special, consequential or incidental damages of any kind relating to or resulting from use of Guardian tools and analyses. Trademarks owned by Guardian Industries, LLC and/or its affiliates may be registered in the United States and other jurisdictions.All other trademarks are property of their respective owners. By accessing this calculator,you agree not to alter or modify the generated report data and information, by any means.Any manual alteration will be your own responsibility and will annul all the content of the report. Program Version:4.1.0.9532 Database Version: 20221010 RECEIVED 10/31/2022 ASPEN BUILDING DES ARVENT FIXED FENESTRATION B001, B002, B003, & B004 r/IWE U. 11/17/2022 jd Intertek 30 tsfORCICOCCUMVLINCE 95438-188 1"hid Total Quality.Assured. NFRC ACCREDITED LAB. REFERENCE PAGE 3 OF THE REPORT. INC .KAWNEER COMPANY CuMPUuER ER SIMULATION REPORT SPECIFIED WINDOW SYSTEM. SCOPE OF WORK 1620UT Glazed Wall System (Fiberglass PP)- NFRC 100/200/500 simulations to determine U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance ratings. REPORT NUMBER J7572.05-116-45 RO TEST DATE 09/09/19 if.1169?Ilir ISSUE DATE 03/25/21 ;I RECORD RETENTION END DATE • 09/09/24 rA PAGES 0 30 DOCUMENT CONTROL NUMBER RECEIVED RT-R-AMER-Test-4044 (01/16/19) ©20171NTERTEK 10/31/2022 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 IEViefel)) 11/17/2022 L in terte k 130 Derry COOFORMINFLIANCE York,30er 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 RFPORT ISSl1F11 TO KAWNEER COMPANY INC. 555 Guth ridge Court Norcross, Georgia 30092 SPECIFIED WINDOW SYSTEM. ---- -- COG U-FACTOR ON PAGE 8 SUMMARY OF THE REPORT. SERIES/MODEL 1620UT Glazed Wall System (Fiberglass PP) Architectural Testing, Inc. (an Intertek company) dba Intertek Building & Construction (B&C) was contracted to perform U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance simulations in accordance with the National Fenestration Rating Council (NFRC). This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. Intertek B&C will service this report for the entire test record retention period. The test record retention period ends five years after the test date. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained for the entire test record retention period. FOR INTERTEK B&C: COMPLETED BY: Allison M. Ford REVIEWED BY: Eric S. Leitner Manager-Simulations TITLE: Simulation Technician TITLE: and Thermal Testing alomMQ SIGNATURE: oo,.rs,a..d,a a..e,d SIGNATURE: DATE: 03/25/21 DATE: 03/25/21 AMF:amf This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement.Intertek assumes no liability to any party,other than to the Client in accordance with the agreement,for any loss,expense or damage occasioned by the use of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety.Any use of thg,`,_ ;11\4`J t_ ' Intertek name or one of its marks for the sale or advertisement of the tested material,product or service must first be approved to L,d, ';-- .1 writing by Intertek.The observations and test results in this report are relevant only to the sample(s)tested.This report by itself does not imply that the material,product,or service is or has ever been under an Intertek certification program. 10/31/2 0 2 2 Version: 01/16/19 Page 2 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 IEVilletel)) 11/17/2022 L In terte k 130 Derry Court ( York,30er 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 sFrTirtm TEST METHODS The products were evaluated in accordance with the following: ANSI/NFRC 100-2020, Procedure for Determining Fenestration Product U-Factors ANSI/NFRC 200-2020, Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence NFRC 500-2017, Procedure for Determining Fenestration Product Condensation Resistance Values *Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. Ratings values included in this report are for submittals to an NFRC-licensed IA and are not meant to be used directly for labeling purposes. Only those values identified on a valid Certificate of Authorization (CA) by an NFRC accredited Inspection Agency (IA) are to be used for labeling purposes. The ratings values were rounded in accordance with NFRC 601, NFRC Unit and Measurement Policy. Intertek B&C is an NFRC accredited simulation laboratory and all simulations were conducted in full compliance with NFRC approved procedures and specifications. The values included in this report are not considered in compliance with ANSI/NFRC 100, ANSI/NFRC 200, and/or NFRC 500 unless the associated validation test requirements have been satisfied, as applicable. RECEIVED 10/31/2022 Version: 01/16/19 Page 3 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 IEVilletel)) 11/17/2022 L intertek 30 D York,PA ( 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 SFCTICIN TEST PROCEDURE The total product, including specific frame, spacer, and glass details,was modeled using NFRC approved software. FRAME AND EDGE MODELING THERM 7.4.4 CENTER-OF-GLASS MODELING WINDOW 7.4.14 TOTAL PRODUCT CALCULATIONS WINDOW 7.4.14 SPECTRAL DATA LIBRARY IGDB 77.0 Modeling Assumptions/Technical Interpretations Any modeling assumptions and technical interpretations required to model this product are listed below. 1) To prevent air infiltration,tape was applied to all interior sash crack locations. 2) This product is available in either a painted or anodized finish. These two finish types may be grouped in accordance with ANSI/NFRC 100-2020, Section 4.2.1.L. The painted finish was simulated since it is the worst case (highest emissivity). 3) The center line modeling approach was conducted using the horizontal intermediate for the head and sill models and the vertical intermediate for the jambs. This procedure is outlined in the NFRC Simulation Manual, Section 8.9. SPECIFIED WINDOW SYSTEM. SECTION z' SIMULATION SPECIMEN DESCRIPTION SERIES/MODEL 1620UT Glazed Wall System (Fiberglass PP) PRODUCT TYPE Glazed Wall System, Curtain Wall FRAME MATERIAL AT-Aluminum w/Thermal Breaks-All Members SASH MATERIAL NA- Not Applicable STANDARD SIZE 2000mm x 2000mm RECEIVED 10/31/2022 Version: 01/16/19 Page 4 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 € itENEU. 11/17/2022 Intertek 1orDerryCourt f lRClinzhi'IJNIt York,DPAerry 17406 linzhid Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No: J7572.05-116-45 Date: 03/25/21 Srrrinni SIMULATION SPECIMEN DESCRIPTION SPACER OPTIONS TYPE PRIMARY SEAL SECONDARY SEAL CODE Royal Kommerling Kodispace 4SG Silicone TP-S GAS FILLING TECHNIQUE FILL TYPE METHOD 48.56%Argon Single Probe, Timed 84.51%Xenon Single Probe, Timed 76.21%Argon Single Probe, Timed 88.54%Argon Single Probe, Timed 78.63%Argon Single Probe, Timed 90.93%Xenon Dual Probe w/Concentration Sensor 96.84%Argon Evacuation Chamber 94.83%Xenon Dual Probe w/Concentration Sensor 74.78%Argon Single Probe, Timed 91.89% Krypton Dual Probe w/Concentration Sensor 62.51%Argon Single Probe, Timed 86.08%Argon Single Probe, Timed 81.60%Xenon Single Probe, Timed 94.54%Xenon Dual Probe w/Concentration Sensor 81.48% Krypton Single Probe, Timed 71.52%Xenon Single Probe, Timed 76.41% Krypton Single Probe, Timed 66.64%Xenon Single Probe, Timed 82.11%Xenon Single Probe, Timed 29.07%Argon Single Probe, Timed 71.72% Krypton Single Probe, Timed 91.21%Argon Single Probe, Timed 56.38%Argon Single Probe, Timed 78.20%Argon Single Probe, Timed 67.02% Krypton Single Probe, Timed 93.26%Argon Single Probe, Timed 76.83% Krypton Single Probe, Timed 78.29%Argon Single Probe, Timed 