HomeMy WebLinkAboutFile Documents.501 Dean St.0019-2022-BCOM (17) Irrifl COMcheck Software Version 4.1.5.1
Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: RESIDENCES AT LITTLE NELL
Project Type: Alteration
Construction Site: Owner/Agent: Designer/Contractor:
501 DEAN STREET Alfred Lafave Tammy Dyce
ASPEN Integrative Development Solutions IMEG Corp
81611 www.idscolorado.com www.imegcorp.com
310-487-3871 303-796-6072
alfred@idscolorado.com tammy.l.dyce@imegcorp.com
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-Entry L1 with stair(Common Space Types:Lobby-General) 1052 0.90 947
2-Reception(Common Space Types:Lobby-General) 461 0.90 415
3-Owner's Lobby(Common Space Types:Lobby-General) 1045 0.90 940
4-Sales Office(Common Space Types:Office-Enclosed) 281 1.11 312
5-Concierge(Common Space Types:Office-Enclosed): Exempt
6-Owner Ski Locker Room(Common Space Types:Locker Room):Exempt
7-Corridor West Level 1 (Common Space Types:Corridor/Transition<8 ft wide) 1121 0.66 740
8-Corridor East Level 1 (Common Space Types:Corridor/Transition<8 ft wide) 1272 0.66 840
9-Corridor West Level 2(Common Space Types:Corridor/Transition<8 ft wide) 663 0.66 438
10-Corridor East Level 2(Common Space Types:Corridor/Transition<8 ft wide) 964 0.66 636
11-Corridor West Level 3(Common Space Types:Corridor/Transition<8 ft wide) 758 0.66 500
12-Corridor East Level 3(Common Space Types:Corridor/Transition<8 ft wide) 997 0.66 658
13-Corridor West Level 4(Common Space Types:Corridor/Transition<8 ft wide) 619 0.66 409
14-Corridor East Level 4(Common Space Types:Corridor/Transition<8 ft wide) 1068 0.66 705
15-Corridor West Level 5(Common Space Types:Corridor/Transition<8 ft wide) 810 0.66 535
16-Corridor East Level 5(Common Space Types:Corridor/Transition<8 ft wide) 703 0.66 464
17-Corridor Level 6(Common Space Types:Corridor/Transition<8 ft wide) 150 0.66 99
18-Corridor Level 7(Common Space Types:Corridor/Transition<8 ft wide) 79 0.66 52
Total Allowed Watts= 8689
Area Category Exemption Qualifications
#Fixtures Total#Watts
Activity Area Pre-Alt. Repl./Added Pre-Alt. Post-Alt.
Concierge(Common Space Types:Office-Enclosed 143 4 0 200.000 200.000
sq.ft.)
Exemption: Less than 50%fixture replacement.
Owner Ski Locker Room (Common Space Types:Locker 33 0 1890.000 1890.000
Room 1109 sq.ft.)
Exemption: Less than 50%fixture replacement.
Proposed Interior Lighting Power
f D
Project Title: RESIDENCES AT LITTLE NELL Refit, t g/14R
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck P�it"3fik0722
ASPEN
BUILDING DEPARTMENT
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
Entry L1 with stair(Common Space Types:Lobby-General 1052 sq.ft.)
4(1:Li: New Downlight:Other: 1 8 17 136
vr2:F2: Deco Chandelier-12 lamp:Other: 1 1 60 60
413:F3: Deco Sconce:Other: 1 2 4 8
4:F4: Deco Sconce:Other: 1 6 10 60
.5:F5: Deco Flush Mount:Other: 3 3 16 48
a6:F6: Deco Flush Mount:Other: 4 2 32 64
4,A7:F7: Deco Flush Mount:Other: 5 1 40 40
XF8:F8: Deco Sconce:Other: 2 5 10 50
(E)Cove:(E)Cove: Existing Cove Transformers:Other: 1 2 250 500
Reception (Common Space Types:Lobby-General 461 sq.ft.)
9:F9: Deco Chandelier:Other: 1 1 24 24
1:L1: New Downlight:Other: 1 4 17 68
t10: F10: Deco Sconce:Other: 1 2 14 28
vr20: F20: Deco Flush Mount:Other: 1 1 12 12
Owner's Lobby(Common Space Types:Lobby-General 1045 sq.ft.)
... 10: F10: Deco Sconce:Other: 1 3 14 42
44:F4: Deco Sconce:Other: 1 8 10 80
vr12: F12: Hardwire Art Light:Other: 1 2 15 30
XF13A: F13A:Deco Pendant:Other: 1 1 35 35
)(F13B: F13B:Deco Pendant:Other: 1 1 25 25
)&2:L2:Shelf Lighting:Other: 1 2 14 29
.13:L3:Shelf Lighting:Other: 1 2 20 39
(E)Wallwasher:(E)WW:Existing Wallwasher: Incandescent 100W: 1 3 100 300
(E)Downlight:(E)Downlight: Existing Downlight: Halogen MR-16 50W: 1 3 50 150
.120: F20: Deco Flush Mount:Other: 1 1 12 12
Sales Office(Common Space Types:Office-Enclosed 281 sq.ft.)
