HomeMy WebLinkAboutFile Documents.200 S Aspen St.0007.2017 (3).ACBK Sound Transmission Class(STC)calculation according to ASTM E413
Assessment of Laboratory Transmission Loss per ASTM E90
Tested Assembly Date of Original Test Test Report Number
12.7 mm Wood Flooring 05-Apr-16 F5689.06-113-11-R0
5 mm Pliteq GenieMat®RSTO5
102 mm NW Composite Deck(TSD) Name of Testing Laboratory
76 mm Fiberglass Insulation Intertek/ATI York
Pliteq GenieClip®RST
22 mm Furring Channel
16 mm Gypsum Board Type C
80
Freq(Hz) TL(dB) Def(dB)50 31 70
63 29
80 35
100 39 60 125 41 0
160 42 0
200 42 3
a
250 44 4 50 —
0
315 44 7
400 46 8 00
T3
500 52 3 w 40 ---
630 59 0
0
800 63 0 N
1000 62 0 £
co
1250 65 0 I` 30 I--
1600 67 0
2000 67 0
2500 68 0 20 3150 71 0
4000 73 0
5000 75
6300 77 10
8000 79
10000 80
0
STC=55
M O O u) O O O In O O O O O O O O O O O
Sum of Def.(dB)=25 CO CO o N COo CO CD CD CO CD rn CD o sLO
— 0
N N CO LO c0 CO CD CV c0 CD N O
N N CO 7
%Octave Band Frequency(Hz)
—Transmission Loss,TL —STC 55 Contour
Pliteq Inc.2016.The information provided is accurate to the best of our knowledge at the time of issue.However,we reserve the right to make changes when necessary
without further notification.This analysis is performed by Pliteq for the benefit of the reader to help interpret data obtained from accredited laboratories.It is not to be
interpreted to be an official test report from the original laboratory.Feb/17
City of Aspen
Received
7/10/17
Building Department
Impact Insulation Class(IIC)calculation according to ASTM E989
Assessment of Laboratory Normalized Impact Sound Pressure Levels per ASTM E492
Tested Assembly Date of Original Test Test Report Number
12.7 mm Wood Flooring 05-Apr-16 F5689.06-113-11-R0
5 mm Pliteq GenieMat®RSTO5
102 mm NW Composite Deck(TSD) Name of Testing Laboratory
76 mm Fiberglass Insulation Intertek/ATI York
Pliteq GenieClip®RST
22 mm Furring Channel
16 mm Gypsum Board Type C
80
Freq(Hz) NISPL(dB) Def(dB)
50 66 70 •
63 69
80 62
100 59 1 60 `
125 63 5 a
z \160 61 3 N
200 62 4 m `�`
v
250 60 2 m 50 --
315 60 2
m
400 62 5
rn
500 58 2 2 40
a
630 56 1 c
°
800 52 0
to
1000 54 1 m
1250 48 0 E 30 —�
1600 42 0 N
2000 35 0
`o
2500 30 0 Z 20
3150 26 0
4000 21
5000 16
6300 10 10 —
8000 10
10000 10
0
IIC=54
CO O O u) O O O In O O O O O O O O O O O
Sum of Def.(dB)=26 CO CO 0 CV CO o CO CD CD CO CD rn CD 0 u� 0
N N M LO CO CO O CV x-
N N M 7
%Octave Band Frequency(Hz)
— NISPL IIC — IIC 54 Contour
Pliteq Inc.2016.The information provided is accurate to the best of our knowledge at the time of issue.However,we reserve the right to make changes when necessary
without further notification.This analysis is performed by Pliteq for the benefit of the reader to help interpret data obtained from accredited laboratories.It is not to be
interpreted to be an official test report from the original laboratory.Feb/17
City of Aspen
Received
7/10/17
Building Department
Intertek
Architectural Testing
F5689.06-113-11-RO
ACOUSTICAL PERFORMANCE TEST REPORT
ASTM E 90 AND ASTM E 492
Rendered to
PLITEQ INC.