84.13%Argon Single Probe, Timed 90.54%Xenon Dual Probe w/Concentration Sensor RECEIVED 10/31/2022 Version: 01/16/19 Page 5 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 U. 11/17/2022 Intertek 1orDerryCourt f lRClinzhi'IJNIt York,DPAerry 17406 linzhid Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No: J7572.05-116-45 Date: 03/25/21 crrrinni SIMULATION SPECIMEN DESCRIPTION EDGE-OF-GLASS CONSTRUCTION INTERIOR CONDITION EPDM gasket between aluminum frame and glass EXTERIOR CONDITION EPDM gasket between aluminum pressure plate and glass WEATHERSTRIPPING TYPE QUANTITY LOCATION None - - FRAME/SASH MATERIALS FINISH INTERIOR Painted Aluminum EXTERIOR Painted Aluminum VALIDATION MATRIX* PRODUCT LINE REPORT NUMBER 1620UT Glazed Wall System (Fiberglass PP) J7572-116-45 1620UT SSG Glazed Wall System (Fiberglass PP) J7574-116-45 *These products are part of a validation matrix. Only one is required for validation testing. RECEIVED 10/31/2022 Version: 01/16/19 Page 6 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004IEVillete 11/17/2022 L intertek 30 D York,PA ( 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 ccrTinm c SPECIALTY PRODUCTS TABLE The specialty products method allows the manufacturer to determine the overall product SHGC and VT for any glazing option. The center of glass SHGC and/or VT must be determined using WINDOW 7.4.14. The method calculates overall product SHGC and VT indexed on center of glass properties. All values used in the calculations are truncated to six decimal place precision. No Dividers Dividers< 1 Dividers > 1 SHGCO 0.005550 0.009028 0.012292 SHGC1 0.919626 0.817078 0.720848 VTO 0.000000 0.000000 0.000000 VT1 0.914076 0.808050 0.708556 SHGC=SHGCO+SHGCc(SHGC1 -SHGCO) VT=VTO+VTc (VT1-VTO) RECEIVED 10/31/2022 Version: 01/16/19 Page 7 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 - ate i'l 11/17/2022 int e r tek 30 D York,PA ( 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 SFCTInN F SIMULATION RESULTS TOTAL PRODUCT CALCULATIONS(1620UT Glazed Wall System (Fiberglass PP)) c c c E ,-I N m C e-1 C N C M C .CU . t . t . t . v +. v +• v ++ v 3 U t j� t j� t 2 t _ a_ H > ~ > ~ > ~ ii Gl I- H a) C. C C. C G. C o. 3 a l7 a l7 a C7 a (7 _1 1- o.c co 6 Z Solar Heat Gain Coefficient Visible Transmittance Condensation c o U-Factor (SHGC) (VT) Resistance p (Btu/Hr-Ft2-F) Grids(None/<1/>=1) Grids(None/<1/>=1) (CR) 1 COG=0.4600 0.225 0.500 0.225 ARG49 CL TP-S N U-Factor 0.49 SHGC(N) 0.65 VT(N) 0.72 CR 50 2 COG=0.4400 0.222 0.500 0.225 XEN85 CL TP-S N U-Factor 0.47 SHGC(N) 0.63 VT(N) 0.67 CR 52 3 COG=0.4200 0.236 0.500 0.225 ARG76 0.654(#2) RC TP-S N U-Factor 0.45 SHGC(N) 0.32 VT(N) 0.30 CR 52 4 COG=0.4000 0.223 0.500 0.225 ARG89 0.571(#2) CL TP-S N U-Factor 0.43 SHGC(N) 0.22 VT(N) 0.15 CR 54 5 COG=0.3800 0.236I0.500 0.225 ARG79 0.465(#2) RC TP-S N U-Factor 0.42 SHGC(N) 0.20 VT(N) 0.13 CR 55 6 COG=0.3600 0.236 0.500 0.225 I XEN91 0.465(#2) SR TP-S N U-Factor 0.40 SHGC(N) 0.19 VT(N) 0.13 CR 56 7 COG=0.3400 0.230 0.500 0.225 1 ARG97 0.331(#2) CL TP-S N U-Factor 0.38 SHGC(N) 0.17 VT(N) 0.12 CR 58 8 COG=0.3200 0.230 0.500 0.225 I XEN95 0.331(#2) CL TP-S N U-Factor 0.36 SHGC(N) 0.16 VT(N) 0.12 CR 59 9 COG=0.3000 0.233 0.500 0.225 ARG75 0.166(#2) CL TP-S N U-Factor 0.35 SHGC(N) 0.41 VT(N) 0.49 CR 61 10 COG=0.2800 0.233 0.500 0.225 KRY92 0.166(#2) CL TP-S N U-Factor 0.33 SHGC(N) 0.41 VT(N) 0.49 CR 64 10/31/2022 Version: 01/16/19 Page 8 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004leAkate i'l 11/17/2022 inte r tek 30 D York,PA ( 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 SFCTInN f (Cnntinuadl SIMULATION RESULTS TOTAL PRODUCT CALCULATIONS (1620UT Glazed Wall System (Fiberglass PP)) c c c E e-I N m Tr u III1111 ' ai a) C7 _1 H v) 6 Z Solar Heat Gain Coefficient Visible Transmittance Condensation c o U-Factor (SHGC) (VT) Resistance p (Btu/Hr-Ft2-F) Grids(None/<1/>=1) Grids(None/<1/>=1) (CR) 11 COG=0.2600 0.223 0.500 0.225 ARG63 0.035(#2) CL TP-S N U-Factor 0.31 SHGC(N) 0.36 VT(N) 0.64 CR 63 12 COG=0.2400 0.223 0.500 0.223 ARG86 0.035(#2)/0.035(#3) CL TP-S N U-Factor 0.29 SHGC(N) 0.34 VT(N) 0.57 CR 65 13 COG=0.2200 0.223 0.500 0.223 XEN82 0.018(#2)/0.018(#3) CL TP-S N U-Factor 0.28 SHGC(N) 0.23 VT(N) 0.48 CR 68 14 COG=0.2000 0.223 0.500 0.223 I XEN95 0.018(#2)/0.018(#3) CL TP-S N U-Factor 0.26 SHGC(N) 0.23 VT(N) 0.48 CR 67 15 COG=0.1800 0.223 0.250 0.003 0.250 0.225 KRY81/AIR o.018042)/0.76(#3)/0.11(#4) CL TP-S N U-Factor 0.24 SHGC(N) 0.23 VT(N) 0.52 CR 73 16 COG=0.1600 0.223 0.250 0.003 0.250 0.223 XEN72/AIR o.omaz)/0.761tt3v0.n(K4)/001805) CL TP-S N U-Factor 0.22 SHGC(N) 0.22 VT(N) 0.42 CR 75 17 COG=0.1400 0.223 0.250 0.003 0.250 0.223 I KRY76 0.018(42)/0.76(43)/011(44)/0018(115) CL TP-S N U-Factor 0.20 SHGC(N) 0.21 VT(N) 0.42 CR 77 18 COG=0.1200 0.223 0.250 0.003 0.250 0.223 XEN67 01s0K2)/0.761tt3v0.11IK4)/0018(tt5) CL TP-S N U-Factor 0.19 SHGC(N) 0.21 VT(N) 0.42 CR 79 19 COG=0.1000 0.223 0.250 0.003 0.250 0.223 XEN82 0.018(42)/0.76(43)/0111441/0 018n151 CL TP-S N U-Factor 0.17 SHGC(N) 0.21 VT(N) 0.42 CR 81 20 COG=0.3072 0.225 0.500 0.225 0.500 0.225 AIR CL TP-S N 1U-Factor 0.35 SHGC(N) 0.57 VT(N) 0.64 CR 63i COG U-FACTOR 10/31/2022 Version: 01/16/19 Page 9 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 �ee f 11/17/2022 in t e r tek 130 Derry York, Derry Court ( 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 SFCTInN f ICnntinuadl SIMULATION RESULTS TOTAL PRODUCT CALCULATIONS (1620UT Glazed Wall System (Fiberglass PP)) c c c E ,-I N m H H H H V Y t Y t Y t Y v +. v +• v ++ v 3 aJ t j3 t j� t j3 t _ a_ H > ~ > ~ > ~ ii Gl G1 H Gl C. C C. C G. C Q 3 73 co 0 cora l7 co C7 co C7 _1 1= rn 6 Z Solar Heat Gain Coefficient Visible Transmittance Condensation c o U-Factor (SHGC) (VT) Resistance p (Btu/Hr-Ft2-F) Grids(None/<1/>=1) Grids(None/<1/>=1) (CR) 21 COG=0.3000 0.225 0.500 0.225 0.500 0.225 ARG29 CL TP-S N U-Factor 0.34 SHGC(N) 0.57 VT(N) 0.64 CR 64 22 COG=0.2800 0.225 0.500 0.225 0.500 0.225 KRY72 CL TP-S N U-Factor 0.32 SHGC(N) 0.57 VT(N) 0.64 CR 66 1 23 COG=0.2600 0.226 0.500 0.225 0.500 0.225 AIR/ARG91 0.384(#2) SR TP-S N U-Factor 0.31 SHGC(N) 0.18 VT(N) 0.15 CR 67 24 COG=0.2400 0.221 0.500 0.225 0.500 0.225 AIR/ARG56 0.198(#2) CL TP-S N U-Factor 0.29 SHGC(N) 0.55 VT(N) 0.63 CR 69 1 25 COG=0.2200 0.221 0.500 0.225 0.500 0.225 ARG78 0.198(#2) CL TP-S N U-Factor 0.27 SHGC(N) 0.56 VT(N) 0.63 CR 70 26 COG=0.2000 0.223 0.500 0.225 0.500 0.225 I KRY67 0.113(#2) CL TP-S N U-Factor 0.25 SHGC(N) 0.50 VT(N) 0.62 CR 72 1 27 COG=0.1800 0.221 0.500 0.225 0.500 0.221 AIR/ARG93 0.198(#2)/0.198(#5) CL TP-S N U-Factor 0.23 SHGC(N) 0.53 VT(N) 0.62 CR 74 28 COG=0.1600 0.221 0.500 0.225 0.500 0.221 I KRY77 0.198(#2)/0.198(#5) CL TP-S N U-Factor 0.21 SHGC(N) 0.54 VT(N) 0.62 CR 77 29 COG=0.1400 0.223 0.500 0.225 0.500 0.223 AIR/ARG78 0.035(#2)/0.035(#5) CL TP-S N U-Factor 0.20 SHGC(N) 0.30 VT(N) 0.51 CR 78 30 COG=0.1200 0.223 0.500 0.225 0.500 0.223 ARG84 0.018(#2)/0.018(#5) CL TP-S N J. U-Factor 0.18 SHGC(N) 0.21 VT(N) 0.43 CR 78K` , 1; ,.,, „orr' 10/31/2022 Version: 01/16/19 Page 10 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 € �ili WE U. 11/17/2022 intertek 1Yor ,PAyCourt f lRClinzhi'IJNIt York,PA 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 SFCTInN f ICnntinuprll SIMULATION RESULTS TOTAL PRODUCT CALCULATIONS(1620UT Glazed Wall System (Fiberglass PP)) c c c E ,-I N m Uf c 0c 0c 0N a w w H V C e-1 C N C m C .vs . _c . t . t . v 4- v +• v ++ v 3 U t -0 t -0 t -0 t _ 0- 1- > ~ > ~ > ~ ii N G1 I . co C. C co C. C G. C co Q ra 3 o_ 0 o- l7 a. 0 o- 0 o I- vc co �i 6 Z Solar Heat Gain Coefficient Visible Transmittance Condensation c o U-Factor (SHGC) (VT) Resistance p (Btu/Hr-Ft2-F) Grids(None/<1/>=1) Grids(None/<1/>=1) (CR) 31 COG=0.1000 0.223 0.500 0.225 0.500 0.223 XEN91 0.018(442)/0.018(#5) CL TP-S N U-Factor 0.16 SHGC(N) 0.21 VT(N) 0.43 CR 79 RECEIVED 10/31/2022 Version: 01/16/19 Page 11 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 r U17/2022 L in terte k 1nuiliCE DerryA Court �p nzh30York, 17406 linzhid Total Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 cErTI( M - DRAWINGS/ BILL OF MATERIALS The drawings which follow have been reviewed by Intertek B&C and are representative of the simulation results reported herein. Any deviations are documented herein or on the drawings. RECEIVED 10/31/2022 Version: 01/16/19 Page 12 of 30 RT-R-AMER-Test-4044 ASPEN BUILDING DEPARTMENT REV/ENE 11/17/2022 I FIXED FENESTRATION B001, B002, B003, & B004 RMcoutcurwuMME linzhid V - ROYAL/KOMMERLING KODISPACE 4SG MATERIAL 0o SILICONE SEALANT VARIES DETAIL FOR THERMAL MODELING OF ROYAL/KOMMERLING KODISPACE 4SG SPACER(TP-S) RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT FIXED FENESTRATION B001, B002, B003, & B004 rU. 11/ill ENE 17/2022 in terte k York,1 Derry Court f lRClinzhi'IJNIt 30Der 17406 linzhid Quality.Assured. Telephone: 717-764-7700 Facsimile: 717-764-4129 www.intertek.com/building TEST REPORT FOR KAWNEER COMPANY INC. Report No:J7572.05-116-45 Date: 03/25/21 CCP'TItV I f REVISION LOG REVISION # DATE PAGES REVISION .05R0 09/09/19 N/A Original report issue. .08R0 03/25/21 N/A Added Options#20-31 (Triple Glazed). RECEIVED 10/31/2022 Version: 01/16/19 Page 30 of 30 RT-R-AMER-Test-4044 ASPEN PIIILDING DEPARTMENT villevE 11/17/2022 44N0' d linzhid FORCOOMMLIANCE ENTRY BIPARTING SLIDING tall g/ DOORS L1 A & L1 B CITY OF ASPEN Memorandum of Policy Building Codes From: Mike Metheny Date: May 10, 2018 Revised: Date: June 1, 2020 Subject: Fenestration U-factor Documentation The following are acceptable methods under the IECC to verify fenestration U- ► factors as part of the building thermal envelope: 0 w 1. NFRC certification, factory assembled: NFRC label applied to window assembly and verified at field inspection. Lu 2. NFRC certification, site assembled: provide an NFRC CPD number or certificate of authorization from an NFRC authorized inspection agency prior to permit approval. To document the chain of custody, project specific NFRC labels must be affixed to the units or a project specific NFRC label certificate must be provided prior to field inspection. 3. Provide a simulation or test by an NFRC-accredited lab in accordance with NFRC-100 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the simulation or test is required prior to field inspection. 4. Provide a calculation using 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3: "U-Factor (Overall Coefficient of Heat Transfer)" prior to permit approval. Calculation is required to be in the standard NFRC window size of 47.2"x 47.2". To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the calculation is required prior to field inspection. 5. Use default values from Table 4 U-Factors for Various Fenestration Products in 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the values is required prior to field inspection. 6. Use default values from IECC tables in chapter 3 of the residential and commercial sections. RECEIVED 10/31/2022 130 South Galena Street Aspen,CO 81611-1975 I P:970.920.5000 I F:970.920.5197 I cityofaspen.com ASPEN BUILDING DEPARTMENT ENTRY BIPARTING SLIDING DOORS L1 A & L1 B onig IN 11/17/2022 U CERTIFICATE OF COMPLIANCE OVERALL RATING i wtE inzhd U-Factor: zhi (Btu/h•ft2•°F) '67 Certificate Authorization SHGC: ,2 7 Name: Company: Richard Middleton Eagle Glass GJ Signature: Date: Aich'ard-Mtlitieton 10-28-2022 CERTIFIES THAT THE MATERIALS LISTED ON THIS CERTIFICATE WERE INSTALLED ON THE PROJECT IDENTIFIED PROJECT INFORMATION: The Residences at The Little Nell Street Address: 501 East Main Street City: State: Zip: Aspen CO 81601 GLAZING CONTRACTOR/INSTALLER: Contact Person: Eaglite DBA Eagle Glass Keegan Simons Street Address: Phone Number: 2520 W Pinyon Ave 970-245-0399 City: State: Zip: Grand Junction CO 81505 GLAZING MATERIAL SUPPLIER: Contact Person: Vitro Architectural Glass Ashley Clark Street Address: Phone Number: 400 Guys Run Rd 415-405-6821 City: State: Zip: Cheswick PA 15024 Glass and Spacer Type: Solarban 60/Air/Clear-6mm 1" _ Center-of-glass(C.O.G.)U-factor: Center-of-glass(C.O.G.)SHGC: .29 Btu/h•ft2•°F .39 FRAMING MATERIAL SUPPLIER: Contact Person: ASSA ABLOY Entrance Systems US Inc _ Brooks Munoz Street Address: Phone Number: 8811 American Way Suite#165 303-858-9915 City: State: Zip: Englewood CO 80112 U-factor Matrix SHGC Matrix (BtU/h•ft2•°F) Product Line: C.O.G. OVERALL C.O.G. OVERALL ASSA ABLOY SL500 R92 U-factor U-factor SHGC SHGC 0.47 0.79 0.75 0.46• - 0.46 0.78 0.70 0.43 The overall ratings for U-factor and SHGC are based on a size of g 0.44 0.77 0.65 0.40 1920 mm x 2090 mm(75.5 in x 82.375 in) w _ 0.42 0.76 _ 0.60 0.37 N 0.40 0.75 0.55 0.35 as required in NFRC 100. w• 0.38 0.74 0.50 0.32 a 0.36 0.73 0.45 0.29 Overall U-factors and Solar Heat Gain Coefficients(SHGC)listed F 0.34 0.72 0.40 0.26 in the matrix were determined in accordance with NFRC 100 and NFRC 200 respectively by a NFRC accredited laboratory. 0.32 0.71 0.35 0.23 0.30 0.70 0.30 0.21 ACCREDITED LABORATORY: 0.28 0.69 0.25 0.18 0.26 0.68 0.20 0.15 Molimo Architectural Product Testing _ 0.24 0.67 0.15 0.12 Reference Test Report#: 0.22 0.66 0.10 0.09 2707.01-111-24 0.20 0.65 0.05 0.07 Directions: Fill out form completely. Determine the Overall 0.18 0.64 Rating for this project by using the C.O.G.U-Factor and C.O.G. 0.16 0.63 M SHGC from Table 1 and looking up the overall ratin D 0.14 0.62 M 2. Indicate the Overall Rating in the space abov ,�► I\FE 0.12 0.61 interpolation is permitted. 0.10 0.60 10/31/2022 APRIL 2021 COCA031 95516ASPEN BUILDING DEPARTMENT o1 5 , vo7. ■ MOIimO ENTRY BIPARTING SLIDING DOORS L1 A & L1 B -A) Architectural Product Testing Page ' Tinzhid� CLIENT INFORMATION: Assa Abloy Entrance Systems US Inc. 1900 Airport Road NFRC ACCREDITED LAB. Monroe, North Carolina 28110 / REFERENCE PAGE 5 OF THE REPORT. TEST LABORATORY: Molimo, LLC L/ 1410 Eden Road York, Pennsylvania 17402 SPECIFIED ENTRY DOOR 717-916-6300 SYSTEM. GLAZING SELECTION AND COMBINATION U-FACTOR SERIES/MODEL: ASSA ABLOY SL500 R92 ON PAGE 8 OF THE REPORT. SIMULATION DATE: 1/21/2021 REPORT DATE: 1/21/2021 RETENTION DATE: 1/21/2026 PROJECT SUMMARY: Molimo, LLC was contracted to perform testing on the above referenced product. Testing was performed to evaluate U-factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance performance of the product. The product description, test procedures, and test results are reported herein. The results are simulated values and were secured by using the following test methods. All results were calculated using the latest approved versions of THERM 7, WINDOW 7, OPTICS 6, and also the International Glazing Database. ANSI/NFRC 100-2020: Procedure for Determining Fenestration Product U-Factors ANSI/NFRC 200-2020: Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence ANSI/NFRC 500-2020: Procedure for Determining Fenestration Product Condensation Resistance Values Program Versions Utilized: THERM/WINDOW 7.7;NFRC 101-2020[E0A1];NFRC Sim Manual 2020 SPECIMEN DESCRIPTION: Type: DDSG -Sliding Glass Door (XX or OX) Frame Material: AL-Aluminum (Non-thermally broken) Sash Material: AL-Aluminum (Non-thermally broken) Standard Size: 2000 mm x 2000 mm (79 in x 79 in) RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT EIPAIEWAVE M 0I1 MO ENTRY BIPARTING SLIDING DOORS L1 A & L1 B 27o7.oi 1- 7i2o22 J����pp��yyyy�; .