EXISTING DOWNLIGHT:(E)DOWNLIGHT: EXISTING DOWNLIGHT: Halogen MR-16 50W: 1 6 50 300
j14: F14: Deco Sconce:Other: 1 2 34 68
Concierge(Common Space Types:Office- Enclosed 143 sq.ft.): Exempt
Owner Ski Locker Room (Common Space Types:Locker Room 1109 sq.ft.): Exempt
Corridor West Level 1 (Common Space Types:Corridor/Transition <8 ft wide 1121 sq.ft.)
w620: F20: Deco Flush Mount:Other: 1 18 12 216
21: F21: Deco Sconce:Other: 1 12 5 60
J22: F22: Deco Sconce:Other: 1 10 5 50
Corridor East Level 1 (Common Space Types:Corridor/Transition <8 ft wide 1272 sq.ft.)
.20: F20: Deco Flush Mount:Other: 1 11 12 132
.21: F21: Deco Sconce:Other: 1 5 5 25
XFF 2: F22: Deco Sconce:Other: 1 4 5 20
4i.F2:F2: Deco Chandelier:Other: 1 2 60 120
Corridor West Level 2 (Common Space Types:Corridor/Transition <8 ft wide 663 sq.ft.)
0: F20: Deco Flush Mount:Other: 1 7 12 84
421: F21: Deco Sconce:Other: 1 8 5 40
Corridor East Level 2(Common Space Types:Corridor/Transition <8 ft wide 964 sq.ft.)
XF20: F20: Deco Flush Mount:Other: 1 9 12 108
XF21: F21: Deco Sconce:Other: 1 6 5 30
�F15: F15: Deco Pendant:Other: 1 1 14 14
Corridor West Level 3 (Common Space Types:Corridor/Transition <8 ft wide 758 sq.ft.)
�FF20: F20: Deco Flush Mount:Other: 1 9 12 108
VrL21: F21: Deco Sconce:Other: 1 9 5 45
Corridor East Level 3(Common Space Types:Corridor/Transition <8 ft wide 997 sq.ft.)
XF20: F20: Deco Flush Mount:Other: 1 10 12 120
XF21: F21: Deco Sconce:Other: 1 7 5 35
Corridor West Level 4 (Common Space Types:Corridor/Transition <8 ft wide 619 sq.ft.)
Project Title: RESIDENCES AT LITTLE NELL Rend EDif D
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck ite/312if20722
ASPEN
BUILDING DEPARTMENT
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
.420: F20: Deco Flush Mount:Other: 1 9 12 108
d21: F21: Deco Sconce:Other: 1 4 5 20
422: F22: Deco Sconce:Other: 1 1 5 5
Corridor East Level 4(Common Space Types:Corridor/Transition <8 ft wide 1068 sq.ft.)
XLLF20: F20: Deco Flush Mount:Other: 1 12 12 144
�/F21: F21: Deco Sconce:Other: 1 7 5 35
`OrF22: F22: Deco Sconce:Other: 1 2 5 10
Corridor West Level 5(Common Space Types:Corridor/Transition <8 ft wide 810 sq.ft.)
d 20: F20: Deco Flush Mount:Other: 1 10 12 120
.21: F21: Deco Sconce:Other: 1 4 5 20
d22: F22: Deco Sconce:Other: 1 4 5 20
Cor idor East Level 5(Common Space Types:Corridor/Transition <8 ft wide 703 sq.ft.)
20: F20: Deco Flush Mount:Other: 1 8 12 96
XF22: F22: Deco Sconce:Other: 1 6 5 30
Co ridor Level 6(Common Space Types:Corridor/Transition <8 ft wide 150 sq.ft.)
20: F20: Deco Flush Mount:Other: 1 2 12 24
421: F21: Deco Sconce:Other: 1 2 5 10
Co44ridor Level 7(Common Space Types:Corridor/Transition <8 ft wide 79 sq.ft.)
20: F20: Deco Flush Mount:Other: 1 1 12 12
•IED 1: F21: Deco Sconce:Other: 1 1 5 5
Total Proposed Watts= 4074
Interior Lighting PASSES
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application.The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.5.1 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Tammy Dyce,Senior Lighting Designer / 10/04/22
Name-Title Signature Date
Project Title: RESIDENCES AT LITTLE NELL Rend ElYft)
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cckte/313if20722
ASPEN
BUILDING DEPARTMENT
COMcheck Software Version 4.1.5.1
Inspection Checklist
Energy Code: 2015 IECC
isil
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or EComplies Requirement will be met.
