HomeMy WebLinkAboutFile Documents.121 E Hyman Ave.0008-2019-BCHO (3) 0008-2019-BCHO_BuildingComments_1
5_121 E Hyman Architectural Drawings.pdf(2)
00 ;_ ,,.�. Subject: PlanCheck The built-in bench creates a
p Page Label: ISTING&PROPOSED ROOF PLAN
Page Index: 7 walking surface beside the
1 —M-7 Author: tonyf guardrail, so the guardrail must
• Color: • extend 36"above the surface of
�.. ..„.e,T,, File Name: 5 121 E Hyman Architectural Drawings.pdf the bench, per COA policy.
— Please revise this detail at all
1 z.. ; . ,� built-in benches.
Subject: PlanCheck
°� — °o _A, Page Label: TERIOR ELEVATIONS Wall cap serving as guard rail
Page Index: 10 must extend 36"above surface
Author: tonyf of built-in benches and side table
*muColor: • per COA policy.Typical. Please
File Name: 5_121 E Hyman Architectural Drawings.pdf revise.
8_121 E Hyman Lighting Drawings.pdf(1)
Subject: PlanCheck o
Page Label: [1] LT 1.0 A minimum of 75/o of all lamps
Page Index: 1 installed in permanent fixtures
I Imust be high efficiency in
Author: tonyf
^4 ' Color: • dwelling
16 i1�" +s, � units. Note this requirement on
ttim File Name: 8_121 E Hyman Lighting Drawings.pdf the
r--'_=_, plans. (2015 IECC R404.1 &
C405.1)
1