HomeMy WebLinkAboutFile Documents.501 Dean St.0019-2022-BCOM (24) CPT1
• COURISTAN®
CONTRACT • HOSPITALITY
Couristan Technical Specification
Quality Reference INTERNATIONAL 9-250-47
STANDARD
Construction ISO 2424 Axminster
Pile Content BS 3655 80%Virgin Wool 20%Anti-Stat Type 6.6 Nylon
Backing Content-Weft ISO 2424 100%Polypropylene
-Warp ISO 2424 Polypropylene/Polyester
Backing Finish ISO 2424 Fray resistant latex compound
Width BS 3655 91/12 /13 2"/1316"/15 2.74m/3.66m/4.00m/4.11 m/4.57m
CO lI Pitch ISO 2424 7.00 per inch 27.56 per dm
Rows ISO 2424 9.00 per inch 35.44 per dm
a
W Yarn Count ISO 2060 2/47 s(Dewsbury) R 660/2(Tex)
0
Z Loom Type Standard High Speed MAX Standard High Speed MAX
0 Total Pile Weight ISO 8543 36.2 oz/sq.yd 36.2 oz/sq.yd 1229 g/sq.mtr 1229 g/sq.mtr
V
Effective Pile Weight ISO 8543 24.2 oz/sq.yd 25.8 oz/sq.yd 820 g/sq.mtr 875 g/sq.mtr
Pile Height Above Backing ISO 1766 0.250 inches 0.267 inches 6.35 mm 6.77 mm
Total Carpet Thickness ISO 1765 0.356 inches 0.354 inches 9.05 mm 8.98 mm
a _
F• Total Weight ISO 8543 62.0 oz/sq.yd 59.2 oz/sq.yd 2101 g/sq.mtr 2007 g/sq.mtr
li Above technical specification is subject to accepted manufacturing tolerances as at date printed-7 October 2014
Cl) — _
0 Key Performance Standards
I Fastness-Light ISO 105-B02 >_5
-Water ISO 105-E01 >_4
-Shampoo BS 1006 >_4
-Rubbing ISO 105-X12 >_4
Flammability- Radiant Panel ASTM E-648 Class 1>0.5 W/cm'
- Smoke Density ASTM E-662 <_450 Dm
Appearance Retention ASTM 5252 >_3.5
Static Electricity AATCC 134 <_2 Kv
Indoor Air Quality GREEN LABEL PLUS Approvals GLP 2211 &2224
Couristan Inc.
Residential and Contract Broadloom Division
Two Executive Drive RECEIVED
Fort Lee,N.J.07024
Phone (201) 585-8500
Fax (201)585-9347 0 3/14/2 0 2 2
www.couristan.com
ASPEN
BUILDING DEPARTMENT
CPT1
Professional Testing Laboratory,Inc.
TEST REPORT
DATE: 10/05/2012 TEST NUMBER: 151772
CLIENT Couristan
ASTM E648-10 Standard Test Method for Critical Radiant Flux of
TEST METHOD CONDUCTED Floor Covering Systems Using A Radiant Heat Energy Source, also
referenced as NFPA 253 and FTM Standard 372
DESCRIPTION OF TEST SAMPLE
IDENTIFICATION
CONSTRUCTION
Axminster
7 pitch, 9 Row
FIBER 47s 80/20 Wool/Nylon
BACKING Woven
GENERAL PRINCIPLE
This procedure is designed to measure the critical radiant flux at flame out of horizontally mounted floor
covering systems exposed to a flaming ignition in a test chamber which provides a graded radiant heat energy
environment. The imposed radiant flux simulates the thermal radiation levels likely to impinge on the floors of a
building whose upper surfaces are heated by flames from a fully developed fire in an adjacent room or
compartment. The test result is an average critical radiant flux (watts/square cm) which indicates the level of
radiant heat energy required to sustain flame propagation in the flooring system once it has been ignited. A
minimum of three test specimens are tested and the results are averaged. Theoretically, if a room fire does not
impose a radiant flux that exceeds this critical level on a corridor floor covering system,flame spread will not occur.
The NFPA Life Safety Code 101 specifies as Class 1 Critical Radiant Flux of .45 watts/sq cm or higher and
Class 2 Critical Radiant Flux as .22- .44 watts/sq cm.
FLOORING SYSTEM ASSEMBLY
SUBSTRATE Mineral-Fiber/Cement Board UNDERLAYMENT Direct Glue Down
ADHESIVE Advanced Adhesive 275 CONDITIONING Minimum of 96 hours at 70 ± 5° F and 50 ± 5%
relative humidity
Distance Burned Time To Flame Out Critical Radiant Flux
Specimen 1 34 cm 25 minutes 0.61 watts/square cm
Specimen 2 33 cm 23 minutes 0.63 watts/square cm
Specimen 3 33 cm 24 minutes 0.63 watts/square cm
Average Critical Radiant Flux 0.62 Watts/Square Cm
Standard Deviation 0.01 Watts/Square Cm
Coefficient of Variation 1.51 %
* NOTE: Meets or exceeds Class 1 rating as specified in NFPA Life Safety Code 101 and IBC 804.2
Classification.
APPROVED BY: 4 447----41- .�I 1V r,?•, IVED
Thu.tidlitai.aoa:di:dbyth:Ntia.o.1 luitaryLabonti�ry:.c.a:dta2ionFRog-amforth: :cmc eccg:of ao=editahon�sds Lab ' :.1: liiii �' .This aeaedtatimdoes
not corettuuansuiors.melt_cax;ncation,orapprou*alb.rITISTorazraa :—0yo2th:Thurt:dStat:s.t;,:mlzffi.sdtortlWprcii2t:t:d.Tkusnpcat.Eproiid:ditr3 c e '2022
,i.:of the Gist to R'lcni it .adir:ss:d.Itmsy h:,i.:�3 i<l it:lEtk7t O:-aaL pro dud arc:ptaro::from duly corcY rt:d artkriti:s.Thu.retort ag�h oryytc tl�r�s@ samgr s/
t:Y:d Yld Is rLctn:c:ssan1y int.::Ln:of apparel i 1116:11 of simihr prc. ict.This r:pow orth:MIL.:of Prcf:ssional T'cur .Lab.a1or;hc.doll rat"?used under
czorm taru::In a ?dstiillg.ti.the:':.11i al pubhc. ASPEN
714 GleirAr_.:,d Place D.aito,t GA 3i1721 Phone:-,35-226-32E3 Fax:7o -2 -6/'/ amail:prote4,61iiiialtIG DEPARTMENT
CPT1
Professional Testing Laboratory,Inc.