[PR4]1 calculations provide all information Does Not
with which compliance can be ❑Not Observable Location on plans/spec: ELECTRICAL PLANS,
determined for the interior lighting ARCHITECTURAL/ID PLANS
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) p������TD
Project Title: RESIDENCES AT LITTLE NELL Re o aF t�: —./ 4
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck it"31ik0?22
ASPEN
BUILDING DEPARTMENT
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID 1 ,
C405.2.1 Lighting controls installed to uniformly ❑Complies 'Requirement will be met.
[EL15]1 I reduce the lighting load by at least ❑Does Not
1 50%. [Not Observable Location on plans/spec: E-9.02 LIGHTING SEQUENCE OF
❑Not Applicable OPERATIONS
C405.2.1 1 Occupancy sensors installed in ❑Complies Exception:Areas such as security or emergency areas that
[EL18]1 I required spaces. ❑Does Not need continuous lighting.
[Not Observable Location on plans/spec:THIS IS A 24-HOUR FACILITY
❑Not Applicable
C405.2.1, Independent lighting controls installed ❑Complies Exception:Areas such as security or emergency areas that
C405.2.2. per approved lighting plans and all ❑Does Not need continuous lighting.
3 manual controls readily accessible and
[EL23]2 visible to occupants. ❑Not Observable Location on plans/spec: E-701.E.1 - LIGHTING CONTROLS
❑Not Applicable ACCESSIBLE TO AUTHORIZED USERS ONLY
C405.2.2. Automatic controls to shut off all ;❑Complies Exception:Areas such as security or emergency areas that
1 building lighting installed in all ❑Does Not need continuous lighting.
[EL22]2 buildings. ❑Not Observable
Location on plans/spec:THIS IS A 24-HOUR FACILITY
❑Not Applicable
01 .3 Daylight zones provided with ;❑Complies Exception: Requirement does not apply.
individual controls that control the ❑Does Not
lights independent of general area ❑Not Observable Location on plans/spec: NO DAYLIGHTING ZONES WITH
lighting. GREATER THAN 150W OF GENERAL LIGHTING.
❑Not Applicable
C405.2.3, Primary sidelighted areas are Complies Exception: Requirement does not apply.
C405.2.3. equipped with required lighting ❑Does Not
1, controls. Location on plans/spec: NO DAYLIGHTING ZONES WITH
C405.2.3. ❑Not Observable GREATER THAN 150W OF GENERAL LIGHTING.
2 ❑Not Applicable
[EL20]1
C405.2.3, Enclosed spaces with daylight area ;❑Complies Exception: Requirement does not apply.
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, are equipped with required lighting ['Not Observable Location on plans/spec: NO SKYLIGHTS OR MONITORS
C405.2.3. controls.
3 ❑Not Applicable
[EL21]1
C405.2.4 Separate lighting control devices for EComplies Requirement will be met.
[EL4]1 specific uses installed per approved ❑Does Not
lighting plans. Location on plans/spec: ELECTRICAL PLANS- EACH
['Not Observable APPLICATION HAS A DIFFERENT LIGHTING ZONE
❑Not Applicable 1
C405.2.4 Additional interior lighting power ❑Complies Requirement will be met.
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is ['Not Observable Location on plans/spec: ALL LIGHTING APPLICATIONS ARE
automatically controlled and CONTROLLED ON SEPARATE ZONES.
separated from general lighting. ❑Not Applicable
i
C405.3 Exit signs do not exceed 5 watts per ❑Complies Requirement will be met.
[EL6]1 face. ❑Does Not
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
(High Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) � ��
Project Title: RESIDENCES AT LITTLE NELL Re o11r t�: / 4���
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck ite/315if20722
ASPEN
BUILDING DEPARTMENT
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, ;Furnished O&M instructions for ❑Complies Requirement will be met.
C408.2.5. systems and equipment to the ❑Does Not
2 building owner or designated
[F117]3 representative. [Not Observable
❑Not Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[F118]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts ['Not Observable
are less than or equal to allowed ❑Not Applicable
watts.
C408.2.5. :Furnished as-built drawings for ❑Complies Requirement will be met.
1 :electric power systems within 90 days ❑Does Not
[F116]3 of system acceptance.
[Not Observable
ENot Applicable
C408.3 1Lighting systems have been tested to ❑Complies Requirement will be met.
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation. Location on plans/spec: DIVISION 26 09 33 SPECIFICATIONS
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 IHigh Impact(Tier 1) 12 Medium Impact(Tier 2) 3 Low Impact(Tier 3) � f D
Project Title: RESIDENCES AT LITTLE NELL Re o t�: g/14
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck lade/3fif20722
ASPEN
BUILDING DEPARTMENT
Project Title: RESIDENCES AT LITTLE NELL ReREt : E/lvf D
Data filename: \\files\Active\Projects\2022\22000596.00\Design\Electrical\little_nell_comcheck.cck ite/31'��20'22
ASPEN
BUILDING DEPARTMENT