HomeMy WebLinkAboutFile Documents.219 E Durant Ave.0094.2018 (7).ACBK 0094.2018.ACBK JEC0I Balancing . � J JEDI Balancing, Inc. 568 Briggs Street(physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Certified Test, Adjust & Balance Report Project Almresi-Aspen Dancing Bear Residences, Mountainside Bldg Address 219 East Durant Ave Unit C-5 Aspen, CO 81611 Architect Pierce+Frye Mechanical Engineer MKK Consulting Engineers Contractor Climate Control Date 10/17/2019 Job Number 2019-8937 Bryan A. Hund TABB Certified Supervisor TABB Firm Certification#BB009003C Stamp Expires 9/30/2020 Warranty Information: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB International Standards for Environmental Systems Balance. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed TABB tolerances, are noted in the TAB report project summary. RR This project has a one-year guarantee on all Testing, Adjusting & Balancing from th R E C E Iv E D listed on this cover page. 0 5/0 4/2 0 2 0 ASPEN BUILDING DEPARTMENT Instrumentation: Instrument I Manufacturer Model Serial Number Calibration Due Tachometer _ Shimpo MT-200 B193B5040P 08-20-2020 Air Temperature Meter _ Cooper-Atkins SRH77A-E 073119012 09-09-2020 Air Temperature Probe Cooper-Atkins 5028 073119012-3 09-09-2020 Immersion Temperature Probe Cooper-Atkins 1075 073119012-1 09-09-2020 Humidity _ Cooper-Atkins 5028 073119012-3 09-09-2020 Volt-Amp Meter 1 Fluke 323 44371155WS 07-23-2020 Air Pressure 1 Evergreen Telemetry S-PVF-1 1800259 08-20-2020 Air Velocity/Airfoil 1 Evergreen Telemetry S-PVF-1 1800259 08-20-2020 Flowhood _ Evergreen Telemetry 3 Pound _ 1900178 06-20-2020 Hydronic Pressure TSI HM-675 71550076 07-24-2020 Hydronic Differential Pressure TSI HM-675 71550076 07-24-2020 Abbreviation Index TAB: Testing,Adjusting&Balancing Cx: Commissioning OD: Outside Diameter AHU:Air Handling Unit Motor FLA:Full Load Amperage Tl: Terminal 1 RTU: Roof Top Unit S.F.: Service Factor T2: Terminal 2 PACU: Packaged Air Conditioning Unit RPM: Revolutions per Minute T3: Terminal 3 MAU:Make Up Air Unit P.F.:Power Factor CS: Circuit Setter FCU: Fan Coil Unit Nom.Elf.:Nominal Efficiency BV: Balance Valve VAV:Variable Air Volume TDH: Total Dynamic Head K Factor: Correction Factor FPB: Fan Powered Box AK: Area Correction PSI: Pounds per Square Inch CUH: Cabinet Unit Heater Valve D.P.:Discharge Pressure UH: Unit Heater Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit EF:Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan SF: Supply Fan RF: Return Fan TF: Transfer Fan Dill.:Differential SEF: Smoke Exhaust Fan DX: Direct Expansion SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure in.wc:Inches Water Column ESP:External Static Pressure HW:Heating Water VP:Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA:Return Air HX: Heat Exchanger OSA: Outside Air SWD: Sidewall Diffuser MA:Mixed Air EAT:Entering Air Temperature OA: Outside Air CD: Ceiling Diffuser EWT:Entering Water Temperature SD: Supply Diffuser ER: Exhaust Register LAT:Leaving Air Temperature MVD:Manual Volume Damper RG: Return Grille LWT:Leaving Water Temperature OBD: Opposed Blade Damper NAC:No Access CFM: Cubic Feet Per Minute CMH: Cubic Meters per Hour NG:Not Given FPM:Feet Per Minute SSD: Square Supply Diffuser NIC:Not in Contract SRD: Square Return Diffuser E: Existing M:Meter TG: Transfer Grille cm: Centimeter Pa: Pascal 1/s:Liters per Second mm:Millimeter kPa:Kilopascal ADM:Air Data Meter(manometer) SPF: Stairwell Pressurization Fan Design D.P.: Design Differential Pressure Actual D.P.:Recorded Differential Pressure Ind.Imp.Dia.Indicated Impeller Diameter CRAC: Computer Room Air Conditioning Unit RECEIVED 05/04/2020 ASPEN BUILDING DEPARTMENT JEDI Balancing Table Of Contents PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 Table Of Contents 1 2019 8937 Almresi Mountainside Building Report Summary.pdf 1 2 Field Note Report 2 3 Air Handling Unit 3 3.1 E-AHU-01 (NIC)/E-VAV-01 3 3.2 E-AHU-01 (NIC)/E-VAV-02 3 3.3 E-AHU-01 (NIC)/E-VAV-03 4 3.4 E-AHU-01 (NIC)/E-VAV-07 5 3.5 E-AHU-01 (NIC)/E-VAV-08 5 4 Fan Unit 6 4.1 EF-04 6 5 Hydronic Pump 7 5.1 HWP-01 (NIC) 7 5.2 P-04A DHW 8 6 Sheets and Views 9 6.1 MO.0 MECHANICAL AND PLUMBING COVER SHEET 1 6.2 M-1P MECHANICAL PARKING LEVEL 6.3 M1.0 LOWER LEVEL MECHANICAL PLAN 4 6.4 M2.1 STREET LEVEL MECHANICAL PLAN 5 6.5 M2.2 MECHANICAL ROOF PLAN 6 6.6 M4.0 MECHANICAL DETAILS 7 6.7 M4.1 MECHANICAL SCHEMATICS 8 6.8 M5.0 MECHANICAL SCHEDULES 2 6.9 M5.1 MECHANICAL SCHEDULES 3 6.10 M6.0 MECHANICAL CONTROLS 9 6.11 M7.0 MECHANICAL SPECIFICATIONS 10 6.12 M7.1 MECHANICAL SPECIFICATIONS 11 6.13 M7.2 MECHANICAL SPECIFICATIONS 12 RECEIVED 05/04/2020 JEDI Balancing, Inc. ASPEN BUILDING DEPARTMENT JEDI Balancing, Inc. 568 Briggs Street(physical) P.O.Box 525 (mail) JEDI Erie,CO. 80516 Balancing Phone(720)839-5333 www.jedihalancing.com Report Summary and Remarks Project: Almresi Mountainside Building Project: 2019 8937 Scope: The Test and Balance (TAB) scope of work consisted of(VAV)-5, Exhaust Fan(EF)-1, (Pump)-1, Valves-6,Not in contract: AHU Procedures: VAV'S The associated VAV's were indexed to full cooling, calibrated and outlets proportioned for design airflow. After each VAV was calibrated, the VAV was indexed to minimum and heating airflow settings with design and measured values recorded on the VAV test report pages. Exhaust Fans with Grilles and Hoods The exhaust fans were energized, measured and set for total airflow. The associated inlets were balanced as noted in this report. The Exhaust Air CFM was measured as individually listed under each unit. Final settings and performance measurements were completed, and data recorded on to the appropriate test report forms. Hydronic Systems The Circulation Pumps were indexed to full flow conditions. Initial pump performance and final pump performance was set and noted in this report. The final system settings were completed, and final performance data was recorded. The water coils were index to full flow conditions. Each coil was then balanced using the circuit setters for the most accurate measurement; in lieu of coil pressure drops. The test results and issues are reported on the individual test pages. Schematic Line Diagrams Report includes reduced mechanical drawings used for the test and balance work. These "Keyed Drawing"were used in place of single line schematic diagrams and include the unique designations for the tested items in the final TAB report. Submittals: Submittals were not provided for the project. to +/-10% of design flow rates Any values outside the specified tolerances are noted on the Equipment Comment Log and the individual test report pages. Previously Forwarded/Accepted As-Is Equipment Comment Log Project Summary The following page(s) lists all project comments and issues. All items described and listed on the following Equipment Comment Log have been previously forwarded for resolution and have been accepted as reported. RECEIVED 05/04/2020 ASPEN BUILDING DEPARTMENT ...•. JEDI Balancing Field Note Report PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 Test System/ Unit Name Date I Contact _ Notes/Comment Logs VAV Box E-AHU-01 (NIC)/E-VAV-07 16-Oct-19 Bryan Hund EXISTING FSD WAS INITIALLY CLOSED. WAS OPENED MANUALLY FOR TESTING. Hydronic Pump P-04A DHW 16-Oct-19 Bryan Hund PUMP TESTED IN CONSTANT SPEED FOR DESIGN FLOW. THEN PLACED INTO AUTO- ADAPT FEATURE AT 29.5 GPM. RECEIVED 05/04/2020 JEDI Balancing, Inc. Page mf9N BUILDING DEPARTMENT .... JEDI Balancing Air Handling Unit PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: E-AHU-01 (NIC)/E-VAV-01 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Measured Data VAV Address 11 Max Design CFM 875 Box Inlet Size 0.55 sq.ft Max Actual CFM 875 Min Design CFM 300 Final Test Data Min Actual CFM 310 K Factor Max Flow 1.37 Reheat Design CFM 780 Reheat Actual CFM 775 E-AHU-01 (NIC)/E-VAV-01 Supply Outlet Summary System/Unit Area Served Outlet Size(in) Design Prelim Final % Instrument Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM ft) Outlet-01 KITCHEN A 8" 220 200 210 95 Flow Hood Outlet-02 KITCHEN A 8" 215 120 220 102 Flow Hood Outlet-03 BAR A 6" 145 160 150 103 Flow Hood Outlet-04 BAR A 8" 145 180 140 97 Flow Hood Outlet-05 ENTRY A 8" 150 160 155 103 Flow Hood Totals: - - - 875 820 875 100 - - - - SYSTEM/UNIT: E-AHU-01 (NIC)/E-VAV-02 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Measured Data I VAV Address 12 Max Design CFM 1000 Box Inlet Size 0.775 sq.ft Max Actual CFM 1010 Min Design CFM 400 Final Test Data Min Actual CFM 410 K Factor Max Flow 0.80 Reheat Design CFM 400 Reheat Actual CFM 405 E-AHU-01 (NIC)/E-VAV-02 Supply Outlet Summary I System/Unit Area Served Outlet Size(in) Design Prelim Final % Instrument Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM ft) Outlet-01 STAIRS A 6" 75 95 80 107 Flow Hood Outlet-02 DINING A 8" 125 90 130 104 Flow Hood Outlet-03 DINING A 8" 200 180 200 100 Flow Hood Outlet-04 CORRIDOR A 8" 150 225 155 103 Flow Hood Outlet-05 STAR A 8" 150 160 145 97 Flow Hood Outlet-06 BAR A 10" 300 310 300 100 Flow Hood Totals: - - - 1000 1060 1010 101 - - - - RECEIVED 05/04/2020 JEDI Balancing, Inc. Page mpiaN BUILDING DEPARTMENT ...•. JEDI Balancing „..........„ , . Air Handling Unit PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: E-AHU-01 (NIC)/E-VAV-03 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Measured Data VAV Address 13 Max Design CFM 1320 Box Inlet Size 0.775 sq.ft Max Actual CFM 1310 Min Design CFM 400 Final Test Data Min Actual CFM 410 K Factor Max Flow 0.86 Reheat Design CFM 400 Reheat Actual CFM 410 E-AHU-01 (NIC)/E-VAV-03 Supply Outlet Summary System/Unit Area Served Outlet Size(in) Design Prelim Final % Instrument Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM _ ft) _ Outlet-01 CORRIDOR A 8" 165 210 160 97 Flow Hood Outlet-02 DINING 2 A 8" 165 240 170 103 Flow Hood Outlet-03 DINING 2 A 8" 165 265 170 103 Flow Hood Outlet-04 DINING 2 A 8" 165 240 160 97 Flow Hood Outlet-05 DINING 2 A 8" 220 230 230 105 Flow Hood Outlet-06 DINING 2 A 8" 220 270 210 95 Flow Hood Outlet-07 DINING 2 A 8" 220 210 210 95 Flow Hood Totals: - - - 1320 1665 1310 99 - - RECEIVED 05/04/2020 JEDI Balancing, Inc. Page 4qgF N BUILDING DEPARTMENT JEDI Balancing .,..........e , . Air Handling Unit PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: E-AHU-01 (NIC)/E-VAV-07 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Measured Data VAV Address 17 Max Design CFM 1265 Box Inlet Size 0.775 sq.ft Max Actual CFM 1280 Min Design CFM 400 Final Test Data Min Actual CFM 410 K Factor Max Flow 0.94 Reheat Design CFM 400 Reheat Actual CFM 410 Log: E-AHU-01 (NIC)/E-VAV-07 10/16/2019 Bryan Hund EXISTING FSD WAS INITIALLY CLOSED.WAS OPENED MANUALLY FOR TESTING. E-AHU-01 (NIC)/E-VAV-07 Supply Outlet Summary System/Unit Area Served Outlet Size(in) Design Prelim Final % Instrument Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM ft) Outlet-01 LL C 10/6 220 150 210 95 Flow Hood Outlet-02 LL C 10/6 175 130 180 103 Flow Hood Outlet-03 LL C 10/6 210 240 220 105 Flow Hood Outlet-04 LL C 10/6 220 210 215 98 Flow Hood Outlet-05 LL C 10/6 155 170 160 103 Flow Hood Outlet-06 LL C 10/6 160 130 165 103 Flow Hood Outlet-07 LL C 10/6 125 155 130 104 Flow Hood Totals: - - - 1265 1185 1280 101 - - - - SYSTEM/UNIT: E-AHU-01 (NIC)/E-VAV-08 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Measured Data VAV Address 14 Max Design CFM 300 Box Inlet Size 0.19 sq.ft Max Actual CFM 305 Min Design CFM 100 Final Test Data Min Actual CFM 110 K Factor Max Flow 0.8 Reheat Design CFM 100 Reheat Actual CFM 110 E-AHU-01 (NIC)/E-VAV-08 Supply Outlet Summary 1 System/Unit Area Served Outlet Size(in) Design Prelim Final % Instrument Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM ft) Outlet-01 LL A 10" 300 240 305 102 Flow Hood Totals: - - - 300 240 305 102 - - - - RECEIVED 05/04/2020 JEDI Balancing, Inc. Page mcIN BUILDING DEPARTMENT JEDI Ba/an cin Fan Unit PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: EF-04 Tested By: Bryan Hund Date: 10/16/2019 Unit Data Motor Data Fan Manufacturer COOK Motor Manufacturer CENTURY Fan Model Number 140CVB Motor HP 3/4 Fan Serial Number 041S129891-00/0000701 Motor RPM 1725 Type of Service EXHAUST Motor Frame J56 Motor Phase 1 Starter Data Motor Rated Volts 115/208-230 Starter Manufacturer THERMALLY PROTECTED Motor FL Amps 11.0/5.4-5.5 Motor Service Factor 1.25 Design Data Total CFM Design 475 Sheave Data Total Connected Design CFM 475 Drive Type BELT Design ESP 1.6 in.wc Motor Sheave Model/Size 1 VL40 Design TSP NOT GIVEN in.wc Motor Sheave Bore 5/8 in. Fan Design RPM 1703 Motor VP Sheave Operating PD 3.8 Fan Motor Design HP 3/4 Fan Sheave Model/Size AK40 Fan Motor Design RPM 1703 Fan Sheave Bore 3/4 in. Fan Motor Design Voltage 115 Sheave Center Line 18 in. Fan Motor Design Phase 1 Number of Belts 1 Belt Size A42 Electrical Test Data Motor Volts 1 Actual 123 Final Data Motor Amps 1 Actual 9.60 Total Fan CFM Actual 490 Corrected Nameplate Amps 10.73 Fan CFM Test Method Flowhood Summation Actual BHP 0.67 Volts/Amps Measured By RMS Clamp Meter Measured Data Fan RPM Actual 1690 Fan Speed/Setpoint Not Applicable Operating Hertz 60 Test Pressures Fan SP In Actual -0.65 in.wc Fan SP Out Actual 0.12 in.wc EF-04 Exhaust Inlet Summary System/Unit Area Served Outlet Size(in) Design Prelim Final % Instruments Open Ak(sq Final Vel Type Reading Reading Reading Final Area(sq ft) FPM ft) Inlet-01 LL D 6/6 75 360 80 107 Flow Hood Inlet-02 KITCHEN D 8/8 200 20 220 110 Flow Hood Inlet-03 KITCHEN D 8/8 200 20 190 95 Flow Hood Totals: - - - 475 400 490 103 - - - - RECEIVED 05/04/2020 JEDI Balancing, Inc. Page F\gF242 N BUILDING DEPARTMENT ...•. JEDI Balancing „..........„ , . Hydronic Pump PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: HWP-01 (NIC) Tested By: Bryan Hund Date: 10/16/2019 Unit Data Type of Service HEATING WATER HWP-01 (NIC) Balance Valve Summary System/Unit Manufacturer Model Size GPM GPM %Final Valve D.P. Valve D.P. Valve Position Number Design Actual Deviation Design Actual _ E-VAV-01 NEXUS ORTURI 2A 3.00 2.80 93 40 35 100 E-VAV-02 NEXUS ORTURI 2A 1.50 1.60 107 10 11.4 7- 5 E-VAV-03 NEXUS ORTURI 2A 1.50 1.63 109 10 11.8 7- 5 E-VAV-07 NEXUS ORTURI 2A 1.50 1.53 102 10 10.5 7- 5 E-VAV-08 NEXUS ORTURI 1A 0.50 0.54 108 15 17.5 100 Totals: - - - 8.00 8.10 101 - - - RECEIVED 05/04/2020 JEDI Balancing, Inc. Page 7,502pN BUILDING DEPARTMENT ...