TEST REPORT
DATE: 10/05/2012 TEST NUMBER: 151772
CLIENT Couristan
ASTM E662-09 Smoke Density (Flaming) Standard Test Method for
TEST METHOD CONDUCTED Specific Optical Density of Smoke Generated by Solid Materials also
referenced as NFPA 258
DESCRIPTION OF TEST SAMPLE
IDENTIFICATION Axminster
CONSTRUCTION 7 pitch,9 Row
FIBER 47s 80/20 Wool/Nylon
BACKING Woven
GENERAL PRINCIPLE
This procedure is designed to measure the specific optical density of smoke generated by the test
specimen within a closed chamber. Each specimen is exposed to an electrically heated radiant-energy source
positioned to provide a constant irradiance level of 2.5 watts/square cm on the specimen surface. Measurements
are recorded through a photometric system employing a vertical beam of light and a photo detector positioned to
detect the attenuation of light transmittance caused by smoke accumulation within the chamber. The light
transmittance measurements are used to calculate specific optical density, a quantitative value which can be
factored to estimate the smoke potential of materials. Two burning conditions can be simulated by the test
apparatus. The radiant heating in the absence of ignition is referred to as the Non-Flaming Mode. A flaming
combustion in the presence of supporting radiation constitutes the Flamin Mode.
CONDITIONS
PREDRYING OF TEST SAMPLE 24 Hours at 140°F
CONDITIONING OF TEST SAMPLE 24 Hours at 70°F and 50%Relative Humidity
FURNACE VOLTAGE 118 V IRRADIANCE ' 2.5 watts/sq cm
CHAMBER TEMPERATURE 95°F CHAMBER PRESSURE 3"H2O
TEST MODE Flaming
AVERAGE MAXIMUM DENSITY CORRECTED (Dmc) FLAMING 149
AVERAGE SPECIFIC OPTICAL DENSITY AT 4.0 MINUTES 161
Specimen 1 Specimen 2 Specimen 3
Maximum Density(Dm) 163.0 136.0 208.0
Time to Dm (minutes) 4.5 4.5 4.0
Clear Beam (Dc) 19.0 16.0 26.0
Corr.Max Density(Dmc) 144.0 120.0 182.0
Density at 1.5 minutes 10.0 9.0 6.0
Density at 4.0 minutes 153.0 126.0 205.0
Time to 90% Dm (minutes) 4.0 4.0 3.5
Specimen Weight(grams) 10.9 10.9 10.7
*This sample PASSES the requirements of 450 or less.
APPROVED BY: V.) IVED
.111iS cilir7 .ac=edtedb7the ' luitar7Lab.adtor7:..=editation)•'IO:Tam1rthe ec>tic:c.ge 2ao=editahon'sdr Lib Gc.i: biii '.'i.This aernediatimdoes r� r�r�
not corettuu ozuiors.emer�cstuacatior,crappronalt...1 ,Torare7a :suryottheThurtedStat.?l;,:mert�u.sd tor tlWprc�duct.teted.Tlti.reporti:.F�rr�?rided2� n!" c a 2022
i.e of the diet to what it .adire.:sed It be u,-.d Ii it:s�erato:-airL pro dud arceptaro:e from duly coreiint:Id.iith rides.'ads retort ag�h oriat:'tll��s@ samp s/
to t d Yld ISnotnece: 112yint.:111,e of apparer¢;i11o:11 of similarprc•iucts.Tluc repot crthe name of FTufessicrLal TecoutgLab.alor7 YLc.slLiJlriatte used tinier ay
circumtu'u:eIn a ?dstt11 . :':.ronal pub hc• ASPEN
714t:lernAr_._,dPlace Dalton,1:,A_0721 Phone:,35-226-32E3 Fax:7o -226-6rK/ protegtObalgitiGDEPARTMENT
SF1, SF2, & SF3
FLOOR AND WALL TILES
specifications
Content European full grain vegetable-tanned aniline-dyed cowhide
Finish Durable protective finish
Thickness 3.0-3.5 mm
Weight Per Square Foot 8.5 oz
Colors Available 32 standard colors
Custom Custom coloring available
Applications Residential,Hospitality,Contract,Aviation,Marine,Retail
Use Vertical and direct applications
Wellness Greenguard indoor air quality certified
Performance Recommended for light-traffic areas,light patina
testing
Durability&Strength Breaking Force ASTM 2208(1001bs):Complies
Crocking ASTM D 5053:Class 5
Elongation ASTM D 2211(20-50%):Complies
Light Fastness 72hrs/ISO 105-B02:Class 3-4
Tearing Strength ASTM D 4705(15lbs):Complies
Flammability Boston Fire Code(BFD 1X-1):Complies
California Technical Bulletin 117-2013:Class 1
Cigarette Ignition Resistance(NFPA 260):Class 1
Surface Building Characteristic of Building Materials(ASTM E 84):Class B
maintenance
If a spill or stain should occur,blot immediately with a clean,absorbent cloth or sponge.Do
not rub with force or pressure.A drop of saddle soap on a damp cloth may remove dirt.
u` a CEIVED
GREENGUARD E DE
A22
FLOOR AND WALL TILES SPECIFICATIONS I PAGE 9 OF 10 L E AT H R
ASPEN
BUILDING DEPARTMENT
SF6
SHAGREEN
specifications
Content European full grain vegetable-tanned aniline-dyed cowhide
Finish Durable protective finish,hand-antiqued,EDGE stain release
Size Avg 28 sf/Platelines 24"/1/2 hide
Average Usable Area 28"x 65"
Thickness 1.2-1.3 mm
Weight Per Square Foot 3 oz
Texture Embossed grain
Colors Available 20 standard colors
Custom Custom coloring available
Applications Residential,Hospitality,Contract,Aviation,Marine,Retail
Use Upholstery and vertical applications
Wellness Greenguard Gold certified
EDGE Stain Release Standard on all colors
Performance Recommended for high-traffic areas,light patina
Considerations Platelines every 24"
testing
Durability&Strength Breaking Force ASTM 2208(1001bs):Complies
Crocking ASTM D 5053:Class 4-5
Elongation ASTM D 2211(20-50%):Complies
Light Fastness 72hrs/ISO 105-B02:Class 4-5
Tearing Strength ASTM D 4705(15lbs):Complies
Flammability Boston Fire Code(BFD 1X-1):Complies
California Technical Bulletin 117-2013:Class 1
Cigarette Ignition Resistance(NFPA 260): Pass
Surface Building Characteristic of Building Materials(ASTM E 84):Class B
maintenance
If a spill or stain should occur,blot immediately with a clean,absorbent cloth or sponge.Do
not rub with force or pressure.A drop of saddle soap on a damp cloth may remove dirt.
mindful IVED
GREENGUARD MATERIALS
GOLD EDE 2022
SHAGREEN SPECIFICATIONS I PAGE 3 OF 5 L EAT H R
ASPEN
BUILDING DEPARTMENT
SF1, SF2, SF3, & SF6
sGs
CLIENT: Teddy & Arthur Edelman Ltd.