�. Architecw,m Product Testing Page L 1"C'nculalANCE linzhid MODELING ASSUMPTIONS OR TECHNICAL INTERPRETATIONS: None SPECIALTY PRODUCTS TABLE: The specialty products method allows manufacturers to determine overall product SHGC / Vt for any glazing option.The center of glass (COG) SHGC/Vt must be determined using the current approved version of WINDOW 7. The method gives overall product SHGC/Vt indexed on COG properties. All values used are truncated to 6 decimal places. No Dividers Dividers< 1 Dividers> 1 SHGCO 0.031516 0.034367 0.037003 SHGC1 0.650874 0.566996 0.489435 VTO 0.000000 0.000000 0.000000 VT1 0.619354 0.532625 0.452428 SHGC=SHGCO+SHGCc(SHGC1 -SHGCO) VT=VTO+VTc (VT1 -VTO) VALIDATION MATRIX: The following products are part of a validation matrix. Only one is required for validation testing. Product Report None - RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT Di2707.01 VIE M OI I mO ENTRY BIPARTING SLIDING DOORS L1 A & L1 B 4 -b Architectural Product Testing Page Mot* ��p42`ro"� linzhid SPACER DESCRIPTION: Primary Secondary Spacer Type Code Sealant Sealant Aluminum Spacer Polyisobutylene Silicone Al-D GRID DESCRIPTION: Grid Size Grid Type Grid Pattern None - - REINFORCEMENT DESCRIPTION: Location Material None - GAS FILL DESCRIPTION: Fill Type Method 90%Argon Single Probe EDGE OF GLASS CONSTRUCTION: Interior EPDM gasket against glass Exterior EPDM gasket against glass WEATHERSTRIPPING: Type Quantity Location None - - FRAME/SASH MATERIALS FINISH: Interior Painted Aluminum Exterior Painted Aluminum RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT DEMON ■ MOIImo ENTRY BIPARTING SLIDING DOORS L1 A & L1 B 2707.01- 12417/2022 2 Architectural Product Testing Page. nzhid Molimo, LLC is an NFRC accreditated simulation laboratory and all simulations were conducted in full compliance with NFRC approved procedures and specifications. The NFRC procedure requires that the computational results be verified through physical test results. A copy of this report, detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Molimo, LLC for a period of five years from the original test date. At the end of this retention period,the service life of this report will expire. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) simulated. This report may not be reproduced, except in full, without the written permission of Molimo, LLC. The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, thermal bridging that may occur due to the specific design and construction of the fenestration system opening.This value is NOT equivalent to a Condensation Resistance Factor(CRF) determined in accordance with AAMA 1503. Ratings values included in this report are for submittals to an NFRC-licensed IA and are not meant to be used directly for labeling purposes. Only those options identified on a valid Certificate of Authorization (CA) by an NFRC accredited Inspection Agency (IA) are to be used for labeling purposes. The rating values were rounded in accordance to NFRC 601, NFRC Unit and Measurement Policy. For MOLIMO, LLC: Joseph Descheemaeker Joseph Descheemaeker Project Manager-Simulations Project Manager-Simulations Simulator-in-Responsible-Charge Simulator-in-Responsible-Charge JRD:dro Attachments(pages): This report is complete only when all attachments listed are included. Appendix A: NFRC 100/200/500 Summary Sheet(1) Appendix B: Drawings and Bills of Material (2) This report was produced from controlled document template MMO-00078, Rev. 0, 11/13/2018. RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT ■ MOlin10 ENTRY BIPARTING SLIDING DOORS L1 A & L1 B 2707.01- . 12417/2022 9) Architectural Product Testing Page Iinzhid� Revision Log Rev.# Date Pages Revisions .01 1/21/2021 All Original report issued RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT rata 11/17/2022 Molimo ENTRY BIPARTING SLIDING DOORS Li A & L1 B -j FOR Architectural Product TestingcCOIRUANCE linzhid Appendix A NFRC 100/200/500 Summary Sheet 2707.01-111-24 RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT ate 11 ■ Molimo ENTRY BIPARTING SLIDING DOORS L1 A & L1 B iiii7i2o22 1...) FORCOOECUMPLIANCE Architecn:ral Product 7e sting linzhid NFRC-ACCREDITED LAB I NFRC 100/200/500 Summary Sheet .7 2707.01-111-24 NFRC 100 SIMULATION SUMMARY ASSA ABLOY SL500 R92 No Grids Grids<1" Grids>1" Option Description Glass Thicknesses Gap Widths Gas Emissivity(SFC) Spacer Divides U-Factor CR Tint SHGC VT SHGC VT SHGC VT 1 Clear-6mm 0.224 - - - - N 1.10 13 CL 0.545 0.552 - - - - 2 Clear-030PVB-Clear-ss LAMI 0.243 - - - - N 1.08 13 CL 0.526 0.548 - - - - 3 Solarban 60(E)-090SGP-Clear-6mm LAMI 0.536 - - 0.035(Embedded) - N 1.04 17 CL 0.312 0.440 - - - - 4 Clear-060PVB-Clear-ds LAMI 0.304 - - - - N 1.06 15 CL 0.515 0.544 - - - - l 5 LoE2-270/90%Argon/Clear-6mm 1" 0.224,0.224 0.500 ARG 0.035(2) A1-D N 0.64 20 CL 0.252 0.419 - - - - 6 ClimaGuard 70/36/90%Argon/Clear-6mm 1" 0.221,0.221 0.500 ARG 0.036(2) Al-D N 0.64 20 CL 0.264 0.425 - - - - e 7 Solarban 60/Air/Clear-6mm 1" 0.223,0.223 0.500 AIR 0.035(2) Al-D N 0.67 20 CL 0.273 0.436 - - - - 8 Solarban 60/90%Argon/Clear-6mm 1" 0.223,0.223 0.500 ARG 0.035(2) Al-D N 0.64 20 CL 0.271 0.436 - - - - 9 Energy Select 40/90%Argon/Clear-6mm 1" 0.224,0.225 0.500 ARG 0.034(2) Al-D N 0.64 20 CL 0.269 0.430 - - - - 10 Energy Advantage/90%Argon/Clear-6mm 1" 0.222,0.223 0.500 ARG 0.157(2) Al-D N 0.67 20 CL 0.416 0.452 - - - - 11 SunGuard SuperNeutral 68/90%Argon/Clear-6mm 1" 0.221,0.221 0.500 ARG 0.039(2) Al-D N 0.64 20 CL 0.262 0.421 - - - - 12 Solarban 70/90%Argon/Clear-6mm 1" 0.223,0.223 0.500 ARG 0.018(2) A1-D N 0.64 20 CL 0.198 0.399 - - - - 13 SunGuard SNX 62/27/90%Argon/Clear-6mm 1" 0.221,0.221 0.500 ARG 0.020(2) Al-D N 0.64 20 CL 0.194 0.382 - - - - 14 Solarban 60/Air/Clear-6mm 0.625" 0.129,0.129 0.375 AIR 0.035(2) A1-D N 0.69 20 CL 0.282 0.449 - - - - 15 Solarban 60/90%Argon/Clear-6mm 0.625" 0.129,0.129 0.375 ARG 0.035(2) A1-D N 0.66 20 CL 0.279 0.449 - - - - 16 Solarban 70/90%Argon/Clear-6mm 0.625" 0.129,0.129 0.375 ARG 0.018(2) A1-D N 0.66 20 CL 0.197 0.389 - - - - RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT reef) Molimo ENTRY BIPARTING SLIDING DOORS Li A & L1 B 11/17/2022 J Architectural Product Tcstieri FORCOOMINFLIANCE linzhid Appendix B Drawings and Bills of Materials 2707.01-111-24 RECEIVED 10/31/2022 WWW.MOLIMO.COM ASPEN BUILDING DEPARTMENT liel#000 ENTRY BIPARTING SLIDING DOORS L1 A & L1 B FORCODCWAVLIANCE linzhid ASSA ABLOY ENTRANCE SYSTEMS ASSA ABLOY SL500 SSA��� 1900 AIRPORT ROAD OVERALL ROUGH CLEAR DOOR BREAKOUT 1K�h1x/'�` MONROE,NC 28110 Windload MODEL NO. FRAME WIDTH OPENING OPENING WIDTH WIDTH PHONE:1-866-237-2687 (A) (B) (C) (0) (E) SPECDESK.NA.ENTRANCE@ASSAABLOY.COM Overhead Concealed,Narrow Stile.Full Breakout,Single Slide AT MAX 96" 96 1/2" 40 1/8" 47 7/8" 44 1/2" WIDTH [2438.4] [2451.1] [1019.2] [1216] [1130.3] ELECTRICAL SUPPLY WIDTH B-1/2" A+1/2" A/2-77/8" A/2-1/4" A- 10" B i-- 110 VAC.60HZ.10A. 4 1/2" FORMULA B-[12.7] A+[12.7] A/2-[200] A/2-[6.35] A-[254.0] BY ELEC.CONTR.TO JUNCTION BOX. [114.7] 92" 92 1/4" 83" n SUPPLY IN SAME LOCATION