HomeMy WebLinkAboutFile Documents.1112 Waters Ave.0024.2019 (13).ARBKWELS Markup #1 1112 Water Ave Page: [1] IR 1112 Waters Ave-IR1.0 Author: rickma Date: 2/20/2019 4:17:18 PM File Name: 04 Irrigation Drawings 2.15.19.pdf Revise all WELS section numbering to be consistent with the latest version of WELS [1] IR 1112 Waters Ave-IR1.0 (3) Page: [1] IR 1112 Waters Ave-IR1.0 Author: rickma Date: 2/20/2019 4:15:54 PM File Name: 04 Irrigation Drawings 2.15.19.pdf Cool Season Turf is VH @ .90 plant factor. Revise accordingly. Page: [1] IR 1112 Waters Ave-IR1.0 Author: rickma Date: 2/26/2019 1:46:03 PM File Name: 04 Irrigation Drawings 2.15.19.pdf Include the language of WELS Section 4.3.2 (m). regarding disturbance under existing trees. Please note that the City Forester requires that cutting roots larger than 2" in diameter is not permitted. 1.APPLICANT IS RESPONSIBLE FOR ASSURING OPERATING PRESSURE ATEACH EMISSION DEVICE IS WITHIN THE MANUFACTURER'SRECOMMENDED PRESSURE RANGE FOR OPTIMAL PERFORMANCE. IFPRESSURE IS NOT WITHIN THE PREFERRED RANGE, ACTIONS DESCRIBED IN SECTION 6.1.10 OF THE WATER EFFICIENT LANDSCAPINGSTANDARDS MUST BE TAKEN.2.SPRINKLERS WITHIN INDIVIDUAL IRRIGATION ZONE SHALL HAVE MATCHED PRECIPITATION RATES, UNLESS OTHERWISE DIRECTED BYTHE MANUFACTURER'S RECOMMENDATIONS.3.ENSURE THERE IS HIGHEST POSSIBLE DISTRIBUTION UNIFORMITY, ANDHEAD-TO-HEAD COVERAGE.4.AN IRRIGATION MAINTENANCE SCHEDULE AND IRRIGATIONMANAGEMENT PLAN IS REQUIRED AS DESCRIBED IN SECTION 6.7THROUGH 6.9 OF THE STANDARDS. CITY OF ASPEN GENERAL NOTES LED BYLOWVERIFY TROLLER INSTALL FORWALLS,N TO BE 0-15 16-25 26-35 36-55 56-80 81-110 111-200 IRRIGATION PIPE SCHEDULE CLASS 200 PVC PIPE SIZE FLOW (GPM) IF THERE IS A DISCREPANCY BETWEEN PIPE SIZES SHOWN ON THE DRAWINGS AND THIS PIPE SCHEDULE, IT IS THE 4" 3" 2-1/2" 2" 1-1/2" 1-1/4" 1" *THE IRRIGATION CONTROLLER INCLUDES A WEATHERMATIC SMARTLINK VARPACKAGED SYSTEM AND MANAGED SERVICES. PLEASE CONTACT PARRY WEBBWITH WEATHERMATIC FOR PRICING 303-638-6268* Revise all WELS section numbering to be consistent with the latest version of WELS AT BED ND ARTLINK VAR T PARRY WEBB Cool Season Turf is VH @ .90 plant factor. Revise accordingly. E UNSIZED PIPE SHOULD NOT BE CONFUSED WITH THE DEFAULT PIPE S IN THE LEGEND. 11.INSTALL TWO (2) #14 AWG CONTROL WIRES ON STANDARD WIRE SYS USE AS SPARES. INSTALL SPARE WIRES FROM CONTROLLER LOCATI EACH DEAD-END OF MAINLINE. COIL 3 FEET OF WIRE IN VALVE BOX. POP-UP SPRAY SPRINKLER: PRESSURE: RADIUS: FLOW (GPM): WEATHERMATIC MAX6PR 8 FEET30 PSI Q-0.26 H-0.52 F-1.05 Include the language of WELS Section 4.3.2 (m). regarding disturbance under existing trees. Please note that the City Forester requires that cutting roots larger than 2" in diameter is not permitted. 4/10/2019 Page: [2] IR 1112 Waters Ave-IR1.1 Author: rickma Date: 2/20/2019 3:34:07 PM File Name: 04 Irrigation Drawings 2.15.19.pdf Include the language of WELS Section 4.3.2 (m) regarding irrigation work done under existing trees. [2] IR 1112 Waters Ave-IR1.1 (4) Page: [2] IR 1112 Waters Ave-IR1.1 Author: rickma Date: 2/20/2019 4:10:58 PM File Name: 04 Irrigation Drawings 2.15.19.pdf These head appear to be on a neighboring property. Page: [2] IR 1112 Waters Ave-IR1.1 Author: rickma Date: 2/20/2019 4:12:21 PM File Name: 04 Irrigation Drawings 2.15.19.pdf Update WELS citations to most recent numbering, which can be found on the CoA website Page: [2] IR 1112 Waters Ave-IR1.1 Author: rickma Date: 2/20/2019 4:09:51 PM File Name: 04 Irrigation Drawings 2.15.19.pdf WELS Section 5.2.3 states that areas less than 10 feet in any direction should not use overhead sprinkler irrigation. The Planting Plan indicates a narrow strip of turf in this location CATIONS. TING EES IN THES IS NOT 9.INSTALL ALL ELECTRICAL POWER TO THE IRRIGATION CONTROL SYSTEM IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE AND ALL APPLICABLE LOCAL ELECTRIC UTILITY CODES. 