HomeMy WebLinkAboutFile Documents.555 E Durant Ave.0025.2019.ACBK 00252019ACBK_BuildingComments_1 Gorsuch -Aspen - Locker Rm 190410 ARCH SET.pdf(8) Page: [1]24442 NON Lockers 190227-AO Cover File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH— Provide additional information _ __ ___ SET.pdf regarding the new mechanical z. 77�= Author: bonniem system including a mechanical plan and calculations showing Subject: PlanCheck - - - Color: • that adequate ventilation will be m-- „== provided per 2015 IEBC 1009.1 -- - ,,,, and 2015 IBC Table 403.3.1.1 Page: [1]24442 NON Lockers 190227-AO Cover 0fr-::*""r File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH.2 Given that the locker room 4_Qea SET.pdf provides changing rooms and __ Author: bonniem lounge space, it more closely e= ==l,y�; resembles a B occupancy than `, Subject: PlanCheck a�, Color: • S 1 which would be strictly II storage. Correct the occupancy _- „ ,,,,, classification on sheet AO goo I::,,.. Page: [2]24442 NON Lockers 190227-A1 Accessibility Plan ]i,. n� Will the snack area contain a ` File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH _�.1 _, �. SET.pdf p service counter or point of sale? �1 i °_ 1 Author: bonniem If yes provide interior elevations :, ._ a �, w_ 1o'm a■ Subject: PlanCheck and/or plan notes showing that p�- ii :: . Ny��nml Color: • they meet the dimension �] w requirements in ICC P . .°. ,®" O �BLrrFL� A117.1-2009. 'Ii ad v s..___ -r -- - Page: [3]24442 NON Lockers 190227-A2 Plans ° ° File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH Provide U-factor information for I t ��1 new exterior door. Must be .77 io,i o SET.pdf �«�, o or better per 2015 IECC C402.4 11...... • nod Author: bonniem �I';:Ex °.° ° 0K0 a Subject: PlanCheck o,ii—ii Color: • II I ra IN rron MN PP Provide U-factor infometian for new : nor door.MustM ICECC 40eroer" IECC C1.4 Page: [3]24442 NON Lockers 190227-A2 Plans Ezo �o"3 File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH Door 2 to the cleaning/storage H�, � ° SET.pdf p area must meet the minimum - 1 ..4 -c c ,.. Author: bonniem clear opening width of 32" O="" —: Subject: PlanCheck 1010.1.1 „a_... Color: • Exception 3 for storage closets y,-,_• _ __a is limited to closets that are 10 .w ... - _ _ e _ sgft or less. Page: [3]24442 NON Lockers 190227-A2 Plans File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH Provide a wall assembly for the Provide a wall p exterior wall that showing that exterioblwalolthat ® SET.pdf showing that the ; Author: bonniem x 1-hour fire resistancethe 1-hour fire resistance rating rating will be Subject: PlanCheck will be maintained. (Table 601) , maintained.(Table 601) Color: ■ — I e 01 MI re To 06 WI TOILET cbluva O,VV000III ,o Page: [5]24442 NON Lockers 190227-A4 Int Elevs and Details 0' 1" File Name: Gorsuch -Aspen- Locker Rm 190410 ARCH SET.pdf Author: bonniem Subject: 3/16"Scale Color: ■ :seem _�_____ I� Page: [5]24442 NON Lockers 190227-A4 Int Elevs and • - w _ 1'1E -- - Details The front of the lavatory must be Rawl a R Raw 34"maximum above the floor s mum File Name: Gorsuch-Aspen- Locker Rm 190410 ARCH measured to whatever is higher -i ` .. ® SET.pdf `�;., I,y �- the rim of the sink or the counter Author: bonniem VIM ° ° o, Subject: PlanCheck surface. Revise so that the rim III h!� ° o L Color: ■ of the sink does not exceed 34" °M�III, �� o ' from the floor. ICC A117.1-2009 _ o- ,,._,C 606.3 Gorsuch -Aspen - Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf(4) Page: 1 L✓ ^I ^m� °°• ^�•f° File Name: Gorsuch -Aspen- Locker Rm 190410 COMcheck Clarify in the description for the LIGHTING COMP REP.pdf HP-2 that the number of fixtures Author: bonniem and wattage per fixture are per p`-,_ linear foot. Subject: PlanCheck Color: ■ oe=1°,a^_ e•e,•I,o,=•„, Page: 1 Cut sheet lists wattage for fixture '• s File Name: Gorsuch-Aspen- Locker Rm 190410 COMcheck m`o•s°a°•TVP•=a°=„°°m=,os=an, ' 2 18 " LIGHTING COMP REP.pdf FM as 32. Correct COMcheck Author: bonniem or provide the correct spec. Cut sheet lists wattage Subject: PlanCheck for fixture FM as 32. Color: • Correct COMcheck or oarlc Nona orc o•provide the correct �3C4a3 oorm,Aspen Report pag•a.1 of e BLDG Ipec. •^ 10< a soolg „,.o vim` Page: 1 The wattage for A4-40 could be .... ...._,,..., 4.,, File Name: Gorsuch-Aspen- Locker Rm 190410 COMcheck LIGHTING COMP REP.pdf amended to 17 watts per . . Author: bonniem housing spec. , . sa,t ._, - r Subject: PlanCheck . z a°�•--T Color: ■ Page: 1 All low voltage lighting needs to File Name: Gorsuch-Aspen- Locker Rm 190410 COMcheck be entered per transformer. ie: CS=°�^0- 7°=.1.�^' Author: bonniem LIGHTING COMP REP.pdf Lamps/fixture= 1,#of fixtures= _= = _ _ `” =- -- Subject: PlanCheck #of transformers,fixture watt= __ = Color: ■ transformer wattage. Put per _= _ transformer in the"fixture __.____._ ID/description".Amend the totals for MP as needed and provide a -- - spec for the transformer. Gorsuch -Aspen - Locker Rm 190410 STRUCT SET.pdf(2) I, p Page: [1] S2.001 File Name: Gorsuch-Aspen- Locker Rm 190410 STRUCT As this is a Type IIIA building, all _ SET.pdf primary structure requires a 1 Author: bonniem hour fire-resistance rating (Table �' Subject: PlanCheck 601). Provide a listed tested iI --;, Color: • assembly for the structural columns. nq Plan(Partial —," S2.( Page: [1] S6.001 =74 OM File Name: Gorsuch-Aspen- Locker Rm 190410 STRUCT The special inspection form = SET.pdf provided does not have all of the ,....._n Author: bonniem required signatures. All s.. Subject: PlanCheck signatures must be received ..... _ Color: • prior to permit issuance. om