80 Pickett District Road
New Milford, CT 06776
Attn: Janet Green
Test Report No.: 176415-02 Date: April 28, 2003 1
SAMPLES SUBMITTED BY CLIENT AS: Style Color Description
#FT05 Dk. Green Floor Tile
#AG01 Pitch Brown All Grain
#FC09 Mocha Fatted Calf
#CCO3 Oyster Cashmere Calf
#RS03 Parchment Royal Suede
DATE OF RECEIPT: April 22, 2003
TESTING PERIOD: April 25, 2003
TEST REQUESTED: California Technical Bulletin 117 Sect. E
TEST RESULTS: Please refer to the following pages
CONCLUSION: The submitted samples meet the requirements of California
Technical Bulletin 117 Section E and are rated as Class 1
Normal Flammability.
PREPA BY: SIGNED FOR A D ON B HALF OF
A/fl7-
‘,/‘.41 . SGS U.S. 1NG C PANY, INC.
In erman
Eduardo E. Rodriguez
Technician - Flammability ManagerTextilg Laboratory
Textiles
rm Page 1 of 4
This report is issued by SGS U.S. Testing Company Inc. under its General Conditions for Testing Services, as printed on reverse side. SGS U.S.
Testing's responsibility under this report is limited to proven negligence and will in no case be more than the amount of the testing fees. Except
by special arrangement, samples are not retained by SGS U.S.Testing for more than 30 days. The results shown on this "�'p
the sampleis){g tested unless otherwise
n'ametated, under the seals, marks nor insignia ofnditions rSGS U S. Testngeed upon. emaylng on be used!s nranyrt should advertsingdor promotional materials
of the engagement. NeitherOr � a�2io`tk
without the prior written approval of SGS U.S.Testing. The test report cannot be reproduced, except in full, without prior t p r i
SGS U.S.Testing Company Inc.I y y inmpuny in teom
e�p C
Testing Services 291 Fairfield Avenue,Fairfield,NJ 07D04 t(973)575.5252 t 19731 1UILDIN& PAR9IMENT
... ___ _,., r..,....,rcn,alt4 Generale de Surveillance)
SF1, SF2, SF3, & SF6
SGS
Report No.: 176415-02
Date: 04/28/03
Page: 2 of 4
CLIENT: Teddy & Arthur Edelman Ltd.
RESULTS:
Flammability
California Technical Bulletin 117 Section E
Sample ID: Style #FT05 Color: Dk. Green Description: Floor Tile
Length Width
Rate of Burning (secs)
Face Back Face Back
DNI DNI DNI DNI
DNI DNI DNI DNI
DNI DNI DNI DNI
DNI DNI DN1 DNI
DNI DNI DNI DNI
Sample ID: Style #AG01 Color: Pitch Brown Description: All Grain
Length Width
Rate of Burning (secs)
Face Back Face Back
DNI DNI DNl DNI
DNI DNI DNI DNI
DNI DNI DNI DNI
DNI DNI DNI DNI
DNI DNI DNI DNI
DNI = Did Not Ignite
RECEIVED
03/14/2022
ASPEN
BUILDING DEPARTMENT
SF1, SF2, SF3, & SF6
96-D Allen Boulevard
Farmingdale, New York 11735-5626 USA
Govmark Tel.+1 (631)293-8944 Fax+1 (631)293-8956
e-mail:testing@govmark.com
Page 1
Received:11/16/2016 Completed:11/17/2016 Letter:G BG P.O.#: Test Report#: 3-16415-0-
Client's Description of Sample:Edelman Leather-Embossed.
Identification
Tested For: Janet Green Key Test: CA TB 117-2013(Section 1-Cover 235
Edelman Leather,LLC Fabric)
80 Pickett District Road Tel: 1-(860)-350-9600 Ext:
New Milford,CT 06776 Fax: 1-(860)-210-2590
CA TB 117 LE: 2013; V 5/16 PC: 24 hrs: 21°± 3°C; less than 55% RH SM/mg
NTR 04/16
TEST PERFORMED: California Technical Bulletin 117-2013 - Requirements, Test Procedure and Apparatus
for Testing the Smolder Resistance of Materials Used in Upholstered Furniture (June 2013 Version)
Section 1, Cover Fabric Test (Upholstery cover material is the outermost layer of fabric or
related material used to enclose the main support system or upholstery materials, or both,
used in the furniture item.)
REFERENCE: ASTM E1353-08ae1
IGNITION SOURCE: SRM 1196 Cigarette
SPECIMEN TEST COMPOSITE:
Upholstery Cover Material: As described in "Client's Identification".
Standard Substrate Material: Non FR polyurethane foam, density 1.8 ± 0.05 lb/ft3
BRIEF DESCRIPTION OF TEST: Miniature cushions are prepared using the client's cover fabric over the
standard filling material. The vertical or back cushions measure 8" x 8" x 2". The horizontal or seat
cushions measure 8" x 5" x 2".
A lighted cigarette is placed in the crevice formed by the vertical cushion and the horizontal cushion.
The test is terminated at 45 minutes if smoldering is no longer observed.
Test measurements and observations are recorded.
-- See Page 3 for "Results" and "Conclusion" --
(Page 1 of 4)
RECEIVEt
03/14/2022
File Copy
ASPEN
BUILDING DEPARTMENT
SF1, SF2, SF3, & SF6
96-D Allen Boulevard
Farmingdale, New York 11735-5626 USA
Govmark Tel.+1 (631)293-8944 Fax+1 (631)293-8956
e-mail:testing@govmark.com
min Page 2
Received:11/16/2016 Completed:11/17/2016 Letter:G BG P.O.#: Test Report#: 3-16415-0-
Client's Description of Sample:Edelman Leather-Embossed.
