Page:A-101 LOWER LEVEL FLOR PLANS
File Name: 2018-6-28_834 E Durant_Permit.pdf Provide structural plans showing
Author: bonniem existing and proposed framing.
Provide structural plans Subject: PlanCheck
showing existing and Color: •
proposed framing.
FP Response:A structural letter has been provided,confirming the structure will
be evaluated at the time of demolition.
Page:A-101 LOWER LEVEL FLOR PLANS
File Name: 2018-6-28_834 E Durant_Permit.pdf 1 hour fire separation +STC
_' ='` Author: bonniem rating of atleast 50 required at
rj----- Subject: PlanCheck dwelling separation between
IIIIMIII■u'.I ADU and residence. Revise wall
j .
« �.�� * 1 e Color. ■
o--1 I j .-, I callouts, and provide required 45
IL ■ I minute rated door.
laili ll FP Response:The ADU has been removed and the space is now a bedroom within the main dwelling unit.
7 ."" o- rly dmf The deed restriction has been vacated and the applicant has mitigated via extinguishment of an Affordable Housing
r,-_;WCI -- Credit.
zE.:'.. 0 Page:A-102 MAIN LEVEL FLOR PLANS This is a VA building therefore
File Name: 2018-6-28 834 E Durant Permit.pdf
Author: bonniem
— — exterior walls are required to
Subject: PlanCheck have a 1 hr fire-resistance rating.
Thia lea VA building Provide wall call outs at the
therebre exterinr walla Color: •
;n,ee"es°tan"�Veari exterior walls and an exterior
tating.Pmvitle wall
call
s lEt. wall assembly detail that
walls and an evtenor
wall assembly detail provides a 1 hour fire rating.
that provides a 1 hour
vzmuwe fire rating.
FP Response:Wall assemblies and details have been updated to reflect the existing fire rated assembly(W-4).
' — Page:A-401 STAIR
4 File Name: 2018-6-28_834 E Durant_Permit.pdf Remove all IRC references
Author: bonniem because this is an IBC building.
Subject: PlanCheck Glass guardrail are to comply
Remove all IRC ; Color: •■ with 2015 IBC 2407
ltM 1\references because
this is an IBC builtling. ,
Glass guartlrai are to
comply with 2015 IBC
2407
I*
7:::16Em 4. _41 FP Response:All IRC references have been updated to IBC.
p p
_ - Page:A-703 ROPOSED UPER LEVEL RCP
File Name: 2018-6-28_834 E Durant Permit.pdf Provide a detail for the recessed
�:—;i — can lights in the 1-hour ceiling.
o-
i 11 - -- Author: bonniem IT S Subject: PlanCheck They must be protected with
I = II Color: • either a drywall box enclosure of
a rated'hat. Cans in contact
{ with insulation must be IC rated.
o- _i__-;_liliil .7 FP Response:Cut sheet on UL rated fire hat provided(sheet A-005-E). RE c E ivE D
11/06/2018