Loading...
HomeMy WebLinkAboutFile Documents.501 Dean St.0019-2022-BCOM (16) 111116 COMcheck Software Version 4.1.5.1 A(1 Interior Lighting Compliance Certificate Project Information Energy Code: 2015 IECC Project Title: RESIDENCES AT LITTLE NELL Project Type: Alteration Construction Site: Owner/Agent: Designer/Contractor: 501 DEAN STREET Alfred Lafave Tammy Dyce ASPEN Integrative Development Solutions IMEG Corp 81611 www.idscolorado.com www.imegcorp.com 310-487-3871 303-796-6072 alfred@idscolorado.com tammy.l.dyce@imegcorp.com Allowed Interior Lighting Power A B C D Area Category Floor Area Allowed Allowed Watts (ft2) Watts/ft2 (B X C) 1-Entry L1 with stair(Common Space Types:Lobby-General) 1052 0.90 947 2-Reception(Common Space Types:Lobby-General) 4614 0.90 415 3-Owner's Lobby(Common Space Types:Lobby-General) 10454 0.90 940 4-Sales Office(Common Space Types:Office-Enclosed): Exempt 5-Concierge(Common Space Types:Office-Enclosed): Exempt 6-Owner Ski Locker Room(Common Space Types:Locker Room):Exempt 7-Corridor West Level 1 (Common Space Types:Corridor/Transition<8 ft wide) 1121 0.66 740 8-Corridor East Level 1 (Common Space Types:Corridor/Transition<8 ft wide) 1272 0.66 840 9-Corridor West Level 2(Common Space Types:Corridor/Transition<8 ft wide) 663 0.66 438 10-Corridor East Level 2(Common Space Types:Corridor/Transition<8 ft wide) 964 0.66 636 11-Corridor West Level 3(Common Space Types:Corridor/Transition<8 ft wide) 758 0.66 500 12-Corridor East Level 3(Common Space Types:Corridor/Transition<8 ft wide) 997 0.66 658 13-Corridor West Level 5(Common Space Types:Corridor/Transition<8 ft wide) 619 0.66 409 14-Corridor East Level 4(Common Space Types:Corridor/Transition<8 ft wide) 1068 0.66 705 15-Corridor West Level 5(Common Space Types:Corridor/Transition<8 ft wide) 810 0.66 535 16-Corridor East Level 5(Common Space Types:Corridor/Transition<8 ft wide) 703 0.66 464 Total Allowed Watts= 8226 Area Category Exemption Qualifications #Fixtures Total#Watts Activity Area Pre-Alt. Repl./Added Pre-Alt. Post-Alt. Sales Office (Common Space Types:Office-Enclosed 281 16 0 890.000 890.000 sq.ft.) Exemption: Less than 50%fixture replacement. Concierge(Common Space Types:Office-Enclosed 143 4 0 200.000 200.000 sq.ft.) Exemption: Less than 50%fixture replacement. Owner Ski Locker Room (Common Space Types:Locker 33 0 1890.000 1890.000 Room 1109 sq.ft.) Exemption: Less than 50%fixture replacement. Proposed Interior Lighting Power Project Title: RESIDENCES AT LITTLE NELL Refit. t Qt 1ypt) Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck P�oVe/1iik0722 ASPEN BUILDING DEPARTMENT A B C D E Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) Fixture Fixtures Watt. Entry L1 with stair(Common Space Types:Lobby-General 1052 sq.ft.) L1:L1: New Downlight:Other: 1 8 17 136 F2:F2: Deco Chandelier-12 lamp:Other: 1 1 60./ 60 F3:F3: Deco Sconce:Other: 1 2 6 4 12 F4:F4: Deco Sconce:Other: 1 6 10 4 60 F5:F5: Deco Flush Mount:Other: 3 3 16 q 48 F6:F6: Deco Flush Mount:Other: 4 2 32 4/ 64 F7:F7: Deco Flush Mount:Other: 5 1 404/ 40 F8:F8: Deco Sconce:Other: 2 5 10X 50 (E)Cove:(E)Cove: Existing Cove Transformers:Other: 1 2 250 500 J Reception (Common Space Types:Lobby-General 461 sq.ft.) F9:F9: Deco Chandelier:Other: 1 1 24 4 24 L1:L1: New Downlight:Other:X 1 4 17 68 F10: F10: Deco Sconce:Other: 1 2 24 X 48 F20: F20: Deco Flush Mount:Other: 1 1 12 4 12 4/Owner's Lobby(Common Space Types:Lobby-General 1045 sq.ft.) F10: F10: Deco Sconce:Other: 1 3 24X 72 F11: F11: Deco Sconce:Other: 1 8 10 80 F12: F12: Hardwire Art Light:Other: 1 2 15 30 F13A: F13A:Deco Pendant:Other:X 1 1 35 35 F13B: F13B:Deco Pendant:Other:X 1 1 25 25 L2:L2:Shelf Lighting:Other: 1 2 15 30 L3:L3:Shelf Lighting:Other: 1 2 20 40 (E)Wallwasher:(E)WW:Existing Wallwasher: Incandescent 100W: 1 3 100 300 (E)Downlight:(E)Downlight: Existing Downlight: Halogen MR-16 50W: 1 3 50 150 F20: F20: Deco Flush Mount:Other: 1 1 12 12 Sales Office(Common Space Types:Office-Enclosed 281 sq.ft.): Exempt /Concierge(Common Space Types:Office- Enclosed 143 sq.ft.): Exempt 4/Owner Ski Locker Room (Common Space Types:Locker Room 1109 sq.ft.): Exempt Corridor West Level 1 (Common Space Types:Corridor/Transition <8 ft wide 1121 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 18 12 216 F21: F21: Deco Sconce:Other: 1 12 5 60 F22: F22: Deco Sconce:Other: 1 10 5 50 Corridor East Level 1 (Common Space Types:Corridor/Transition <8 ft wide 1272 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 11 12 132 F21: F21: Deco Sconce:Other: 1 5 5 25 F22: F22: Deco Sconce:Other: 1 4 5 20 F23: F23: Deco Chandelier:Other: 1 2 604 120 Corridor West Level 2 (Common Space Types:Corridor/Transition <8 ft wide 663 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 7 12 84 F21: F21: Deco Sconce:Other: 1 8 5 40 Corridor East Level 2(Common Space Types:Corridor/Transition <8 ft wide 964 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 9 12 108 F21: F21: Deco Sconce:Other: 1 6 5 30 F15: F15: Deco Pendant:Other: 1 1 14 14 Corridor West Level 3(Common Space Types:Corridor/Transition <8 ft wide 758 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 9 12 108 F21: F21: Deco Sconce:Other: 1 9 5 45 Corridor East Level 3(Common Space Types:Corridor/Transition <8 ft wide 997 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 10 12 120 F21: F21: Deco Sconce:Other: 1 7 5 35 Corridor West Level 5(Common Space Types:Corridor/Transition <8 ft wide 619 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 9 12 108 F21: F21: Deco Sconce:Other: 1 4 5 R 20 rt Rend EDIF Project Title: RESIDENCES AT LITTLE NELL Re IIJ Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck 86§71iik0722 ASPEN BUILDING DEPARTMENT A B C D E Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D) Fixture Fixtures Watt. F22: F22: Deco Sconce:Other: 1 1 5 5 Corridor East Level 4 (Common Space Types:Corridor/Transition <8 ft wide 1068 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 12 12 144 F21: F21: Deco Sconce:Other: 1 7 5 35 F22: F22: Deco Sconce:Other: 1 2 5 10 Corridor West Level 5(Common Space Types:Corridor/Transition <8 ft wide 810 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 10 12 120 F21: F21: Deco Sconce:Other: 1 4 5 20 F22: F22: Deco Sconce:Other: 1 4 5 20 Corridor East Level 5(Common Space Types:Corridor/Transition <8 ft wide 703 sq.ft.) F20: F20: Deco Flush Mount:Other: 1 8 12 96 F22: F22: Deco Sconce:Other: 1 6 5 30 Total Proposed Watts= 3711 Interior Lighting PASSES Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Tammy L Dyce,Senior Lighting Designer 09/02/2022 _ Name-Title Signature Date Project Title: RESIDENCES AT LITTLE NELL Rend ElYf I) Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck P�86§71iik0722 ASPEN BUILDING DEPARTMENT COMcheck Software Version 4.1.5.1 Inspection Checklist Energy Code: 2015 IECC isil Requirements: 100.0% were addressed directly in the COMcheck software Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Section # Plan Review Complies? Comments/Assumptions & Req.ID C103.2 Plans, specifications, and/or EComplies Requirement will be met. [PR4]1 calculations provide all information Does Not with which compliance can be ❑Not Observable Location on plans/spec: ELECTRICAL PLANS, determined for the interior lighting ARCHITECTURAL/ID PLANS and electrical systems and equipment ❑Not Applicable and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts,transformers and control devices. Additional Comments/Assumptions: 1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) p������TD Project Title: RESIDENCES AT LITTLE NELL Re o aF t�: / 2 Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck oVe/1iik0722 ASPEN BUILDING DEPARTMENT Section # Rough-In Electrical Inspection Complies? Comments/Assumptions & Req.ID 1 , C405.2.1 Lighting controls installed to uniformly ❑Complies 'Requirement will be met. [EL15]1 I reduce the lighting load by at least ❑Does Not 1 50%. [Not Observable Location on plans/spec: E-9.02 LIGHTING SEQUENCE OF ❑Not Applicable OPERATIONS C405.2.1 1 Occupancy sensors installed in ❑Complies Exception:Areas such as security or emergency areas that [EL18]1 I required spaces. ❑Does Not need continuous lighting. [Not Observable Location on plans/spec:THIS IS A 24-HOUR FACILITY ❑Not Applicable C405.2.1, Independent lighting controls installed ❑Complies Exception:Areas such as security or emergency areas that C405.2.2. per approved lighting plans and all ❑Does Not need continuous lighting. 