Series/Model: Vintage Floors Wood Flooring on Pliteq GenieMatTM RSTO5 - Pliteq
GenieClipTM RST Ceiling with R8 Fiberglass Insulation
Specimen Type: Concrete on Steel Decking
Overall Size: 3023 mm by 3632 mm (119" by 143")
STC 55
IIC 54
Test Specimen Identification:
Floor Topping: 12.7 mm(0.5")Vintage Floors Wood Flooring
Floor Underlayment: 4.97 mm(0.2")Pliteq GenieMatTM RSTO5 Rubber Underlayment
Concrete Slab: 101.6 mm(4") Standard 4000 PSI Concrete
Deck: 50.8 mm(2") 18 Gage Vulcraft 2VLI Composite Floor Deck
Insulation: 76.2 mm(3")Johns Manville R8 Fiberglass Insulation
Ceiling Isolation: 25.4 mm(1")Pliteq GenieClipTM RST Rubber/Galvanized Steel Mounting Clip
Ceiling Isolation: 22.2 mm(0.87") Super Stud 25 Gage Furring Channel
Ceiling: 15.9 mm(0.63")USG SHEETROCK®Brand FIRECODE® C Core Gypsum Panel
Reference should be made to Intertek-ATI Report F5689.06-113-11 for complete test specimen
description. This page alone is not a complete report.
City of Pfourt p. 717.764.7700
Recei www•archtest.com • www.intertek.com/building
t , PA 17406 f. 717.764.4129
7/10/17
Building Department
Intertek F5689.06-1 13-1 1-R0
Page 1 of 4
Architectural Testing
Acoustical Performance Test Report
PLITEQ INC.
1370 Don Mills Road
Toronto, Ontario M3B 3N7
CANADA
Report F5689.06-113-11
Test Date 04/05/16
Report Date 05/03/16
Project Scope
Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct
airborne sound transmission loss and impact sound transmission tests. The complete test data is
included as attachments to this report. The client provided the test specimen. The specimen was
constructed on the date of testing.
Test Methods
The acoustical tests were conducted in accordance with the following standards. The equipment
listed in the attachments meets the requirements of the following standards.
ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions
ASTM E 413-10, Classification for Rating Sound Insulation
ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound
Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine
ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)
ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in
Sound Insulation Test Methods
Test Procedure
All testing was conducted in the VT test chambers at Intertek-ATI located in York,
Pennsylvania. The microphones were calibrated before conducting the tests.
The airborne transmission loss test was conducted in accordance with the ASTM E 90 test
method using the single direction method. Two background noise sound pressure level and five
sound absorption measurements were conducted at each of five microphone positions. Four
sound pressure level measurements were made simultaneously in both rooms, at each of five
microphone positions.
City of Pfourt p. 717.764.7700
Recei www•archtest.com • www.intertek.com/building
t , PA 17406 f. 717.764.4129
7/10/17
Building Department
I ntertek F5689.06-113-11-R0
Page 2 of 4
Architectural Testing
Test Procedure (Continued)
The impact sound transmission test was conducted in accordance with the ASTM E 492 test
method. Two background noise sound pressure level, two sound pressure level measurements
with the tapping machine operating at each position specified by ASTM E 492, and five sound
absorption measurements were conducted at each of five microphone positions.
The air temperature and relative humidity conditions were monitored and recorded during all
measurements.
Test Conditions
Source Room Receive Room
Average Temperature 21.5°C(70.7°F) Average Temperature 20.1°C(68.2°F)
Average Relative Humidity 50% Average Relative Humidity 49%
Test Calculations
The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated
in accordance with ASTM E 413 and ASTM E 989, respectively.
Test Specimen Materials and Installation Details
Dimensions Thickness Average
Material (mm/inch) (mm/inch) Manufacturer and Series Quantity Weight
Varied by 127 12.7/0.5 Vintage Floors 10.98 m 15.7 kg/m2
Wood Flooring Varied by 5 118.19 ft23.22 lb/ft2
Note:Loose laid
Rubber 1219 by 3632 5/0.2 Pliteq GenieMatTM RSTOS 10.98 mZ 4 kg/m2
48 by 143 118.19 ft 0.821b/ft2
Underlayment Note:Loose laid
Standard 4000 PSI 3023 by 3632 101.6/4 N/A 10.98 m2 180.42 kg/m2
119 by 143 118.19 ft2 36.95 lb/ft2
Concrete Note:Poured directly on the floor deck and allowed to cure for a minimum of 28 days.
3023 by 3632 50.8/2 18 Ga e Vulcraft 2VLI 10.98 m2 12.74 kg/m2
Composite Floor 119 by 143 g 118.19 ft2 2.61 lb/ft2
Note:Installed per manufacturer's specifications in a test frame with the top of the concrete flush with
Deck the source room. All seams and gaps underneath the deck were plugged with backer rod and sealed
with Pecora AC-20 Acoustical Sealant.