WOOD,STEEL AT MAX HEIGHT ® L J REGARDLESS OF HANDING OR CONCRETE, ' [2336.8] [2343.2] [2108.2] � ' HEIGHT B-1.35 A+1.35 A-9" _- FORMULA B-[6.35] A+[6.35] A-[228.6] ACCESS COVER --��+�" GLASS FORMULA:OFW/2-5 5/8[142.9]X OFH-17"[431.8] OPTIONAL S[11Y- MUNTINS p� +_ MOTION/PRESENCE FSENSORS tS0 *.l...lirli,3 POINT STANDARD �111 A/R#1850 SERIES I I�]': NOTES: LOCK BODY w/THUMBTURN $ ;�I' STANDARD PACKAGE CONSISTS OF: SINGLE POINT RELEASE [204.5] - STANDARD FINISH: I PER ACTIVE PANEL CLASS 1,.018MM,CLEAR-AA-M12C22A41 ROUGH CLASS 1..018MM,DARK BRONZE-AA-M12C22A44 LOCK OPENING I� • AUTOMATIC OPERATOR HEIGHIi' • NARROW STILE RAILS (B) THRESHOLD • 3-POINT LOCK WITH LOCK INDICATOR • 1/4"[6mm]TEMPERED GLASS _ • DRY GLAZED 41 1/2" �+ • MOTION/PRESENCE SENSORS [1054.1] L i�~ CLEAR • 5-POSITION KNOB SWITCH �nla�l �nla�1 OVERALL OPENING � BALL CATCH II L FRAMEHEIGHT DUAL CONCEALED SWEEPS IN SX&SO PANELS A HEIGHT iIiii (C) •OPTIONS"BOTTOM RAILS -] F.F.L. NS AVAILABLE: • SPECIAL FINISHES • PANIC EXIT DEVICE EXTERIOR ELEVATION BR DE UT 1111 III' /10"BOTTOM RAILS R DIVIDEDS SHOOL AD-UP, EE SHEET AA-30 FOR DETAILS TRUE• SCALE-1:5 FLOOR MUST BE WITHIN 1/8"OF LEVEL ''O D , Lai • FALSE MUNTINS ALONG OVERALL FRAME WIDTH. f r� � LH SLIDE SHOWN OPENING NOT TO BE CONCAVE. -'� SEE SHEET OS-10 FOR ALL OTHER OPTIONS AND (RH SLIDE OPPOSITE) I�I OPTION DETAILS 4" [101.6] �: �'d��I II ) [/ SWEEP FOR MAXIMUM CURRENT DRAW,SEE PRODUCT SPECIFICATION, 0 0 . -�'�1 ]E ,I INSTALLATION INSTRUCTIONS,OR THE UL LABEL ON THE EQUIPMENT. ,_ OPTIONAL FACTORY PREP _i_ PIVOT POINT F.F.L. ��� L�`�� TEST PROTOCOLS:ASTM F842-17 GRADE xn FOR SWITCH LOCATION @ 1/4" 1/2" ASTM E 283 TESTED TO 1.57PSF FOR 1.0 CFM/SF/MIN 74-1/2"H[1892.3] -® ROUGH OPENING WIDTH(B) [6.4] [12.7] REFER TO TEST REPORT XXXXXXX FOR DETAILS __ SECTION B-B U-VALUE INFO HERE: OVERALL FRAME WIDTH(A) 1/4" SCALE-1:1 DOOR WIDTH(D) [6.4] REFER TO RELEVANT[LOCAL,STATE,NATIONAL,OR AHJ] SHIM TYP BUILDING CODE FOR MIN DOOR HEIGHT&MIN/MAX WIDTH ALLOWABLE FOR EGRESS REQUIREMENT IN CONJUNCTION WOOD.STEEL "�� \ T • WITH TABLE. OR CONCRETE\ v = , \ +Q qr 4 1/2" M o I i m o•• o� [114.3] ■no w. i`J / 1 Architectural Product Testing / Report#: 2707.01-111-24 .w"° 1021497 BREAKOUT SIDE I i / 1 3/4" I / / °""a I°"" I�,r.". Io',E I I ccc9/9/20: SECTION A-AI [44.5] Date: 2/10/2021 SJF 9/9/2020 0 SCALE-1:1 DOOR WIDTH(D) / / LH SLIDE SHOWN /1E11 //�/ CLEAR OPENING WIDTH(C) By: J RD (RH SLIDE OPPOSITE) J s ir-1 ,-- • - BREAKOUT WIDTH(E) ASSA AlEIL09,E-r-BVELD ASSA ABLOY (MANUFACTURER) SHOP DRAWINGS 0/31/2022 WITH STAMP OF THE NFRC-ACCREDITED LAB, CONFIRMING SPECIFIED SYSTEM COMPLIANCE. ASPEN BUILDING DEPARTMENT i..,-, ASS 1900 AIRPORT ENTRANCE SYSTEMS GENERAL DOOR OPTIONS 1/17/2022 9)1900 AIRPORT ROAD MONROE, NC 28110 PHONE: 1-866-237-2687 ASSA ABLOY SL500 RESILIENCE GLASS SIZES I il"Z i J SPECDES K.NA.ENTRANCE@ASSAABLOY.COM (°• 59 ) ENTRY BIPARTING SLIDING (0.68") ® DOORS L1 A & L1 B • o o 0 o o a0 © • ) O Mama 9/16" LEVEL D Architectural Product Testing 9/16" LEVEL E Report#: 2707.01-111-24 Date: 2/10/2021 (1/4") ,• 1 (1") By: MD D CI © 0 0 O ED 0 . r \ • oiØO , rj1,,. ril4H ON 4.1. NON-IMPACT 1" INSULATED IMPACT LEVEL D ASSA ABLOY(MANUFACTURER) SHOP DRAWINGS Resilience Package Glass Options WITH STAMP OF THE NFRC-ACCREDITED LAB, CONFIRMING SPECIFIED SYSTEM COMPLIANCE. Product Glass Size Impact Rating R104 9/16" Level D 9/16" Level E 1" Level D 1/4" Non-Impact R128 1/4" Non-Impact 9/16" Level D ITEM NO. PART NUMBER DESCRIPTION QTY. 1 1015700 Resilience Gutter 4 2 1015701 Resilience Snap, 9/16" glass 3 3 1015702 Resilience Snap, 1" IG 1 DwcNo. 4 1703425 Tremco TR-23824E Wedge Seal 1 1017987 5 1703424 Tremco TR-23823E Fixed Seal 1 DRN BY DBN DATE 10/16/18 CHK BY SF DATE 10/18/19 REV.3.0 DATE 12/17/19 6 1703423 Tremco TR-2321E Wedge Seal 2 7 1703422 Tremco TR-4506P Wedge Seal 1 8 1703638 Tremco TR-4869 Fixed Seal 2 RECEIVED 9 1703421 Tremco TR-10510P Fixed Seal 1 10 1016294 Glazing Spacer Block 4 11 glass 1"Insulated Glass 1 10/31/2022 12 glass 1/4" Non-Impact Glass 1 13 glass 9/16" Level E Impact Glass 1 ASSAABLIN 14 glass 9/16" Level D Impact Glass 1 ASPEN BUILDING DEPARTMENT villevE 11/17/2022 44N0' d linzhid FORCOOMMLIANCE DOUBLE SWING tall g/ DOORS L2 A & L2 B CITY OF ASPEN Memorandum of Policy Building Codes From: Mike Metheny Date: May 10, 2018 Revised: Date: June 1, 2020 Subject: Fenestration U-factor Documentation The following are acceptable methods under the IECC to verify fenestration U- ► factors as part of the building thermal envelope: 0 w 1. NFRC certification, factory assembled: NFRC label applied to window assembly and verified at field inspection. Lu 2. NFRC certification, site assembled: provide an NFRC CPD number or certificate of authorization from an NFRC authorized inspection agency prior to permit approval. To document the chain of custody, project specific NFRC labels must be affixed to the units or a project specific NFRC label certificate must be provided prior to field inspection. 3. Provide a simulation or test by an NFRC-accredited lab in accordance with NFRC-100 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the simulation or test is required prior to field inspection. 4. Provide a calculation using 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3: "U-Factor (Overall Coefficient of Heat Transfer)" prior to permit approval. Calculation is required to be in the standard NFRC window size of 47.2"x 47.2". To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the calculation is required prior to field inspection. 5. Use default values from Table 4 U-Factors for Various Fenestration Products in 2013 (or later) ASHRAE Fundamentals Handbook chapter 15, pg. 15.3 prior to permit approval. To document the chain of custody, an affidavit or other evidence from the manufacturer confirming compliance with the values is required prior to field inspection. 6. Use default values from IECC tables in chapter 3 of the residential and commercial sections. RECEIVED 10/31/2022 130 South Galena Street Aspen,CO 81611-1975 I P:970.920.5000 I F:970.920.5197 I cityofaspen.com ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B riElfiaii) 7/2022 CERTIFICATE OF COMPLIANCE OVERALL RATING Eclat zh PL U-Factor: inZnia (Btu/h•ftz•°F) .66 Certificate Authorization SHGC: ,23 Name: Company: Richard Middleton Eagle Glass GJ Signature: Date: hinyrNit°n 10-28-2022 CERTIFIES THAT THE MATERIALS LISTED ON THIS CERTIFICATE WERE INSTALLED ON THE PROJECT IDENTIFIED PROJECT INFORMATION: The Residences at the Little Nell Street Address: 501 East Dean Street City: State: Zip: Aspen CO 81601 GLAZING CONTRACTOR/INSTALLER: Contact Person: Eaglelite DBA Eagle Glass Keegan Simmons Street Address: Phone Number: 2520 W Pinyon Ave. 970-245-0388 City: State: Zip: Grand Junction CO 81505 0 GLAZING MATERIAL SUPPLIER: Contact Person: Manko Window Systems Sam Sloan Street Address: Phone Number: 17500 E 22nd Ave 720-326-3491 City: State: Zip: Aurora CO 80011 Glass and Spacer Type: Quanex Tri-Seal Center-of-glass(C.O.G.)U-factor: Center-of-glass(C.O.G.)SHGC: .24 Btu/h•ft2•°F .36 FRAMING MATERIAL SUPPLIER: Contact Person: Kawneer Cameron Hendrix Street Address: Phone Number: 4837 W 2400 S Suite 100 801-974-9022 City: State: Zip: West Valley City UT 84120 U-factor Matrix (Btu/h•ft2•°F) SHGC Matrix Product Line: C.O.G. OVERALL C.O.G. OVERALL 350/350 Tuffline/350 Heavy Wall U-factor U-factor SHGC SHGC Door Pair 0.47 0.79 0.75 0.46 4 0.46 0.78 0.70 0.43 The overall ratings for U-factor and SHGC are based on a size of 0.44 0.77 0.65 0.40 1920 mm x 2090 mm(75.5 in x 82.375 in) 0.42 0.76 0.60 0.37 N 0.40 0.75 0.55 0.35 as required in NFRC 100. iTa 0.38 0.74 0.50 0.32 Overall U-factors and Solar Heat Gain Coefficients(SHGC)listed 0.36 0.73 0.45 0.29 in the matrix were determined in accordance with NFRC 100 and 0.34 0.72 0.40 0.26 NFRC 200 respectively by a NFRC accredited laboratory. 