10.THE FOLLOWING SHOULD BE NOTED REGARDING PIPE SIZING: IF A SECTION OF UNSIZED PIPE IS LOCATED BETWEEN THE IDENTICALLY SIZED SECTIONS, THEUNSIZED PIPE IS THE SAME NOMINAL SIZE AS THE TWO SIZED SECTIONS. THE UNSIZED PIPE SHOULD NOT BE CONFUSED WITH THE DEFAULT PIPE SIZE NOTED IN THE LEGEND. 11.INSTALL TWO (2) #14 AWG CONTROL WIRES ON STANDARD WIRE SYSTEMS FOR USE AS SPARES. INSTALL SPARE WIRES FROM CONTROLLER LOCATION TO EACH DEAD-END OF MAINLINE. COIL 3 FEET OF WIRE IN VALVE BOX. POP-UP SPRAY SPRINKLER: PRESSURE: RADIUS: FLOW (GPM): WEATHERMATIC MAX6PRS30-CV W/RAIN BIR 8 FEET30 PSI Q-0.26 H-0.52 F-1.05 Include the language of WELS Section 4.3.2 (m) regarding irrigation work done under existing trees. ER S A V E N U E R - O - W HA L T TIL I T Y E A S E M E N T TC H B O O K 2 A P A G E 2 8 203 P A G E 4 7 9 ER S A V E N U E R - O - W HA L T TIL I T Y E A S E M E N T TC H B O O K 2 A P A G E 2 8 203 P A G E 4 7 9 These head appear to be on a neighboring property. 1.APPLICANT IS RESPONSIBLE FOR ASSURING OPERATING PRESSURE ATEACH EMISSION DEVICE IS WITHIN THE MANUFACTURER'SRECOMMENDED PRESSURE RANGE FOR OPTIMAL PERFORMANCE. IF PRESSURE IS NOT WITHIN THE PREFERRED RANGE, ACTIONS DESCRIBEDIN SECTION 6.1.10 OF THE WATER EFFICIENT LANDSCAPING STANDARDS MUST BE TAKEN.2.SPRINKLERS WITHIN INDIVIDUAL IRRIGATION ZONE SHALL HAVE MATCHED PRECIPITATION RATES, UNLESS OTHERWISE DIRECTED BYTHE MANUFACTURER'S RECOMMENDATIONS. 3.ENSURE THERE IS HIGHEST POSSIBLE DISTRIBUTION UNIFORMITY, ANDHEAD-TO-HEAD COVERAGE.4.AN IRRIGATION MAINTENANCE SCHEDULE AND IRRIGATION MANAGEMENT PLAN IS REQUIRED AS DESCRIBED IN SECTION 6.7THROUGH 6.9 OF THE STANDARDS. CITY OF ASPEN GENERAL NOTES 0-15 IRRIGATION PIPE SCHEDULE CLASS 200 PVC PIPE SIZE FLOW (GPM) 1" WITH WEATHERMATIC FOR PRICING 303-638-6268* Update WELS citations to most recent numbering, which can be found on the CoA website WAT E R S 60' R - O ASP H A L 10' U P WAT E R S 60' R - O ASP H A L 10' U P A2 Drip 1" A3 9.17 1.15 1" A4 6.56 0.91 1" 30 30 OZZLES OZZLES OZZLES OZZLES NOZZLE WELS Section 5.2.3 states that areas less than 10 feet in any direction should not use overhead sprinkler irrigation. The Planting Plan indicates a narrow strip of turf in this location 4/10/2019 Page: [3] BG_IZ_L Series-L002 NOTES Author: rickma Date: 2/20/2019 3:27:08 PM File Name: 03 Landscape Irrigation Drawings 2.15.19.pdf Include the language of WELS Section 4.2- Mulch Criteria [3] BG_IZ_L Series-L002 NOTES (1) Page: [7] BG_IZ_L Series-L400 Author: rickma Date: 2/20/2019 4:19:49 PM File Name: 03 Landscape Irrigation Drawings 2.15.19.pdf Cool Season Turf is Very High water. Revise. [7] BG_IZ_L Series-L400 (1) E 1.MUL PLAN SHO 2.THE 3.HYD MAY DUR AN O Include the language of WELS Section 4.2- Mulch Criteria ZONE 3 - NATIVE SEED MEDIUM WATER ZONE 2 - PERENNIAL AN PLANTINGS - LOW WATE HYDROZONE LEGEN IRRIGATION HYDROZONES ZONE 1 - SOD - HIGH W Cool Season Turf is Very High water. Revise. 4/10/2019