3 manual controls readily accessible and [EL23]2 visible to occupants. ❑Not Observable Location on plans/spec: E-701.E.1 - LIGHTING CONTROLS ❑Not Applicable ACCESSIBLE TO AUTHORIZED USERS ONLY C405.2.2. Automatic controls to shut off all ;❑Complies Exception:Areas such as security or emergency areas that 1 building lighting installed in all ❑Does Not need continuous lighting. [EL22]2 buildings. ❑Not Observable Location on plans/spec:THIS IS A 24-HOUR FACILITY ❑Not Applicable 01 .3 Daylight zones provided with ;❑Complies Exception: Requirement does not apply. individual controls that control the ❑Does Not lights independent of general area ❑Not Observable Location on plans/spec: NO DAYLIGHTING ZONES WITH lighting. GREATER THAN 150W OF GENERAL LIGHTING. ❑Not Applicable C405.2.3, Primary sidelighted areas are Complies Exception: Requirement does not apply. C405.2.3. equipped with required lighting ❑Does Not 1, controls. Location on plans/spec: NO DAYLIGHTING ZONES WITH C405.2.3. ❑Not Observable GREATER THAN 150W OF GENERAL LIGHTING. 2 ❑Not Applicable [EL20]1 C405.2.3, Enclosed spaces with daylight area ;❑Complies Exception: Requirement does not apply. C405.2.3. under skylights and rooftop monitors ❑Does Not 1, are equipped with required lighting ['Not Observable Location on plans/spec: NO SKYLIGHTS OR MONITORS C405.2.3. controls. 3 ❑Not Applicable [EL21]1 C405.2.4 Separate lighting control devices for EComplies Requirement will be met. [EL4]1 specific uses installed per approved ❑Does Not lighting plans. Location on plans/spec: ELECTRICAL PLANS- EACH ['Not Observable APPLICATION HAS A DIFFERENT LIGHTING ZONE ❑Not Applicable 1 C405.2.4 Additional interior lighting power ❑Complies Requirement will be met. [EL8]1 allowed for special functions per the ❑Does Not approved lighting plans and is ['Not Observable Location on plans/spec: ALL LIGHTING APPLICATIONS ARE automatically controlled and CONTROLLED ON SEPARATE ZONES. separated from general lighting. ❑Not Applicable i C405.3 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met. [EL6]1 face. ❑Does Not ❑Not Observable ❑Not Applicable Additional Comments/Assumptions: (High Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) � �� Project Title: RESIDENCES AT LITTLE NELL Re orr t�: / 2��� Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck Pape/ L1,5 gf„o722 V 9 ASPEN BUILDING BUILDING DEPARTMENT Section # Final Inspection Complies? Comments/Assumptions & Req.ID C303.3, ;Furnished O&M instructions for ❑Complies Requirement will be met. C408.2.5. systems and equipment to the ❑Does Not 2 building owner or designated [F117]3 representative. [Not Observable ❑Not Applicable C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values. [F118]1 lighting power is consistent with what ❑Does Not is shown on the approved lighting plans, demonstrating proposed watts ['Not Observable are less than or equal to allowed ❑Not Applicable watts. C408.2.5. :Furnished as-built drawings for ❑Complies Requirement will be met. 1 :electric power systems within 90 days ❑Does Not [F116]3 of system acceptance. [Not Observable ENot Applicable C408.3 1Lighting systems have been tested to ❑Complies Requirement will be met. [F133]1 ensure proper calibration, adjustment, ❑Does Not programming, and operation. Location on plans/spec: DIVISION 26 09 33 SPECIFICATIONS [Not Observable ❑Not Applicable Additional Comments/Assumptions: 1 IHigh Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) � f D Project Title: RESIDENCES AT LITTLE NELL Re o t�: g/12 Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck Pape/1,6 gf„0722 V 9 ASPENL/ L BUILDING DEPARTMENT Project Title: RESIDENCES AT LITTLE NELL ReREt : E/l212fD Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck Nei 1L� 0722 ASPEN BUILDING DEPARTMENT