Identification
Tested For: Janet Green Key Test: CA TB 117-2013(Section 1-Cover 235
Edelman Leather,LLC Fabric)
80 Pickett District Road Tel: 1-(860)-350-9600 Ext:
New Milford,CT 06776 Fax: 1-(860)-210-2590
PASS/FAIL/REPEAT CRITERIA: A material is considered to pass or fail based on the following criteria:
1. A single mock-up test specimen fails to meet the requirements of this test procedure
if any of the following criteria occurs:
a) The mock-up test specimen continues to smolder after the 45 minute test duration;
b) A vertical char length (measured as specified in step 11.9 of ASTM E1353-08ae1)
of more than 1.8 inches (45 mm) develops on the cover fabric.
c) The mock-up test specimen transitions to open flaming.
2. The cover fabric passes the test if three initial mock-up specimens pass the test, i.e.,
the cigarettes burn their entire length and the mock-ups are no longer smoldering.
3. If more than one initial specimen fails, the cover fabric fails the test.
4. If any one of the three initial specimens fails, repeat the test on additional three
specimens.
5. If all three additional specimens pass the test, the cover fabric passes the test. If
any one of the additional three specimens fails, the cover fabric fails the test.
DISCUSSION: The current version of California Technical Bulletin 117-2013 has no provision to
recognize cigarettes that self-extinguish prior to burning their entire length. However, ASTM E 1353
does recognize this phenomenon.
The Govmark report evaluates replacement cigarettes as follows:
If a cigarette self extinguishes (SE) before burning its entire length, a new cigarette
is placed into the test. If the new (replacement) cigarette self-extinguishes or burns
its entire length, the result for that specimen will then be evaluated as if the cigarette
burned its entire length when assigning the "Passing/Failure" conclusion.
(Page 2 of 4)
RECEIVED
03/14/2022
File Copy
ASPEN
9UUILDING DEPARTMENT
SF1, SF2, SF3, & SF6
96-D Allen Boulevard
Farmingdale, New York 11735-5626 USA
,.: Goir rk Tel.+1 (631)293-8944 Fax+1 (631)293-8956
e-mail:testing@govmark.com
Page 3
Received:11/16/2016 Completed:11/17/2016 Letter:G BG P.O.#: Test Report#: 3-16415-0-
Client's Description of Sample:Edelman Leather-Embossed.
Identification
Tested For: Janet Green Key Test: CA TB 117-2013(Section 1-Cover 235
Edelman Leather,LLC Fabric)
80 Pickett District Road Tel: 1-(860)-350-9600 Ext:
New Milford,CT 06776 Fax: 1-(860)-210-2590
RESULTS:
Char Length SE SB45 TOF
Specimen # (inches) (yes/no) (yes/no) (yes/no)
Initial: 1 0 Yes No No
2 0 Yes No No
3 0 Yes No No
Replacement: 1 0 Yes No No
(If needed) 2 0 Yes No No
3 0 Yes No No
Repeat Tests: 1
(If needed) 2
3
EXPLANATION:
Initial.: These are the first 3 cigarettes where the results could be sufficient to
draw a test conclusion.
Replacement: If any of the initial cigarettes self-extinguish before burning their complete
length, a new test is conducted with a fresh cigarette.
Repeat Test: Depending on the initial or replacement results, repeat tests might be required
to draw a conclusion.
CODES USED:
SE = Cigarette self-extinguished; See "Discussion" on Page 2
SB45 = Smolder beyond 45 minutes
TOF = Transitions to open flaming
MNR = Measurement not recorded as smoldering exceeded 45 minutes or specimen
transitioned to open flames
EC = Escalating smoldering combustion: Extinguished by technician at:
(mm:ss) due to unsafe conditions.
CONCLUSION:
The above results reported for the initial and / or replacement cigarettes are sufficient to
indicate:
[x] Passing; [ 3 Failure; 1 ] Repeat test on 3 additional specimens
The results after conducting the repeat tests indicate:
1 3 Passing; [ ] Failure ��
(Page 3 of 4) 114
03/1CI 2022
FleCay
ASPEN
'3UILDING DEPARTMENT
SF1, SF2, SF3, & SF6
96-D Allen Boulevard
Farmingdale,New York 11735-5626 USA
e Govmark Tel.+1 (631)293-8944 Fax+1 (631)293-8956
e-mail:testing@govmark.com
■� Page 4
Received:11/16/2016 Completed:l 1/17/2016 Letter:G BG P.O.#: Test Report#: 3-16415-0-
Client's Description of Sample:Edelman Leather-Embossed.
Identification
Tested For: Janet Green Key Test: CA TB 117-2013 (Section 1-Cover 235
Edelman Leather,LLC Fabric)
80 Pickett District Road Tel: 1-(860)-350-9600 Ext:
New Milford,CT 06776 Fax: 1-(860)-210-2590
REMARKS: None.
CERTIFICATION: I certify that the above results were obtained after testing specimens in accordance
with the procedures and equipment specified above.
MS: . ! !T#S'
An RIZED SIGNATURE NOV1 8 2016 •
GOVMARK 1
/mg l.tfll J;
(Page 4 of 4)
RECEIVED
0The results contained in this report relate only to item(s)tested.The test report shall not be 3 14 2
File Copy
2 2
reproduced,except in full,without written approval from Govmark. ASPEN
BUILDING DEPARTMENT
wc1
COMMERCIAL TESTIMC� COMP
.IAEA
11EtMY
_ "' ii
"- 1215 South Hamilton Street Post Office Box 985 , Dalton,GA 30722
Telephone(706)278-3935 Facsimile(706)278-3936
Standard Method of Test for
Surface Burning Characteristics of Building Materials
ASTM E 84-07
20 oz.Fabric Backed Vinyl Wallcovering using Low Phenol Film
Report Number 08-06242
Test Number 4012-3651
June 26,2008
J.Josephson,Inc.
South Hackensack,New Jersey
Commercial Testing Company
(Authorized Signature)
This report is provided for the exclusive use of the client to whom it is addressed.It may be used in its entirety to gain product
acceptance from duly constituted authorities. The test results presented in this report apply only to the samples tested and are
not necessarily indicative of apparent identical or similar materials. Sample selection and identification were provided by the
client.A sampling plan,if described in the referenced test procedure,was not necessarily followed. This report,or the name of
Commercial Testing Company,shall not be used under any circumstance in advertising to the general public.