0.32 0.71 0.35 0.23 0.30 0.70 0.30 0.21 ACCREDITED LABORATORY: 0.28 0.69 0.25 0.18 0.26 0.68 0.20 0.15 Architectural Testing 0.24 0.67 0.15 0.12 Reference Test Report#: 0.22 0.66 0.10 0.09 A8170.04-116-45 0.20 0.65 0.05 0.07 Directions: Fill out form completely. Determine the Overall 0.18 0.64 I Rating for this project by using the C.O.G.U-Factor and C.O.G. 0.16 0.63 SHGC from Table 1 and looking up the overall ratin f NED 0.14 0.62 2. Indicate the Overall Rating in the space abov ,.fir 0.12 0.61 I interpolation is permitted. 0.10 0.60 10/31/2022 APRIL 2021 COCA031 95516A1T EN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B D �j NO N•RESIDENTIAL FENESTRATIO NCALCULATIO NREPO RT / BID REPO RT 11/17/2022 91 ACCO RDING TO NFRC CM APRO CEDURES-NFRC STANDARD SIZE. FORCCOttAAWUNICE linzhid NO 7E: This is NO Tan NFRC Label Certificate. This document can NO The used in place of a NFRC Label Certificate and can be used only for Bid and Design Purposes. , , Project Information/Number: BR-KAW-18751 Bid Report G eierated By: K awneer Corn pany Inc. ProjectName: Residences at Little Nell Project Address: 501 East Dean Street Project City: Aspen State: CO ZIP code: 81611 Specifying Company Name: Kawneer Corn pony Inc. Specifying Authority Contact Person: S G eg B McKenna pecifying Company Phone: 770-840-6433 Frame Component Uploaded By: Approved Entity Frame Component Status: Approved Spacer Com ponent Uploaded By: Approved Entity Spacer Com ponent Status: Approved PRO DUCT LISTING : Performance at NFRC Standard Size ID Name Framing Ref I G azing Ref S pacer Ref U SHG C VT Btu/h•ft2•F - - P-KAW- 1620UT System FA-KAW- G AG N-25366 S A-NFC-7183 0.28 0.30 0.53 116437 1 FG R3 Triple 145508 G I SG SN68 (#2)Clr, Air,Clr,Air,IS20 (#6)Clr, Warm l ,e) Edge Spacer P-KAW- 350 Door Pair, FA-KAW- G AG N-25325 S A-NFC-7183 0.66 0.23 0.37 116440 SG SN68 (#2) 145349 Clr, Air, IS20 (#4) Clr, Warm Edge Spacer Copy FRAM E, G LAZING AND SPACER ASSEM BLIES: G LAZING LISTING : G bzing Ref S upplier ID D escription G N-25325 G ardian 1 /4" SunG Lard SN68 (#2) Clr, 1/2" Air, 1/4" IS20 (#4) Clr G A N-25366 G ardian 1 /4" SunG Lard SN68 (#2) Clr, 1/2"Air, 1/4" Clr, 1/2"Air, 1/4" IS20 (#6) Clr SPACER LISTING : Spacer Ref S upplier ID D escription SA-NFC-7183 N e FRC G neric Warm Edge Spacer Non Metallic NFRC Path I, G pup 4 FRAM NG LISTING :Framing Ref S upplier ID D escription RECEIVED FA-KAW-145349 K awneer Company Inc. ' L-KAW-1720 350 Non Therm al Door Pair 10/31/2 02 2 ASPEN BUILDING DEPARTMENT FRAM NG LISTING : DOUBLE SWING DOORS L2 A & L2 B regfii-)1 7/2022 IV Framing Ref S upplier ID D escription , FORC011tiVailiitiCE 1inlzhid FA-KAW-145508 K awneer Corn pony Inc. ' L-KAW-6438 1620UT System 1 FG FP Triple G tize q (7, O (-.- 0° 10 0 O \vie ck) O / \,:. F 0 O, o (c::: 0 ":::::„7 +CI RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT ORINEWAET �..y; DOUBLE SWING 28.october.2022 GLASSIAN PERFORMANCE ��MI (� DOORS L2 A & L2 B By Sloan,Sam WIND O SYSTEMS INC. �` _�a cpocib1• CALCULATOR -1FCRODOMX111/FIJANCE linzhid New Project 05 Visible Light Solar Energy Thermal Properties Make-up Glass 1 & Glass 2& Transmitt Transmitt Reflectan Solar Heat Make-up Name Reflectance U-Value Icon Coating Coating ance ance ce Gain Coefficient Visible (T %) p %out %in Solar(re%) p %out (SHGC) Winter Night Summer Day v v pv e (Btu/hr.ftr F) (Btu/hrft'F) SunGuar SunGuar d®IS 20 d®SN 68 Interior (North Surface America) LE(North Default Make-up 01 14 on America) 66 12 13 32 33 0.36 0.238 0.217 Guardian on Clear Guardian Glass Clear (North Glass America) (North America) SunGuar d®SN 68 AGC (North Energy America) Select® on Default Make-up 02 ik Guardian 73 Plus 65 13 16 32 34 0.36 0.236 0.215 Clear (IGDB)on Glass PureVisio (North n(IGDB) America) Calculation Standard:NFRC 2010 Default Make-up 01 Outdoors Guardian Clear Glass(North America) #1 GLASS 1 Thickness=1/4"(6mm) #2 SunGuard®SN 68(North America) GAP 1 100%Air,1/2"(12.7mm) Guardian Clear Glass(North America) #3 GLASS 2 Thickness=1/4"(6mm) #4 SunGuard®IS 20 Interior Surface LE(North America) Total Unit(Nominal)=1 in Slope=90° Window Height=1 meter Estimated Nominal Glazing Weight:5.75 lb/ft2 Indoors IS 20 must be heat-treated for all applications and uses. RECEIVED 10/31/2022 ASPEN BUILDING DE15ARI 1T DOUBLE SWING DOORS L2 A & L2 BA 1832E gat U 9543 11/17/2022 14 FORCElinzhidlNIICE lin:m*1 Architectural Testing NFRC ACCREDITED LAB. REFERENCE PAGE 11 OF THE REPORT. NFRC U-FACTOR,SHGC,VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: KAWNEER COMPANY,INC. SPECIFIED DOOR SYSTEM. SERIES/MODEL: I/ 190 Pair Door 350 Tuffline Pair Door/350 Heavy Wall Pair Door/350 Pair Door 500 Tuffline Pair Door/500 Heavy Wall Pair Door/500 Pair Door Report Number: A8170.04-116-45 Report Date: 03/03/11 RECEIVED 130 Derry Court York, PA 17406-8405 1 0/3 1/2 0 2 2 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 1s3�6 . 9543 , 11/17/2022 14 FORC linzhidlNIICE linzhid Architectural Testing NFRC U-FACTOR, SHGC,VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: KAWNEER COMPANY,INC. 555 Guthridge Court Norcross, Georgia 30092 Report Number: A8170.04-116-45 Simulation Date: 03/03/11 Report Date: 03/03/11 Project Summary: Architectural Testing, Inc. was contracted to perform U-Factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance* computer simulations in accordance with the National Fenestration Rating Council (NFRC). The products were evaluated in full compliance with NFRC requirements to the standards listed below. *NFRC's Condensation Resistance rating is NOT equivalent to a Condensation Resistance Factor(CRF) determined in accordance with AAMA 1503. Standards: NFRC 100-2010: Procedure for Determining Fenestration Product U-Factors NFRC 200-2010: Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence NFRC 500-2010: Procedure for Determining Fenestration Product Condensation Resistance Values Software: Frame and Edge Modeling: THERM 6.3.19 Center-of-Glass Modeling: WINDOW 6.3.9 Total Product Calculations: WINDOW 6.3.9 Spectral Data Library: 18.0 SPECIFIED DOOR SYSTEM WITH WARM EDGE SPACER ON GLASS. Simulations Specimen Description: U-FACT ON PAGE 8 OF THE REPORT. Series/Model: 190 Pair Door 350 Tuffline Pair Door/350 Heavy Wall Pair Door/350 Pair Door 500 Tuffline Pair Door/500 Heavy Wall Pair Door/500 Pair Door Type: Swinging Door,Double Leaf Entrance Door Frame Material: AL Aluminum(Non-thermally broken) Sash Material: AL Aluminum (Non-thermally broken) Standard Size: 1920mm x 2090mm RECEIVED 130 Derry Court York, PA 17406-8405 1 0/3 1/2 0 2 2 phone: 717-764-7700 fax: 717-764-4129 ASPEN www.archtest.com BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 9543 183 11/17/2022 . 1.4) FCIRC01nzh1VIJANCE A8170.04-116-45 linzhid Architectural Testing Page2of12 Technical Interpretations: None Modeling Assumptions: 1) To prevent air infiltration,tape was applied to all interior sash crack locations. 