609.6 by 3048 76.2/3 Johns Manville R8 10.98 m2 0.86 kg/m2
Fiberglass Insulation 24 by 120 118.19 ft2 0.18 lb/ft2
Note:Laid directly over ceiling channels
38.1 by 63.5 25.4/ 1 Pliteq GenieClipTM RST 0.05 m2 20.62 kg/m2
Rubber/Galvanized 1.5 by 2.5 0.54 ft2 4.22 lb/ft2
Steel Mounting Clip Note: The mounting clips were fastened through the floor deck to the concrete with 38.1 mm (1.5")
Tapcon screws in a 609.6 mm by 1219.2 mm(24"by 48")grid pattern.
3022.6 by 63.6 22.2/0.87 Super Stud 21.21in m 0.57 kg/m
25 Gage Furring 119 by 2.5 69.4 lin ft 0.38 lb/ft
Channel Note: The furring channels were installed into the clips, spaced 610 mm (24") on center. The
measured steel thickness is 1.2 mm(0.05').
City of Aspen
Received
7/10/17
Building Department
Intertek F5689.06-113-11-R0
Page 3 of 4
Architectural Testing
Test Specimen Materials and Installation Details (Continued)
Dimensions Thickness Average
Material (mm/inch) (mm/inch) Manufacturer and Series Quantity Weight
1219 by 3023 15.9/0.63 USG SHEETROCK®Brand 10.98 m2 11.9 kg/m2
48 by 119 FIRECODE®C Core 118.19 ft2 2.441b/ft2
Gypsum Panel Note: The gypsum panels were fastened to the furring channels on 304.8 mm (12")centers along the
channel with 25.4 mm (1') #6 fine-thread drywall screws. The seams of the gypsum panels were
sealed with Sikaflex 15LM Construction Sealant and covered with pressure sensitive tape. The
perimeter was sealed with Sikaflex 15LM Construction Sealant.
Comments
The total weight of the floor/ceiling assembly was 2490.4 kg / 5491.5 lbs. Intertek-ATI will
store samples of the test specimen for four years. Photographs of the test specimen are included
in the attachments. The client did not supply drawings of the test specimen.
Intertek-ATI will service this report for the entire test record retention period. Test records,
such as detailed drawings, datasheets, representative samples of test specimens, or other
pertinent project documentation, will be retained by Intertek-ATI for the entire test record
retention period. The test record retention period ends four years after the test date.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
specimen tested. This report is intended to help in the client's quality assurance program, but it
does not represent a continuous or exhaustive evaluation of the specimen tested or of other
products or materials that were not evaluated. The statements and data provided herein do not
constitute approval, disapproval, certification, or acceptance of performance or materials.
This report may not be reproduced, except in full, without the written approval of
Intertek-ATI.
FOR INTERTEK-ATI:
''
Digitally SBaotl by Cody S ytlar plgllally SlOaetl ay:J.Man SlryS.e
Cody R. Snyder Jordan Strybos
Technician II-Acoustical Testing Project Manager- Acoustical Testing
Attachments (6 Pages): This report is complete only when all attachments are included.
*Stated by Client/Manufacturer
N/A-Non Applicable
City of Aspen
Received
7/10/17
Building Department
Intertek F5689.06-113-11-R0
Page 4 of 4
Architectural Testing
Revision Log
Revision Date Page(s) Description
RO 05/03/16 N/A Original Report Issue
This report produced from controlled document template ATT 00629(d),Revised 02/09/15.
City of Aspen
Received
7/10/17
Building Department
Intertek F5689.06_1 13-11-R0
Architectural Testing
Attachments
Instrumentation
Instrument Manufacturer Model ATI Number Date of
Calibration
Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *
Microphone Calibrator Norsonic 1251 INT00127 01/16
Receive Room Microphone Scantek 378B20 63748 05/15
Receive Room Microphone PCB Piezotronics 378B20 63744 05/15
Receive Room Microphone PCB Piezotronics 378B20 63745 05/15
Receive Room Microphone PCB Piezotronics 378B20 63746 05/15
Receive Room Microphone PCB Piezotronics 378B20 63747 05/15
Receive Room Environmental 63810 10/15
Indicator Comet T7510 63811 10/15
Source Room Microphone PCB Piezotronics 378B20 63738 04/15
Source Room Microphone PCB Piezotronics 378B20 63739 04/15
Source Room Microphone PCB Piezotronics 378B20 63740 04/15
Source Room Microphone PCB Piezotronics 378B20 63742 04/15
Source Room Microphone Scantek 378B20 63741 04/15
Source Room Environmental Comet T7510 63812 11/15
Indicator
Tapping Machine Look Line s.r.l. EM50(TM50) 65351 02/16
*The calibration frequency for this equipment is every two years per the manufacturer's recommendation.