TESTED TO BE SURE®
Since 1974
RECEIVED
03/14/2022
ASPEN
BUILDING DEPARTMENT
WC1
INTRODUCTION
This report is a presentation of results of a surface flammability test on a material submitted by J.
Josephson,Inc.,South Hackensack,New Jersey.
The test was conducted in accordance with the ASTM International fire test response standard E 84-07,
Surface Burning Characteristics of Building Materials, sometimes referred to as the Steiner tunnel test. This
test is applicable to exposed surfaces such as walls and ceilings. The test is conducted with the specimen
in the ceiling position with the surface to be evaluated exposed face down to the ignition source. The
ASTM E 84 test method is the technical equivalent of NFPA No.255 and UL No.723.
This standard is used to measure and describe the response of materials, products, or assemblies to heat
and flame under controlled conditions, but does not by itself incorporate all factors required for
fire—hazard or fire—risk assessment of materials,products,or assemblies under actual fire conditions.
PURPOSE
The purpose of the test is to provide only the comparative measurements of surface flame spread and
smoke development of materials with that of select grade red oak and fiber—reinforced cement board,
Grade II,under specific fire exposure conditions.The test exposes a nominal 24-foot long by 20-inch wide
test specimen to a controlled air flow and flaming fire adjusted to spread the flame along the entire length
of a red oak specimen in 5.50 minutes. During the 10-minute test duration, flamespread over the
specimen surface and density of the resulting smoke are measured and recorded. Test results are
calculated relative to red oak, which has an arbitrary rating of 100, and fiber—reinforced cement board,
Grade II,which has a rating of 0.
The test results are expressed as Flame Spread Index and Smoke Developed Index. The Flame Spread
Index is defined in ASTM E 176 as "a number or classification indicating a comparative measure derived
from observations made during the progress of the boundary of a zone of flame under defined test
conditions." The Smoke Developed Index, a term specific to ASTM E 84, is defined as "a number or
classification indicating a comparative measure derived from smoke obscuration data collected during
the test for surface burning characteristics." There is not necessarily a relationship between the two
measurements.
The method does not provide for measurement of heat transmission through the surface tested,the effect
of aggravated flame spread behavior of an assembly resulting from the proximity of combustible walls
and ceilings,or classifying a material as noncombustible solely by means of a Flame Spread Index.
The zero reference and other parameters critical to furnace operation are verified on the day of the test by
conducting a 10—minute test using 1/4—inch fiber—reinforced cement board,Grade II.Periodic tests using
NOFMA certified 23/32—inch select grade red oak flooring provide data for the 100 reference.
TEST SAMPLE
The test sample, selected by the client, was identified as 20 oz.Fabric Backed Vinyl Wallcovering using
Low Phenol Film, a wallcovering with a total weight of 13.2 ounces per square yard. Three test panels,
each measuring two feet wide by eight feet in length,were prepared by adhering the material to 1/4—inch
thick fiber—reinforced cement board, Grade II, using Gardner—Gibson Dynamite 111 Heavy Duty
Wallcovering Adhesive. The adhesive was applied with a roller to the back of the wallcovering,booked 5
to 7 minutes, the material placed onto the smooth side of the cement board,and smoothed with a brush
and roller. After dead—stacking overnight, the prepared panels were transferred to storage racks and
conditioned to equilibrium in an atmosphere with the temperature maintained at 71±2°F and the relative
humidity at 50 ± 5 percent. For testing,the panels were placed end—to—end on the ledges of the tunnel
furnace and tested with no auxiliary support mechanism.This method of sample preparation is described
in ASTM International Standard Practice E 2404 06, Specimen Preparation and Mounting of Paper or Vinyl
Wall or Ceiling Coverings to Assess Surface Burning Characteristics,Section 8.2.
RECEIVED
03/14/2022
ASPEN
BUILDING DEPARTMENT
WC
TEST RESULTS
The test results, calculated on the basis of observed flame propagation and the integrated area under the
recorded smoke density curve,are presented below.The Flame Spread Index obtained in E 84 is rounded
to the nearest number divisible by five. Smoke Developed Indices are rounded to the nearest number
divisible by five unless the Index is greater than 200. In that case,the Smoke Developed Index is rounded
to the nearest 50 points. The flame spread and smoke development data are presented graphically on
Page 4 of this report.
Test Specimen Flame Spread Index Smoke Developed Index
Fiber-Reinforced Cement Board,Grade II 0 0
Red Oak Flooring 100 100
20 oz.Fabric Backed Vinyl Wallcovering 20 45
using Low Phenol Film
OBSERVATIONS
Specimen ignition over the burners occurred at 0.12 minute. Surface flame spread was observed to a
maximum distance of 4.17 feet beyond the zero point at 1.85 minutes. The maximum temperature
recorded during the test was 573°F.
CLASSIFICATION
The Flame Spread Index and Smoke Developed Index values obtained by ASTM E 84 tests are frequently
used by code officials and regulatory agencies in the acceptance of interior finish materials for various
applications. The most widely accepted classification system is described in the National Fire Protection
Association publication NFPA 101 Life Safety Code,where:
Class A 0 - 25 Flame Spread Index 0-450 Smoke Developed Index
Class B 26 - 75 Flame Spread Index 0-450 Smoke Developed Index
Class C 76 - 200 Flame Spread Index 0-450 Smoke Developed Index
Class A, B, and C correspond to Type I, II, and III respectively in other codes. They do not preclude a
material being otherwise classified by the authority of jurisdiction.
RECEIVED
03/14/2022
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE '
6220 CULEBRA ROAD 78238-5166 • P.O.DRAWER 28510 78228-0510 • SAN ANTONIO,TEXAS,USA • (210)684-5111 • WWW.SWRI.ORG
CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT
WWW.FIRE.SWRI.ORG
FAX(210)522-3377
January 21, 2020
(1111)
NSF-ISR
Mr. David Berkowitz toe5'o`900,
Maya Romanoff Corporation
3435 Madison St.
Skokie, IL 60076
Subject: SwRI®Project No. 01.24921.20.103b TEST DATA
(Consisting of 7 Pages)
Dear Mr. Berkowitz:
A fire performance evaluation was conducted on January 13, 2020, for Maya Romanoff
Corporation in general accordance with Part 2,Smoke and Toxicity Test,of Annex 1 of the International
Maritime Organization (IMO), International Code for Application of Fire Test Procedures (2010 FTP
Code). Test was considered to be in general accordance because only one sample in each exposure mode
was conducted instead of three,per the standard. The first run was conducted at 50 kW/m2 in the non-
flaming(NF)mode. Depending on the presence of ignition,the second run was conducted at 25 kW/m2
in the non-flaming or flaming mode(FL),whichever did not occur. The third run was conducted at the
exposure with the highest smoke density with gas sampling for toxicity measurements and analyzed
using a Fourier Transform Infrared(FTIR) spectrometer.
