Sent: Tuesday, October 02, 2018 9:19 AM
To: Brendan Hamlet
Subject: RE: 1112 Waters - Builder of the Day meeting
Hello Brendan,
Yes,that matches what we had discussed previously. You will also need to fire rate the underside of eaves that are less
than 5'to the property lines, similar to the exterior wall. Ideally we would like to see the eave on that corner taken back
as far as possible to try and comply with IRC 302.1 (not projecting closer than 2' to the property line), but as this is an
existing condition we would accept an alteration that gets it off the neighbor's property as a move towards compliance.
Thank you,
hig
QTYOFAIPQI
Justin Hahn
Community Development
Plans Examiner
201 N. Mill St.
Aspen, CO 81611
p 970.429.2784
c 970.319.1610
www.cityofaspen.com
www.aspencommunityvoice.com
Notice and Disclaimer:
This message is intended only for the individual or entity to which it is addressed and may contain information that is confidential and exempt from
disclosure pursuant to applicable law. If you are not the intended recipient,please reply to the sender that you have received the message in error and
then delete it. Further,the information or opinions contained in this email are advisory in nature only and are not binding on the City of Aspen. If
applicable,the information and opinions contain in the email are based on current zoning,which is subject to change in the future,and upon factual
representations that may or may not be accurate. The opinions and information contained herein do not create a legal or vested right or any claim of
detrimental reliance.
From: Brendan Hamlet<bhamlet@zone4architects.com>
Sent: Monday, October 1, 2018 2:30 PM
To:Justin Hahn <Justin.Hahn@cityofaspen.com>
Subject: 1112 Waters- Builder of the Day meeting
Hello Justin,
Thank you for taking to the time to talk through Building Department implications of our remodel at 1112 Waters
Ave. This is what we discussed:
1. Insulation—If existing structure to remain is exposed the cavities must be filled to capacity even though , �`
insulation values may not meet current code requirements. l '
2. Stairs— Existing non-conforming stairs can remain and have finish(es) replaced.
1 02/05/2019
ASPEN
BUILDING DEPARTMENT
3. Egress Windows—Existing non-conforming egress windows can be replaced with dimensionally improved
windows even though replacement windows may not meet code.
4. Property Line— Existing roof and walls exist within 5' of property line. Roof will be cut back to be contained on
site. While improving the exterior envelope a layer of Densglass (or sim) must be installed underneath siding in
areas within 5' of property line.
Please confirm we can proceed with remodel plans using the aforementioned strategies as basis of design.
Thank You,
Brendan Hamlet