Subject: PlanCheck This comment was intended to
Page:A-7.22 ELECTRICAL EQUIPMENT ENCLOSURE AND
CONDENSER ENCLOSURE apply to the condensers:
r Page Index: 3
Author: nickt At all equipment screens,
provide and dimension the
Color: •
® File Name: 395 THUNDERBOWL-CO2 Responses-ARCH following per 2015 IMC 306:
DRAWINGS.pdf 1. 30"x30"clear working space
in front of the control side of
each piece of equipment for
service access. 306.1
2. Provide a door that when
opened, provides a minimum 24"
clearance, provided the
equipment can be removed
without dismantling the screen.
Otherwise, make the door wide
enough to remove the appliance.
306.2
3. Provide clearances as
required by manufacturer's
installation instructions.