•. JEDI Balancing Hydronic Pump PROJECT: ALMRESI MOUNTAINSIDE BLDG DATE: 10/17/2019 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2019-8937 SYSTEM/UNIT: P-04A DHW Tested By: Bryan Hund Date: 10/16/2019 Unit Data Motor Data Pump Manufacturer GRUNDFOS Motor Manufacturer GRUNDFOS Pump Model Number MAGMA 32-100 F165 Motor HP 9.7-178 watts Pump Serial Number 2019 Motor HP Decimal Variable Type of Service DHW Motor RPM Not Given Motor Frame Not Given Starter Data Motor Phase 1 Starter Manufacturer Thermally Protected Motor Rated Volts 115/230 Motor F.L.Amps 1.61 Design Data Motor S.F. 1.0 Pump Design GPM 29 GPM Design TDH 20 Ft Measured Data Total Connected GPM 8 GPM Pump Off Pressure 15.00 PSI Pump Design RPM 1750 Pump RPM Actual DIRECT DRIVE Motor Design HP 0.5 Valve Manufacturer TACO Design Impeller Diam. NOT GIVEN in. Valve Model 2"SWEAT Valve Design D.P. 9.5 in Final Test Data Valve Actual D.P. 9.8 in Final GPM Actual 29.5(See Notes)GPM Valve GPM 29.5 Final D.P. See Notes PSI Valve Position 0 Valve Setting 100% Differential Pressure Setpoint Not Applicable PSI Electrical Test Data Motor Volts 1 122 Volts Motor Amps 1 1.50 Amps Corrected Nameplate Amps 1.58 Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: P-04A DHW 10/16/2019 Bryan Hund PUMP TESTED IN CONSTANT SPEED FOR DESIGN FLOW.THEN PLACED INTO AUTO- ADAPT FEATURE AT 29.5 GPM. RECEIVED 05/04/2020 JEDI Balancing, Inc. Page4F4N BUILDING DEPARTMENT MECHANICAL LEGEND 111 (PIPING PLUMBING GENERAL NOTES: MKK (FOR ALL PLUMBING AND MECHANICAL DRAWINGS) CONSULTING ENCINFFRS,INC �IMEG —HWS— HEATING WATER SUPPLY ----- DOMESTIC COLD WATER 1. EXISTING MECHANICAL SYSTEMS SHOWN LIGHT LINE WEIGHT. NEW MECHANICAL SYSTEMS SHOWN HEAVY LINE WEIGHT. —HWR— HEATING WATER RETURN ------- DOMESTIC HOT WATER A Mechanical,Electrlcal8 2. THE INSTALLATION OR REMOVAL OF DUCTS,PIPES AND EQUIPMENT MAY REQUIRE THE REMOVAL OF Energy Consultants —CWS- CHILLED WATER SUPPLY ----180---- DOMESTIC HOT WATER(TEMP.SHOWN) CONSULTING ENGINEERS,INC. EXISTING WALLS AND CEILINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND —CWR— CHILLED WATER RETURN —"'— DOMESTIC HOT WATER CIRCULATING REPAIRING THESE WALLS AND/OR CEILINGS SO THEY MATCH THE EXISTING WHERE NOT REPLACED Mechanical,Electrical&Energy Consultants UNDER ARCHITECTURAL DIVISION. —CS— CONDENSER WATER SUPPLY —T— TEMPERED WATER 7600 East Orchard Road,Suite 250-S 3. OWNER SHALL HAVE FIRST RIGHT OF REFUSAL ON ALL FIXTURES AND EQUIPMENT REMOVED AND NOT —CR— CONDENSER WATER RETURN —NP— NON-POTABLE WATER Greenwood Village,CO 80111-2518 REUSED. ANY SUCH FIXTURE AND EQUIPMENT THAT GOES UNCLAIMED BY THE OWNER SHALL BE —CHS— DUAL TEMPERATURE SUPPLY —NG#PSIG— NATURAL GAS,PRESSURE AS IDENTIFIED 303.796.6000 REMOVED AND PROPERLY DISPOSED OF. ___ www.mkkeng.com 4. PATCH OPENINGS(AIR TIGHT)IN DUCTS WHICH ARE TO REMAIN ACTIVE AND HAVE HAD A SECTION PIERCE —CHR— DUAL TEMPERATURE RETURN ----V- PLUMBING VENT PIPE REMOVED.ALSO REPAIR DUCT INSULATION SO THAT IT IS CONTINUOUS. —D— DRAIN PIPE SOW— S SAND AND OIL WASTE PIPE Denver Billings + FRY E 5. INFORMATION ON THE DRAWINGS HAS BEEN ASCERTAINED FROM EXISTING DRAWINGS AND FIELD —HPS— HIGH PRESSURE STEAM SAN . SANITARY WASTE PIPE 7600 East Orchard Rd Suite 250-S 175 North 27th Street,Suite 13(2 OBSERVATIONS. THIS INFORMATION IS AS ACCURATE AS CONDITIONS WOULD ALLOW. IT IS THE Greenwood Village,CO 80111-2539 Billings,MT 59101-2048 RESPONSIBILITY OF THE CONTRACTOR TO VISIT THE SITE,PRIOR TO BID,AND BECOME FAMILIAR WITH —HPR— HIGH PRESSURE COND.RETURN —OWE GREASE WASTE PIPE 303.796.6000 406.545.6420 THE EXTENT OF THE REMODEL WORK REQUIRED.NO EXTRAS WILL BE ALLOWED FOR ALTERATIONS OF ARCH I T E C T S —LPS— LOW PRESSURE STEAM STD STORM DRAIN/BUILDING STORM SEWER PIPE Cheyenne Salt Lake City A FORESEEABLE NATURE REQUIRED TO ACHIEVE THE END RESULT AS INDICATED BY CONTRACT 500 West 18th Street,Suite 200 4760 S.Highland Drive,Suite 106 DOCUMENTS. —LPR— LOW PRESSURE COND.RETURN ——OST— OVERFLOW STORM DRAIN PIPE Cheyenne,WY 82001-4368 Salt Lake City,UT 84115 8. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO REVIEW THE ENTIRE PROJECT CONSTRUCTION —CP— CONDENSATE PUMP DISCHARGE —CA— COMPRESSED AIR PIPE 307.459.6100 801.360.7024 DOCUMENT PACKAGE,PRIOR TO BID,AND BECOME FAMILIAR WITH THE EXTENT OF THE WORK AND San Francisco Office Helena Bogota,Colombia COORDINATION REQUIRED. NO EXTRAS WILL BE ALLOWED FOR ALTERATIONS OF A FORESEEABLE Tel:415.392.4433 —FOS— FUEL OIL SUPPLY II HORIZONTAL CLEANOUT P.O.Box 9643 Calle 406#8-68 Edi0cio Torre San Marcos,501 NATURE REQUIRED TO ACHIEVE THE END RESULT AS INDICATED BY CONTRACT DOCUMENTS. —FOR— FUEL OIL RETURN VERTICAL CLEANOUT Helena,MT 59604 Bogota D.C.110231 Colombia 7. CONTRACTOR TO SEAL ALL AUDIBLE AND VISIBLE LEAKS ON ALL REUSED SUPPLY DUCTWORK. Vail Office 406.438.1467 +57.1.485.0689 Tel:970.949.0899 ---FOV--- FUEL OIL VENT 8. CONTRACTOR IS TO PROVIDE COMPLETE CONNECTIONS TO ALL NEW AND RELOCATED OWNER —RS— REFRIGERANT SUCTION HVAC DUCTORK FURNISHED EQUIPMENT. W www.PlerceFrye.com —RL— REFRIGERANT LIQUID 9. ALL PIPING AND DUCTS INDICATED TO BE REMOVED UNDER THIS CONTRACT SHALL BE REMOVED infm®PierceFrye.com ® FIRE DAMPER COMPLETELY TO POINTS OF CONNECTION AT THE MAINS OR BRANCHES AND CAPPED OR MAINTAINED —RD— REFRIGERANT DISCHARGE ® PROJECT INFORMATION FOR REUSE AS SHOWN ON NEW PLAN. aI5 SMOKE DAMPER PROJECT LOCATION: ASPEN,COLORADO 10. WORK UNDER THIS CONTRACT IS IN OCCUPIED SPACES,STORAGE ROOMS AND EQUIPMENT ROOMS. VALVES&SPECIALTIES CONTRACTOR IS TO SCHEDULE AND COORDINATE THE WORK AND ANY EXISTING EQUIPMENT L— ®FS COMBINATION FIRE/SMOKE DAMPER PROJECT ALTITUDE: 8000 FEET ABOVE SEA LEVEL DOWNTIME WITH THE OWNER OR PROPERTY MANAGER PRIOR TO BEGINNING WORK. CJ FLOW INDICATOR SUMMER DESIGN TEMPERATURE: 85.9°F DRY BULB,56.7°F WET BULB(ASHRAE 1%DESIGN) TURNING VANES SHOWN IN 90°ELBOW. WINTER DESIGN TEMPERATURE: -15°F DRY BULB,0%RH(ASHRAE 99.6%) 11. CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING,COORDINATE ANY EQUIPMENT DOWNTIME, x- —Pi— SHUT-OFF VALVE SUMMER ROOM DESIGN TEMP: 75°F DRY BULB-NO HUMIDITY REQUIREMENT AND COORDINATE GENERAL WORK SCHEDULE WITH THE PROPERTY MANAGER. —1.4— GLOBE VALVE WINTER ROOM DESIGN TEMP: 70°F DRY BULB-NO HUMIDITY REQUIREMENT OPPOSED BLADE DAMPER(O.B.D.) SUMMER ROOM SETBACK TEMP: 90°F DRY BULB-NO HUMIDITY REQUIREMENT(ASHRAE 90.1) 12 EXISTIN. THE G PIIPE NGS ROUTING AND EXISTING DUCT ROUT NG.CONTRACTOR INDICATE THE GENERAL ARRANGEMENT OF THEEXEQUIPMENT TO INSTA STING LM NE EQU PMENT, rjf —� CHECK VALVE WINTER ROOM SETBACK TEMP: 55°F DRY BULB-NO HUMIDITY REQUIREMENT(ASHRAE 90.1) DUCTS,AND PIPING IN LOCATIONS REQUIRED TO AVOID INTERFERENCE WITH EXISTING FACILITIES, O —B'�- FLOW CONTROL VALVE W/CHECK L EQUIPMENT,DUCTS AND PIPING. CONTRACTOR IS RESPONSIBLE FOR RAISING AND LOWERING DUCT SIZES ARE OUTSIDE SHEET METAL DIMENSIONS.1st EXISTING EQUIPMENT AND MAKING PROPER OFFSETS IN DUCTS AND PIPING TO AVOID CONFLICTS. ' Q CALIBRATED BALANCING SHUT-OFF VALVE. NO.IS SIZE OF SURFACE SHOWN.2nd Na IS DUCT DEPTH. ray U LETTERS AFTER DIM.CORRESPOND TO FOLLOWING: 13. CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING BID,AND VERIFY DIMENSIONS AND EXISTING —I-CI— PLUG VALVE. CONDITIONS RELATED TO THE WORK. m-ROUND DUCTWORK -!i BALL VALVE D-DOUBLE WALL CONSTRUCTION CONTROLS LEGEND (SYMBOLS LOCATED IN BUILDING AUTOMATION SYSTEM SCHEMATICS) 14. ALL EXISTING EQUIPMENT AND MATERIALS CALLED TO BE REMOVED UNDER THIS CONTRACT SHALL BE 0_ e' Q PRESSURE INDEPENDENT AUTOMATIC BALANCING VALVE UL-UNLINED DUCTWORK REMOVED FROM OCCUPIED SPACES DAILY. = < V-OVAL DUCTWORK FLOW DIFFERENTIAL PRESSURE SIZE 15. ALL CUTTING,PATCHING AND CORE DRILLING FOR THE INSTALLATION OF NEW EQUIPMENT,DUCTS, rYlt N.O.VALVE W/LOCKING COVER CFM REFRIGERANT DETECTOR SENSOR HANGERS,ETC.SHALL BE HELD TO A MINIMUM AND BE ACCOMPLISHED IN A CAREFUL MANNER.ALL SUPPLY DIFFUSER.ALL DIFFUSERS FOUR-WAY THROW In CONTROL WIRING PATCHING SHALL MATCH EXISTING CONSTRUCTION,TEXTURE AND FINISH AND BE DONE BY SKILLED I — PLUG OR BALANCINGC CSHUT-OFF VALVE IN RISER TYPE I I UNLESS NOTED OR THROWS SHOW IN PLAN.SEE HI LOW CRAFTSMAN OF THE TRADES INVOLVED AT THE CONTRACTOR'S EXPENSE. I SF EIVED SCHEDULE FOR TYPE. _11 DAMPER U fS5,�/I'�1( NHLS X x x CONTROL AIR PIPING SIZE RETURN/TRANSFER/EXHAUST AIR TAG.SEE SCHEDULE I��I 16. CONTRACTOR TO COORDINATE THE LOCATION OF ALL DUCTWORK,CEILING DEVICES,GRILLES, C DRAIdVE1Nf LiOSE END CF� FOR TYPE. O MAIN AIR ITN REGISTERS AND DIFFUSERS WITH REFLECTED CEILING PLAN AND STRUCTURE PRIOR TO BEGINNING ®CA u U V4 LV LV O GAUGE CURRENT SENSOR WORK. U D I I STRAINER W BL W-OFF VALVE&HOSE END SECTION THRU OUTSIDE AIR INTAKE OR �b A P NIIII II► PUMP 17. DUCT DIMENSIONS GIVEN ARE OUTSIDE SHEET METAL DIMENSIONS. C CD Cll pp I����IITT���tJ((;;II11��pppp77�f�1���Id SUPPLY AIR DUCT TEMISERXTl7fTEPCONTYCtSL VALVE,3-WAY DAMPER ACTUATOR XXX ANALOG INPUT OR 18. MECHANICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT NECESSARILY INDICATE EVERY REQUIRED 2 11 SECTION THRU RETURN AIR OR FAN XXX OUTPUT SYMBOL OFFSET,FITTING,ETC.DRAWINGS ARE NOT TO BE SCALED FOR DIMENSIONS.TAKE ALL DIMENSIONS EXHAUST DUCT FROM ARCHITECTURAL DRAWINGS,CERTIFIED EQUIPMENT DRAWINGS AND FROM THE STRUCTURE C� TEMPERATURE CONTROL VALVE,2-WAYITSELF I - 1 OA,RA OR EXH DUCT DOWN REMOTE BULB AM BINARY INPUT OR q L/ OTHER BEFORE FROM AND INSTALL THE SYSTEMS INFABRICATING ANY WORK, IFY THE SPACE PROVIDED WITHOUT EALL SPACE REQUIREMENTSOXTTRA TH CHARGES ORDINATING ITO +.., • PRESSURE INDEPENDENT 2-WAY CONTROL VALVE m OWNER.AIR FLOW MEASURING SENSOR/CONTROLLER THE C I,,SRZ I SUPPLY AIR DUCT DOWN STATION ® OUTPUT SYMBOL CU L PRESSURE REDUCING VALVE O HUMIDISTAT/HUMIDITY SENSOR 19. THE OWNER AND ENGINEER ARE NOT RESPONSIBLE FOR THE CONTRACTOR'S SAFETY PRECAUTIONS $,� CHANGE OF ELEVATION UP(UP)DOWN(DN)IN I �O FILTER ® SNOW/ICE SENSOR EMERGENCY PULL SWITCH OR TO MEANS,METHODS,TECHNIQUES,CONSTRUCTION SEQUENCES,OR PROCEDURES REQUIRED TO C r SAFETY OR RELIEF VALVE =El ® 1 DIRECTION OF AIR FLOW PERFORM HIS WORK. lagp coo CARBON MONOXIDE SENSOR EMERGENCY POWER OFF SWITCH , 20. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE STATE CODES,LOCAL CODES • � Y MANUAL AIR VENT I— FLEXIBLE CONNECTION ®. CARBON DIOXIDE SENSOR O END SWITCH AND OWNER'S STANDARDS INDICATED BY THE CONSTRUCTION DOCUMENTS. .,) w T COIL NITROGEN DIOXIDE SENSOR 0SWITCH 21.ALL EXTERIOR WALL AND ROOF PENETRATIONS SHALL BE SEALED WATERPROOF. as CSl Y AUTOMATIC AIR VENT ] BACKDRAFT DAMPER I ®. INDOOR AIR QUALITY SENSOR S 22.ALL MECHANICAL WORK UNDER THIS CONTRACT IS TO FIVE(5)FEET OUTSIDE THE BUILDING. 0 CV MOTOR PRESSURE SWITCH T PRESSURE-TEMP.TAP STARTER ROOM THERMOSTAT/TEMP SENSOR Pg 23.XXR4f#REFERS TO EQUIPMENT DESIGNATION.SEE SPECIFICATIONS AND EQUIPMENT SCHEDULES FOR 24024 RETURN AIR GRILLE W/SOUND BOOT. 0 FLOW SWITCH FURTHER INFORMATION IN REFERENCE TO THAT DESIGNATED PIECE OF EQUIPMENT. SHADING INDICATES OPEN END. SUBSCRIPTS: 4 Issue Date: PRESSURE GAUGE W/PIG TAIL&COCK VARIABLE FREQUENCY DRIVE S- W/STAINLESS STEEL COVER 07/182018 Permit Set ' THERMOMETER 0 24x12 RETURN AIR GRILLEW/SOUND BOOT. CO A- W/SETPOINT ADJUSTMENT0131 I- W/TEMP INDICATION FLOW METER 02282019 Building Psrnit Resubmigal SHADING INDICATES OPEN END. yV• VACUUM BREAKER 1E1 24o24 RETURN AIR GRILLE Al- W/TEMP AND ADJUSTMENT 3-WAY G- W/LOCKING GUARD PIPE EXPANSION JOINT 13 24x12 RETURN AIR GRILLE ' BUTTERFLY VALVE FLEXIBLE PIPE CONNECTOR(STAINLESS STEEL BRAIDED) OR Y"yA 1/- Y FLEXIBLE DUCT C DUCT AVERAGING TEMPERATURE MECHANICAL/ELECTRICAL EQUIPMENT SCHEDULE —DM— FLEXIBLE EQUIPMENT CONNECTOR(RUBBER DOUBLE BELLOWS) SENSOR 2-WAY CONTROLS(NOTE B.BELOW)REFERENCES THE"CONTROLS"COLUMN OF THE EQUIPMENT SCHEDULES. III— PIPE UNION CONTROLS(IN PLAN) BUTTERFLY PIPE CAP VALVE NOTES: 0 THERMOSTAT/TEMP SENSOR /� 0 WATER DIFFERENTIAL PRESSURE —•-- PIPE ANCHOR S ti�1 �'L MODULATING 3-WAY& A. SEE SPECIFICATIONS DIVISION 26'ELECTRICAL EQUIPMENT AND WIRING FOR MECHANICAL DIVISION" _ PIPE GUIDE TEMP SENSOR W/STAINLESS STEEL COVER I]LC`I 2-WAy VALVES SENSOR/CONTROLLED FOR FURTHER INFORMATION. 0 p' TEMP SENSOR W/SETPOINT ADJUSTMENT HI LO �1MI IMI� PREMANUFACTURED PIPE EXPANSION LOOP.REQUIRED HI B. CONTROLS:(1)FROM LIGHT SWITCH(2)SEPARATE WALL SWITCH(3)SWITCH WITH PILOT LIGHT(4) LJ EXPANSION COMPENSATION LISTED.PROVIDE GUIDES& 0 I TEMP SENSOR W/TEMP INDICATION 2 QJ 2 POSITION 3-WAY& LO RUNS CONTINUOUSLY(5)INTERLOCK TO RUN WITH OTHER EQUIPMENT(6)CONTROLLED BY DIVISION 15" ANCHORS AS RECOMMENDED BY MANUFACTURER. ®Al /2-WAY VALVES I I DUCT STATIC 23(7)CYCLE FROM REMOTE THERMOSTAT(8)INTERGRAL TO UNIT(9)FIRE ALARM(10)OTHER:SEE TEMP SENSOR W/SET POINT ADJUSTMENT S PRESSURE SENSOR REMARKS'CARRIES FULL CURRENT.WIRING DONE BY DIVISION 26 FOR CONTROL.SEE AND TEMP INDICATION _ SPECIFICATIONS.ALSO SEE'TEMPERATURE CONTROL°SPECIFICATIONS. FIRE PROTECTION OG THERMOSTAT/TEMP SENSOR WITH LOCKING GUARD ` , I L ° DUCT SMOKE DETECTOR BUILDING STATIC PRESSURE SENSOR C. MAGNETIC STARTERS TO HAVE MAINTAINED CONTACT UNLESS NOTED.ALL STARTERS BY 0 N NIGHT THERMOSTAT MECHANICAL UNLESS NOTED TO BE BY ELECTRICAL. FLOW SWITCH CO CARBON MONOXIDE SENSOR LO Ot�;D•4 t/CF HI D. MOTORS 1/2 HP AND LESS TO BE 1750 RPM,115/60/1,MOTORS 3/4 HP AND ABOVE TO BE AS NOTED IN QY. SCHEDULES. V,.•••N.JO `P F.A. El CARBON DIOXIDE SENSOR LOW TEMPERATURE d '`/y,v �� HORN/STROBE FIRE ALARM ® Q WATER TEMPERATURE SENSOR '+ DETECTION THERMOSTAT I `' NITROGEN DIOXIDE SENSOR � E. THREE PHASE STARTERS ON MOTORS 5 HP OR GREATER TO HAVE PHASE MONITOR CONTROL RELAY, WITH WELL % FIRE PIPE CC INDOOR AIR QUALITY SENSOR SEE SPECIFICATION. c,(� FIRE PIPING FROM FDC TO FIRE ENTRY SCHEMATIC61 HUMIDISTAT/SENSOR li,.:.. O EXISTING FIRE SPRINKLER EXISTING FIRE SPRINKLER TO BE RELOCATED El STARTERS" o�-s ABBREVIATIONS z-zt. • NEW FIRE SPRINKLER PRESSURE SWITCH ADA AMERICANS WITH DISABILITIES ACT FLA FULL LOAD AMPS LF LINEAR FEET RH RELATIVE HUMIDITY Drawing Title: EXISTING FIRE SPRINKLER TO BE REMOVED AFF ABOVE FINISHED FLOOR FPM FEET PER MINUTE LRA LOCKED ROTOR AMPS RLA RUNNING LOAD AMPS 122 DIFFERENTIAL AIR PRESSURE SENSOR AFG ABOVE FINISHED GRADE FPS FEET PER SECOND LN/T LEAVING WATER TEMPERATURE RPM REVOLUTIONS PER MINUTE O.S.