2) The 350 Tuffline, 350 Heavy Wall and 350 Door were grouped with the 350 Tuffline as the group leader per CMA Approved groupings and is not in compliance with NFRC standard grouping rules 3) The 500 Tuffline, 500 Heavy Wall and 500 Door were grouped with the 500 Tuffline as the group leader per CMA Approved groupings and is not in compliance with NFRC standard grouping rules Specialty Products Table: The specialty products method allow the manufacturer to determine the overall product SHGC and VT for any glazing option. The center of glass SHGC and/or VT must be determined using WINDOW 5.2. The method gives overall product SHGC and VT indexed on center of glass properties. All values used in the calculations are truncated to six decimal place precision. 190 Pair Doors: No Dividers Dividers< 1 Dividers> 1 SHGCO 0.031870 0.034724 0.037366 SHGC1 0.660887 0.576386 0.498184 VTO 0.000000 0.000000 0.000000 VT1 0.629018 0.541662 0.460818 350 Pair Doors: No Dividers Dividers< 1 Dividers> 1 SHGCO 0.038280 0.040977 0.043461 SHGC1 0.599261 0.519423 0.445 884 VTO 0.000000 0.000000 0.000000 VT1 0.560981 0.478447 0.402423 500 Pair Doors: No Dividers Dividers< 1 Dividers> 1 SHGCO 0.044319 0.046835 0.049139 SHGC1 0.530513 0.456017 0.397528 VTO 0.000000 0.000000 0.000000 VT1 0.486194 0.409182 0.338681 SHGC= SHGCO+SHGCc (SHGC1 - SHGCO) VT=VTO+VTc(VT1 -VTO) Validation Matrix: The following products are part of a validation matrix. Only one is required for validation testing. Product Line Report Number RECEIVED None - 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 183j D °' f" VIEVIE- 9543 11/17/2022 pORCOItCEIYii'I�AIICE A8170.04-116-45 linzhid Architectural Testing Page3of12 Spacer Option Description Sealant Spacer Type Primary Secondary Desiccant Aluminum Spacer Butyl Rubber Butyl Rubber Yes Grid Option Description Grid Size Grid Type Grid Pattern None - - Reinforcement Option Description Location Material None - Gas Filling Technique Description Fill Type Method 84.5%Xenon Single probe timed 76.1%Argon Single probe timed 85.8%Argon Single probe timed 83%Argon Single probe timed 88.7%Argon Single probe timed 87.4%Argon Single probe timed 65%Argon Single probe timed 74.7%Argon Single probe timed 60.8%Argon Single probe timed 62.4%Argon Single probe timed 86%Argon Single probe timed 81.7%Xenon Single probe timed 94.6%Xenon Evacuated chamber 76.9%Krypton Single probe timed 71.6%Xenon Single probe timed 76.5%Krypton Single probe timed 66.7%Xenon Single probe timed 82.2%Xenon Single probe timed Edge-of-Glass Construction Interior Condition EPDM gasket between frame and glass Exterior Condition EPDM gasket between frame and glass RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 183� 9543 , 11/17/2022 FORCOMGUIVEIJANIZ A8170.04-116-45 linzhidzhid Architectural Testing Page 4of12 Weatherstripping Type Quantity Location EPDM flap gasket 1 row Bottom sash rail Vinyl bulb gasket 1 row Top frame rail and jamb stiles Nylon pile 2 rows Meeting Stile - 190, 350 and 500 Series Nylon pile 1 row Meeting Stile- 350 and 500 Series Frame/Sash Materials Finish Interior Painted Aluminum Exterior Painted Aluminum RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B Aligwig El 5432� 9543 t 11/17/2022 °Tk. A8170.04-116-45 linzhid Architectural Testing Page5of12 NFRC 100/200/500 Summary Sheet 190 Pair Door N M d' e h y y y d da� - a N a M a �y q �y t a aR a a � a b a C a C a (.3 a C ° 2. rn 0 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/x1) Grids(None`/.<1/>=1) Resistance 1 COG=0.4735(C1r/C1r) 0.225 0.500 0.225 AIR CL Al-D N U-Factor 0.73 SHGC(N) 0.47 VT(N) 0.49 CR 17. 2 COG=0.4400 0.222 0.500 0.225 XEN84.48 CL Al-D N U-Factor 0.71 SHGC(N) 0.46 VT(N) 0.46 CR 17 3 COG=0.4200 0.222 0.500 0.225 ARG76.1 0.652(#2) GY Al-D N U-Factor 0.70 SHGC(N) 0.20 VT(N) 0.15 CR 17 4 COG=0.4000 0.220 0.500 0.225 ARG85.82999 0.566(#2) GY Al-D N U-Factor 0.69 SHGC(N); 0.20 VT(N) 0.13 CR 17, 5 COG=0.3800 0.226 0.500 0.225 ARG83.03 0.471(#2) OT Al-D N U-Factor 0.68 SHGC(N) 0.14 VT(N) 0.10 CR; 17 6 COG=0.3600 0.220 0.500 0.225 ARG88.65 0.395(#2) GY Al-D N U-Factor 0.67 SHGC(N)` 0.12- VT(N) 0.04; CR 17 7 COG=0.3400 0.232 0.500 0.225 ARG87.41 0.318(#2) GY Al-D N U-Factor 0.66 SHGC(N) 0.32 VT(N) 0.36; CR ;17 8 COG=0.3200 0.223 0.500 0.225' ARG64.98 0.215(#2) CL Al-D N U-Factor 0.64 SHGC(N) 0.42. VT(N) 0.46 CR 17 9 COG=0.3000 0.233 0.500 0.225 ARG74.7 0.166(#2) CL Al-D N U-Factor 0.63 SHGC(N) 0:31 VT(N) ' i 0.34 CR 17 10 COG=0.2800 0.223 0.500 0.225 ARG60.78 0.087(#2) CL Al-D N U-Factor 0.62 SHGC(N)s' 0.37 VT(N) 0.48- CR 18 R..ECEIVE CI) 10/31/2022 ASPEN BUILDING DEPARTMENT IllEVE DOUBLE SWING DOORS L2 A & L2 B . 183� 9543 11/17/2022 14 FURCCtnGW"(yIJNNCE A8170.04-116-45 lizhid Architectural Testing Page 6 of 12 NFRC 100/200/500 Summary Sheet 190 Pair Door r N M c1 z y U (n yr v q� -- q� N M p c i U ,�C U .x1 3 3 w et cl et el et og et C7 a C7 a C7 a C7 P" vh C7 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/r-1) Grids(None/<1/r_1) Resistance 11 COG=0.2600 0.223 0.500 0.225 ARG62.43 0.035(#2) CL Al-D N U-Factor 0.61 SHGC(N) 0.27 VT(N) 0.44 CR ` ;,18 12 COG=0.2400 0.223 0.500 0.223 ARG86.02 0.035(#2)/0.035(#3) CL Al-D N U-Factor 0.60 SHGC(N) _ 0.26 VT(N) 0.39 CR 18 13 COG=0.2200 0.223 0.500 0.223 XEN81.67 0.018(#2)/0.018(#3) CL Al-D N U-Fac tor 0.59 SHGC(N) 0.19 VT(N) 0.33 CR 18, 14 COG=0.2000 0.223 0.500 0.223 XEN94.6 0.018(#2)/0.018(#3) CL Al-D N U-Factor 0.58 SHGC(N) 0.19 VT(N) 0.33 CR 18 15 COG=0.1800 0.223 0.250 0.003 0.250 0.221 KRY76.87A1R 0.018(#2)/0.76(#3)/0.11(#4)/0.028(#5) CL Al-D N U-Factor 0.56 SHGC(N) 0.18 VT(N):.: 0.28 CR 18 16 COG=0.1600 0.223 0.250 0.003 0.250 0.223 XEN71.59AIR 0.018(#2)/0.76(43)/0.1104)/0.018(#5) CL A 1-D N U-Factor 0.55 SHGC(N) 0.18 VT(N) 0.29 CR ; 18 17 COG=0.1400 0.223 0.250 0.003 0.250 0.223 KRY76.46 0.01802)/0.76(#3)/0.11(#4)/0.018(#5) CL Al-D N U=Factor 0.54 SHGC(N) 0.18 VT(N) :; 0.29 '`' CR • 18 18 COG=0.1200 0.223 0.250 0.003 0.250 0.223 XEN66.67 0.018(#2)/0.76(#3)/0.11(#4)/0.018(#5) CL Al-D N U-Factor 0.53 SHGC(N) 0.18 VT(N) 0.29 CR 18 19 COG=0.1000 0.223 0.250 0.003 0.250 0.223 XEN82.15 0.018(#2)/0.7603)/0.1104)/0.018(#5) CL Al-D N U-Factor 0.52 SHGC(N)� t 0.18 VT(N) 0.29 :CR 18 .RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 183r EWLig l i A 95437/2022 Feac01nz ifttNC A8170.04-116-45 linzhid Architectural Testing Page 7 of 12 NFRC 100/200/500 Summary Sheet 350 Tuffline Pair Door/350 Heavy Wall Pair Door/350 Pair Door t - N M '�r ^ n m n yr y U r-I N ens i. a "n U . .' a N 3 H 3 H 3 w Q d CD w d o u �a a a Cl. a a a a et • a R a c a R a � aO N ck c37 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/x1) Grids(None/<1/>=1) Resistance 20 COG=0.4735(C1r/C1r) 0.225 0.500 0.225 AIR CL Al-D N U-Factor 0.79 SHGC(N) 0:43 VT(N) 0.44 CR 16 21 COG=0.4400 0.222 0.500 0.225 XEN84.48 CL Al-D N U-Factor 0.77 SHGC(N) 0.42 VT(N) 0.41 CR 16 22 COG=0.4200 0.222, 0.500 0.225 ARG76.1 0.652(#2) GY Al-D N U-Factor 0.76 SHGC(N) 0.19 VT(N) 0.13 CR 16 23 COG=0.4000 0.220 0.500 0.225 ARG85.82999 0.566(#2) GY Al-D N U-Factor 0.75 SHGC(N) 0.19 VT(N) 0.11 CR 16 24 COG=0.3800 0.226 0.500 0.225 ARG83.03 0.471(#2) OT Al-D N U-Factor 0.74 SHGC(N) 0.14 VT.(N),. 0.09 CR 16 25 COG=0.3600 0.220 0.500 0.225 ARG88.65 0.395(#2) GY Al-D N U-Factor 0.73 SHGC(N) 0.12 VT(N) 0.04 CR 16 26 COG=0.3400 0.232 0.500 0.225 ARG87.41 0.318(#2) GY Al-D N U-Factor 0:72. SHGC(N) 0.30' VT(N) 0.32 CR 16 I 27 COG=0.3200 0.223 0.500 0.225 ARG64.98 0.215(#2) CL Al-D N U-Factor 0.71 SHGC(N) 0.38 •VT(N) 0.41-. ,CR 16 28 COG=0.3000 0.233 0.500 0.225 ARG74.7 0.166(#2) CL AI-D N U-Factor 0.70 SHGC(N) 0.29 VT(N) 0.30 CR 16`: 29 COG=0.2800 0.223 0.500 0.225 ARG60.78 0.087(#2) CL Al-D N U-Factor ;,.0.69 SHGC(N) 0.34 VT(N). 