SwRI received the wallcovering material on November 22, 2019, and the samples were
prepared by SwRI personnel at a later date. An aluminum substrate was primed with Sherwin Williams
Extreme Bond Primer and allowed to dry. Then adhesive was applied by brush to the primed substrate
and the wallcovering material was attached and allowed to cure for 48 h. The samples were conditioned
to a constant mass at an ambient temperature of 73°F ± 5°F (23°C ± 3°C) and a relative humidity of
50%± 5%. Constant mass was achieved on December 17, 2019. The samples are described below in
Table 1.
Table 1. Sample Description.
Nominal Tested Nominal Tested
Material ID Description Color
Dimensions* Mass _
Woven wool and polyester
MR-CZ Series 75 x 75 x 7 mm** printed wallcovering applied 95 g** Black
to an aluminum substrate
*Assessed by SwRI personnel.
**Includes substrate
This report is for the information of the client.This report shall not be reproduced except in full,without the written approval of SwRI. RE EIVED
Neither this report nor the name of the Institute shall be used in publicity or advertising.
rki 03/14/2022
Benefiting government, industry and the public through innovative science and technology
ASPEN
BUILDING DEPARTMENT
WC5
Maya Romanoff Corporation
SwRI Project No.: 01.24921.20.103b
January 21, 2020
Page 2
A summary of the test results are shown below in Tables 2-3 and graphical data can be found
in Appendix A. Photographic documentation is located in Appendix B.
Table 2.IMO Part 2 Summary of Maximum Optical Density Results.
IMO Part 2 Acceptance Criteria MR-CZ Series
Bulkhead,wall and ceiling linings <200
50 kW/m2 NF: 229
Floor coverings <500 25 kW/m2 NF: 143
Primary deck coverings <400
Plastic Pipes <400
*Reported for informational purposes only.Testing was conducted in general accordance.
Table 3.IMO Part 2 Summary of Maximum Gas Concentrations Detected(ppm).
IMO Part 2 Acceptance CO HBr HCl HCN HF NO. SO2
Criteria < 120(200 for
(exposure mode) < 1,450 <600 <600 < 140 <600 <350
floor coverings)
MR-CZ Series 50 kW/m2 NF 1347 — — 32 -
-Represents gas not detected
*Reported for informational purposes only.Testing was conducted in general accordance.
If you should have any questions or comments, or if I can be of further assistance, please feel
free to contact me by phone at(210)522-3971 or by email at natasha.albracht@swri.org.
Sincerely, Approved:
MakirA 0/f)1Q(—
ASV(
Natasha Albracht Matthew S. Blais,Ph. D.
Research Engineer Director
Material Flammability Section Fire Technology Department
RECEIVED
03/14/2022
ASPEN
BUILDING DEPARTMENT
WC5
APPENDIX A
GRAPHICAL TEST DATA
(CONSISTING OF 2 PAGES)
RECEIVED
03/14/2022
Maya Romanoff Corporation SwRI Project No.01.24921.20.103b
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE
IMO Pt. 2 SMOKE DENSITY DATA SHEET
Material ID:MR-CZ Series SwRI Project No.: 01.24921.20.103b
Trade Name: Cozy Heat Flux: 25 kW/in'
Orientation: Horizontal Exposure Mode: No pilot(nonflaming)
Time to Max.
1.5 min 4.0 min Maximum Correction Corrected Max.
Test No. Test ID Ds
Ds Ds Ds Factor Ds
(s)
Run 1 20-009M ay aRom2 0 0 143 1196 1 l 1 31
Average 0 0 143 1196 111 31
OBSERVATIONS
Observed Time to Flames to Initial Flame Second
Test No. Observed Smoke Intumesence Blistering Ignition Top Out Ignition Final Flame Out
(s) (s) (s) (s) (s) (s) (s) (s)
Run 1 375 ❑ ❑ ❑ ❑ ❑ ❑ ❑
❑ ❑ ❑ ❑ ❑ ❑ ❑
❑ ❑ ❑ ❑ ❑ ❑ ❑
Average 375 ❑ ❑ ❑ ❑ ❑ ❑ ❑
OPTICAL DENSITY CHART
Uncorrected Ds at 25 kW/m2 without Pilot Flame
150
-Run 1
C 125
2 100
A
75
50
25
0 IIIII i I i I i I i I i I i I 1
0 120 240 360 480 600 720 840 960 1080 1200
Time (s)
RECEIVED
03/14/2022
Maya Romanoff Corporation A-1 SwRI Project No.01.24921.20.103b
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE
IMO Pt. 2 SMOKE DENSITY DATA SHEET
Material ID: MR-CZ Series SwRI Project No.: 01.24921.20.103b
Trade Name: Cozy Heat Flux: 50 kW/m2
Orientation: Horizontal Exposure Mode: No Pilot(Nonflaming)
Time to Max.
1.5 min 4.0 min Maximum Correction Corrected Max.
Test No. Test ID D D D Ds Factor D
Ds s s s
(s)
Run 1 20-009MayaRoml 4 133 232 480 60 172
Run 2 20-013M ayaRom3 12 116 226 567 19 206
Average 8 124 229 524 40 189
OBSERVATIONS
Observed Smoke L►tumesence Observed Time to Flames to Initial Flame Second Final Flame Out
Test No. Blistering Ignition Top Out Ignition
(s) (s) (s) (s) (s) (s) (s) (s)
Run 1 15 ❑ ❑ 15 ❑ 353 ❑
Run 2 10 ❑ ❑ 10 ❑ 249 ❑
Average 13 ❑ ❑ 13 ❑ 301 ❑
OPTICAL DENSITY CHART
Uncorrected Ds at 50 kW/m2 without Pilot Flame
250
— . .Run 1
g 200 —Run 2
.y
5 150
A
100
O
50
0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
0 200 400 600 800 1000 1200
Time (s)
RECEIVED
03/14/2022
Maya Romanoff Corporation A-2 SwRI Project No.01.24921.20.103b
ASPEN
BUILDING DEPARTMENT
WC5
APPENDIX B
PHOTOGRAPHIC DOCUMENTATION
(CONSISTING OF 1 PAGE)
RECEIVED
03/14/2022
Maya Romanoff Corporation SwRI Project No.01.24921.20.103b
ASPEN
BUILDING DEPARTMENT
WC5
•
•
•
•
•
•
•
•
Figure B-1.Typical test sample.