Test Chambers
VT Receive Room Volume 158.86 m3(5610.1 ft3)
VT Source Room Volume 190 m3(6709.79 ft3)
City of Aspen
Received
7/10/17 Page 1 of 6
Building Department
Intertek F5689.06-1 13-1 1-RO
Architectural Testing /N
AIRBORNE SOUND TRANSMISSION LOSS \\Ii/j
ASTM E 90 ACCREDITED'
Testing
Laboratory
Test Date 04/05/16
Data File No. F5689.06
Client Pliteq Inc.
12.7 mm(0.5")Vintage Floors Wood Flooring,4.97 mm(0.2")Pliteq GenieMattm RST05 Rubber Underlayment, 101.6 mm(4")
Description
Standard 4000 PSI Concrete,50.8 mm(2")18 Gage Vulcraft 2VLI Composite Floor Deck,76.2 mm(3")Johns Manville R8 Fiberglass
Insulation,25.4 mm(1")Pliteq GenieClipT"'RST Rubber/Galvanized Steel Mounting Clip,22.2 mm(0.87")Super Stud 25 Gage Furring
Channel,15.9 mm(0.63")USG SHEETROCK®Brand FIRECODE®C Core Gypsum Panel
Specimen Area 10.98 m2
Technician Cody R. Snyder
Background Source Receive Specimen 95% Number
Freq Absorption
SPL SPL SPL TL Confidence of
(Hz) (dB) (m2) (dB) (dB) (dB) Limit Deficiencies
50 39.5 27.8 100 66 31 3.80 -
63 36.8 25.6 100 68 29 3.70 -
80 34.5 18.0 109 72 35 4.30 -
100 31.2 14.4 107 68 39 2.00 -
125 31.3 11.1 106 66 41 1.10 0
160 28.1 10.9 107 67 42 1.70 0
200 25.3 13.0 104 62 42 1.70 3
250 24.4 11.7 103 59 44 1.00 4
315 20.6 11.2 105 61 44 0.80 7
400 19.3 10.2 104 58 46 0.60 8
500 24.0 9.1 104 53 52 0.30 3
630 20.0 8.8 105 49 59 0.40 0
800 21.8 8.8 105 44 63 0.30 0
1000 17.1 8.4 104 45 62 0.40 0
1250 14.1 8.6 105 42 65 0.50 0
1600 9.7 8.5 104 39 67 0.30 0
2000 8.2 9.5 104 39 67 0.30 0
2500 7.7 10.6 102 36 68 0.20 0
3150 8.3 11.2 103 33 71 0.20 0
4000 8.7 13.2 104 31 73 0.40 0
5000 8.3 15.3 104 28 75 0.50 -
6300 7.8 19.7 97 19 77 0.70 -
8000 7.7 25.4 97 15 79 0.80 -
10000 7.2 32.3 91 8 80 0.50 -
STC Rating 55 (Sound Transmission Class)
Deficiencies 25 (Sum of Deficiencies)
Rw Rating 56 (Sound Reduction Index)
tes: 1)Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
City of As p e n 2)Specimen TL levels listed in red indicate the lower limit of the transmission loss.
Received 3)Specimen TL levels listed in green indicate that there has been a filler wall correction applied
7/1 OA 1 0614 Revised 02/09/15 Page 2 of 6
Building Department
Intertek F5689.06.113.11_R0
Architectural Testing /
LaS
AIRBORNE SOUND TRANSMISSION LOSS
ASTM E 90 ACCREDITED'
Testing
Laboratory
Test Date 04/05/16
Data File No. F5689.06
Client Pliteq Inc.
Description 12.7 mm(0.5")Vintage Floors Wood Flooring,4.97 mm(0.2")Pliteq GenieMal'.RST05 Rubber Underlayment, 101.6 mm(4")
Standard 4000 PSI Concrete,50.8 mm(2")18 Gage Vulcraft 2VLI Composite Floor Deck,76.2 mm(3")Johns Manville R8 Fiberglass
Insulation,25.4 mm(1")Pliteq GenieClipT'.RST Rubber/Galvanized Steel Mounting Clip,22.2 mm(0.87")Super Stud 25 Gage Furring
Channel,15.9 mm(0.63")USG SHEETROCK®Brand FIRECODE®C Core Gypsum Panel
Specimen Area 10.98 m2
Technician Cody R. Snyder
Airborne Sound Transmission Loss
100 -
90
80 -
70
,co 60 • • •
5 04111
50
40
30 —
20 -
10 f Specimen TL
Contour Curve
0 I I I
N O� O O O O O
rn O O O O
Frequency (Hz)
City of Aspen
Received
7/1 O470614 Revised 02/09/15 Page 3 of 6
Building Department
Intertek F5689.06-1 13-1 1-R0
Architectural Testing /N
IMPACT SOUND TRANSMISSION \\Ii/j
ASTM E 492 ACCREDITED'
Testing
Laboratory
Test Date 04/05/16
Data File No. F5689.06
Client Pliteq Inc.