&V VALVE ALT ALTITUDE FT FOOT,FEET,FEET WATER COLUMN MAX MAXIMUM SA SUPPLY AIR MECHANICAL AND O SWITCH BHP BRAKE HORSEPOWER FU FIXTURE UNITS MBH BTU PER HOUR(THOUSAND) SENS SENSIBLE SHUT-OFF VALVE W/TAMPER SWITCH BTU BRITISH THERMAL UNIT GA GAUGE MCA MINIMUM CIRCUIT AMPS SL SEA LEVEL PLUMBING FM FLOW METER C COMMON PORT GAL GALLONS MIN MINIMUM SP STATIC PRESSURE CFM CUBIC FEET PER MINUTE GPH GALLONS PER HOUR N/A NOT APPLICABLE SPEC SPECIFICATION � R SHEET FIRE DEPARTMENT CONNECTION-WALL TYPE SCFM CFM,STANDARD CONDITIONS GPM GALLONS PER MINUTE N.C. NORMALLY CLOSED SQ SQUARE LT CU FT CUBIC FEET HD HEAD N.O. NORMALLY OPEN STD STANDARD MISCELLANEOUS LOW LIMIT THERMOSTAT CU IN CUBIC INCH HG MERCURY NC NOISE CRITERIA TD TEMPERATURE DIFFERENCE Co COEFFICIENT,VALVE FLOW HGT HEIGHT NIC NOT IN CONTRACT TEMP TEMPERATURE B POINT OF DUCT OR PIPE DISCONNECTION dB DECIBEL HORZ HORIZONTAL NO OR# NUMBER THRU THROUGH CONTROL DAMPER DB DRY BULB HP HORSEPOWER NTS NOT TO SCALE TJO THROUGH JOIST OPENINGS Date: March 16,2018 m POINT OF DUCT OR PIPE CONNECTION NEW TO EXISTING © • DCW DOMESTIC COLD WATER HR HOUR(S) OA OUTSIDE AIR TONS TONS OF REFRIGERATION DEG OR° DEGREE HWC HOT WATER CIRCULATING(DOMESTIC) OD OUTSIDE DIAMETER TSP TOTAL STATIC PRESSURE Project No: 2018.01.0077 • Z POINT OF PIPE CONNECTION NEW TO EXISTING DHW DOMESTIC HOT WATER HZ HERTZ % PERCENT TSTAT THERMOSTAT I SMOKE DETECTOR(DUCT) DIA DIAMETER ID INSIDE DIAMETER PH OR 0 PHASE(ELECTRICAL) TYP TYPICAL SECTION CUT:(A)SECTION I.D. DN DOWN IE INVERT ELEVATION PPM PARTS PER MILLION V VOLT Drawn by: MJK (1)SHEET NO.WHERE SHOWN. (E) EXISTING IJS IN JOIST SPACE PRESS PRESSURE VAV VARIABLE AIR VOLUME PD PRESSURE DIFFERENTIAL SENSOR EAT ENTERING AIR TEMP. IN INCHES PSF POUNDS PER SQUARE FOOT VEL VELOCITY Checked by: MJK UNDERCUT DOOR,1'. ®P EMERGENCY POWER OFF SWITCH EFF EFFICIENCY IN W.C. INCHES IN INCHES WATER COLUMN PSI POUNDS PER SQUARE INCH VERT VERTICAL ELEV ELEVATION KW KILOWATT PSIA PSI ABSOLUTE VOL VOLUME Sheet: O REFERENCE DESIGNATION FOR PLUMBING ISOMETRIC ESP EXTERNAL STATIC PRESSURE KWH KILOWATT HOUR PSIG PSI GAUGE W WATT EVJT ENTERING WATER TEMP. LAT LEAVING AIR TEMPERATURE RA RETURN AIR WB WET-BULB SPOT ELEVATION TAG.TAG INDICATES BOTTOM OF EXH EXHAUST LBS OR# POUNDS RECIRC RECIRCULATE WPD WATER PRESSURE DROP \ 0•0 DIFFUSER OR EQUIPMENT ABOVE FINISHED FLOOR. F FAHRENHEIT WT WEIGHT M 02018/2019 PIERCE FRYE ARCHITECTS DUCTWORK INSULATION (WRAP & LINER)SCHEDULE Mn VAV CONTROL BOX SCHEDULE EXISTING ror���r�x�Eu��x... �IMEG EXPOSED CONCEALED ITEM TYPE AIR FLOW HEATING COIL CAPACITY DUCT MANUFACTURER NOTES CON- SYSTEM LOCATION SERVICE MINIMUM R-VALUE SPECIFIC NOTES Mechanical,Electrical& NOTE 1 RECTANGULAR ROUND/OVAL RECTANGULAR ROUND/OVAL MAX MIN MAX CAP. EAT LAT ELECTRIC HTG HTG WATER INLET 8 MODEL NO. TROLS Energy Consultants CLG CFM HTG MBH °F °F kW V-PH STAGES EWT LWT GPM WPD GLY RUNOUT SIZE MAIN 1-1/2"LINER 1-1/2"LINER 1-1/2"LINER 1-1/2"LINER R-6 CFM CFM NOTE 1 °F °F FT % SIZE IN MAIN TO 1 NOTE 2 SUPPLY AIR INDOOR TERMINAL 1-1/2"LINER -- 1-1/2"LINER 2"WRAP R-6 (E)VAV-1 REHEAT 875 300 780 24.9 55 95 - - -- 180 160 0.23 30% 3/4 10 CARRIER 35E 2 6 TERMINAL TO (E)VAV-2 REHEAT 000 400 400 12.8 55 95 - - -- 180 160 0.39 30% 3/4 12 CARRIER 35E 2 6 1-1/2"LINER -- 1-1/2"LINER 2"WRAP R-6 GRD (E)VAV-3 REHEAT 1 0 400 400 12.8 55 95 - - -- 180 160 0.51 30% 3/4 12 CARRIER 35E 2 6 PIERCE MAIN 1"LINER 1"LINER 1"LINER 1"LINER R-4 (E)VAV-7 REHEAT 1265 400 400 12.8 55 95 - - -- 180 160 0.30 30% 3/4 12 CARRIER 35E 2 6 RETURN AIR INDOOR (E)VAV-8 REHEAT 300 100 100 3.2 55 95 - - -- 180 160 0.17 30% 3/4 6 CARRIER 35E 2 6 + FRY E BRANCH 1"LINER -- 1"LINER 1-1/2"WRAP R-4 MAIN -- -- -- -- -- 1,2 EXHAUST AIR INDOOR BRANCH -- -- -- -- -- 1,2 NOTES: 1)STAGES SHOWN SHALL BE THE MINIMUM ACCEPTABLE NUMBER.WHERE"SCR"IS NOTED PROVIDE THE MANUFACTURER'S PACKAGED PULSE MODULATION CONTROL. 2)THE NOTED LWT IS A DESIRED TARGET ONLY AND AS SUCH DURING ACTUAL COIL SUBMITTAL THIS VALUE CAN VARY WITHIN A+/-10°F RANGE OF THE LISTED VALUE ARCHITECTS GENERAL NOTES: 1)MINIMUM R-VALUE BASED ON 2015 IECC REQUIREMENTS. 2)DUCT SIZES SHOWN ARE OUTSIDE SHEET METAL DIMENSIONS.LINER,WHERE USED,HAS ALREADY BEEN FACTORED INTO THE DUCT SIZE TO ACCOMMODATE GRILLES, REGISTERS, & DIFFUSERS SCHEDULE San Francisco Office PROPER FREE AREA. Tel:415.392.4433 3)THE INSULATION THICKNESS GIVEN MEETS OR EXCEEDS THE REQUIRED R-VALUE FOR THE BASIS OF DESIGN(JOHNS MANVILLE).INSTALLED PRODUCT SHALL Vail Office EQUIP MOUNTING DAMPER MANUFACTURER& MEET OR EXCEED THE LISTED R-VALUE;INSULATION THICKNESS AND CORRESPONDING DUCT SIZE(FOR LINER)SHALL BE INCREASED FOR ALTERNATES THAT TAG TYPE FACE SIZE IN. TYPE REQUIRED MATERIAL MODEL NO. PLAN INFO SPECIFIC NOTES Tel:970.949.0899 CANNOT MEET THIS THICKNESS TO PERFORMANCE CONDITION. 4)R-VALUES FOR WRAP SHALL BE SHOWN USING THEIR INSTALLED CONDITION RATING AS NOTED ON THE MANUFACTURER'S SPECIFICATION SHEET. r A PLAQUE FACE CEILING DIFFUSER 24"x 24" HARD CLG YES STEEL KRUEGER PLQ NECK/CFM 1,5 www.PleroeFrye.com info@PierceFrye.com 5)JACKET(PVC OR METAL)SHALL BE INSTALLED AS REQUIRED BY THE SPECIFICATIONS. B PERFORATED FACE CEILING RETURN GRILLE -- -- SEE NOTES STEEL KRUEGER 6490/6690 NECK/CFM' 2,3,4 6)FLEXIBLE DUCT SHALL BE AS NOTED IN THE"AIR DUCT ACCESSORIES"SPECIFICATION. C SUPPLY REGISTER -- -- YES STUALUM KRUEGER AF880 NECK/CFM 1 7)DUCT WRAP IS ALLOWED TO BE BLANKET OR BOARD;CONTRACTOR OPTION. D EXHAUST GRILLE YES STEEL KRUEGER S80H NECK/CFM 1 8)MULTIPLE LAYERS OF WRAP OR LINER TO ACHIEVE TOTAL R-VALUE ARE ACCEPTABLE IF INSTALLED PER MANUFACTURER'S INSTRUCTIONS. 00 GENERAL NOTES: = �0 SPECIFIC NOTES: 1.SEE PLANS FOR NECK SIZE "a CO 1)INSULATION PROVIDED FOR ACOUSTICS OR OTHER PERFORMANCE CRITERIA,NO ENERGY CODE REQUIREMENT 2.ALL GRDs REQUIRING DAMPERS SHALL BE EQUIPPED WITH A REMOTE BALANCING DAMPER THAT IS ADJUSTABLE THROUGH THE GRD FACE OR •- 0 2)EXHAUST SYSTEMS SHALL BE PROVIDED WITH 1"WRAP INSULATION BETWEEN SYSTEM BACKDRAFT DAMPER AND PENETRATION OF BUILDING EXTERIOR ANOTHER APPROVED LOCATION UNLESS SUPPLIED FROM AN ACCESSIBLE TAKE-OFF WITH LOCKING DAMPER.FACE DAMPERS SUCH AS INTEGRAL OBDs ARE NOT ACCETABLE. OR ALL DUCT WITHIN 20'OF BUILDING EXTERIOR PENETRATION WHICHEVER IS LESS TO PREVENT CONDENSATION. 3.VERIFY GRD FINISH AND CLG/WALUSILUFLOOR MOUNTING TYPE WITH ARCHITECT FOR EACH APPLICATION PRIOR TO ORDERING. 4.PROVIDE 4-WAY THROW FOR DIFFUSERS UNLESS OTHERWISE SHOWN ON PLANS. DEFINITIONS: 5.PROVIDE MANUFACTURERS ROUND TO RECTANGULAR ADAPTIVE COLLAR FOR DIFFUSERS AND GRILLES AS REQUIRED,MATCH DUCT SIZE AND TYPE '`ry O U EXPOSED DUCT:DUCT THAT IS EXPOSED TO VIEW IN OCCUPIED OR UNOCCUPIED SPACES THAT ARE CONDITIONED. 6.MATERIAL SHALL BE STEEL UNLESS OTHERWISE INDICATED OR SPECIFIED.MATERIAL SHALL BE SUITABLE FOR INSTALLED ENVIRONMENT.FOR WET CONCEALED DUCT:DUCT THAT IS CONCEALED IN CHASES,SHAFTS,CEILING PLENUMS OR OTHER ASSEMBLY WITHIN THE INSULATED BUILDING ENVELOPE. LOCATIONS SUCH AS LOCKER ROOMS,RESTROOMS,SHOWER ROOMS,KITCHENS,POOL ROOMS,ETC....PROVIDE ALUMINUM IN LIEU OF THE STEEL NOTED. N MAIN DUCT:DUCT FROM THE AIR HANDLING UNIT TO FINAL TERMINAL TAKEOFF. 7.WHERE MULTIPLE DIFFUSERS ARE LOCATED IN A SINGLE ROOM;FACE SIZES SHALL BE THE SAME UNLESS NOTED OTHERWISE. 0-, = CD- MAIN TO TERMINAL DUCT:THIS IS A BRANCH DUCT;TYPICALLY THE DUCT FROM THE MAIN TAKEOFF TO THE TERMINAL(VAV BOX OR EQUIVALENT). 8.AFTER INSTALLATION,ADJUST DIFFUSERS,REGISTERS AND GRILLES TO AIR PATTERNS INDICATED,OR AS DIRECTED,BEFORE STARTING AIR BALANCING. ® Q TERMINAL TO GRD DUCT:THIS IS A BRANCH DUCT DOWNSTREAM OF THE TERMINAL(VAV BOX,HEAT PUMP,FAN COIL OR EQUIVALENT). WHERE CFM IS INDICATED ON PLANS FOR RETURN AND TRANSFERS,BALANCE TO AIRFLOW INDICATED. L.r) INDOOR:DOUTSIDE UCT R E LOCATIONS WITHIN THEMPERED:TEMPERED WE WEUTS AIRIS Al tylA ENVELOPE. T IS Lill ED OR COOLED TO WITHIN 10 DEG F OF THE SPACE/SURROUNDING TEMPERATURE. g 1 U OUTDOOR:DUCT LOCATIONS OUTSIDE OF THE INSULATED BUILDING ENVELOPE(ON GRADE,ROOF,EXTERIOR SOFFIT,EXTERIOR CHASE,ATTIC,CRAWLSPACE,ETC.). i 1 SPECIFIC NOTES: E ® 05/04/2020 1.PROVIDE SMALLEST FACE AVAILABLE FOR NECK LISTED IN PLANS U D 2.PROVIDE DAMPER FOR A DUCTED RETURN/TRANSFER AIR SYSTEM THAT REQUIRES AIR BALANCE AT RETURN/TRANSFER OPENINGS AS INDICATED BYASPEN ST c BUILDING DEPARTMENT 03- AIRFLOW(CFMs)ON DRAWINGS. c 3.AS IDENTIFIED ON THE PLANS PROVIDE 12"x24"FACE FOR 10"x22"NECKS,PROVIDE 24"x24"FACE FOR 22"x22"NECKS "Cf) 5 4.PROVIDE BACKPAN WHERE CONNECTED TO DUCT OR SOUND BOOT;WHERE NOT DUCT OR SOUND BOOT IS PRESENT PROVIDE PERFORATED PANEL ONLY. 5.FOR THE INLET(NECK)SIZE CALLED FOR ON THE PLAN PROVIDE THE FOLLOWING BACKPAN SIZES:6"(9x9"),8"(9x9"),10"(12x12"),12"(15x15") CsO C L M 7 PUMP SCHEDULE 0 c ITEM TYPE SERVICE GPM GLY. TOTAL EFF MOTOR DATA OP MANUFACTURER NOTES CON- L) ll L HEAD HP RPM V-PH STRTR WGT &MODEL NO. TROLS as Cl FT.W.C. LBS ® N P- IN-LINE DHW GENERATOR ' 29 30 20.0 ME 0.5 1750 120-1 VFD 77 B&G SERIES E-601.25X1.25x5.25 2 DDC NOTES: Issue Date: 1.PROVIDE 24/7 DIGITAL TIMECLOCK WITH AQUASTAT 07/18/2018 Permit Set 2.PROVIDE DISCONNECT 02R8/2019 Building Pemnit Resubmigal DOMESTIC HOT WATER GENERATOR(WATER TO WATER) DOMESTIC WATER HEATING WATER ELECTRICAL DIAMETER TANK STORAGE OP.WT. ITEM IN. ORIENTATION LENGTH IN. GAL. EWT LWT GLY WPD LBS. MANUFACTURER&MODEL NO. NOTES CONTROLS GPH EWi°F LWT°F GPM °F "F % F7 VOLT PH ST-2 46 VERT 88 400 340 40 140 29 180 160 30 10 120 1 4517 PVI 700L400AQWD-13AGH-180 1,2,3 DDC SPECIFIC NOTES: 1.PROVIDE DOUBLE WALL HX FOR HEATING WATER.UNIT TO INCLUDE TAP FOR TC THERMOMETER WELL. 2.PROVIDE ACCESSORIES,ALARM AND COMMUNICATIONS PACKAGE. 3.PROVIDE WITH INTRA-TANK CIRCULATOR.120V,20 AMP CIRCUIT o�pg11. </pe" ELECTRIC HEATER SCHEDULE �'0�"�°`%:e C3'� �: (� CAP. AIR MANUFACTURER& y'3t) ITEM TYPE KW AMPS V-PH CFM EAT LAT MODEL# NOTES CONTROLS OF• <'=!(('' 'PA F F ECH-1 CABINET UNIT HEATER 4.0 19.2 208-1 250 50 90 QMARK MCSSAR4808 1,2,3 8 Z.-=6-/9 NOTES: 1.PROVIDE UNIT MOUNTED DISCONNECT. 2.INTEGRAL THERMOSTAT. Drawing Title: 3.WALL FLUSH MOUNT.COLOR SELECTED BY ARCHITECT MECHANICAL SCHEDULES Date: March 16,2018 Project No: 2018.01.0077 Drawn by: MJK Checked by: MJK Sheet: M5.0 ©2018/2019 PIERCE FRYE ARCHITECTS M ( ( "' CONSULTING MINERS,INC �IMEG Mechanical,Electrical& ASHRAE STANDARD 62.1-2013/ IMC 2015 VENTILATION RATE PROCEDURE CALCULATIONS Energy Consultants OCCUPANT OCCUPANT BREATHING TABLE 6-2 ZONE TOTAL SUPPLY SYSTEM OUTDOOR AREA DENSITY OVER-VENTILATION ZONE AIR AIR TO ZONE AT ZONE VENTILATION MINIMUM MINIMUM UNIT FLOOR ROOM ROOM NAME ZONE TYPE AREA AIRFLOW OUTDOOR PEOPLE OCCUPANT PERCENTAGE OUTDOOR DISTRIBUTION CONDITION VENTILATION EFFICIENCY PERCENTAGE OUTSIDE AIRFLOW NUMBER SQ FT RATE AIRFLOW RATE PER 1000 QUANTITY AIRFLOW RATE EFFECTIVENESS ANALYZED EFFICIENCY NOTE 2 AIRFLOW AT AT UNIT CFM/PER CFM/SO FT SQ FT CFM (Ez) CFM-NOTE 1 (Eva) (Ev) UNIT NOTE 3 PIERCE (E)AHU-1 B07 LOWER HALL Corridors 108 0.0 0.06 0 0 0% 6 1.0 125 1.18 0.67 - - B01,02,03,05 LOWER DRY/GENERAL STORAGE Storage rooms 718 0.0 0.12 0 0 0% 86 1.0 1140 1.16 0.67 - - + FRYE 108 DINNING AREA-3A Restaurant dining rooms 89 7.5 0.18 70 6 0% 63 1.0 200 0.92 0.67 - - 108 DINNING AREA-3B Restaurant dining rooms 72 7.5 0.18 70 5 0% 51 1.0 125 0.83 0.67 - - 107 ENTRY STAIR Main entry lobbies 40 5.0 0.06 10 0 0% 4 1.0 75 1.17 0.67 - - ARCH I T E C T S 106 DINNING AREA-2 Restaurant dining rooms 350 7.5 0.18 70 25 0% 247 1.0 990 0.98 0.67 - - 105 DINNING AREA-1 Restaurant dining rooms 137 7.5 0.18 70 10 0% 97 1.0 330 0.94 0.67 - - 104 BAR Bars,cocktail lounges 153 7.5 0.18 100 15 0% 142 1.0 300 0.76 0.67 - - 111 UPPER KITCHEN Kitchen(cooking) 900 7.5 0.12 20 iS 0% 243 1.0 435 0.67 0.67 - - San Francisco Office 0 CORRIDOR-1 Corridors 53 0.0 0.06 0 0 0% 3 1.0 75 1.19 0.67 - - Tel:415.392.4433 0 CORRIDOR-2 Corridors 196 0.0 0.06 0 0 0% 12 1.0 300 1.19 0.67 - - 101102 HOST/ENTRY Main entry lobbies 80 5.0 0.06 10 1 0% 9 1.0 150 1.17 0.67 - - Vail Office 103 BAR SEATING AREA Bars,cocktail lounges 77 7.5 0.18 100 8 0% 72 1.0 215 0.90 0.67 - - Tel:970.949.0899 (E)AHU-1 ITOTALS 1 I 4460 I - I 0.67 I 34% 1 1536 www.PlerceFrye.com info@PierceFrye.com SPECIFIC NOTES: 1.TOTAL SUPPLY AIR AT CONDITION ANALYZED USES THE MAXIMUM AIRFLOW PROVIDED TO THE ZONE DURING THE HEATING OR COOLING MODE,WHICHEVER IS BEING ANALYZED. 2.AS DETERMINED USING THE ASHRAE 62.1-2010"62 MZ Cale"SPREADSHEET.SYSTEM VENTILATION EFFICIENCY IS EQUAL TO THE LOWEST ZONE VENTILATION EFFICIENCY OF ALL ROOMS SERVED BY THE UNIT. Unit Outside Airflow Balance Setpoint[cfm] 1800 3.SEE UNIT EQUIPMENT SCHEDULE FOR ACTUAL OUTSIDE AIR SETPOINT FOR BALANCING;WHICH WILL MEET OR EXCEED THE MINIMUM REQUIREMENT NOTED HEREIN. Unit Meets ASHRAE 62.1 Requirements Yes C s.O 4.OCCUPANT QUANTITY MAY VARY FROM OCCUPANT DENSITY FROM IMC.IN THOSE CASES OCCUPANT QUANTITY IS ADJUSTED TO MEET DATA PROVIDIDED BY THE CLIENT.THIS IS ACCEPTABLE PER IMC 403.3 EXCEPTION. -0 co " OCCUPANCY RATES GREATER THAN CODE NOTED WITH AN BOLD UNDERLINE.OCCUPANCY RATES LESS THAN CODE NOTED WITH AN BOLD DOUBLE UNDERLINE. Existing AHU-1 Minimum OSA-1800 CFM = 0 Existing AHU-1 Maximum OSA-2430 CFM L ad O 0 LI U Ws E al ' ® Q Lrj RECEIVED I v 05/04/2020 a u D ASPEN BUILDING DEPARTMENT = 7 c cu j Q FAN SCHEDULE ITEM TYPE AREA SERVED CFM ESP DRIVE SONES BHP MOTOR DATA STRTR OP WT LBS MANUFACTURER&MODEL NO. NOTES CONTROLS INWC TYPE H.P. RPM V-PH EF-4 INLINE LL_STREET 475 1.60 BELT 18.0 0.5 3/4 1703 115-1 -- 208 COOK 14CVB 1 5 "- LL M as NOTES: 0 cV 1.PROVIDE DISCONNECT,SPRING ISOLATORS,FLEXIBLE CONNECTION ON INLET AND OUTLET. Issue Date: 0711812018 Permit Set 02128/2019 Building Pemnit Resubmittal 04110/2019 PC3 Building Permit Re-submittal Simd v;.4;V �3%N J pF"Y�J"o 4-10-2019 Drawing Title: MECHANICAL SCHEDULES Date: March 16,2018 Project No: 2018.01.0077 Drawn by: ARD MJK Checked by: ARD MJK Sheet: M5.1 02018/2019 PIERCE FRYE ARCHITECTS MKCONSULTING rK °`RS,INC +IMEG Mechanical,Electrical& FLAG NOTES (THIS SHEET): Energy Consultants 1. SUPPLY GRILLE.REFER TO GRD SCHEDULE ON DRAWING M5.0 FOR MORE INFORMATION. 1 2. EXISTING GRILLE.REFER TO GRD SCHEDULE ON DRAWING M5.0 FOR MORE T T P I ERCE INFORMATION. 3 T ® r-c) + FRYE 3. EXISTING VAV BOX VAV-H.REFER TO SCHEDULE ON DRAWING M5.0 FOR MORE INFORMATION. A ARCHITECTS 4. FINAL EXHAUST DUCT VERTICAL ROUTING TO BE FIELD VERIFIED WITH EXISTING CONDITIONS. San Francisco Office 5. EXISTING EXHAUST DUCTWORK TO TO ROOFTOP TERMINATION TO REMAIN. 0 Tel:41.5.392.4433 Fl LDVE-FY : T OC-.TIO A D ON EC 10 Vail Office 6. ROUND DUCT TAKE-OFF FITTING,REFER TO DETAIL ON DRAWING M4.0 FOR A Tel:970.949.0899ilil MORE INFORMATION,TYPICAL. FS 1P/g UP www.PlerceFrye.com 1111 4/8 • 7. MOUNT THERMOSTAT AT 48"A.F.F. � r 4 10X6 info@PierceFrye.com 8. EXPANSION TANK ET-5.REFER TO SCHEDULE ON DRAWING P5.0 ANDAt _ I1� 220 SCHEMATIC ON DRAWING M4.1. , I \ '4"2 I 9. HOT WATER GENERATOR ST-2.REFER TO SCHEDULE ON DRAWING M5.0 AND - I I III I 8„O — SCHEMATIC ON DRAWING M4.1. III CO 10. HYDRONIC PUMP P_4.REFER TO SCHEDULE ON DRAWING M5.0 AND SCHEMATIC 1175 Z h a II11111 1 1 .I111111 ON DRAWING M4.1. EF 4 0 11. DOMESTIC HOT WATER RECIRCULATION PUMP RCP-2.REFER TO SCHEDULE ON " • 24/14 U DRAWING P5.0 AND SCHEMATIC ON DRAWING M4.1. III , imilir 10 ld -� — — — PII — 0 . N °N 1i11i1i11i1i11i1i1111i11i1i11iii1 NM — — 0— = 0- GENERAL NOTES (MECHANICAL): �µ I� 7 A. ALL EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S WRITTEN I.O.M. — 0 ly 1111111 _ -- —® ` INSTRUCTIONS WITH ALL REQUIRED CLEARANCES MAINTAINED. P ICJ 10X6 DESK ©(E)V. 7 O 10"Q rr''``�.. B. ALL EQUIPMENT IN MECHANICAL ROOMS SHALL BE PR� q/ I 0 220 L.... 0 1 — 0 i c49 HOUSEKEEPING PAD UNLESS NOTED OTHERWISE.EX-MOOED,ED, — — — — r IT — '` , I• __/_'� �c — — — — — — C EQUIPMENT SHALL BE PROVIDED WITH 4"HOUSEKEEPING �11 }}��NNL $$�spp��TTAILED ® u D OTHERWISE BY THE STRUCTURAL ENGINEERING DRAWIN�9��"4 "1" IE EXIT T .11 6X6 - C��p �S PERO C. FIELD COORDINATE EXACT ROUTING OF DUCTWORK WITH EXIS'HN pp!! I OHS. 4.7.