IIIIIIII IIII III IIIIII III IIII I Cf ient ID nO-CZ Series 655447 2 3"Pt•2..n • •••
655417 2 l Pt 2
Client- Mayo Romano(' Corporation Client ID MR-CZ Series
Client ID MR-CZ Series Client Maya Ronanoff Corporation
Client Maya Romano'(Corporation "4Q !
1./ -✓ r •
41
Figure B-2.MR-CZ Series after 25 kW/m2 NF and 50 kW/m2 NF(left to right)exposure.
RECEIVED
03/14/2022
Maya Romanoff Corporation B-1 SwRI Project No.01.24921.20.103b
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE®
6220 CULEBRA ROAD 78238-5166 • P.O.DRAWER 28510 78228-0510 • SAN ANTONIO,TEXAS,USA • (210)684-5111 • WWW.SWRI.ORG
CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT
WWW.FIRE.SWRI.ORG
FAX(210)522-3377
el
NSFISR
LI
m oo wm
FIRE PERFORMANCE EVALUATION IN ACCORDANCE WITH
PART 5 OF ANNEX 1 OF THE 2010 IMO FTP CODE, TEST FOR
SURFACE FLAMMABILITY
MATERIAL ID: MR-CZ Series
TRADE NAME: Cozy
FINAL REPORT
Consisting of 10 Pages
SwRI®Project No.: 01.24921.20.103c
Test Date: March 13, 2020
Report Date: April 2, 2020
Prepared for:
Maya Romanoff Corporation
3435 Madison St.
Skokie,IL 60076
This test was conducted in accordance with the applicable standard;and to the best of our
knowledge, it contains no errors, omissions, or false statements.
Submitted by: Approved by:
Natasha Albracht Matthew S. Blais,Ph.D.
Research Engineer Director
Material Flammability Section Fire Technology Department
This report is for the information of the client. It may be used in its entirety for the purpose of securing product acceptance from duly C IVE
constituted approval authorities. This report shall not be reproduced except in full,without the written approval of SwRI. Neither this Arm
report nor the name of the Institute shall be used in publicity or advertising.
03/14/2022
Benefiting government, industry and the public through innovative science and technology
ASPEN
BUILDING DEPARTMENT
WC5
1.0 INTRODUCTION
This report describes a fire performance evaluation conducted for Maya Romanoff Corporation
in accordance with Part 5, Test for Surface Flammability, of Annex 1 of the International Maritime
Organization (IMO), International Code for Application of Fire Test Procedures (2010 FTP Code).
Testing was conducted at Southwest Research Institute's (SwRI)Fire Technology Department, located
in San Antonio, Texas.
This test method should be used to measure and describe the properties of materials, products,
or assemblies in response to heat and flame under controlled laboratory conditions and should not be
used to describe or appraise the fire hazard or fire risk of materials,products,or assemblies under actual
fire conditions. However, results of this test may be used as elements of a fire risk assessment which
takes into account all the factors that are pertinent to an assessment of the fire hazard of a particular end
use.
This report describes the testing of the assembly tested and the results obtained. The results
presented in this report apply specifically to the material tested, in the manner tested, and not to the
entire production of these or similar materials, nor to the performance when used in combination with
other materials.
2.0 SAMPLE DESCRIPTION
SwRI received the samples on March 3, 2020, and they were prepared by SwRI at a later date.
The Roman Pro-935 primer was applied to a steel substrate with a roller and allowed to dry a minimum
of 12 h. The wallcovering material was then adhered to the substrate using Roman ECO-888 which
was applied with a roller at an application rate of 330 ft2/g and allowed to cure for 24 h. The sample is
described below in Table 1. The samples were conditioned to a constant mass at an ambient temperature
of 73°F ± 5°F (23°C ± 3°C) and a relative humidity of 50% ± 5%. Constant mass was achieved on
March 10, 2020.
Table 1. Sample Description.
Trade Nominal Tested Nominal
Material ID Description Received Color
Name Dimensions* Mass*
Woven wool and
MR-CZ Series Cozy 800 x 155 x 1.2 mm** Polyester,printed wall 3.18 kg** Black
covering applied to a steel
substrate
*Assessed by SwRI personnel.
**Includes substrate.
RECEIVED
03/14/2022
Maya Romanoff Corporation 2 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
3.0 TEST SETUP
Part 5 of the annex to the 2010 FTP Code is used primarily for determining the surface burning
characteristics of bulkhead, wall, ceiling, floor, and primary deck covering materials. The burning
characteristics are determined by heat release and flame front propagation measurements. A specimen
measuring 800 mm x 155 mm is exposed to a graded radiant flux field supplied by a gas-fired radiant
panel using the apparatus described in ISO 5658-2, except the equipment for measuring heat release.
The lateral flame spread rate over the specimen surface is determined by measuring the time for the
flame front to advance in 50-mm increments. The specimen is located under an exhaust stack that is
instrumented with a thermopile to measure the heat release rate.
4.0 TEST RESULTS
A summary of the test results is provided below in Table 2. Part 5 states that an exemption
from Part 2 requires that surface materials and primary deck coverings with both the total heat release
(Qt)of not more than 0.2 MJ and the peak heat release rate(Qp)of not more than 1.0 kW are considered
to comply with the requirements of Part 2 of Annex 1 without further testing. Further testing for IMO
Part 2 was not required for this test program. The detail test results can be found in Appendix A and
photographic documentation is presented in Appendix B. A copy of the calibration record sheet is on
file.
Table 2. IMO Part 5 Summary of Averaged Test Results.