0.43 CR 16 RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B A 183 9543 , 11/17/2022 rniT 1sORC011r<GE1tlVIJANCE zhid lin A8170.04-116-45 Architectural Testing Page 8 of 12 NFRC 100/200/500 Summary Sheet 350 Tuffline Pair Door/350 Heavy Wall Pair Door/350 Pair Door ,-, N M V ^ m v) o cn y U G - N 3 M p w H 3 H 3 H 3 H wCID 4k) cp d a C7 a, C7 a C7 a C7 ,3 E: cn 6 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/>=1) Grids(None/<1/>=1)`. Resistance 30 COG=0.2600 0.223 0.500 0.225 ARG62.43 0.035(#2) CL Al-D N U-Factor 0.68 SHGC(N) 0.25 VT(N) 0.39 CR 16. 31 COG=0.2400 0.223 0.500 0.223 ARG86.02 0.035(#2)/0.035(#3) CL Al-D N U-Factor; 0.67 SHGC(N) 0.24 VT(N) 0.35 CR 16 32 COG=0.2200 0.223 0.500 0.223 XEN81.67 0.018(#2)/0.018(#3) CL Al-D N U-Factor 0.66 SHGC(N) 0.18 VT(N) 0.29 CR 16 33 COG=0.2000 I 0.223 0.500 0.223 XEN94.6 0.018(#2)/0.018(#3) CL Al-D N U-Factor 0.65 SHGC(N); 0.18 VT(N) 0.29 CR 16 1 34 COG=0.1800 0.223 0.250 0.003 0.250 0.221 KRY76.87A1R 0.018(#2)/0.76(#3)/0.11(#4)/0.028(#5) CL A 1-D N U-Factor 0.64 SHGC(N) 017 VT(N) 0.25 CR 16 35 COG=0.1600 0.223 0.250 0.003 0.250 0.223 XEN71.59A1R 0.018(#2)/0.76(#3)/O.I 1(#4)/0.018(#5)I CL A 1-D N U-Factor 0.63 SHGC(N) 0.17 VT(N) 0.26 CR 16 36 COG=0.1400 0.223 0.250 0.003 0.250 0.223 KRY76.46 o.o1s(#2)/O.76(#3)/O.11(#4)/0.o18(#s) CL Al-D N U-Factor 0.62 SHGC(N) . 0.17' VT(N). 0.26 CR 16 37 COG=0.1200 0.223 0.250 0.003 0.250 0.223 XEN66.67 o.o1s(#2)/O.76(#3)/O.11(#4)/0.o18(#s) CL Al-D N U-Factor 0.61 SHGC(N) 0.17 VT(N) 0.26. CR 16.. 38 COG=0.1000 0.223 0.250 0.003 0.250 0.223 XEN82.15 0.018(#2)/0.76(#3)/0.11(#4)/0.018(#5) CL A 1-D N U-Factor 0.60 SHGC(N) 0.17 VT(N) U-FACTOR RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B A 1832 oiligwig II 9543 t 11/17/2022 14 � i�lRC01)tihlllt>UNIICE� A8170.04-116-45 linzhid Architectural Testing Page 9of12 NFRC 100/200/500 Summary Sheet 500 Tuffline Pair Door/500 Heavy Wall Pair Door/500 Pair Door .--i N M �t T^ y y d C) 3 ; � N 3 M t A E • 3 F 3 3 H w d a> a =a a a a a a d C. a • w C7 w Cy a 3 4 3 F 2. 0 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/>=1) Grids(None/<1/>=1) Resistance 39 COG=0.4735 (Cir/CIr) 0.225 0.500 0.225 AIR CL Al-D N U-Factor 0.82 SHGC(N) 0.39 VT(N) 0.38 CR 16 40 COG=0.4400 0.222 0.500 0.225 XEN84.48 CL Al-D N U-Factor 0.81 SHGC(N) 0.38 VT(N) 0.36 CR 16 41 COG=0.4200 0.222 0.500 0.225 ARG76.1 0.652(#2) GY Al-D N U-Factor 0.80 SHGC(N)' 0.17 VT(N) 0.11 CR 16 42 COG=0.4000 0.220 0.500 0.225 ARG85.82999 0.566(#2) GY Al-D N U-Factor 0.79 SHGC(N) 0.17 VT(N) 0.10 CR 16 43 COG=0.3800 0.226 0.500 0.225 ARG83.03 0.471(#2) OT Al-D N U-Factor 0.78 SHGC(N) 0.13 VT(N) 0.07, CR 16. 44 COG=0.3600 0.220 0.500 0.225 ARG88.65 0.395(#2) GY Al-D N U-Factor 0.77 SHGC(N)., 0.11 VT(N) 003 CR 16 45 COG=0.3400 0.232 0.500 0.225 ARG87.41' 0.318(#2) GY Al-D N U-Factor 0.77 SHGC(N) 0.27 VT(N) 0.28 CR 16 46 COG=0.3200 0.223 0.500 0.225 ARG64.98 0.215(#2) CL Al-D N U-Factor, 0.76 SHGC(N);, 0.34 VT.(N) 0.36 CR 16 47 COG=0.3000 0.233 0.500 0.225 ARG74.7 0.166(#2) CL Al-D N U-Factor 0.75 SHGC(N) 0.26 • VT 0.26 CR 16 48 COG=0.2800 0.223 0.500 0.225 ARG60.78 0.087(#2) CL Al-D N U-Factor 0.74 SHGC(NV)'' 0.31 VT(N) 0.37 CR 16' RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 1832 � i i 9543 11/17/2022 ixf1RC01lnzhinzh i>IJANCE A8170.04-116-45 id Architectural Testing Page 10 of 12 NFRC 100/200/500 Summary Sheet 500 Tuffline Pair Door/500 Heavy Wall Pair Door/500 Pair Door N en. . . d V q LO 6. u 4.. 4. c a b b � 3 a 3 F 3 H w y 6) R R C7 a a 12 a C El G "L a C7 a a C7 a C7 a E+ cn 0 U-Factor Solar Heat Gain Coefficient(SHGC) Visible Transmittance(VT) Condensation Grids(None/<1/x1) Grids(None/<1/>=1) Resistance 49 COG=0.2600 0.223 0.500 0.225 ARG62.43 0.035(#2) CL Al-D N U-Factor 0.73 SHGC(N) 0.23 VT(N) 0.34 CR '16 50 COG=0.2400 0.223 0.500 0.223 ARG86.02 0.035(#2)/0.035(#3) CL Al-D N U-Factor 0.72 SHGC(N) 0.22. VT(N) 0.30 CR 16 51 COG=0.2200 0.223 0.50010.223 XEN81.67 0.018(#2)/0.018(#3) CL Al-D N U-Factor 0.71 SHGC(N) 0.17 VT(N) 0.25 CR 16 52 COG=0.2000 0.223 0.50010.223 XEN94.6 0.018(#2)/0.018(#3) CL Al-D N U-Factor 0.70 SHGC(N). 0.17 VT(N) 0.25 CR 16; 53 COG=0.1800 0.223 0.25010.003 0.250 0.221 KRY76.87AIR 0.018(#2)/0.76(#3)/0.11(#4)/0.028(#5) CL A l-D N U-Factor 0.70 SHGC(N) 0.16 VT(N) 0.21 CR 16 54 COG=0.1600 0.223 0.250 0.003 0.250 0.223 XEN71.59AIR 0.01802)/0.76(0)/0.11(#4)/0.018(0) CL A 1-D N U-Factor 0.69 SHGC(N) 0.16 VT(N) 0.22 CR 16 55 COG=0.1400 0.223 0.250 0.003 0.250 0.223 KRY76.46 0.018(#2)/0.76(#3)/0.11(#4)/0.018(#5) CL Al-D N U-Factor 0.68 SHGC(N) 0.16 VT(IV)" 0.22 CR 16 56 COG=0.1200 0.223 0.250 0.003 0.250 0.223 XEN66.67 0.018(#2)/0.76(#3)/0.1iO4)/0.0i105) CL Al-D N U-Factor 0.67 SHGC(N): 0.16 VT(N) 0.22 CR 16;;1 57 COG=0.1000 0.223 0.250 0.003 0.250 0.223 XEN82.15 0.018(#2)/0.76(0)/0.1104)/0.018(#5) CL Al-D N U-Factor 0.66 SHGC(N) 0.16-, ? VT(N) 0.22. CR 16 RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 18 E . 9543 11/17/2022 F RC013ihlll(> NCE A8170.04-116-45 linzhid Architectural Testing Page 11 of 12 The Condensation Resistance results obtained from this procedure are for controlled laboratory conditions and do not include the effects of air movement through the specimen, solar radiation, and the thermal bridging that may occur due to the specific design and construction of the fenestration system opening. Ratings values included in this report are for submittals to an NFRC-licensed IA and are not meant to be used directly for labeling purposes. Only those values identified on a valid Certification Authorization Report (CAR) by an NFRC accredited Inspection Agency (IA) are to be used for labeling purposes. The ratings values were rounded in accordance to NFRC 601, NFRC Unit and Measurement Policy. NFRC ACCREDITED LAB. Architectural Testing, Inc. is an NFRC accredited simulation laboratory and all simulations were conducted in full compliance with NFRC approved procedures and specifications. the NFRC procedure requires that the computational results be verified through actual test results. Detailed drawings, simulation data files, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are simulated values and were secured by using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the product simulated. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: SIMULATED BY: REVIEWED BY: 2iai`m4 %tiddrr2Gv DlgibI Sigel by:Kevin Lauder Diarwh Signal by:WbbnL.LWc6beger O Kevin S. Louder Kristen L. Livelsberger Project Engineer Senior Simulation Technician S imulator-In-Responsible-Charge KSL:ksl A8170.04-116-45 Attachments(pages): This report is complete only when all attachments listed are included. Appendix A:Drawings and Bills of Material(54) RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B 183� 1 ail u 9543 t 11/17/2022 F RC013t A8170.04-116-45 linG(44 1"CEzhid Architectural Testing Page 12 of 12 Revision Log Rev.# Date Page(s) Revision(s) .01 RO 3/3/2011 All Original Report Issue This report produced from controlled document template ATI 00037,Revised 08/31/2009. RECEIVED 10/31/2022 ASPEN BUILDING DEPARTMENT DOUBLE SWING DOORS L2 A & L2 B . 1832 I agagliT 9543 , 11/17/2022 FORC013ta l ieLIA110E linzhid Architectural Testing All drawings and Bills of Material used to simulate this product are enclosed in this Appendix Appendix A A8170.04-116-45 Er FIVE'( 10/31/2022 • ASPEN - BUILDING DEPARTMENT