�' 75 F. BUILDING DE AT2IMEN�1 — ia it /1t'182I 1 c D. NOT USED. 1 — ,Ili�- it liiii - j D. NOT USED. LS LJ 2 ., 1 E. NOT USED. E�IT -ii -T I J 36/16 CZ C —Pans CU] I 9 I (:),„ �I T C 1 \ JJJ J C 4 F1 B^0 J ® N H a l a 1 iOO I I I r\C _ F Issue Date: 0711812018 Permit Set — / I 02/282019 Building Permit Resubmitlal / �I \ I 1 O \\,,. \ (E)EXISTING`\ 30/14 ET-5 /` (N.I.C.) TRANSFER L� Dom __ D( ) \ / 1 OPENING �XX I I I 13 •XXX\� X)XXX XXXXXXXX EIq�zIT IN) F O � FS C I FS / 1 \ E • Hws�-Z I (/ i I (E)EXISTING L nl XTURE - HWR�-� SPA MECH. o —0 \u----i4 o I\ / II 14/8 \ (N.I.C.) w% w 1J o�p(tADOti�F2. = 1. c,.....7N.Jpfj•2,9 P� zu (E)RCP-1 1 1 1 1 1 F0 c' -....-- C 04 Fr, \`I ACCESS t SS 1 (.... rixS = PANEL IIE AI, /(� — — 7ID 2x2 (El (El IF�2x2 IEk1( IEI 2x2 Z,-:,r LEDI?I AC ACCESS LLUI'!I )ASSAGE LEDI?I J rr -III I FIXTURE P �/AV 8 PANEL FIXTU 300 CFM FIXTURE I`'1U (E) 1 i r \ SMOKE GUARD �� —_ Drawing Title: 180W / �E�F-X-,� IEI LOUIER LEVEL x\ Iv l I� `\\ — 1 FS 1 L e MECHANICAL PLAN 1 LOWER LEVEL MECHANICAL PLAN MECHANICAL ROOM PASSAGE FS (2)-) SCALE:1/4"=1'-0" IEI EXIT CAR LIFT Date: March 16,2018 ACCESS ACE IEI E BY (N.I.C.) (I F Protect No: 2018.01.0077 °z Drawn by: MJK T _ — — — — — — — p,q Checked by: MJK j IT �� e Sheet: AIRar , 2 LOWER LEVEL MECHANICAL PLAN — PROPOSED ,,,,,,\ M1 .0 SCALE:1/4"=1'-0" ©2018/2019 PIERCE FRYE ARCHITECTS MKCONSULTING IK °`�IMEG \ Mechanical,Electrical& O Energy Consultants (� T T T 5.5 T -- PIERCE FLAG NOTES (THIS SHEET): + FRYE 1. SUPPLY DIFFUSER.REFER TO GRD SCHEDULE ON DRAWING M5.0 TO I T -I 1 FOR MORE INFORMATION.TYPICAL. STREET 1 I ARCHITECTS 1 11 1 ^ , 2. RETURN GRILLE.REFER TO GRD SCHEDULE ON DRAWING M5.0 AND I / \ SOUND BOOT DETAIL ON DRAWING M4.0 FOR MORE INFORMATION. 12/8 DNOg 8"0 1 1 / \ TYPICAL. ik 1 0 215 1 // T San Francisco Office 12/8 / Tel:415.392.4433 3. EXISTING VAV BOX VAV-#.REFER TO SCHEDULE ON DRAWING M5.0 I \ J - -- ,-� —f, 1= 0 t140 I., - 1 \\ - - Vail Office FOR MORE INFORMATION.TYPICAL. EXIT _ - Tel:970.949.0899 EF O4co 4. ROUND DUCT TAKE-OFF FITTING,REFER TO DETAIL ON DRAWING �.�IE���I 215 \� 150 /T www.PleroeFrye.com M4.0 FOR MORE INFORMATION,TYPICAL. - "'— Q Ii ��raI 1111,_ I 8"H ¢ COAT �� �� // A\ inROOF rceFrye.coer Ill�j _ _ --:� F o2lHosr 1 Ne 5. MOUNT THERMOSTAT AT 48"A.F.F.TYPICAL - � �_ III, I --iiii 8X8 / A,2 0 200 A BAR SEATING AREA 5 / 'I / - -\� 6. RELOCATED THERMOSTAT,MOUNT AT 48"A.F.F. _ ��.'3 8"! � II le,. . EXIT \ _ ___ 7. RELOCATED RETURN SLOT DIFFUSER. v •-�• 'i,� 6"3 r0 /> MIMI 8. ELECTRIC CABINET HEATER ECH-1.REFER TO SCHEDULE ON - I == rJ � i\.! _rai; / / "= O 6"e `erg 24x24 O ECH-1 DRAWING M5.0 FOR FURTHER INFORMATION. D 8X8 0 75 Bil / `� \ // IM rr, _ __ 'y�` M2pp • - @� 9. FINAL EXHAUST DUCT VERTICAL ROUTING TO BE FIELD VERIFIED e - - - _■I - �-- - pi-_© -�- © • - , - �Lp - AS WITH EXISTING CONDITIONS. • 8"0"e r^'_________-_-_-_ Nil U sLY 10. 45°DUCT TAKE-OFF FITTING.REFER TO DETAIL ON DRAWING M4.0 - ON UP _ '' ■ - 'rye 8 0rci a) FOR MORE INFORMATION,TYP. �I I 111,{HN�I !Ell IiUIR — J1111 III���1i:9i' (E)VAV3 S�AR � _»r�l _;.I 1' ¢ 1 zaxz 5 I- Q 3r� �I{�I,'r, \W�I ni'lli I �r°165 EMIEI 220 _III,,J C , 8„a G NB(ALTEIN (MECHANICAL): I / — — A. N I U IEI I STA9 A ��d (E)12"O N U c49 A. ALL EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S WRITTEN EYJT / ® I�..II `� 8"0 ® CI)CA U E I.r5 fF l$QzOS WITH ALL REQUIRED CLEARANCES MAINTAINED. r S- I V I C ��1 B. FIELD jNATE EXACT ROUTING OF DUCTWORK WITH EXISTING A 5 IN 11 1���,�1 0 ' I r�6 I 8"e ffAILV4INPS VPARTMENT _ I a°e- 1-"....... 3 osIoININc AREA s C. EXACT DIFFUSER LOCATION TO BE COORDINATED WITH THE ARCHITECT. n �I� �....( 165 r 0 8"0 �_ �$O _ ��ICS,.��� a �; ,�\ zzo - I Io 8500 Iii / --1,--, gyp, I►1so p e"° tel: �_ (E)ELEVATORP2 J 165 L 2 7 O SlAt:GUARD p i I� ) 24x2 B 7 08 IpB "� �J OVE ¢ III 6 0 IE III 8"0 as I 8.O I a* 165 III 0 zzo s BOO I ,� ® c� it � = M Issue Date: 07/18/2018 Permit Set El 8„g Z UP4R ' - 02/28/2019 Building Pamit Resubmitlal 1 3 I DI S"0 TO VAV-3 e 20. .. fillI O r_tI 24 (E)VAVI2 j__ II 11IO 1 --- I • 3 (E)VAV-4 — - / • (E)RESID':NCE HALL / (N..C.) 2) II„V � .4111 W Id L� (E)VAV-5 / (E)RESIDENCE gADO N1�. O tip ❑ . I / ACCESS ,,C)o.N.r'If.. I Ar i O� ofUa�0 $ ® (E RESIDENCE \ i tr � ® 0 �ESIBULE \ r ;•' "7 - 1 NLC) v (E)ELEVATOR Al (E)ELEVATOR n ACCESSI: E UNISEX \\ 11 LOBBY UNISE I ��STROOM \ Z I y (N.LC.) (NLCj SMOKE GUARD �I NI Drawing°HOVE /� X gTitle: —r - _ �7 ' J O STREET LEVEL I' X _ MECHANICAL N F PLAN 1 STREET LEVEL MECHANICAL PLAN - PROPOSED Date: March 16,2018 SCALE:1/4"=1I-0" Project No: 2018.01.0077 /\ H Drawn by: MJK >N Checked by: MJK e Sheet: M2.1 ©2018/2019 PIERCE FRYE ARCHITECTS (i--) E ' c'l T 2.i--) T T 4.5 T 5.5 O MKK CONSULTING ENCINFFRS,INC ,IMEG Mechanical,Electrical& Energy Consultants 0 STAIR BELOW A PIERCE 0 0 FLAG NOTES (THIS SHEET): + FRYE � 1. EXISTING EXHAUST TERMINATION TO BE REUSED FOR GENERAL KITCHEN AND JANITOR MOP SERVICE BASIN EXHAUST.SEE PENTHOUSE ATTACHED IMAGE FOR REFERENCE. - -- -. TERRACE BELOW ARCHITECTS 2. NOT USED. 0 I II I 'i IiI 0 3. NOT USED. San Francisco Office Tel:415.392.4433 PENTHOUSE ,. ON STAIR"2 4. NOT USED. TERRACE BELOW Vail Office I I I 5 NOT 970.949.0899 nn S. USED. Tel: fi.1 — — — -' _ ,(It_•_•_�II 11 ter_=.�. ••yL _ p••••y1L-_IL� � «.fY--_ ---= � ___ �_ � � ,]F- ' � — — — Q 6. NOT USED. www.PeroeFrye.com info®PierceFrye.com E)ELEVATOR ' 7. NOT USED. 61 cXHAUST FAN _� (E)PENTHOUSE_7 FIREPLACE 8. NOT USED. I r_,J VENT = NO A CO 0 = O (E)PENTHOUSE xll J O •`� AT.DISH& \-y (E)ELEVATO ncs O BASE RELIEF VENT - -21 l• 0 OL 1 ate—+ 0— c rtn __ (E)PEVTHOUSE e _ 'a1 ® Q --- CONDENSING _ UNIT LA RECE VED (E)36116 H g A I MUA DUCT s E ,p' 05/04)2020 STUB-UP ° D $ ASPEN — 0 — — �_ —Fo IA— O i'2 C c ai BUILDING DEPARTMENT (E)PENTHOUSE t MUAAli E .:,,,),7) I r (E)BOILER FLUE �� ,/�i� Q by Yim it Fib �T r1-0 J i I• c-1 6 n w n (E)ELEVATO is 0") L —(E)PENTHOUSE Irl RELIEF VENT 0 N FIREPLACE (E)ELEVATOR i'1 VENT EXHAUST FAN 1 D .t 6 .•i r D Issue Date: �- (E)PENTHOUSE 07/18/2018 Permit Set 02/28/2019 Building Permit Resubmigal RANGE HOOD — Id EXHAUST • m =' t II I, D.4 — -- — uL �— —� — en --_L___n�e —J — — — 0 F PENTHOUSE TERRACE BELOW 57AIR fl I I I I II DN �I I I I D.5 _ __ D.5 -!--fir" ld -'".. .. .. '" .. .. `- ... .. : __1_=„wr__„__,'+r , PENTHOUSE til :,-4 -' : TERRACE BELOW E 1u mF G N�j0• yj• D.8 U j D.8 f•`•"� F��S3 L — J .. -. .. .. .. -. oFes/04 .:. L--16-ICI I I I I Drawing Title: I 1.5 3 2 2.5 3 0 0 5 5.5 0 ROOF PLAN Date: March 16,2018 A Project No: 2018.01.0077 l 1 MECHANICAL ROOF PLAN p� Drawn by: ARD MJK I SCALE:3116"=1'-0" Checked by: ARD MJK e Sheet: M2.2 ©2018/2019 PIERCE FRYE ARCHITECTS M i °`CONSULTING ENCINFFRS,INC +IMEG SUSPEND FROM STRUCTURE USING 2 STRAPS. TYPICAL OBTRUCTION TO DUCT PATH Mechanical,Electrical& FIBERGLASS DUCT OR Energy Consultants SHEET METAL BOOT W/1" DUCT LINER.MINIMUM SIZE =12x24. ROUND OR RECTANGULAR II DUCT,TYPICAL NO TURNING VANES. } � 1U° MA � MAX Mi,X PIERCE AIRFLOW + — + FRY E IM 2/3 D" 12"MIN. ARCHITECTS ELEVATION VIEW f RETURN GRILLE San Francisco Office TYPICAL OBTRUCTION DO NOT TRANSITION DUCT Tel: 2.4433 TO DUCT PATH TO SIDE,TYPCAL Vail Office DUCT DIM Tel 970.949.0899 RETURN AIR GRILLE (SEE PLAN) DTR UP TRANS. y SOUND BOOT infm9PierceFrye.com NO SCALE DEPRESSED DUCT (SEE ELEVATION VIEW) PLAN VIEW NOTE:USE DETAIL WHERE REQUIRED BY FIELD CONDITIONS. = DUCT"VENTURI" DEPRESSION DETAIL ▪ co NO SCALE . =▪ 0 • Q USE GASKETED FITTING. USE DUCT SEALANT OR ATTACH PER MANUFACTURERS GASKETED FITTING. `ry 6 TD 14MINIMUM.OFR RECOMMENDATIONS. = U LATERAL TAKE-OFF FITTING ROUND TWIST-IN FITTING 'aS E. WI MANUAL DAMPER, �..r WI MANUAL DAMPER, �, e' (Z HANDLE,&LOCK NUT. HANDLE,8 LOCK NUT. 10,4,, 001 FLE%DUCT FLEX DUlI CT Q RECEIVED i, 4 j; F D r ' WORM DRIVE S.S. ® ®d E 05/04/2020 /" WORM DRIVE S.S. CLAMP(ONINNER 6..d D (MANUAL VOLUME i LINER)(ON INNER LINER). C ASPEN DAMPER. Sa BUILDING DEPARTMENT SEAL AIRTIGHT E 72 2 AROUND ENTIRE V) TAKE-OFF. LATERAL TAKE-OFF FITTING SPIN-IN FITTING ) j 45° DUCT TAKE OFF ROUND DUCT TAKE-OFF FITTINGS NO SCALE NO SCALE a) L M 7 121.0 1 C "I Y Lll ®• N Issue Date: 07/18/2018 Permit Set 02128/2019 Building Posit Rewbmidal z-,z-Iq Drawing Title: MECI-IANICAL DETAILS Date: March 16,2018 Project No: 2018.01.0077 Drawn by: MJK Checked by: MJK Sheet: M4.0 02018/2019 PIERCE FRYE ARCHITECTS VIKK "`+IME� Mechanical,Electrical& 120'DHW Energy Consultants a a II SETUP VALVE DOMESTIC HW RECIRCULATION PUMP (RCP-1) 15" PIERCE TYP. OF 2FRYE 140'DHW 1 DPS THERMOMETER MIXER MASTER 120°DHW RECIRC P=1 SNOW MELT .= MI (TYPICAL) WMV-1 I r ..�3 ARCHITECTS SMR CAS RELIEF VALVE 3 UNION HEAT TRAP ,0 - N C T C� (TYPICAL)�� ON INLET 0 San Francisco Office .4 AS 3 a Tel:415.392.4433 BYPASS �_ AIR SEPARATOR T. 3„ TEMPERATURE SENSOR TOE Vail Office Z SMS Il I� .. { N.C. DDC SYSTEM �/ Tel:970.949.0899 �3 /1 _ L E _ i'�� www.PlerteFrye.tom Ni `d 3 info®PierceFrye.com c. I o (EXISTING) _i_l__LR1 fff,,,111 HOT WATER Iil 1 t 3 GENERATOR SNOW MELT o0 I o' ,,,L. m. °5• 0 O i x 1 R - i 0 .. VFD o CHEMICAL POT FEEDER ASSEMBLY 1 L ' BYPASS i- X _NI, T HWR �_ J E III EXPANSION TANK CW MAKE-UP erg U REFER TO DETAIL. IT , ill HWS ETET 4 _ u � Gill = - `5� - "- `- �� • BALL VALVE -, eL ET-3 GF-3 HTX-1 I (TYPICAL) EXPANSION GLYCOL FEEDER SNOW MELT PLATE AND ® Q 8, TANK FRAME HEAT EXCHANGER, $ T -r FINISHED FLOOR CHECK VALVE RECEIVEDP=3 PUMP (TYPICAL) i a 05/04/2020 CA u D ASPEN c a BUILDING DEPARTMENT AIR VENT, -0 = TYP. 2" c HWR HWR r CU > -/ 2 > PRESSURE CIII - 7� 2" _ ) CZ C 12" 5" SWITCH, TYP. . J. .. 140"DHW C AS-1 AIR m TEMP. �l MAX. M1, �N: SEPARATOR i II SETUP VALVE ,a/SENSOR _ICJ DOMESTIC HW RECIRCULATION M = HWS TEMP. B YPASS PUMP RCP-2 1 ( �, 18" ,�, SENSOR TO ST-1 C V, A_ MIN. / HWS 0 L1J 5 140°DHW D4 MASTER • II t� t4„ THERMOMETER MIXER - II fV___ 140°DHW RECIRC 0 (TYPICAL) WMV-3 —II ICI I • AO Z ...--14" CHEMICAL POT FEEDER Issue Date: 1 I A UASTWIRED FOR AT EGH 07/18/2018 Permit Set I Q HEAT TRAP LIMIT CONTROL.SET AT 120°F 02R8YL019 Building Pemnit Resubmigal ON INLET z WITH 5°RANGE 111 UNION / ` SAFETY RELIEF VALVE, WALL DISCONNECT SWITCH,COORDINATE 1 00 (TYPICAL) EXTEND FULL SIZE INSTALLATION WITH DIVISION 26 1 DRAIN TO FLOOR DRAIN CONTRACTOR Ill Ill qi - O . 3 AND DISCHARGE WITH 0. L L C4' _ I A_ __ 2"AIR GAP. �"��r _ I . / HOT WATER IIDo- )----- �___, \ E /1 GENERATOR I = I /\I s TEMPERATURE SENSOR TO ST-2 (EXISTING) 8=2 (EXISTING) GF-1 HDP-1 HDP-2 DDC SYSTEM ig B=1 CONDENSING BOILER CONDENSING BOILER GLYCOL FEEDER ET-1 HEATING HEATING / i 30%GLYCOL EXPANSION WATER WATER TANK. DISTRIBUTION DISTRIBUTION g�rr�� I PUMP PUMP XHWR )T -� VF g �_ :, , g HWS ] � � EXPANSION TANK CW MAKE-UP �V��E N.JOfr SF BALL PICAL f�rlpo:"" 47' - '�/Y I �4 (TYPICAL) r 9S,•...... '7,.,,% L'1 4 c,,,. 1-' FINISHED FLOOR )) CHECK VALVE Z,`(_Iq (TYPICAL) HEATING WATER SCHEMATIC -TUBE-PULL INSACCESSLS AREA,SO UNIT IS Drawing Title: TO BE INSTALLED SO THAT THIS NO SCALE AREA REMAINS CLEAR SO THAT TUBE BUNDLE MAY BE REMOVED WITHOUT -1"DRAIN VALVE,EXTEND 1"DRAIN FROM VALVE TO FLOOR � I I MODIFICATIONS TO BUILDING OR DRAIN AND DISCHARGE WITH 2"AIR GAP. MECHANICAL OTHER EQUIPMENT INSTALLATIONS. CONNECT PER MANUFACTURER'S SCHEMATICS INSTRUCTIONS. Date: March 16,2018 Project No: 2018.01.0077 Drawn by: ARD MJK Checked by: ARD MJK Sheet: M4.1 ©2018/2019 PIERCE FRYE ARCHITECTS M i °`+IMEG Z GENERAL CONTROL NOTES: or Mechanical,Electrical& 1. THE CONTROL DRAWINGS AND SEQUENCES OF OPERATION DEPICTED SHOW THE DESIGN INTENT FOR CONTROL Energy Consultants m OF THESE SYSTEMS.THE CONTROLS CONTRACTOR SHALL PROVIDE ALL ADDITIONAL SENSORS,DAMPERS, 3 —— ACTUATORS,CONTROLLERS,WIRING,AND APPURTENANCES AS REQUIRED TO ACHIEVE THE DESIGN INTENT. x CLOSE COORDINATION WITH THE SELECTED EQUIPMENT MANUFACTURERS SHALL BE REQUIRED. HEATING WATER PUMP ON THE INLET OF DOMESTIC WATER GENERATOR,P-4 RCP-2 SHALL MODULATE TO MAINTAIN A 140 DEG.F.DOMESTIC HOT WATER ME HW RECIRC PUMP 2. MANY OF THE INDICATED CONTROL POINTS ALONG WITH UNIT SAFETIES MAY BE PROVIDED WITH ANY SPECIFIED SUPPLY TO THE BUILDING.IF THE DOMESTIC WATER SUPPLY TEMPERATURE " ———— EQUIPMENT THAT USES PACKAGED SYSTEM CONTROLS.THE CONTROLS CONTRACTOR SHALL COORDINATE FALLS BELOW 95 DEG.F,AND ANY PORTION OF THE BUILDING IS IN PIERCEOCCUPIED MODE,AN ALARM SHALL BE INDICATED AT THE EXISTING CENTRAL DDC WITH THE SELECTED UNIT MANUFACTURERS TO ENSURE THAT THE DESIGN INTENT IS ACHIEVED. FACILITY STATION.HOT WATER GENERATOR SHALL OVERRIDE BOILER RESET IF SETPOINT x Illgillild 3. THE CONTROLS CONTRACTOR SHALL COORDINATE AND FURNISH WELLS,VALVES AND SWITCHES FOR + FRYE INSTALLATION IN MECHANICAL SYSTEMS. DROPS BELOW 130 DEG.WITH 5 DEG.RANGE. 4. ALL SET POINTS INDICATED IN THE SEQUENCES SHALL BE ADJUSTABLE. AECIRCULATION PUMP RCP-1 SHALL RUN BASED OFF OCCUPIED/UNOCCUPIED ARCH T E C T 5 SCHEDULE AND INTERLOCKED WITH AQUASTAT WIRED FOR HIGH LIMIT CONTROL. 5. THE CONTROLS CONTRACTOR SHALL COORDINATE WITH THE FIRE ALARM CONTRACTOR TO ENSURE PROPER ENT(WHERE SET AT 140 DEG.WITH 5 DEG.RANGE. STAT INTERFANDACECOMBINAHTI WIT TH ONE FIREFIRE/SMOKE ALARM SYSTEM.RI INTERFACE ITH DUCT/REQUNIT UOKE p� DETECTORSUS TEMPERATURE W CONTROL IE SRSMOKE a- PRESENT). San Francisco Office '' —— 6. THIS PROJECT SHALL UTILIZE AN EXISTING HIGH-SPEED NETWORK USING BACNET PROTOCOL OVER IP Tel:415.392.4433 COMMUNICATIONS BETWEEN THE TRENDING SERVER,BUILDING CONTROLLERS AND THE WORKSTATIONS. Vail Office MOZM SUB-NETWORKS SHALL BE USED FOR COMMUNICATION BETWEEN BUILDING CONTROLLERS,CUSTOM Tel:970.949.0899 VFD ST-2 APPLICATION CONTROLLERS AND APPLICATION SPECIFIC CONTROLLERS. MEM DOMESTIC HOT WATER GENERATOR 7. THIS CONTRACTOR SHALL PROVIDE ALL COMMUNICATION MEDIA,CONNECTORS,REPEATERS,HUBS,AND www.PlerceFrye.com ROUTERS NECESSARY FOR THE DDC SYSTEM TO COMMUNICATE WITHIN THE BUILDING. info@PierceFrye.com l'43(E5V IZM 74017 8. THE CONTROLS CONTRACTOR SHALL COORDINATE CLOSELY WITH THE ELECTRICAL CONTRACTOR TO ENSURE ALL BUILDING AUTOMATION SYSTEMS CONTINUE TO RUN ON POWER FAILURE.WHERE CONTROLLERS ARE NOT FED FROM A BUILDING WIDE U.P.S.CIRCUIT ALL CONTROLLERS SHALL BE PROVIDED WITH LOCAL U.P.S. SYSTEMS TO ENSURE CONTINUED OPERATION,INCLUDING REMOTE CONNECTIONS FOR OFF SITE ALARMS, ST 2 CONTROLLER UNTIL GENERATOR POWER IS PROVIDED(OR NORMAL POWER IS RESTORED). - BINARY INPUTS BINARY OUTPUTS 9. THE CONTROLS CONTRACTOR SHALL COORDINATE CLOSELY WITH THE ELECTRICAL CONTRACTOR TO ENSURE CO BI- PFST PUMP 4 STATUS BO- PFSS PUMP 4 START STOP PROPER STATUS INTERFACE WITH ATS(S),ELECTRICAL USE METER(S),AND OTHER DEVICES TO MONITOR `5 BI- VFDALM VFD ALARM BUILDING POWER STATUS. IM iz IC. THE CONTROLS CONTRACTOR SHALL COORDINATE WITH THE ELECTRICAL CONTRACTOR TO PROVIDE d) 0 ANALOG INPUTS ANALOG OUTPUTS ADDITIONAL 120V ELECTRICAL CIRCUITS AS REQUIRED FOR THEIR SCOPE OF WORK. Al- DHWST DOMESTIC HOI WA FER SUPPLY TEMP AO- VFDMOD PUMP 4 TEMP.MODULATION O 11. THE CONTROLS CONTRACTOR SHALL COORDINATE WITH THE LOW VOLTAGE SYSTEM INSTALLER AND THE c�r9 U BUILDING OWNER INFORMATION TECHNOLOGY STAFF TO ENSURE INTERNET CONNECTIONS ARE PROVIDED •' HOT WATER GENERATOR SEQUENCE OF OPERATION WHERE REQUIRED. eL NO SCALE 12. THE CONTROLS CONTRACTOR SHALL WORK WITH THE BUILDING ENGINEER TO PROVIDE THE DESIRED ® Q CONNECTIONS INTO REMOTE LOCATIONS FOR OFFSITE MONITORING. 