Bulkhead,Wall
IMO Part 5 Surface Primary Deck
Flammability Criteria and Ceiling Floor Coverings Coverings MR-CZ Series
Linings
Average Critical Flux at >20.0 >7.0 >7.0 22.55
Extinguishment(CFE) (kW/m2): — — —
Average Heat for Sustained > 1.5 >0.25 >0.25 5.28
Burning(Qsb)MJ/m2): — — —
Average Total Heat Release(Qt) <0.7 <2.0 <2.0 0.0
(MJ): — — —
Average Peak Heat Release Rate <4.0 < 10.0 < 10.0 0.3
(Qp) (kW): — — —
Burning droplets Not produced TNo more than 10 Not produced None
burning drops
Required Substrate Any Any Steel Steel
Meets IMO Requirements Yes Yes Yes All applications
Considered to comply with
IMO Part 2 without further Qt<0.2 MJ and Qp< 1.0 kW Yes
testing
RECEIVED
03/14/2022
Maya Romanoff Corporation 3 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
APPENDIX A
DETAIL TEST RESULTS
(CONSISTING OF 3 PAGES)
RECEIVED
03/14/2022
Maya Romanoff Corporation SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE
2010 IMO FTP Code Part 5 - Surface Flammability Test Report
Material ID:MR-CZ Series SRI Project No.: 01.24921.20.103c
Trade Name: Cozy Test Date: 13-Mar-2020
Filename: 20-073May01 Time of Test: 11:25 AM
Sample ID: 660714 Calibration Heat Flux Reading: 24.4 kW/m2
350-nun Heat Flux Reading: 24.0 kW/m2
Calibration Flame Front Heat for
Distance Heat Flux Arrival Time Sust.Burning
(mm) (kW/m2) (s) (MJ/me)
50 50.5 109 5.48
100 50.1 109 5.47
150 47.4 110 5.23
200 42.9 119 5.10
250 37.2 153 5.69
300 30.9 202 6.25
350 24.4 293
400 18.4
450 13.1
500 9.0
550 6.0
600 4.2
650 3.3
700 2.6
750 1.5
Run 1
10
8
6
C4
a 4
a 2
0 .,.�
-2
-180 0 180 360 540 720 900 1080 1260 1440 1620 1800 1980 2160
Time (s)
CFE: 23.2 kW/m2 Time to Ignition: 105 s
Q,b: 5.57 MJ/m2 Heat for Ignition: 5.2 MJ/m2
Qi: 0.0 MJ Extinguishment Location: 360 mm
Qp: 0.3 kW Extinguishment Time: 330 s
NOTES AND OBSERVATIONS:Smoke at 50 s.
RECEIVED
03/14/2022
Maya Romanoff Corporation A-1 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE
2010 IMO FTP Code Part 5 -Surface Flammability Test Report
Material ID:MR-CZ Series SwRI Project No.: 01.24921.20.103c
Trade Name: Cozy Test Date: 13-Mar-2020
Filename: 20-073May02 Time of Test: 1:20 PM
Sample ID: 660714 Calibration Heat Flux Reading: 24.4 kW/m2
350-mm Heat Flux Reading: 23.9 kW/m2
Calibration Flame Front Heat for
Distance Heat Flux Arrival Time Sust.Burning
(mm) (kW/m2) (s) (MJ/m2)
50 50.5 99 4.99
100 50.1 100 4.99
150 47.4 100 4.76
200 42.9 115 4.91
250 37.2 163 6.05
300 30.9 210 6.47
350 24.4 274
400 18.4
450 13.1
500 9.0
550 6.0
600 4.2
650 3.3
700 2.6
750 1.5
Run 2
10
8
Q, 6
x n
• 4
1
2
llllllllllllllllllllllllll
-2
-180 0 180 360 540 720 900 1080 1260 1440 1620 1800 1980 2160
Time(s)
CFE: 21.3 kW/m2 Time to Ignition: 97 s
Qsb: 5.55 MJ/m2 Heat for Ignition: 4.8 MJ/m2
Qt: 0.0 MJ Extinguishment Location: 375 mm
Qp: 0.4 kW Extinguishment Time: 364 s
NOTES AND OBSERVATIONS:Smoke at 55 s.
RECEIVED
03/14/2022
Maya Romanoff Corporation A-2 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
SOUTHWEST RESEARCH INSTITUTE
2010 IMO FTP Code Part 5 - Surface Flammability Test Report
Material ID:MR-CZ Series SwRIProjectNo.: 01.24921.20.103c
Trade Name: Cozy Test Date: 13-Mar-2020
Filename: 20-073May03 Time of Test: 1:47 PM
Sample ID: 660714 Calibration Heat Flux Reading: 24.4 kW/m2
350-mm Heat Flux Reading: 24.0 kW/m2
Calibration Flame Front Heat for
Distance Heat Flux Arrival Time Sust.Burning
(mm) (kW/m2) (s) (MJ/m2)
50 50.5 71 3.60
100 50.1 72 3.59
150 47.4 72 3.42
200 42.9 106 4.57
250 37.2 136 5.04
300 30.9 188 5.82
350 24.4 283
400 18.4
450 13.1
500 9.0
550 6.0
600 4.2
650 3.3
700 2.6
750 1.5
Run 3
to
8
6
a _
4
2
0
-2
-180 0 180 360 540 720 900 1080 1260 1440 1620 1800 1980 2160
Time (s)
CFE: 23.2 kW/m2 Time to Ignition: 71 s
Qsb: 4.71 MJ/m2 Heat for Ignition: 3.4 MJ/m2
Qt: 0.0 MJ Extinguishment Location: 360 mm
Qp: 0.2 kW Extinguishment Time: 343 s
NOTES AND OBSERVATIONS:Smoke at 35 s.
RECEIVED
03/14/2022
Maya Romanoff Corporation A-3 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
APPENDIX B
PHOTOGRAPHIC DOCUMENTATION
(CONSISTING OF 2 PAGES)
RECEIVED
03/14/2022
Maya Romanoff Corporation SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
,--L4
16
1.
03/
Figure B-1. Tests 1 and 2 (left to right)before fire exposure.
II
•
03/13/200Z0 `l
Figure B-2. Tests 1-3 (left to right) after fire exposure.
RECEIVED
03/14/2022
Maya Romanoff Corporation B-1 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT
WC5
ru I �
4 j
•
_ V-.,
. 81!I WIIIIIIMIN — Wr' — ,...
a
if ) . ,. . : , ,.., :
_It i ,e 11. •
�. �,..._ -- ' tea
, •
Figure B-3. Tests 1-3 (top to bottom) during fire exposure.
RECEIVED
03/14/2022
Maya Romanoff Corporation B-2 SwRI Project No.01.24921.20.103c
ASPEN
BUILDING DEPARTMENT