12.7 nun(0.5")Vintage Floors Wood Flooring,4.97 mm(0.2")Pliteq GenieMattm RST05 Rubber Underlayment, 101.6 mm(4")
Description
Standard 4000 PSI Concrete,50.8 mm(2")18 Gage Vulcraft 2VLI Composite Floor Deck,76.2 mm(3")Johns Manville R8 Fiberglass
Insulation,25.4 mm(1")Pliteq GenieClipT"'RST Rubber/Galvanized Steel Mounting Clip,22.2 mm(0.87")Super Stud 25 Gage Furring
Channel,15.9 mm(0.63")USG SHEETROCK®Brand FIRECODE®C Core Gypsum Panel
Specimen Area 10.98 m2
Technician Cody R. Snyder
Freq Background SPL Absorption Normalized Impact 95% Number
SPL Confidence of
(Hz) (dB) (m2) (dB) Limit Deficiencies
50 38.7 26.2 66 2.9 -
63 34.3 49.3 69 6.0 -
80 32.1 17.8 62 4.1 -
100 32.3 13.0 59 2.7 1
125 31.1 11.9 63 3.1 5
160 27.2 11.4 61 2.8 3
200 22.5 13.0 62 2.7 4
250 24.0 11.0 60 1.1 2
315 20.3 11.1 60 1.4 2
400 17.9 10.2 62 0.4 5
500 24.6 9.1 58 0.1 2
630 20.1 8.6 56 0.2 1
800 21.5 8.7 52 0.7 0
1000 20.6 8.3 54 0.7 1
1250 13.4 8.6 48 0.3 0
1600 8.7 8.7 42 0.4 0
2000 4.7 9.5 35 0.3 0
2500 3.8 10.5 30 0.2 0
3150 3.9 11.2 26 0.4 0
4000 4.5 13.1 21 0.2 -
5000 5.3 15.3 16 0.3 -
6300 5.7 19.5 10 0.5 -
8000 6.1 25.5 10 1.0 -
10000 6.2 32.3 10 0.8 -
IIC Rating 54 (Impact Insulation Class)
Deficiencies 26 (Sum of Deficiencies)
Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.
City of Aspen
Received
7/1 OA 1670615 Revised 02/09/15 Page 4 of 6
Building Department
Intertek F5689.06.1 13-1 1-Ro
Architectural Testing /
LaS
IMPACT SOUND TRANSMISSION
ASTM E 492 ACCREDITED'
Testing
Laboratory
Test Date 04/05/16
Data File No. F5689.06
Client Pliteq Inc.
Description 12.7 nun(0.5")Vintage Floors Wood Flooring,4.97 mm(0.2")Pliteq GenieMal'.RST05 Rubber Underlayment, 101.6 mm(4")
Standard 4000 PSI Concrete,50.8 mm(2")18 Gage Vulcraft 2VLI Composite Floor Deck,76.2 mm(3")Johns Manville R8 Fiberglass
Insulation,25.4 mm(1")Pliteq GenieClipT"'RST Rubber/Galvanized Steel Mounting Clip,22.2 mm(0.87")Super Stud 25 Gage Furring
Channel,15.9 mm(0.63")USG SHEETROCK®Brand FIRECODE®C Core Gypsum Panel
Specimen Area 10.98 m2
Technician Cody R. Snyder
Impact Sound Transmission
100 — 10
90 — 20
80 30
70 40
'ti C
60 50 el
. . • .
U
50 60
a
1-1
40 70
o �
E
30 80 F"
20 90
10 f Normalized Impact SPL • • 100
Contour Curve
0 I I I 110
N okn 0 0 0 0 0
N rn 0 0 0 0
N 00
Frequency(Hz)
City of Aspen
Received
7/1 OA 1670615 Revised 02/09/15 Page 5 of 6
Building Department
Intertek F5689.06-113-11-R0
Architectural Testing
Photographs
i i ir r
4,.
Ar --itectural Te
1
gic rill i
4' - —
,.
Source Room View of Test Specimen Installation
\ a
■ ■ F- - 4/
,,..... / 40
, ‘1";111:lig,-- -I* 41 '1
Receive Room View of Test Specimen Installation
City of Aspen
Received
7/10/17 Page 6 of 6
Building Department