13. THE CONTROLS CONTRACTOR SHALL WORK WITH THE BUILDING OWNER TO PROVIDE THE DESIRED REMOTE Ln RECEIVEDALERTS(PAGE,TEXTS,EMAILS,APPs).COORDINATE SPECIFICALLY THE HIERARCHY FOR NOTIFICATION ALARMS. g I a 14. THE OPEN PROTOCOL INTERFACE TO THE UNITS,BACNET,LON OR MODBUS,SHALL BE USED ALONG WITH c45 ADDITIONAL DIRECT POINT CONNECTIONS TO PROVIDE THE DESIGN INTENT.THE CONTROLS CONTRACTOR u C 05/04/2020 SHALL PROVIDE ANY NECESSARY GATEWAYS FOR COMMUNICATION WITH THE BACNET,LONWORKS AND C MODBUS INTERFACES THAT ARE PROVIDED WITH THE UNIT. p_ c RETURNmilli• wr SUPPLY ` ORDINATE WITH OWNER FOR ^ THERMOSTAT AIR AIR T UNIINTT. TO i r 1 T -Z 15. SCHEDULINGPROVIDE CPARAM PARAMETERS.AS REQUIRED UPIED/UNOCCUPIED, BY THDE OWNER SOME AREAS OF HOLIDAY SCHEDULES; OTTH THE WILLOTT HAVE AN ul a) C BUILDING ETHERNET r r UNOCCUPIED CYCLE. Q NETWORK f r Ir i6. FULL SYSTEM TRENDING AND OUTPUT REPORTING WILL BE PROVIDED AS SPECIFIED. +--r UNIT CONTRLSEM CONTROLLER I C TVP. ADDRESS 17. CONTRACTOR TO PROVIDE A DETAILED LISTING OF INDIVIDUAL CONTROL POINTS AS PART OF SHOP DRAWING i BACNET STATIC IP ELECTRICAL PROTOCOL INTERNET REVIEW.THE POINT NAME SHALL INCLUDE THE PIPE OR EQUIPMENT THE POINT IS TIED TO,THE#OF THE M 7 POWER O ❑ EQUIPMENT,ETC.FOR EXAMPLE,"Al/RT.'="HX3HWRT"FOR THE TEMPERATURE SENSOR ON THE HOT WATER SEQUENCE OF OPERATION: RETURN OUTLET OF HEAT EXCHANGER OF HX-3. , HVAC WIT SETPOINTS: CONTROLLER 0 18 REVIEWNDDCOSYS SYSTEM DYNAMIC GRAPHICAL I TERFACE VIAA HEA REMOTE RED tINTERNELY ESS ACCOUNT FOR ENGINEER TO . T. = �j HEATING SETPOINT:60 DEG.F(ADJ.) TYP ti COORD FINAL LOCATIONPO In CWS/WEB W/IT STAFF&SYSTEM 19. PROJECT CLOSE OUT(PRIOR TO COMMISSIONING):UPON THE COMPLETION OF THE INSTALLATION,USING 0 INOCCUPIED/UNOCCUPIED CYCLE: SERVER WITHON SENSING A NEED FOR HEAT THE FAN AND ELECTRIC COIL SHALL ENERGIZE AND CONTRACTOR FOR DATA TWO-WAY COMMUNICATION(AS REQUIRED)COMPLETELY VALIDATE THE PROPER OPERATION AND LABELING OF PROGRAMMING DROP TO BUILDING ALL INPUT AND OUTPUT POINTS.VALIDATION SHALL BE DONE BY PHYSICALLY AFFECTING THE I/O POINTS WHILE RUN AS REQUIRED TO SATISFY THE SPACE HEATING SET POINT. TOOL CONTROL UNIT THE PERSON ON THE OTHER END OBSERVES FOR PROPER RESPONSE.CONTRACTOR SHALL INCLUDE VALIDATION CERTIFICATION IN OPERATION AND MAINTENANCE MANUALS.ADJUST ALL THERMOSTATS,VALVES, Issue Date: DAMPERS,ETC.PROVIDED.FINAL ADJUSTMENT SHALL BE PERFORMED DYNAMICALLY ON OPERATING 07/18/2018 Permit Set NOTE:SYSTEM ARCHITECTURE SHOWN IS DIAGRAMMATIC AND MAY NOT APPLY TO ALL 02/28/2019 Building Permit Resubmitlal MANUFACTURERS. SYSTEM(S). ELECTRIC CABINET HEATER TERMINAL 20. THIS VALIDATION SHALL BE SUBMITTED TO ENGINEER AND COMMISSIONING AGENT PRIOR TO THE EXISTING SYSTEM ARCHITECTURE COMMISSIONING AGENTS FUNCTIONAL TESTING AND THE ENGINEER'S FINAL CHECKOUT OF THE CONTROL CONTROL DRAWING AND SEQUENCE OF OPERATION NO SCALE NO SCALE 21. COMMISSIONING:THE CONTROLS CONTRACTOR SHALL WORK WITH THE 3RD PARTY COMMISSIONING AGENT AS REQUIRED BY THE COMMISSIONING PLAN. 22. TESTING AND BALANCING:THE CONTROLS CONTRACTOR SHALL WORK WITH THE TESTING AND BALANCING CONTRACTOR AS NEEDED TO ACHIEVE THE PROJECT REQUIREMENTS. 23. EXI TI G AV CO S 0 REM'IN WIT E 1ST NG CO TRHLS.A EF-4 EXHr H _J > I KEC DISHWASHER PpDO(/ 9 V•�N.Jpr✓J'� Al- FREEZER COOLER S `i?5 FT m POWERICAL/ ❑ r/.S-•_ Oy Fr'• .'" z-u-/q SEQUENCE OF OPERATION: A Drawing Title: OCCUPIED/UNOCCUPIED CYCLE: THE EXHAUST FAN SHALL OPERATE WITH RESTAURANT OCCUPIED/UNOCCUPIED SCHEDULE THROUGH THE EXISTING DDC. C CL SEQUENCE OF OPERATION CONTROLS UNIT SHALL BE PROVIDED WITH A FACTORY CONTROLLER.DDC TO MONITOR FREEZER AND U.�l.�V I I��I-S COOLER TEMPERATURE.PROVIDE ALARM WHEN EITHER DROP OUT OF SETPOINT. UPON FAILURE AN ALARM SHALL BE DISPLAYED AT THE OPERATOR'S WORKSTATION. EXHAUST FAN CONTROL DRAWING AND SEQUENCE OF OPERATION Date: March 16,2018 NO SCALE Project No: 2018.01.0077 KITCHEN FREEZER/COOLER COMPRESSOR Drawn by: MJK CONTROL DRAWING AND SEQ. OF OPERATION Checked by: MJK NO SCALE Sheet: M6.0 02018/2019 PIERCE FRYE ARCHITECTS SECTION 21 0010-COMMON FIRE PROTECTION REQUIREMENTS H.MAKE PROVISIONS FOR SAFE DELIVERY AND SECURE STORAGE OF ALL MATERIALS. 3.02 DOMESTIC COLD WATER PIPE,VALVES AND FITTINGS: 4.CHECK DUTY:USE BRONZE CHECK VALVES FOR PIPING NPS 2AND SMALLER.USE IRON CHECK VALVES 5.WILO USA LLC V■M�. FORNPS2-1/2 AND LARGER. �w w „'' PART 1 GENERAL I. OBTAIN AND ARRANGE FOR ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK A.INSULATE WITH U.L.APPROVED,FLAME RESISTANT,WHITE VAPOR BARRIER JACKETED,GLASS FIBER B.DESCRIPTION:FACTORY-ASSEMBLED AND-TESTED,MIN-LINE,CLOSE-COUPLED,CANNED-MOTOR, lollt■ulTlus■[us-iu[[■at l-u[ IIMEG 1.01SUMMARY AND PAY ALL ASSOCIATED FEES. SNAP-ON INSULATION PER PIPING INSULATION SCHEDULE.INSULATE VALVES AND FITTINGS WITH GLASS B.USE CHECK VALVES TO MAINTAIN CORRECT DIRECTION OF DOMESTIC WATER FLOW TO AND FROM SEAL-LESS,OVERHUNG-IMPELLER CENTRIFUGAL PUMPS. A.WORK SHALL CONSIST OF FURNISHING ALL LABOR AND MATERIALS NECESSARY FOR THE INSTALLATION OF J.ALL EQUIPMENT AND PRODUCTS TO BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK WITH FIBER BLANKET INSULATION AND PREMOLDED PVC COVERS(COVERS TO BE U.L.25/50 RATED).WHERE THE EQUIPMENT. C.PUMP CONSTRUCTION: COMPLETE AND OPERATING FIRE PROTECTION SYSTEMS. ALL STICKERS,MARKING AND THE LIKE SHALL BE REMOVED.REMOVE ALL RUBBISH,DEBRIS,SCRAPS AND USE OF PVC COVERS IN PLENUMS,ETC.,IS RESTRICTED BY VARIOUS CODES VALVES AND FITTINGS SHALL C.IRON GROOVED-END VALVES MAY BE USED WITH GROOVED-END PIPING. BE INSULATED BY WRAPPING WITH BLANKET INSULATION.COVER BLANKETS TO SAME DEPTH AS THE PIPE 1. PUMP AND MOTOR ASSEMBLY:HERMETICALLY SEALED,REPLACEABLE-CARTRIDGE TYPE WITH MOTOR Mechanical,Electrical& B.DELEGATED DESIGN:DESIGN SPRINKLER SYSTEM(S)USING PERFORMANCE REQUIREMENTS AND DESIGN THE LIKE FROM THE JOB SITE. END OF SECTION AND IMPELLER ON COMMON SHAFT AND DESIGNED FOR INSTALLATION WITH PUMP AND MOTOR SHAFT CRITERIA.DESIGN SHALL INCLUDEACOMPREHENSIVE ENGINEERING ANALYSIS BYAQUALIFIED 1.023UBMRTALS INSULATION WITH INSULATING CEMENT,TROWELED SMOOTH.IT IS THE CONTRACTOR'S AND HORIZONTAL. Energy Consultants MANUFACTURER'S RESPONSIBILITY TO BE CERTAIN THE CODE AUTHORITY WILL APPROVE ANY PRODUCT PROFESSIONAL ENGINEER OR NICET CERTIFIED DESIGNER AS REQUIRED BY THE AUTHORITIES HAVING A.PRODUCT DATA:FOR EACH TYPE OF PRODUCT INDICATED WITHIN DIVISION 22.INCLUDE RATED TO BE INSTALLED ON THE PROJECT.MAXIMUM K-VALUE SHALL BE 0.24 BTU-IN/HR-Sp FT/DEGREES. 2.CASING:BRONZE,WITH THREADED OR COMPANION-FLANGE CONNECTIONS. JURISDICTION. SECTION 221316-SANITARY WASTE AND VENT PIPING AND SANITRY SEWER SPECIALTIES CAPACITIES,OPERATING CHARACTERISTICS,ELECTRICAL CHARACTERISTICS,AND FURNISHED B.DOMESTIC HOT WATER PIPING AND FITTINGS. 3.IMPELLER:PLASTIC, C.SPRINKLER SYSTEM DESIGN SHALL BE APPROVED BY THE AUTHORITIES HAVING JURISDICTION. SPECIALTIES AND ACCESSORIES. PART I GENERAL 1. ALL HOT WATER SUPPLY LINES AND CIRCULATING WATER LINES INSULATE WITH U.L.APPROVED,FLAME 4.MOTOR:SINGLE SPEED,UNLESS OTHERWISE INDICATED. D.COMPLETE ALL WORK IN ACCORDANCE WITH ANY AND ALL APPLICABLE NFPA STANDARDS.COMPLY WITH 1.03WARRANTY 1.01SUMMARY RESISTANT,WHITE ALL SERVICE JACKETED,GLASS FIBER SNAP-ON PIPE INSULATION 1"THICK. D.SEE SCHEDULE FOR CAPACITY AND CHARACTERISTICS. ALL REQUIREMENTS AND CODES OF THE AUTHORITIES HAVING JURISDICTION.COMPLY WITH THE A.THE PLUMBING CONTRACTOR SHALL PROVIDE TO THE OWNER A ONE(1)YEAR(FROM THE DATE OF FINAL INSULATE FITTINGS WITH GLASS FIBER BLANKET INSULATION AND PREMOLDED PVC COVERS.MAXIMUM A.SECTION INCLUDES PIPING MATERIALS FOR SANITARY SEWER AND VENT SYSTEMS AS WELL AS REQUIREMENTS OF THE OWNER'S INSURANCE CARRIER.THE JURISDICTIONAL AUTHORITIES AND CODES ACCEPTANCE)WARRANTY OF ALL PLUMBING EQUIPMENT AND SYSTEMS PROVIDED UNDER THIS K-VALUE SHALL BE 0.24 BTU-IN/HR-Sp FT/DEGREES. SPECIALTIES ASSOCIATED WITH THE SANITARY SEWER SYSTEM. PART3 EXECUTION PIERCE SHALL TAKE PRECEDENCE OVER THE DRAWINGS AND SPECIFICATIONS,IN THE EVENT OF DISPUTE OR CONTRACT.ALL DEFECTIVE EQUIPMENT OR MATERIALS WHICH APPEAR DURING THE WARRANTY PERIOD PART 2 PRODUCTS 3.01 EXAMINATION DISCREPANCY BETWEEN REQUIREMENTS OF CONTRACT DOCUMENTS AND INSURANCE RATING C.HANDICAPPED FIXTURES AUTHORITY OR CODE. SHALL BE REPLACED OR REPAIRED BY THE CONTRACTOR IN A TIMELY FASHION. 1. INSULATION OF PIPES UNDER HANDICAPPED LAVATORIES:INSULATE ANGLE STOP ASSEMBLIES AND 2.01 PIPING MATERIALS A.EXAMINE ROUGHING-IN OF DOMESTIC-WATER-PIPING SYSTEM TO VERIFY ACTUAL LOCATIONS OF + FRYE E.GOOD WORKMANSHIP AND APPEARANCE ARE CONSIDERED EQUAL TO PROPER OPERATION. PART 2 PRODUCTS DRAIN LINES WITH FOAM INSERT COVERED WITH 1/8"MINIMUM ABRASIVE RESISTANT EXTERIOR COVER A.HUBLESS,CAST IRON SOIL PIPE AND FITTINGS.COMPLY WITH ASTM A888 OR CISPI 301. CONNECTIONS BEFORE WATER HEATER,COMPRESSION TANK OR PUMP INSTALLATION. F.PROVIDE ALL CORE DRILLING,CHANNELING,CUTTING,PATCHING,TRENCHING AND BACKFILL AS REQUIRED 2.01 GENERAL WITH FASTENERS LOCATED OUT OF SIGHT,BROCAR TRAP WRAP KIT DOOR AND SOOHS,OR EQUIVALENT. 3.02 INSTALLATION-WATER HEATERS 1. CISPI,HUBLESS-PIPING COUPLINGS:COMPLY WITH ASTM C 1277 AND CISPI 310.PRODUCTS SHALL BE FOR INSTALLATION OF FIRE PROTECTION EQUIPMENT.SEAL HOLES WITH FIREPROOFING AND/OR WATER A.THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND ACCESSORIES NECESSARY WHETHER END OF SECTION STAINLESS-STEEL CORRUGATED SHIELD WITH STAINLESS-STEEL BANDS AND TIGHTENING DEVICES; A.COMMERCIAL DOMESTIC-WATER HEATER MOUNTING:INSTALL FLOOR MOUNTED COMMERCIAL, ARCHITECTS PROOFING WHERE NECESSARY AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE SPECIFICALLY STATED OR NOT TO MAKE THE REQUIRED PLUMBING SYSTEMS COMPLETE AND AND ASTM C 564,RUBBER SLEEVE WITH INTEGRAL,CENTER PIPE STOP DOMESTIC-WATER HEATERS ON CONCRETE BASE.MAINTAIN MANUFACTURER'S RECOMMENDED DAMAGED BY WORK. OPERATIONAL. SECTION 221116-DOMESTIC WATER PIPING AND SPECIALTIES B.COPPER TUBE AND FITTINGS: CLEARANCES.ARRANGE UNITS SO CONTROLS AND DEVICES THAT REQUIRE SERVICING ARE ACCESSIBLE. G.MAKE PROVISIONS FOR SAFE DELIVERY AND SECURE STORAGE OF ALL MATERIALS. B.ALL EQUIPMENT PROVIDED SHALL BE NEW EXCEPT AS OTHERWISE STATED ON THE DRAWINGS.ALL 1. HARD COPPER TUBE:ASTM B88,TYPE L,WATER TUBE,DRAWN TEMPER.COPPER PRESSURE FITTINGS: B.INSTALL COMBINATION TEMPERATURE-AND-PRESSURE RELIEF VALVES IN TOP PORTION OF STORAGE EQUIPMENT PROVIDED SHALL BE ACCEPTABLE FOR INSTALLATION BY THE AUTHORITY HAVING PART 1 GENERAL TANKS.USE RELIEF VALVES WITH SENSING ELEMENTS THAT EXTEND INTO TANKS.EXTEND San Francisco Office H.OBTAIN AND ARRANGE FOR ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK COPPER FITTINGS:ASME Bi6.1 R,CAST-COPPER-ALLOY OR ASME Bi6.22,WROUGHT-COPPER, AND PAY ALL ASSOCIATED FEES. JURISDICTION. 1.01SUBMITTALS COMMERCIAL-WATER-HEATER RELIEF-VALVE OUTLET,WITH DRAIN PIPING SAME AS DOMESTIC-WATER Tel:415.392.4433 SOLDER-JOINT FITTINGS,FURNISH WROUGHT-COPPER FITTINGS IF INDICATED. C.THE EQUIPMENT SCHEDULES ON THE DRAWINGS AND THROUGHOUT THESE SPECIFICATIONS PROVIDE A.SUBMITTAL REQUIREMENTS SHALL BE AS IDENTIFIED IN SPECIFICATION SECTION 220010 COMMON PIPING IN CONTINUOUS DOWNWARD PITCH,AND DISCHARGE BV POSITIVE AIR GAP ONTO CLOSEST FLOOR 2.SOLDER:ASTM B 32,LEAD FREE WITH ASTM B 813,WATER-FLUSHABLE FLUX. I. ALL EQUIPMENT AND PRODUCTS TO BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK WITH PLUMBING REQUIREMENTS. A Vail Office STICKERS,MARKING,PACKING MATERIAL AND THE LIKE REMOVED,REMOVE ALL RUBBISH,DEBRIS, MANUFACTURER AND MODEL INFORMATION.THIS SERVES AS THE STANDARD OF QUALITY FOR C.FLOOR DRAINS,FLOOR SINKS AS SCHEDULED OR EQUIVALENT PRODUCTS EQUIPMENT BY DIFFERENT MANUFACTURERS.THE SPECIFICATION ALLOWS FOR DIFFERENT 1,02QUALITY ASSURANCE C.NOT USED. Tel:970.949.0899 SCRAPS AND THE LIKE FROM THE JOB SITE. MANUFACTURERS TO BE USED FOR THE EQUIPMENT.HOWEVER,REFER TO THE ARCHITECTURAL PART 3 EXECUTION D.INSTALL WATER-HEATER DRAIN PIPING AS INDIRECT WASTE TO SPILL BY POSITIVE AIR GAP INTO OPEN J.PROVIDE ALL SIGNAGE AND SPARE SPRINKLER HEADS AS REQUIRED BY NFPA. SPECIFICATIONS FOR SUBSTITUTIONS BY MANUFACTURERS OTHER THAN THOSE LISTED IN THE A.POTABLE-WATER PIPING AND COMPONENTS SHALL COMPLY WITH NSF 14 AND NSF 61.PLASTIC PIPING 3.01 PIPING INSTALLATION DRAINS OR OVER FLOOR DRAINS.INSTALL HOSE-END DRAIN VALVES AT LOW POINTS IN WATER PIPING www.PlerReF COMPONENTS SHALL BE MARKED WITH"NSF-PW." rye.COm K.COORDINATE TN THIS WORK A WITH THE INSTALLATION CONNECTI OF THE RE ALARM SYSTEM.ALL DEVICES PROVIDED SPECIFICATIONS.WHERE NR EQUIPMENT ISECIFICATION IS PROVIDED,THE SCHEDULED D EQUIPMENT FOR DOMESTIC-WATER HEATERS THAT DO NOT HAVE TANK DRAINS. infa®PierceFrye.com BY THIS CONTRACTOR THAT REQUIRE CONNECTION TO THE FIRE ALARM SYSTEM SHALL BE PROVIDED BY MANUFACTURER SHALL SERVE AS THE BASIS OF DESIGN AND ANY SUBSTITUTIONS SHALL MEET THE B.ALL FITTINGS SHALL BE LEAD FREE(ASTM LISTED)AND SHALL BE MADE WITH CORROSION-RESISTANT A.DRAWING PLANS,SCHEMATICS, DIAGRALOCATIONS AND RRAN TEGENERAL SWERE USED AND ARRANGEMENT EPIPE AND CALCULATEF THIS CONTRACTOR TO OPERATE AS REQUIRED WITH THE FIRE ALARM SYSTEM PROVIDED. QUALITY STANDARD SET BY THE BASIS OF DESIGN. MATERIALS.MANUFACTURER SHALL PROVIDE UPON REQUEST THIRD PARTY CERTIFICATION TESTED IN PIPING SYSTEMS.INDICATED LOCATIONS ARRANGEMENTS WERE USED TO SIZE PIPE AND E.INSTALL THERMOMETERS ON OUTLET PIPING OF DOMESTIC-WATER HEATERS. ACCORDANCE WITH EN ISO 6509 REGARDING DEZINCIFICATION CORROSION RESISTANCE AND STRESS FRICTION LOSS,EXPANSION,PUMP SIZING,AND OTHER DESIGN CONSIDERATIONS.INSTALL PIPING AS F.INSTALL PIPING-TYPE HEAT TRAPS ON INLET AND OUTLET PIPING OF DOMESTIC-WATER HEATER STORAGE 1.02SUBMITTALS D.CONTRACTOR TO BE RESPONSIBLE FOR ANY CHANGES AND COSTS TO ACCOMMODATE ANY EQUIPMENT CORROSION CRACKING. INDICATED UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON COORDINATION DRAWINGS. TANKS WITHOUT INTEGRAL OR FITTING-TYPE HEAT TRAPS. EXCEPT THE MANUFACTURER LISTED IN THE EQUIPMENT SCHEDULES,DRAWING NOTES AND/OR CALLED A.APPROVED SHOP DRAWINGS AND DELEGATED-DESIGN SUBMITTAL:WORKING PLANS,PREPARED OUT WITHIN THE SPECIFICATIONS.IF NO SCHEDULES ARE INCLUDED ON THE DRAWING THAN THE FIRST PART 2 PRODUCTS B.INSTALL PIPING IN CONCEALED LOCATIONS UNLESS OTHERWISE INDICATED AND EXCEPT IN EQUIPMENT 3.03 INSTALLATION-PUMPS MO ACCORDING TO NFPA,THAT HAVE BEEN APPROVED BY AUTHORITIES HAVING JURISDICTION,INCLUDING NAMED IN THE SPECIFICATION IS THE STANDARD OF DESIGN. ROOMS AND SERVICE AREAS. 