May 4th, 2018
Bryan May &Adam Link
Rowland+Broughton Architecture
234 E Hopkins Ave
Aspen, CO 81611
Re: Kagan Residence
Dear Bryan &Adam,
This document is intended to show compliance of the remodel of the Kagan Residence at Units 3A &3B
of 520 E Hyman Ave, Aspen, CO with the 2015 International Energy Conservation Code (2015 IECC). We
propose to use a prescriptive approach per sections R402.1-R402.3 and R403.2.1 of the 2015 IECC.
Project
The project at 520 E Hyman Ave is a remodel of the existing penthouse apartment with a floor area of
2,915 sf. For heat load calculations, please refer to the Appendix. The heat load calculations are
performed using the Carrier Hourly Analysis Program and provides a more detailed and accurate load
than Manual J.
Building Envelope
The following table lists the mandatory minimum insulation and fenestration requirements for the project
climate zone (7). All new assemblies will meet the following requirements.
Fenestration Skylight Ceiling Wood frame Floor Basement Slab
U-factor U-factor R-value wall R-value R-value wall R-value R-value
Code 0.28 (1) 0.55 49 20+5 or 38 (3) 15/19 (4) 10 (5)
Minimums 13+10 (2)
Notes: 1) Fenestration SHGC requirements do not apply in climate zone (7)
2) First value is cavity insulation, second value is continuous insulation
3) Or insulation sufficient to fill the framing cavity, R-19 minimum
4) R-15 continuous insulation on the interior or exterior, or R-19 cavity insulation on the interior
of the basement wall. Can be satisfied with R-13 cavity plus R-5 continuous
5) 4 ft deep and R-15 edge insulation for heated slabs
Sincerely,
Alex Timberlake
Mechanical Engineer
40801 US Hwy 6&24, Suite 214, Eagle-Vail, CO 81620 Post Office Box 8489, Avon, CO `K 0 '_ fir"
phone: 970-748-8520 email: stan(a,aec-vail.com web: www.aec-vail.com 0 6 11 2 018
ASPEN
BUILDING DEPARTMENT
Zone Sizing Summary for Whole House Load
Project Name: 18008-Kagan HLHG(1) 05/03/2018
Prepared by:AEC 11:25AM
Air System Information
Air System Name Whole House Load Number of zones 1
Equipment Class UNDEF Floor Area 2655.0 ft2
Air System Type SZCAV Location Aspen,Colorado
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates Calculation Months Jan to Dec
Space CFM Individual peak space loads Sizing Data Calculated
Zone Sizing Data
Maximum Design) Minimum Time Maximum Zonel
l Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft2) CFM/ft2
Zone 1 51.5 4052 4052 Aug 1400 40.5 2655.0 1.53
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name/ Sensible of Flow Load Area Space)
Space Name Mult. (MBH) Load (CFM) (MBH)1 (ft2) CFM/ft2
Zone 1
302 LIVING RM 1 12.1 Sep 1400 887 7.5 380.0 2.33
303 DINING ROOM 1 5.6 Jul 1500 412 4.5 410.0 1.01
304 KITCHEN 1 13.4 Jul 1500 980 9.8 555.0 1.77
307 DEN/BEDROOM 1 5.6 Oct 1300 410 3.2 155.0 2.65
308 BATH 1 0.4 Jul 1500 28 0.3 45.0 0.63
309 MASTER BEDROOM 1 6.6 Sep 1300 484 5.2 315.0 1.54
316 MASTER CLOSET 1 0.2 Jul 1500 17 0.2 35.0 0.49
315 MASTER BATH 1 1.4 Jul 1500 101 0.6 95.0 1.07
314 CORRIDOR 1 2.1 Jul 1400 151 1.3 135.0 1.12
310 BEDROOM 1 3.1 Jul 1400 228 2.2 155.0 1.47
311 BATH 1 0.5 Jul 1500 39 0.7 50.0 0.77
312 BED/BUNK ROOM 1 3.4 Jul 1500 252 4.0 255.0 0.99
313 BATH 1 0.8 Jul 1500 61 0.9 70.0 0.87
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS yjp'PC RHG, -..
OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 82 °F V`��.�- p'_
INDOOR TEMPERATURE 70 °F INDOOR TEMPERATURE 75 °F :0aR.'' b ' ' ,
TOTAL HEAT LOSS 40,535 BTU/HR SENSIBLE HEAT GAIN 55,250 BTU/HR : c.�, `��4
LATENT HEAT GAIN 2,940 BTU/HR ' SS/ONALE-,.'''
TOTAL HEAT GAIN 58,190 BTU/HR
RECEIVED
06/11/2018
Hourly Analysis Program v4.50 AttiRat 1