2.01 PIPING AND JOINT MATERIALS A.PUMPS:INSTALL IN-LINE,SEAL-LESS CENTRIFUGAL PUMPS WITH SHAFT HORIZONTAL UNLESS OTHERWISE HYDRAULIC CALCULATIONS BASED ON PERFORMANCE REQUIREMENTS AND DESIGN CRITERIA,INCLUDING 2.02 IDENTIFICATION C.INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT INDICATED. ANALYSIS DATA SIGNED AND SEALED BY THE QUALIFIED PROFESSIONAL RESPONSIBLE FOR THEIR A.HARD COPPER TUBE:ASTM B 88,TYPE L WATER TUBE,DRAWN TEMPER. RIGHT ANGLES OR PARALLEL TO BUILDING WALLS.DIAGONAL RUNS ARE PROHIBITED UNLESS PREPARATION.INCLUDE PRODUCT DATA FOR EACH TYPE OF PRODUCT INDICATED. A.PROVIDE PIPE AND EQUIPMENT IDENTIFICATION IN ACCORDANCE WITH ANSI A13,1 AND OR THE BUILDING 2.02 VALVES AND DOMESTIC WATER SPECIALTIES SPECIFICALLY INDICATED OTHERWISE. 3.04 CONNECTIONS •1.03WARRANTY STANDARDS. A.WATER HEATERS:WHERE INSTALLING PIPING ADJACENT TO DOMESTIC-WATER HEATERS,ALLOW SPACE = 0 A.BALL VALVES-BRONZE:TWO-PIECE,FULL-PORT,BRONZE BALL VALVES WITH BRONZE TRIM.VALVE SHALL D.INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL. A.THE FIRE PROTECTION CONTRACTOR SHALL PROVIDE TO THE OWNER A ONE(1)YEAR(FROM THE DATE OF 2.03 MISCELLANEOUS SPECIALTIES BE RATED TO 150 PSIG SWP AND 600 PSIG CWP.BODY SHALL BE ASTM B61,B62 OR B584 BRONZE WITH A FOR SERVICE AND MAINTENANCE OF WATER HEATERS.ARRANGE PIPING FOR EASY REMOVAL OF IM mi E.INSTALL PIPING AT INDICATED SLOPES. DOMESTIC-WATER HEATERS. FINAL ACCEPTANCE)WARRANTY OF ALL FIRE PROTECTION EQUIPMENT AND SYSTEMS PROVIDED UNDER A.SLEEVES AND SLEEVE SEALS: CHROME-PLATED BRASS BALL ALL COMPONENTS SHALL BE"DEZINCIFICATION RESISTANT"AND 0 THIS CONTRACT.ALL DEFECTIVE EQUIPMENT OR MATERIALS WHICH APPEAR DURING THE WARRANTY CERTIFIED"LEAD-FREE." F.INSTALL SOIL AND WASTE DRAINAGE AND VENT PIPING AT THE FOLLOWING MINIMUM SLOPES UNLESS B.PUMPS:INSTALL PIPING ADJACENT TO PUMPS TO ALLOW SERVICE AND MAINTENANCE.CONNECT 1 WHERE PIPING PASSES THROUGH NEW MASONRY OR CONCRETE WALLS OR CONCRETE FLOORS, PERIOD SHALL BE REPLACED OR REPAIRED BY THE CONTRACTOR IN A TIMELY FASHION. OTHERWISE INDICATED: DOMESTIC WATER PIPING TO PUMPS.INSTALL SUCTION AND DISCHARGE PIPING EQUAL TO OR GREATER PROVIDE PIPE SLEEVES.SLEEVES SHALL BE CONSTRUCTED OUT OF GALVANIZED STEEL CAST IRON OR B.BALL VALVES-IRON:CLASS 125 IRON BALL VALVES.VALVE SHALL BE RATED TO 200 PSIG CWP.BODY B.P2 PRODUCTS(NOT APPLICABLE) PVC.SET SLEEVES IN FORMS PRIOR TO CONCRETE PLACEMENT.SLEEVES IN FLOORS SHALL EXTEND 2" SHALL BE ASTM A 126 GRAY IRON WITH A STAINLESS STEEL BALL AND STEM.ALL COMPONENTS SHALL BE 1. SANITARY DRAIN:2PERCENT(1/4INCH PER FOOT)DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS THAN SIZE OF PUMP NOZZLES.INSTALL SHUTOFF VALVEANDSTRAINERON SUCTION SIDE OF EACH PUMP, = U ABOVE THE FINISHED FLOOR ELEVATION.WHERE LOCATESINEXTERIOR WALLS,PROVIDE WATER CERTIFIED"LEAD-FREE" 3AND SMALLER;1 PERCENT(1/8 INCH PER FOOT)DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS 4 AND CHECK,SHUTOFF,AND THROTTLING VALVES ON DISCHARGE SIDE OF EACH PUMP.INSTALL VALVES C.P3 EXECUTION(NOT APPLICABLE) AND LARGER. SAME SIZE AS CONNECTED PIPING.INSTALL PRESSURE GAGE AT SUCTION OF EACH PUMP AND PRESSURE •t_� C STOP IN SLEEVE, C.BUTTERFLY VALVES:IRON SINGLE-FLANGE BUTTERFLY VALVES WITH EPDM SEAT AND ALUMINUM-BRONZE END OF SECTION 2.VENT PIPING:1 PERCENT(1/8 INCH PER FOOT)DOWN TOWARD VERTICAL FIXTURE VENT OR TOWARD GAGE AT DISCHARGE OF EACH PUMP. e CL 2.PIPING WHICH PASSES THROUGH A RATED WALL SHALL BE PROVIDED WITH A UL DETAIL SUITABLE FOR DISC.VALVE SHALL BE RATED TO 200 PSIG CWP.BODY SHALL BE ASTM A 126 CAST IRON OF ASTM A 536 En VENT STACK. 3.05 FIELD QUALITY CONTROL e�a PIPE MATERIAL AND SIZE.SLEEVE SHALL ONLY BE REQUIRED IF THE UL DETAIL REQUIRES THE SLEEVE. DUCTILE IRON WITH A STAINLESS STEEL STEM,EPDM SEAT AND ALUMINUM BRONZE DISC.ALL a-9d = Q SECTION 21 1313-WET PIPE SPRINKLER SYSTEMS WHERE SLEEVES ARE REQUIRED AS NOTED ABOVE,PROVIDE A UL DETAIL THAT UTILIZES A SLEEVE. COMPONENTS SHALL BE CERTIFIED"LEAD-FREE" G.INSTALL CAST-IRON SOIL PIPING ACCORDING TO CISPI'S"CAST IRON SOIL PIPE AND FITTINGS HANDBOOK," A.PERFORM TESTS AND INSPECTIONS.LEAK TEST:AFTER INSTALLATION,CHARGE SYSTEM AND TEST FOR PART I GENERAL B.ESCUTCHEONS: D.DOMESTIC HOT WATER BALANCING:PROVIDE CIRCUITSOLVER BY THEMOMEGATECH. CHAPTER IV,"INSTALLATION OF CAST IRON SOIL PIPE AND FITTINGS." LEAKS.REPAIR LEAKS AND RETEST UNTIL NO LEAKS EXIST.OPERATIONAL TEST:AFTER ELECTRICAL ® H.HANGER ROD AND SPACING AS REQUIRED BY THE IPC FOR THE SIZE OF PIPE BEING INSTALLED. CIRCUITRY HAS BEEN ENERGIZED,START UNITS TO CONFIRM PROPER OPERATION.TEST AND ADJUST 1.01SUMMARY 1. WHERE NEW PIPE PASSES THROUGH A FINISHED WALL,PROVIDE A CHROME PLATED ESCUTCHEON. E.DRAIN VALVES:BALL-VALVE-TYPE HOSE-END DRAIN VALVES SHALL BE RATED TO 400 PSIG CWP.BODY CONTROLS AND SAFETIES.REPLACE DAMAGED AND MALFUNCTIONING CONTROLS AND EQUIPMENT. g I U A.RELATED SECTIONS:REFERENCE SECTION 22 0010"COMMON FIRE PROTECTION REQUIRRRIVED ESCUTCHEON SHALL BE CONSTRUCTED IN ONE PIECE. SHALL BE COPPER ALLOY WITH A CHROME-PLATED BRASS BALL WITH A THREADED OUTLET WITH BRASS I. TEST SANITARY DRAINAGE AND VENT PIPING ACCORDING TO PROCEDURES OF AUTHORITIES HAVING COMMON FIRE PROTECTION DESIGN REQUIREMENTS INCLUDING SUBMITTAL AND DELEGATED DESIGN C.ACCESS DOORS CHAIN ATTACHED CAP. JURISDICTION 3.06 ADJUSTING (g) REQUIREMENTS. F.CHECK VALVES-BRONZE:CLASS 150 BRONZE SWING CHECK VALVES WITH BRONZE DISC.VALVE SHALL BE END OF SECTION A.WATER HEATERS:ADJUST INITIAL TEMPERATURE SET POINTS. CA I_ 05/04/2020 1. WHERE NOTED,PROVIDE THE TYPE AND SIZE OF ACCESS DOOR TO FULLY ACCESS THE ITEM THAT IS ® D C PART 2 PRODUCTS LOCATED WITH THE WALL OR CAVITY.PROVIDE FIRE RATED DOORS WHERE INSTALLED IN FIRE RATED RATED TO 300 PSIG CWP.BODY SHALL BE ASTM B81,B62 OR B584 BRONZE.ALL COMPONENTS SHALL BE B.PUMPS:ADJUST DOMESTIC WATER PUMPS TO FUNCTION SMOOTHLY,AND LUBRICATE AS RECOMMENDED C ASSEMBLIES. "DEZINCIFICATION RESISTANT'AND CERTIFIED"LEAD-FREE." BY MANUFACTURER.ADJUST INITIAL RECIRCULATION TEMPERATURE SET POINTS.SET FIELD-ADJUSTABLE2.01 GENERAL ASPEN SECTION 223300-DOMESTIC WATER HEATERS a BUILDING DEPARTMENT'.s EXECUTION G.PRESSURE GAUGES:SHALL BE DIRECT-MOUNTED DIAL-TYPE WITH A CAST ALUMINUM OR DRAWN STEEL SWITCHES AND CIRCUIT-BREAKER TRIP RANGES AS INDICATED. A.ALL MATERIAL SHALL BE UL LISTED. CASE.PROVIDE 4-1/2 INCH NOMINAL DIAMETER UNITS.ACCURACY SHALL BE PLUS OR MINUS 1 PERCENT PART 1 GENERAL END OF SECTION e,rJ 3.01 GENERAL 2.02 PIPING AND FITTINGS OF MIDDLE HALF OF SCALE RANGE.SCALE SHALL BE 0 TO 100 PSI FOR DOMESTIC WATER. 1.01SUBMITTALS A.OBTAIN AND ARRANGE FOR ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK A.PIPING MATERIALS SHALL BE NEW AND DESIGNED FOR 175 PSI WORKING PRESSURE,CONFORMING TO H.THERMOMETERS:SHALL BE DIRECT-MOUNTED LIGHT-ACTIVATED DEG F ADJUSTABLE ANGLE A.SUBMITTAL REQUIREMENTS SHALL BE AS IDENTIFIED IN SPECIFICATION SECTION 220010 COMMON SECTION 22 4000-PLUMBING FIXTURES AND EQUIPMENT AND PAY ALL ASSOCIATED FEES. ASTM SPECIFICATIONS.PIPING SHALL HAVE THE MANUFACTURER'S NAME OR BRAND,ALONG WITH THE THERMOMETERS WITH 9-INCH PLASTIC CASE DISPLAY SHALL BE DIGITAL.WHERE UNIT IS MOUNTED IN A PLUMBING REQUIREMENTS. 4-•I APPLICABLE ASTM STANDARD,MARKED ON EACH LENGTH OF PIPE B.PROVIDE ALL CORE DRILLING,CHANNELING,CUTTING,PATCHING,TRENCHING AND BACKFILL AS REQUIRED CEILING PLENUM OR OTHER DARK LOCATION PROVIDE DIAL TYPE THERMOMETER.SCALE SHALL BE 0 TO PART 1 GENERAL C 1.020UALITY ASSURANCE CZ B.WHERE SYSTEM PRESSURES ARE BETWEEN 175 PSI AND 300 PSI,STANDARD WALL PIPE SHALL BE USED AS FOR INSTALLATION OF PLUMBING EQUIPMENT AND OR MECHANICAL EQUIPMENT.SEAL HOLES, 150 DES F FOR DOMESTIC COLD WATER AND OTO 250 DES F FOR DOMESTIC HOT WATER. 1.01SUBMITTALS CU L FIREPROOFING WHERE NECESSARY,AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE A.ELECTRICAL COMPONENTS,DEVICES,AND ACCESSORIES:LISTED AND LABELED AS DEFINED IN NFPA 70, PERMITTED BY ANSI STANDARDS AND ASSOCIATED SYSTEMS SHALL BE PROVIDED WITH UL LISTED I. STRAINERS:V-PATTERN STRAINERS SHALL BE 125 PSIS PRESSURE RATED.BODY SHALL BE BRONZE FOR A.SUBMITTAL REQUIREMENTS SHALL BE AS IDENTIFIED IN SPECIFICATION SECTION 22 0010 COMMON I� = DAMAGED BY MECHANICAL WORK, BYA QUALIFIED TESTING AGENCY,AND MARKED FOR INTENDED LOCATION AND APPLICATION. (21PRESSURE REDUCING ASSEMBLIES WHERE REQUIRED AS APPROVED BY THE AUTHORITIES HAVING NPS 2 AND SMALLER;CAST IRON FOR NPS 2-1/2 AND LARGER.ALL COMPONENTS SHALL BE CERTIFIED PLUMBING REQUIREMENTS. Or) JURISDICTION. C.ALL EQUIPMENT AND PRODUCTS TO BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK WITH "LEAD-FREE." B.ASHRAE/IESNA COMPLIANCE:APPLICABLE REQUIREMENTS IN ASHRAE/IESNA 90.1. PART3 EXECUTION C ALL STICKERS,MARKINGS,AND THE LIKE REMOVED,REMOVE ALL RUBBISH,DEBRIS,SCRAPS AND THE LIKE C.ASME COMPLIANCE:WHERE ASME-CODE CONSTRUCTION IS INDICATED,FABRICATE AND LABEL C.ALLOWABLE PIPING MATERIAL WHERE APPROVED BY THE AUTHORITIES HAVING JURISDICTION INCLUDE J.PRESSURE AND TEMPERATURE TAPS:SHALL BE BRASS OR STAINLESS STEEL WITH CORE INSERTS AND 2.01 EXAMINATION CO SCHEDULE 40 BLACK STEEL PIPE,SCHEDULE IO BLACK STEEL PIPE,SCHEDULE 5 AND TYPE"K"OR"L„ FROM THE JOB SITE. GASKETED WITH A THREADED CAP.INCLUDE EXTENDED STEM ON UNITS TO BE INSTALLED IN INSULATED COMMERCIAL,DOMESTIC-WATER HEATER STORAGE TANKS TO COMPLY WITH ASME BOILER AND C.J 1.1.J COPPER TUBE. 3.02 FLUSHING AND CLEANING PIPING.THREAD SIZE SHALL BE NPS V.CORE INSERT SHALL BE EPDM SELF-SEALING RUBBER. PRESSURE VESSEL CODE:SECTION VIII,DIVISION 1. A.EXAMINE ROUGHING-IN OF WATER SUPPLY AND SANITARY DRAINAGE AND VENT PIPING SYSTEMS TO C D.NSF COMPLIANCE:FABRICATE AND LABEL EQUIPMENT COMPONENTS THAT WILL BE IN CONTACT WITH VERIFY ACTUAL LOCATIONS OF PIPING CONNECTIONS BEFORE FIXTURE INSTALLATION.EXAMINE CO D.ALLOWABLE PIPE FITTINGS WHERE APPROVED BY THE AUTHORITIES HAVING JURISDICTION INCLUDE A.BEFORE FINAL CONNECTIONS ARE MADE IN THE PIPING SYSTEMS,SYSTEMS SHALL BE BLOWN OUT WITH K.BACKFLOW PREVENTERS: EMENTOW PREVENTERS ARE ADICATOF-DESIGN PRODUCT;SUBJECT TO COUNTERS,WALLS AND FLOORS FOR SUITABLE CONDITIONS WHERE FIXTURES WILL REINSTALLED. SCREWED FITTINGS,FLANGED FITTINGS,WELD FITTINGS,GROOVED FITTINGS/COUPLINGS,AND AIR AND THEN COMPLETELY WASHED OUT WITH CLEANING COMPOUNDS COMPATIBLE WITH FINAL FLUID COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT INDICATED ON DRAWINGS. POTABLE WATER TO COMPLY WITH NSF 61,"DRINKING WATER SYSTEM COMPONENTS-HEALTH EFFECTS." 0 Ill WROUGHT-COPPER SOLDER-JOINT. TO AVOID CONTAMINATION.THE SYSTEMS SHALL THEN BE FLUSHED FOR THE COMPLETE REMOVAL OF NO US D. 1 1.03WARRANTY 2.02 INSTALLATION ALL FOREIGN MATERIALS.FURNISH ALL TEMPORARY CONNECTIONS,VALVES,ETC.,REQUIRED FOR THIS A.MOP SERVICE BASIN INSTALLATION: E.ALL VALVES SHALL BE UL LISTED AND SHALL INCLUDE VALVE SUPERVISORY SWITCHES. A.WARRANTY PERIODS:FROM DATE OF SUBSTANTIAL COMPLETION. PURPOSE M.TEMPERATURE-ACTUATED WATER MIXING VALVES:MIXING VALVES ARE A BASIS-OF-DESIGN PRODUCT; 1. SET FLOOR-MOUNTED SINKS IN LEVELING BED OF CEMENT GROUT. Issue Date: F.EXPANSION,SLEEVES,ESCUTCHEONS,HANGERS,IDENTIFICATION AND THE LIKE SHALL BE PROVIDED SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT INDICATED ON DRAWINGS.VALVES 1. COMMERCIAL,STORAGE,DOMESTIC-WATER HEATERS: B.AFTER FLUSHING,STERILIZE THE DOMESTIC WATER SYSTEM IN ACCORDANCE WITH AWWA STANDARD 07/18/2018 Permit Set WHERE REQUIRED. C651-(CURRENT EDITION),DISINFECTING WATER MAINS,AND ALL SUBSEQUENT ADDENDA.AFTER SHALL BE MADE OF BRONZE AND PRESSURE RATED FOR 125 PSIG.VALVES SHALL BE RATED TO ASSE 1017 a,STORAGE TANK:THREE YEARS. 2.INSTALL WATER-SUPPLY PIPING WITH STOP ON EACH SUPPLY TO EACH SINK FAUCET.INSTALL STOPS IN 02/282019 Building PenInit Reeubmittal 2.03 SPRINKLERS FOR MASTER MIXERS AND ASSE 1070 FOR POINT OF USE VALVES, LOCATIONS WHERE THEY CAN BE EASILY REACHED FOR OPERATION, MINIMUM CONTACT PERIOD,FLUSH THE SYSTEM WITH CLEAN WATER UNTIL THE RESIDUAL CHLORINE IS b.CONTROLS AND OTHER COMPONENTS:ONE YEAR, A.SPRINKLERS SHALL BE UL LISTED STANDARD SPRAY SPRINKLER HEADS,NOMINAL TEMPERATURE RATING NO GREATER THAN THE CITY WATER.SUBMIT TO THE ARCHITECT,WRITTEN CERTIFICATION THAT N.OUTLET BOXES:ICEMAKER/COFFEE MACHINE OR WASHING MACHINE OUTLET BOXES AREA B.SUPPORT INSTALLATION:INSTALL SUPPORTS,AFFIXED TO BUILDING SUBSTRATE,FOR WALL-MOUNTED (160°F)EXCEPT WHERE HIGH TEMPERATURE HEADS ARE REQUIRED. STERILIZATION HAS BEEN PERFORMED AND INCLUDE A COPY IN OPERATION AND MAINTENANCE MANUALS. BASIS-OF-DESIGN PRODUCT;SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT PART 2 PRODUCTS FIXTURES, PROVIDE A TEST ANALYSIS BY THE STATE HEALTH DEPARTMENT OF A RANDOM WATER SAMPLE,IF INDICATED ON DRAWINGS.BOXES AND FACE PLATE SHALL BE PLASTIC AND FIRE-RATED IF INSTALLED IN A 2.0 COMMERCIAL WATER TO WATER HOT WATER GENERATOR: C.JOINT SEALING:SEAL JOINTS BETWEEN FIXTURES AND WALLS AND FLOORS USING SANITARY-TYPE, B.NEW HEADS TO BE SAME MAKE AND MODEL AS EXISTING EXCEPT WHERE NOT ALLOWED BY THE REQUESTED BY THE ARCHITECT. RATED ASSEMBLY,PROVIDE WITH INTEGRAL BALL VALVES AND WATER HAMMER ARRESTORS,ALL A.TYPE:AUTOMATIC,WATER TO WATER,VERTICAL STORAGE. ONE-PART,MILDEW-RESISTANT SILICONE SEALANT.MATCH SEALANT COLOR TO FIXTURE COLOR, AUTHORITIES HAVING JURISDICTION. COMPONENTS SHALL BE CERTIFIED"LEAD-FREE" PART3 EXECUTION END OF SECTION B.TANK:ASME LABELED;UNLINED DUPLEX STAINLESS STEEL 2.03 CONNECTIONS •.NOT USED.A 3.01 INSTALLATION C.HEAT EXCHANGER;ASME LABELED;DOUBLE WALL COPPER U-TUBE HEAT EXCHANGER WITH NONFERROUS A.CONNECT FIXTURES WITH WATER SUPPLIES AND SOIL,WASTE,AND VENT PIPING,USE SIZE FITTINGS AND SECTION 22 PLUMBING INSULATION P.WA R-'AMINES ARRESTERS'WATER-HAMMER ARRESTERS AREABASIS-OF-DESIGN PRODUCT;SUBJECT TUBE SUPPORTS AND WATERSIDE TUBE SHEET, TRANSITION FITTINGS AS REQUIRED MATCHING FIXTURES AND FIXTURE CONNECTION SIZES AS IDENTIFIED A.INSTALLATION SHALL BE PER NFPA STANDARDS ALONG WITH THE REQUIREMENTS/CODES OF THE TO COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT INDICATED ON DRAWINGS.WATER-HAMMER ON DRAWINGS,TRANSITION FITTINGS SHALL BE MADE AT THE FIXTURE.WHERE INSTALLING PIPING AUTHORITIES HAVING JURISDICTION. PART 1 GENERAL ARRESTERS SHALL BE ASSE 1010 LISTED METAL BELLOWS TYPE.ALL COMPONENTS SHALL BE CERTIFIED D.ACCESSORIES: ADJACENT TO FIXTURES,ALLOW SPACE FOR SERVICE AND MAINTENANCE.INTEGRAL VACUUM BREAKERS B.INSPECT PROCEEDING WORK,VERIFY ALL DIMENSIONS BEFORE PROCEEDING WITH WORK AND 1.01SUMMARY "LEAD-FREE." 1. WATER CONNECTIONS:BRASS. SHALL BE PROVIDED AT ALL OUTLETS WITH HOSE CONNECTIONS. COORDINATE ALL WORK AND PLACEMENT OF COMPONENTS WITH OTHER TRADES.COORDINATE EXACT A.SECTION INCLUDES INSULATION FOR PLUMBING PIPING. Q.TRAP-SEAL PRIMER VALVES:TRAP-SEAL PRIMER VALVES ARE A BASIS-OF-DESIGN PRODUCT;SUBJECT TO 2.DIP TUBE:BRASS. 2.04 CLEANING AND PROTECTION PIPE LOCATIONS WITH DRAWINGS AND OTHER TRADES BEFORE DESIGN APPROVAL AND FABRICATION OF COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT INDICATED ON DRAWINGS,TRAP-SEAL VALVES 3. DRAIN VALVE PART 2 PRODUCTS A.AFTER COMPLETING INSTALLATION OF FIXTURES,INSPECT AND REPAIR DAMAGED FINISHES.CLEAN PIPING.THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ANY REDESIGN AND FABRICATION REQUIRED TO SHALL BE ASSE 1018 LISTED BRONZE TYPE.ALL COMPONENTS SHALL BE CERTIFIED"LEAD-FREE." 4.ANODE:MAGNESIUM. FIXTURES AND FITTINGS WITH MANUFACTURERS'RECOMMENDED CLEANING METHODS AND MATERIALS. FIT SYSTEM INTO ALLOWABLE SPACE. 2.01 INSULATION R.FLEXIBLE CONNECTORS'STAINLESS-STEEL-HOSE FLEXIBLE CONNECTORS: 1 5. TEMPERATURE AND PRESSURE RELIEF VALVE:ASME LABELED. INSTALL PROTECTIVE COVERING FOR INSTALLED FIXTURES AND FITTINGS.DO NOT ALLOW USE OF .PIPING SHALL BE INSTALLED IN THE MOST DIRECT,STRAIGHT AND MECHANICAL MANNER AS POSSIBLE AND CORRUGATED-STAINLESS-STEEL TUBING WITH STAINLESS-STEEL WIRE-BRAID COVERING AND ENDS FIXTURES FOR TEMPORARY FACILITIES UNLESS APPROVED IN WRITING BY OWNER. AS CLOSE TO WALLS AND CEILINGS AS IS CONSISTENT WITH GOOD WORKMANSHIP,ALL LINES SHALL BE WELDED TO INNER TUBING.ALL COMPONENTS SHALL BE CERTIFIED"LEAD-FREE".WORKING-PRESSURE 6.CIRCULATOR PUMP. RUN HIGH ENOUGH TO PERMIT RELOCATION OF LIGHTS,ALL VERTICAL LINES SHALL BE PLUMB AND r RATING:MINIMUM 200 PSIG.END CONNECTIONS NPS 2 AND SMALLER:THREADED STEEL-PIPE NIPPLE. D. E-IFI •F•-T F•LO"IN .P' CA 0 END OF SECTION 2.02 PROTECTIVE SHIELDING GUARDS1 ORI ON L L ES SHA L R N PART EL 0 B ILDI G L NES A.DESCRIPTION:MANUFACTURED PLASTIC WRAPS FOR COVERING PLUMBING FIXTURE HOT-AND END CONNECTIONS NPS 2-1/2 AND LARGER:FLANGED STEEL NIPPLE. 1. AUTOMATIC STORAGE WATER HEATER, D.ALL PIPING IN FINISHED AREAS SHALL BE CONCEALED UNLESS SHOWN OTHERWISE,ALL OTHER PIPING CAN COLD-WATER SUPPLIES AND TRAP AND DRAIN PIPING.COMPLY WITH AMERICANS WITH DISABILITIES ACT S.DIELECTRIC FITTINGS:ASSEMBLY OF COPPER ALLOY AND FERROUS MATERIALS WITH SEPARATING 2.FOR OPERATION IN HIGH ALTITUDE INSTALLATIONS. .c., BE EXPOSED, (ADA)AND ANSI A117.1 REQUIREMENTS.TRUEBRO OR EQUIVALENT. NONCONDUCTIVE INSULATING MATERIAL.INCLUDE END CONNECTIONS COMPATIBLE WITH PIPES TO BE rep1yA0O(i - JOINED.DIELECTRIC NIPPLES AND COUPLINGS COMPLYING WITH IAPMO PS 66. ELECTROPLATED STEEL E.SEE DRAWING SCHEDULE FOR PERFORMANCE CHARACTERISTICS AND CAPACITIES. OV ,Ce E.INSTALL HORIZONTAL PIPING GRADED TO LOW POINTS AND IN A MANNER TO MAKE IT POSSIBLE TO TEST 2.03 FIELD APPLIED JACKETS :6'32 �ti•N'JAR,•,��J NIPPLE COMPLYING WITH ASTM F 1545.PRESSURE RATING AND TEMPERATURE:300 PSIG AT 225 DEG F. 2.02 WATER HEATER ACCESSORIES AND EMPTY ENTIRE SYSTEM.PROVIDE VALVES AT LOW POINTS TO FACILITATE SYSTEM DRAINAGE. A.PVC JACKET:HIGH-IMPACT-RESISTANT,UV-RESISTANT PVC COMPLYING WITH ASTM D 1784,CLASS 16354-C; LINING SHALL BE INERT AND NONCORROSIVE,PROPYLENE. A.ALL WATER HEATERS SHALL BE PROVIDED WITH TEMPERATURE,PRESSURE AND/OR VACUUM RELIEF7' ��F,PIPE AND FITTINGS SHALL BE INSPECTED FOR SOUNDNESS AND CLEANED OF ALL DIRT AND OTHER THICKNESS AS SCHEDULED;ROLL STOCK READY FOR SHOP OR FIELD CUTTING AND FORMING.THICKNESS ��[[C "• 1" PARTS EXECUTION VALVES IN ACCORDANCE WITH THE WATER HEATER MANUFACTURER'S INSTRUCTIONS WHICH COMPLY �• 1 FOREIGN MATTER PRIOR TO BEING INSTALLED.ALL DAMAGED PIPE AND FITTINGS WILL BE REJECTED. IS INDICATED IN FIELD-APPLIED JACKET SCHEDULES. 3.01 PIPING SCHEDULE WITH THE REQUIREMENTSOF THE AUTHORITY HAVING JURISDICTION. G.ALL SPRINKLER HEADS SHALLBE CENTERED CEILING TILE WHERE TILE CEILINGS OCCUR.WHERE HEADS B.ALUMINUM JACKET:COMPLY WITH ASTM B 209,ALLOY 3003,3005,3105,OR 5005,TEMPER H-14. a • WILL BE SUBJBJECTTTO DAMAGE, HEAD GUARDSS SHALL BE FURNISHEDED. 2.03 DOMESTIC-WATER COMPRESSION TANKS: • 1. SHEET AND ROLL STOCK READY FOR SHOP OR FIELD SIZING. A.BASIS-OF-DESIGN PRODUCT:SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCT END OF SECTION 2. FINISH AND THICKNESS ARE INDICATED IN FIELD-APPLIED JACKET SCHEDULES. B.ABOVEGROUND INDICATED ON DRAWINGS OR COMPARABLE PRODUCT BY ONE OF THE FOLLOWING: Z.-:.a-Ig 1. NPS 2 AND SMALLER: 3.MOISTURE BARRIER FOR OUTDOOR APPLICATIONS:3-MIL-THICK,HEAT-BONDED POLYETHYLENE AND 1. AMTROL INC. SECTION 22 0010-COMMON PLUMBING REQUIREMENTS KRAFT PAPER. a.HARD COPPER TUBE,ASTM B 88,TYPE L;WROUGHT-COPPER,SOLDER-JOINT FITTINGS;AND BRAZED JOINTS. 2.ARMSTRONG,INC. Drawing Title: PART 1 GENERAL 4.FACTORY-FABRICATED FITTING COVERS: 3. ARMSTRONG PUMPS,INC 1.01SUMMARY a.SAME MATERIAL,FINISH,AND THICKNESS AS JACKET. b.HARD COPPER TUBE,ASTM B 88,TYPE L;COPPER PRESSURE-SEAL-JOINT FITTINGS;AND PRESSURE-SEALED JOINTS. 4.BELL 8 GOSSETT DOMESTIC PUMP;A DIVISION OF ITT INDUSTRIES A.WORK SHALL CONSIST OF FURNISHING ALL LABOR AND MATERIALS NECESSARY FOR THE INSTALLATION OF b.PREFORMED 2-PIECE OR GORE,45-AND 90.DEGREE,SHORT-AND LONG-RADIUS ELBOWS. c.HARD COPPER TUBE,ASTM B88,TYPE L;EXTRUDED-TEE CONNECTIONS AND BRAZED JOINTS. 5. SMITH,A.O.WATER PRODUCTS CO.;A DIVISION OF A.O.SMITH CORPORATION trI�/'' /���/' COMPLETE AND OPERATING PLUMBING SYSTEMS. c.TEE COVERS. I IEl.il••IA V ICAI_ A 0.FLANGE AND UNION COVERS. 2. NPS 2-1/2 TO NPS 4: 6.STATE INDUSTRIES • ALL PLUMBING WORK SHALL COMPLY WITH CURRENT STATE AND LOCAL BUILDING CODES AS REQUIRED BY a.HARD COPPER TUBE,ASTM 888,TYPE L;WROUGHT-COPPER,SOLDER-JOINT FITTINGS;AND BRAZED P. TACO,INC SPECIFICATIONS THE AUTHORITIES HAVING JURISDICTION,THE INTERNATIONAL PLUMBING CODE,THE INTERNATIONAL MECHANICAL CODE,THE INTERNATIONAL FIRE CODE,APPLICABLE PUBLICATIONS OF THE NATIONAL FIRE e.END CAPS. JOINTS. B.DESCRIPTION:ASME STEEL PRESSURE-RATED TANK CONSTRUCTED WITH WELDED JOINTS AND •RO.CT•N:55• IA ON FP•.A•AP•RO-RI• E. HR• S'ND'RD. f. BEVELED COLLARS. b.HARD COPPER TUBE,ASTM 1388,TYPE L;COPPER PRESSURE-SEAL-JOINT FITTINGS;AND FACTORY-INSTALLED BUTYL-RUBBER DIAPHRAGM.INCLUDE AIR PRE-CHARGE TO MINIMUM C.THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF THE GENERAL CONDITIONS, 9.VALVE COVERS. PRESSURE-SEALED JOINTS. SYSTEM-OPERATING PRESSURE AT TANK. SUPPLEMENTAL GENERAL CONDITIONS OF THE PROJECT SPECIFICATIONS,ALL CONTRACT DOCUMENTS, h.FIELD FABRICATE FITTING COVERS ONLY IF FACTORY-FABRICATED FITTING COVERS ARE NOT c.HARD COPPER TUBE,ASTM B 88,TYPE L;GROOVED-JOINT,COPPER-TUBE APPURTENANCES;AND C.CONSTRUCTION: AND ANY BASE BUILDING SPECIFICATIONS AND BUILDING CRITERIA INCLUDED IN THIS PROJECT. AVAILABLE. GROOVED JOINTS. 1. INTERIOR FINISH:COMPLY WITH NSF 61 BARRIER MATERIALS FOR POTABLE-WATER TANK LININGS, Date: March 16,2018 D.DRAWINGS ARE DIAGRAMMATIC IN NATURE.TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, PART3 EXECUTION C.FLANGES AND UNIONS:FLANGES AND UNIONS MAY BE USED FOR ABOVEGROUND PIPING JOINTS UNLESS INCLUDING EXTENDING FINISH INTO AND THROUGH TANK FITTINGS AND OUTLETS. CERTIFIED EQUIPMENT DRAWINGS,AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK. g 01 GENERAL INSTALLATION OTHERWISE INDICATED. 2.AIR-CHARGING VALVE FACTORY INSTALLED. Project NO: 2018.01.0077 E.THE DRAWINGS INDICATE THE LOCATION,TYPE AND SIZES OF VARIOUS UTILITIES WITHIN THE SITE WHERE A.PIPING INSULATION SCHEDULE:SEE SCHEDULE ON DRAWINGS FOR INSULATION REQUIREMENTS. D.TRANSITION AND SPECIAL FITTINGS:TRANSITION AND SPECIAL FITTINGS WITH PRESSURE RATINGS AT D.SEE SCHEDULE FOR CAPACITY AND CHARACTERISTICS. KNOWN.ANY RELOCATION OR REMODELING REQUIRED MUST BE APPROVED BY THE ARCHITECT BEFORE LEAST EQUAL TO PIPING RATING MAY BE USED UNLESS OTHERWISE INDICATED. Drawn by: MJK PROCEEDING.INVESTIGATE ALL UTILITIES SUCH AND WATER AND MAKE ARRANGEMENTS WITH THE B.PROTECTIVE SHIELDING GUARDS:INSTALL PROTECTIVE SHIELDING GUARDS ON ALL LAVATORIES,SINKS 2.04 DOMESTIC-WATER RECIRCULATION PUMPS: AND OTHER APPLICABLE PLUMBING FIXTURES AS REQUIRED TO COMPLY WITH THE REQUIREMENTS OF 3.02 VALVE SCHEDULE Checkedb MJK PROPER AUTHORITY TO PAY FOR ANY CHARGES ASSOCIATED WITH CONNECTING THOSE UTILITIES. A.BASIS-OF-DESIGN PRODUCT: COMPARABLE COMPLIANCE WITH REQUIREMENTS,PROVIDE PRODUCTY AMERICANS WITH DISABILITIES ACT(ADA)AND ANSI A117.1. A.WHERE SPECIFIC VALVE TYPES ARE NOT INDICATED,THE FOLLOWING REQUIREMENTS APPLY: INDICATED ON DRAWINGS OR COMPARABLE PRODUCT BY ONE OF THE FOLLOWING: F.GOOD WORKMANSHIP AND APPEARANCE ARE CONSIDERED EQUAL TO PROPER OPERATION. 1. SHUTOFF DUTY AND THROTTLING DUTY:USE BALL VALVES FOR PIPING NPS 2 AND SMALLER.USE Sheet: C.FIELD-APPLIED JACKETS: 1. ARMSTRONG PUMPS,INC G.PROVIDE ALL CORE DRILLING,CHANNELING,CUTTING,PATCHING,TRENCHING AND BACKFILL AS REQUIRED BUTTERFLY OR BALL VALVES WITH FLANGED ENDS FOR PIPING NPS 2-1/2 AND LARGER. FOR INSTALLATION OF MECHANICAL EQUIPMENT.SEAL HOLES WITH FIREPROOFING AND/OR WATER 1. ALL FITTINGS SHALL 8E PROVIDED WITH PVC JACKETS. 2.BELL 8 COSSETS DOMESTIC PUMP;A DIVISION OF ITT INDUSTRIES 2. HOT-WATER CIRCULATION PIPING,BALANCING DUTY:CICUITSOLVER. •0 PROOFING WHERE NECESSARY AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE 2.PROVIDE PVC OR ALUMINUM JACKETS AS AND WHERE NOTED.CONFORM TO BUILDING COLOR CODING 3. GRUNDFOS PUMPS CORP. DAMAGED BY WORK. FOR PVC JACKETS. 3, DRAIN DUTY:HOSE-END DRAIN VALVES. 4.TACO,INC 02018/2019 PIERCE FRYE ARCHITECTS SECTION 23 0010-COMMON MECHANICAL REQUIREMENTS F.SEAL:MECHANICAL SEAL,225 DEGREES F(107 DEGREES C)MAXIMUM CONTINUOUS OPERATING ni_K[u +IMEG PART 1 GENERAL TEMPERATURE comm.. sluHut Iv SECTION 230713-MECHANICAL INSULATION /1� G-DRIVE;FLEXIBLE COUPLING. A.WORK SHALL CONSIST OF FURNISHING ALL LABOR AND MATERIALS NECESSARY FOR THE INSTALLATION OF PART 1 GENERAL PART 3 EXECUTION Mechanical,Electrical& COMPLETE AND OPERATING PLUMBING SYSTEMS. 1.01SUMMARY 3.01 INSTALLATION Energy Consultants B.ALL MECHANICAL WORK SHALL COMPLY WITH CURRENT STATE AND LOCAL BUILDING CODES AS REQUIRED BY THE AUTHORITIES HAVING JURISDICTION,THE INTERNATIONAL PLUMBING CODE,THE INTERNATIONAL A.SEE SECTION 233000-METAL DUCTS FOR DUCT LINING REQUIREMENTS. A.INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. FUEL GAS CODE,THE INTERNATIONAL MECHANICAL CODE,THE INTERNATIONAL FIRE CODE, B.SECTION INCLUDES INSULATING THE FOLLOWING DUCT SERVICES: B.PROVIDE ACCESS SPACE AROUND PUMPS FOR SERVICE.PROVIDE NO LESS THAN MINIMUM SPACE INTERNATIONAL ENERGY CONSERVATION CODE AND APPLICABLE PUBLICATIONS OF THE NATIONAL FIRE RECOMMENDED BY MANUFACTURER. 1. INDOOR,CONCEALED SUPPLY AND OUTDOOR AIR. PROTECTION ASSOCIATION(NFPA)SUCH AS NFPA 90A AND APPROPRIATE ASHRAE STANDARDS(15,55, END OF SECTION 62.1,90.1,111,135,189). 2. INDOOR,CONCEALED RETURN LOCATED IN UNCONDITIONED SPACE. C.THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF THE GENERAL CONDITIONS, 3. SECTION INCLUDES INSULATING THE FOLLOWING HVAC EQUIPMENT THAT IS NOT FACTORY INSULATED. SECTION 23 2900-ENCLOSED CONTROLLERS AND VARIABLE FREQUENCY DRIVE PIERCE SUPPLEMENTAL GENERAL CONDITIONS OF THE PROJECT SPECIFICATIONS,ALL CONTRACT DOCUMENTS, 4 SECTION INCLUDES INSULATING THE FOLLOWING HVAC PIPING SYSTEMS: AND ANY BASE BUILDING SPECIFICATIONS AND BUILDING CRITERIA INCLUDED IN THIS PROJECT. a.CONDENSATE DRAIN PIPING,INDOORS. PART 1 GENERAL + FRYE D.DRAWINGS ARE DIAGRAMMATIC IN NATURE.TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, PART 2 PRODUCTS 1.01SUMMARY CERTIFIED EQUIPMENT DRAWINGS,AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK. A.SECTION INCLUDES THE FOLLOWING ENCLOSED CONTROLLERS RATED 600 V AND LESS' 2.01 MINERAL FIBER E.THE DRAWINGS INDICATE THE LOCATION,TYPE AND SIZES OF VARIOUS UTILITIES WITHIN THE SITE WHERE 1. FULL-VOLTAGE MAGNETIC. ARCHITECTS KNOWN.ANY RELOCATION OR REMODELING REQUIRED MUST BE APPROVED BY THE ARCHITECT BEFORE A.MINERAL-FIBER BLANKET INSULATION:MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING PROCEEDING.INVESTIGATE ALL UTILITIES SUCH AS GAS AND WATER AND MAKE ARRANGEMENTS WITH RESIN.COMPLY WITH ASTM C 553,TYPE II AND ASTM C 1290,TYPE III WITH FACTORY-APPLIED FSK JACKET 2. VARIABLE FREQUENCY DRIVES THE PROPER AUTHORITY TO PAY FOR ANY CHARGES ASSOCIATED WITH CONNECTING THOSE UTILITIES. OR TYPE III WITH FACTORY-APPLIED FSP JACKET. PART 2 PRODUCTS F.GOOD WORKMANSHIP AND APPEARANCE ARE CONSIDERED EQUAL TO PROPER OPERATION. 1. PRODUCTS:SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE ONE OF THE FOLLOWING: 2.01 FULL-VOLTAGE CONTROLLERS a.CERTAINTEED CORP.;SOFTTOUCH DUCT WRAP. A.GENERAL REQUIREMENTS FOR FULL-VOLTAGE CONTROLLERS:COMPLY WITH NEMA ICS 2,GENERAL San Francisco Office G.PROVIDE ALL CORE DRILLING,CHANNELING,CUTTING,PATCHING,TRENCHING AND BACKFILL AS REQUIRED Tel:415.392.4433 FOR INSTALLATION OF MECHANICAL EQUIPMENT.SEAL HOLES WITH FIREPROOFING AND/OR WATER b.JOHNS MANVILLE;MICROLITE. PURPOSE,CLASS A. PROOFING WHERE NECESSARY AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE c.KNAUF INSULATION;FRIENDLY FEEL DUCT WRAP. 2.02 THE VFD PACKAGE AS SPECIFIED HEREIN SHALL BE ENCLOSED IN A UL LISTED TYPE ENCLOSURE, Vail Office DAMAGED BY WORK. U.MANSON INSULATION INC.;ALLEY WRAP. PART 3 EXECUTION (ENCLOSURES WITH ONLY NEMA RATINGS ARE NOT ACCEPTABLE.) Tel:970.949.0899 H.MAKE PROVISIONS FOR SAFE DELIVERY AND SECURE STORAGE OF ALL MATERIALS. e.OWENS CORNING;SOFTR ALL-SERVICE DUCT WRAP. 3.01 EXAMINATION A.ENVIRONMENTAL OPERATING CONDITIONS:0 TO 400 C(32 TO 1040 F)CONTINUOUS.ALTITUDES TO 6000 I. OBTAIN AND ARRANGE FOR ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK 2. MINERAL-FIBER,PREFORMED PIPE INSULATION TYPE I,850 DEG F MATERIALS:MINERAL OR GLASS A.VERIFY THAT CONDITIONED POWER SUPPLY IS AVAILABLE TO CONTROL UNITS AND OPERATOR FEET ABOVE SEA LEVEL,LESS THAN 95%HUMIDITY,NON-CONDENSING.ALL CIRCUIT BOARDS SHALL HAVE w200.PIerBeFrye.00m AND PAY ALL ASSOCIATED FEES. FIBERS BONDED WITH A THERMOSETTING RESIN.COMPLY WITH ASTM C 547,TYPE I,GRADE A,WITH WORKSTATION. ONFORMAL GATING. inf0®PierceFrye.com SECTION 23 2000-HYDRONIC PIPING,SPECIALTIES AND EQUIPMENT :.ENCLOSURE SHALL BE UL RATED. 1 J.ALL EQUIPMENT AND PRODUCTS TO BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK WITH FACTORY-APPLIED ASJ. B.VERIFY THAT DUCT-,PIPE-,AND EQUIPMENT-MOUNTED DEVICES ARE INSTALLED BEFORE PROCEEDING ALL STICKERS,MARKING,PACKING MATERIALS AND LIKE OR SIMILAR ITEMS REMOVED.REMOVE ALL PART 1 GENERAL AL r S' L- 0 OWING STANDARD FEATURES: a.PRODUCTS:SUBJECT TO COMPLIANCE WITH REQUIREMENTS,PROVIDE ONE OF THE FOLLOWING: WITH INSTALLATION. RUBBISH,DEBRIS,SCRAPS OR OTHER MATERIAL NOT NEED FOR THE FINAL PRODUCT FROM THE JOB SITE. 1.01SUMMARY 1)JOHNS MANVILLE;MICRO-LOK 3.02 SYSTEM INSTALLATION 1. ALL VFDS SHALL HAVE THE SAME CUSTOMER INTERFACE,INCLUDING DIGITAL DISPLAY,AND KEYPAD, 1.02SUBMTTTALS A.THIS SECTION INCLUDES PIPE AND FITTING MATERIALS,JOINING METHODS,SPECIAL-DUTY VALVES,AND REGARDLESS OF HORSEPOWER RATING.THE KEYPAD SHALL BE REMOVABLE,CAPABLE OF REMOTE 2)KNAUF INSULATION;1000-DEGREE PIPE INSULATION A.INSTALL SOFTWARE IN CONTROL UNITS AND OWNER'S EXISTING OPERATOR WORKSTATION(S). O� �_ A.PRODUCT DATA:FOR EACH TYPE OF PRODUCT INDICATED WITHIN DIVISION 23.INCLUDE RATED SPECIALTIES FOR THE FOLLOWING: MOUNTING AND ALLOW FOR UPLOADING AND DOWNLOADING OF PARAMETER SETTINGS AS AN AID FOR 3)MANSON INSULATION INC.;ALLEY-K. IMPLEMENT ALL FEATURES OF PROGRAMS TO SPECIFIED REQUIREMENTS AND AS APPROPRIATE TO START-UP OF MULTIPLE VFDS. = CO CAPACITIES,OPERATING CHARACTERISTICS,ELECTRICAL CHARACTERISTICS,AND FURNISHED SEQUENCE OF OPERATION. 1. HOT-WATER HEATING PIPING. SPECIALTIES AND ACCESSORIES. 4)OWENS CORNING;FIBERGLAS PIPE INSULATION 2.CONDENSATE-DRAIN PIPING. 2.THE KEYPAD SHALL INCLUDE HAND-OFF-AUTO SELECTIONS AND MANUAL SPEED CONTROL THERE B.CALIBRATE ALL SENSORS FOR THE PROJECT ELEVATION. e 1.03WARRANTY PART 3 EXECUTION 3.DIELECTRIC FITTINGS SHALL BE FAULT RESET AND"HELP"BUTTONS ON THE KEYPAD.THE HELP BUTTON SHALL INCLUDE .- 0 3.01 GENERAL INSTALLATION REQUIREMENTS 3.03 FIELD QUALITY CONTROL "ON-LINE"ASSISTANCE FOR PROGRAMMING AND TROUBLESHOOTING. A.THE MECHANICAL CONTRACTOR SHALL PROVIDE TO THE OWNER A ONE(1)YEAR(FROM THE DATE OF FINAL 4.BALANCING VALVES ACCEPTANCE)WARRANTY OF ALL MECHANICAL EQUIPMENT AND SYSTEMS PROVIDED UNDER THIS A.INSTALL INSULATION MATERIALS,ACCESSORIES,AND FINISHES WITH SMOOTH,STRAIGHT,AND EVEN A.MANUFACTURER'S FIELD SERVICE:ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO 3.THE VFD SHALL HAVE INTERNAL 5%IMPEDANCE REACTORS TO REDUCE THE HARMONICS TO THE IM tv INSPECT, AND ADJUST FIELD-ASSEMBLED COMPONENTS AND EQUIPMENT INSTALLATION, 5. STRAINERS POWER LINE AND TO ADD PROTECTION FROM AC LINE TRANSIENTS,NO EXCEPTIONS. CONTRACT.ALL DEFECTIVE EQUIPMENT OR MATERIALS WHICH APPEAR DURING THE WARRANTY PERIOD SURFACES;FREE OF VOIDS THROUGHOUT THE LENGTH OF PIPING INCLUDING FITTINGS,VALVES,AND 1:1.) 0 SHALL BE REPLACED OR REPAIRED BY THE MECHANICAL INATIMELY FASHION. SPECIALTIES. CONNECTIONS,AND TO ASSIST IN FIELD TESTING.REPORT RESULTS IN WRITING. PART 2 PRODUCTS 4.THE INPUT CURRENT RATING OF THE VFD SHALL BE NO MORE THAN 3%GREATER THAN THE OUTPUT PART 2 PRODUCTS B.INSTALL INSULATION MATERIALS,FORMS,VAPOR BARRIERS OR RETARDERS,JACKETS,AND THICKNESSES B.PERFORM THE FOLLOWING FIELD TESTS AND INSPECTIONS AND PREPARE TEST REPORTS: 2.01 COPPER TUBE AND FITTINGS CURRENT RATING.VFD'S WITH HIGHER INPUT CURRENT RATINGS REQUIRE.THE UPSTREAM WIRING, 0 (r9 `0 2.01 GENERAL REQUIRED FOR EACH ITEM OF PIPE SYSTEM AS SPECIFIED IN INSULATION SYSTEM SCHEDULES. 1. OPERATIONAL TEST:AFTER ELECTRICAL CIRCUITRY HAS BEEN ENERGIZED,START UNITS TO CONFIRM A.DRAWN-TEMPER COPPER TUBING:ASTM BOB.TYPE LASTM B 88,TYPE M. PROTECTION DEVICES,AND SOURCE TRANSFORMERS TO RE OVERSIZED PER NEC 430.120. V PROPER UNIT OPERATION.REMOVE AND REPLACE MALFUNCTIONING UNITS AND RETEST. 5.THE VEX SHALL PROVIDE A PROGRAMMABLE LOSS-OF-LOAD(BROKEN BELT/BROKEN COUPLING) A.THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT AND ACCESSORIES NECESSARY WHETHER C.INSTALL ACCESSORIES COMPATIBLE WITH INSULATION MATERIALS AND SUITABLE FOR THE SERVICE. B.ANNEALED-TEMPER COPPER TUBING:ASTM B88,TYPE K. FORM-C RELAY OUTPUT.THE DRIVE SHALL BE PROGRAMMABLE TO SIGNAL THE LOSS-OF-LOAD C7SN SPECIFICALLY STATED OR NOT TO MAKE THE REQUIRED MECHANICAL SYSTEMS COMPLETE AND INSTALL ACCESSORIES THAT DO NOT CORRODE,SOFTEN,OR OTHERWISE ATTACK INSULATION OR JACKET 2.TEST AND ADJUST CONTROLS AND SAFETIES. + OPERATIONAL. IN EITHER WET OR DRY STATE. 3.04 ELECTRICAL WIRING AND CONNECTION INSTALLATION 2.02 STEEL PIPE AND FITTINGS CONDITION VIA A KEYPAD WARNING,FORM-C RELAY OUTPUT,AND/OR OVER THE SERIAL �_ �e A A.STEEL PIPE:SCHEDULE 40,ASTM A 53/A 53M,TYPE E BLACK STEEL WITH PLAIN ENDS:TYPE,GRADE. COMMUNICATIONS BUS. a-- d Q B.ALL EQUIPMENT PROVIDED SHALL BE NEW EXCEPT AS OTHERWISE STATED ON THE DRAWINGS.ALL D.INSTALL INSULATION WITH LONGITUDINAL SEAMS AT TOP AND BOTTOM OF HORIZONTAL RUNS. A.INSTALL RACEWAYS,BOXES,AND CABINETS ACCORDING TO SECTION 260533'RACEWAYS AND BOXES FOR 6.THE VFD SHALL HAVE THE FOLLOWING PROTECTIVE CIRCUITS AND/OR PROGRAMMABLE FEATURES: EQUIPMENT PROVIDED SHALL BE ACCEPTABLE FOR INSTALLATION BY THE AUTHORITY HAVINGELECTRICAL SYSTEMS." 2.03 VALVES E.INSTALL MULTIPLE LAYERS OF INSULATION WITH LONGITUDINAL AND END SEAMS STAGGERED. OVERCURRENT,SHORT CIRCUIT,GROUND FAULT,OVER VOLTAGE,UNDER VOLTAGE,INPUT PHASE Lin JURISDICTION. B.INSTALL BUILDING WIRE AND CABLE ACCORDING TO SECTION 26 0519'LOW-VOLTAGE ELECTRICAL POWER A.GATE,GLOBE,CHECK,BALL,AND BUTTERFLY VALVES LOSS,LOSS,OUTPUT DEVICE OVER TEMPERATURE,LOSS OF ANALOG INPUT,PANEL LOSS,EXTERNAL FAULT, 3.02 PIPING AND DUCT INSULATION SCHEDULES C.THE EQUIPMENT SCHEDULES ON THE DRAWINGS AND THROUGHOUT THESE SPECIFICATIONS y���1pp���� ,I CONDUCTORS AND CABLES.' 2.04 WYE-PATTERN STRAINERS: MOTOR THERMAL PROTECTION,STALL UNDER LOAD,MOTOR PHASE LOSS AND GROUND FAULT. I U MANUFACTURER AND MODEL INFORMATION.THIS SERVES AS THE STANDARD OF QUALITY FV1�`��E f YE PDE SCHEDULE IIPING AND DNCLUUCT IDED ONTTHE DRAWINGSION SHALL . WITH THE TYPE AND INSULATION THICKNESS NOTED IN C.INSTALL SIGNAL AND COMMUNICATION CABLE ACCORDING TO THE REQUIREMENTS OF SECTION 271005 A.BODY:ASTM A 126,CLASS B,CAST IRON WITH BOLTED COVER AND BOTTOM DRAIN CONNECTION. D.ALL VFDS TO HAVE THE FOLLOWING ADJUSTMENTS: (9J ++ EQUIPMENT BY DIFFERENT MANUFACTURERS.THE SPECIFICATION ALLOWS FOR DIFFERENT "STRUCTURED CABLING FOR VOICE AND DATA'AND THE REQUIREMENTS LISTED BELOW.IN CASE OF � C MANUFACTURERS TO BE USED FOR THE EQUIPMENT,HOWEVER,REFER TO THE ARCHITECTURH0S/OA ZI ",y.JOT USED. B.END CONNECTIONS:THREADED ENDS FOR NP52AND SMALLER;FLANGED ENDS FOR NPS 2-1/2 AND 1. RUN PERMISSIVE CIRCUIT-THERE SHALL BEARUN PERMISSIVE CIRCUIT FOR MAMPEROR VALVE ®�, y t CONFLICT BETWEEN THE STATEMENTS HEREIN AND SECTION 271005 THE MOST STRINGENT LARGER. CONTROL.REGARDLESS OF THE SOURCE OF A RUN COMMAND(KEYPAD COMMAND,INPUT CONTACT C® u D SPECIFICATIONS FOR SUBSTITUTIONS BY MANUFACTURERS OTHER THAN THOSE LISTED IN THE END OF SECTION REQUIREMENTS SHALL BE MET. CLOSURE,TIME-CLOCK CONTROL OR SERIAL COMMUNICATIONS),THE VFD SHALL PROVIDE A DRY SPECIFICATIONS.WHERE NO EQUIPMENT SPECIFICATION IS PROVIDED THE SCHEDULED EQUIPMENT ASPEN 1. CONCEAL CABLE,EXCEPT IN MECHANICAL ROOMS AND AREAS WHERE OTHER CONDUIT AND PIPING ARE C.STRAINER SCREEN:40-MESH STARTUP STRAINER,AND PERFORATED STAINLESS-STEEL BASKET WITH 50 CONTACT CLOSURE THAT WILL SIGNAL THE DAMPER TO OPEN(VFD MOTOR DOES NOT OPERATE). N 0) 03 MANUFACTURER SHALL SERVE AS THE BASIS OF DESIGN AND ANY SUBSTITUTIONS SHALL ME PERCENT FREE AREA. �BTITINGDEPARTMENT EXPOSED. WHEN THE DAMPER IS FULLY OPEN,A NORMALLY OPEN DRY CONTACT(ENDSWITCH)SHALL CLOSE. _ - QUALITY STANDARD SET BY THE BASIS OF DESIGN. SECTION 230900-INSTRUMENTATION AND CONTROLS D.CWP RATING:125 PSIG. 0 D.CONTRACTOR TO BE RESPONSIBLE FOR ANY CHANGES AND COSTS TO ACCOMMODATE ANY EQUIPMENT PART 1 GENERAL 2.INSTALL EXPOSED CABLE IN RACEWAY(FLEXIBLE CONDUIT SHALL BE LIMITED TO 3 FOOT LENGTHS THE CLOSED END-SWITCH IS WIRED TOAVFD DIGITAL INPUT AND ALLOWS VFD MOTOR OPERATION.A P� 4) MAXIMUM). PART3 EXECUTION MINIMUM OF TWO SEPARATE SAFETY INTERLOCK INPUTS SHALL BE PROVIDED.WHEN ANY SAFETY IS - EXCEPT THE MANUFACTURER LISTED IN THE EQUIPMENT SCHEDULES,DRAWING NOTES AND/OR CALLED 1.01SUMMARY OPENED,THE MOTOR SHALL BE COMMANDED TO COAST TO STOP AND THE DAMPER SHALL BE L= 3. INSTALL CONCEALED CABLE IN RACEWAY(FLEXIBLE CONDUIT SHALL BE LIMITED TO 3 FOOT LENGTHS 3.01 PIPING INSTALLATIONS OUT WITHIN THE SPECIFICATIONS.IF NO SCHEDULES ARE INCLUDED ON THE DRAWING THAN THE FIRSTCOMMANDED TO CLOSE. . �-•/ NAMED IN THE SPECIFICATION IS THE STANDARD OF DESIGN. A.THIS SECTION INCLUDES CONTROL EQUIPMENT FOR HVAC SYSTEMS AND COMPONENTS,INCLUDING MAXIMUM). A.DRAWING PLANS,SCHEMATICS,AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF C PIPING SYSTEMS.INDICATE PIPING LOCATIONSAND ARRANGEMENTS IF SUCH WERE USED TO SIZE PIPE CONTROL COMPONENTS FOR TERMINAL HEATING AND COOLING UNITS NOT SUPPLIED WITH 2.THE VFD CONTROL SHALL INCLUDE A PROGRAMMABLE TIME DELAY FOR VFD START AND A KEYPAD CZ 2.02 IDENTIFICATION FACTORY-WIRED CONTROLS. 3.05 DEMONSTRATIONINDICATION THAT THIS TIME DELAY IS ACTIVE.A FORM C RELAY OUTPUT PROVIDES A CONTACT CU L AND CALCULATE FRICTION LOSS,EXPANSION,PUMP SIZING,AND OTHER DESIGN CONSIDERATIONS. A.PROVIDE PIPE AND EQUIPMENT IDENTIFICATION IN ACCORDANCE WITH ANSI A13.1 AND OR THE BUILDING B.PROJECT SCOPE INCLUDES CONNECTION TO OWNER'S EXISTING CONTROL SYSTEM.ALL NEW A.ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN OWNER'S MAINTENANCE CLOSURE TO SIGNAL THE VAV BOXES OPEN.THIS WILL ALLOW VAV BOXES TO BE DRIVEN OPEN BEFORE M = PERSONNEL TO ADJUST,OPERATE,AND MAINTAIN HVAC INSTRUMENTATION AND CONTROLS.REFER TO B.INSTALL PIPING IN CONCEALED LOCATIONS,UNLESS OTHERWISE INDICATED AND EXCEPT IN EQUIPMENT THE MOTOR OPERATES. STANDARDS. COMPONENTS SHALL BE COMPATIBLE WITH THIS SYSTEM. OD 121 SECTION 017900"DEMONSTRATION AND TRAINING' ROOMS AND SERVICE AREAS. 3.THE VFD SHALL INCLUDE A FIREMAN'S OVERRIDE INPUT.THE MODE SHALL OVERRIDE ALL OTHER yP 2.03 MISCELLANEOUS SPECIALTIES C.EXTENSION AND REWORK OF EXISTING DDC CONTROLS SYSTEM SHALL BE PERFORMED IN A MANNER SO C rn END OF SECTION C.INSTALL PIPING INDICATED TO BE EXPOSED AND PIPING IN EQUIPMENT ROOMS AND SERVICE AREAS AT INPUTS(ANALOG/DIGITAL,SERIAL COMMUNICATION,AND ALL KEYPAD COMMANDS),EXCEPT A.SLEEVES AND SLEEVE SEALS: AS TO HAVE NO NEGATIVE IMPACT ON THE EXISTING SYSTEM.PRODUCTS AND DEVICES SHALL BE IN RIGHT ANGLES OR PARALLEL TO BUILDING WALLS.DIAGONAL RUNS ARE PROHIBITED UNLESS CUSTOMER DEFINED SAFETY RUN INTERLOCKS,AND FORCE THE MOTOR TO RUN AT A PRESET SPEED •L) w 1. WHERE PIPING PASSES THROUGH NEW MASONRY OR CONCRETE WALLS OR CONCRETE FLOORS, CONFORMANCE WITH EXISTING SYSTEM. A SPECIFICALLY INDICATED OTHERWISE. ORIN A SEPARATE PID MODE. C PROVIDE PIPE SLEEVES.SLEEVES SHALL BE CONSTRUCTED OUT OF GALVANIZED STEEL CAST IRON OR 1.02SEQUENCE OF OPERATION C9S D.INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL. PARTS EXECUTION PVC.SET SLEEVES IN FORMS PRIOR TO CONCRETE PLACEMENT. SLEEVES IN FLOORS SHALL EXTEND SEE MECHANICAL DRAWINGS FOR CONTROL DRAWINGS AND SEQUENCE OF OPERATION.THESE ,. (V 2"ABOVE THE FINISHED FLOOR ELEVATION.WHERE LOCATED INEXTERIOR WALLS,PROVIDE WATER E.INSTALL PIPING TO PERMIT VALVE SERVICING. 3.01 INSTALLATION DRAWINGS SHOW GENERAL INTENT AND MINIMUM POINT REQUIREMENTS.IF MORE REAL OR VIRTUAL STOP IN SLEEVE. POINTS ARE REQUIRED TO PROVIDE THE SEQUENCES NOTED,IT IS THE INSTRUMENTATION AND CONTRO F.INSTALL PIPING AT INDICATED SLOPES. A.WALL-MOUNTED CONTROLLERS:INSTALL ENCLOSED CONTROLLERS ON WALLS WITH TOPS AT UNIFORM 2.PIPING WHICH PASSES THROUGH A RATED WALL SHALL BE PROVIDED WITH A UL DETAIL SUITABLE FOR CONTRACTOR'S RESPONSIBILITY TO PROVIDE THE ADDITIONAL EQUIPMENT,ACCESSORIES AND G.INSTALL PIPING FREE OF SAGS AND BENDS. HEIGHT UNLESS OTHERWISE INDICATED,AND BY MOUNTING ON LIGHTWEIGHT STRUCTURAL-STEEL PIPE MATERIAL AND SIZE.SLEEVE SHALL ONLY BE REQUIRED IF THE UL DETAIL REQUIRES THE SLEEVE. PROD' ITI/EN CES AR TO'E.O. TH SE QU NC S. CHANNELS BOLTED TO WALL TO ENSURE AIR FLOW BEHIND CONTROLLER.FOR CONTROLLERS NOT AT Issue Date: A iiY I H.INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS. WALLS,PROVIDE FREESTANDING RACKS COMPLYING WITH DIVISION 26 SECTION"HANGERS AND 07/18/2018 P¢rmll Set WHERE SLEEVES ARE REQUIRED AS NOTED ABOVE,PROVIDE A UL DETAIL THAT UTILIZES A SLEEVE. B.WHERE CONTROL DRAWINGS AND SEQUENCE OF OPERATION ARE NOT IDENTIFIED,INDUSTRY STANDARD 02/282019 Building Porn))Resubmidal I. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION. SUPPORTS FOR ELECTRICAL SYSTEMS." B.ESCUTCHEONS: SEQUENCES AND CONTROL DEVICES SHALL BE PROVIDED TO ACCOMMODATE PROPER SYSTEM OPERATION AND SAFETY CONTROL OF ALL DEVICES SPECIFIED IN DIVISION 22 AND DIVISION 23. J.SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM B.COORDINATE LAYOUT AND INSTALLATION OF VFDS WITH OTHER CONSTRUCTION INCLUDING CONDUIT, 1. WHERE NEW PIPE PASSES THROUGH A FINISHED WALL,PROVIDE A CHROME PLATED ESCUTCHEON. OPERATING PRESSURE. PIPING,EQUIPMENT,AND ADJACENT SURFACES.MAINTAIN REQUIRED WORKSPACE CLEARANCES AND ESCUTCHEON SHALL BE CONSTRUCTED IN ONE PIECE. C.PROVIDE EQUIPMENT SAFETIES AS NOTED HEREIN. REQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS AND PANELS. C.ACCESS DOORS D.UNLESS SPECIFICALLY NOTED OTHERWISE MODULATE/STAGING DOWN SEQUENCES SHALL BE THE K.INSTALL GROUPS OF PIPES PARALLEL TO EACH OTHER,SPACED TO PERMIT APPLYING INSULATION AND SERVICING OF VALVES. 1. WALL-MOUNTING CONTROLLERS:INSTALL VFDS ON WALLS WITH TOPS AT UNIFORM HEIGHT AND WITH 1. WHERE NOTED,PROVIDE THE TYPE AND SIZE OF ACCESS DOOR TO FULLY ACCESS THE ITEM THAT IS OPPOSITE OF THE MODULATE/STAGING UP SEQUENCE SHOWN. DISCONNECT OPERATING HANDLES NOT HIGHER THAN 79 INCHES ABOVE FINISHED FLOOR UNLESS LOCATED WITH THE WALL OR CAVITY.PROVIDE FIRE RATED DOORS WHERE INSTALLED IN FIRE RATED PART 2 PRODUCTS L.INSTALL DRAINS,CONSISTING OF ATEE FITTING,ABS 3/4 BALL VA VE,AND SHORT NPS 3/4 THREADED OTHERWISE INDICATED,AND BY BOLTING UNITS TO LIGHTWEIGHT STRUCTURAL-STEEL CHANNELS NIPPLE WITH CAP,AT LOW POINTS IN PIPING SYSTEM MAINS AND ELSEWHERE AS REQUIRED FOR SYSTEM ASSEMBLIES. 2.01 CONTROL SYSTEM DRAINAGE. BOLTED TO WALL ENSURING AIR FLOW TO THE BACK OF THE VFD.FOR CONTROLLERS NOT ON WALLS, PART 3 EXECUTION PROVIDE FREESTANDING RACKS COMPLYING WITH DIVISION 26 SECTION'HANGERS AND SUPPORTS A.BUILDING'S EXISTING CONTROL SYSTEM IS BY CARRIER. M.REDUCE PIPE SIZES USING ECCENTRIC REDUCER FITTING INSTALLED WITH LEVEL SIDE UP. FOR ELECTRICAL SYSTEMS.. 3.01 GENERAL B.CONTROL SYSTEM SHALL CONSIST OF SENSORS,INDICATORS,ACTUATORS,FINAL CONTROL ELEMENTS, N.INSTALL BRANCH CONNECTIONS TO MAINS USING MECHANICALLY FORMED OR STANDARD TEE FITTINGS IN A.OBTAIN AND ARRANGE FOR ALL PERMITS AND APPROVALS REQUIRED FOR THE EXECUTION OF THE WORK INTERFACE EQUIPMENT,OTHER APPARATUS,ACCESSORIES,AND SOFTWARE CONNECTED TO MAIN PIPE,WITH THE BRANCH CONNECTED TO THE BOTTOM OF THE MAIN PIPE.FOR UP-FEED RISERS, AND PAY ALL ASSOCIATED FEES. DISTRIBUTED CONTROLLERS OPERATING IN MULTIUSER,MULTITASKING ENVIRONMENT ON CONNECT THE BRANCH TO THE TOP OF THE MAIN PIPE. B.PROVIDE ALL CORE DRILLING,CHANNELING,CUTTING,PATCHING,TRENCHING AND BACKFILL AS REQUIRED TOKEN-PASSING NETWORK AND PROGRAMMED TO CONTROL MECHANICAL SYSTEMS.AN OPERATOR O.INSTALL VALVES ACCORDING TO SECTION 230523"GENERAL-DUTY VALVES FOR HVAC PIPING." FOR INSTALLATION OF MECHANICAL EQUIPMENT.SEAL HOLES,FIREPROOFING WHERE NECESSARY,AND WORKSTATION PERMITS INTERFACE WITH THE NETWORK VIA DYNAMIC COLOR GRAPHICS WITH EACH REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE DAMAGED BY MECHANICAL WORK. MECHANICAL SYSTEM,BUILDING FLOOR PLAN,AND CONTROL DEVICE DEPICTED BY POINT-AND-CLICK P.INSTALL UNIONS IN PIPING,NPS 2 AND SMALLER,ADJACENT TO VALVES,AT FINAL CONNECTIONS OF GRAPHICS. EQUIPMENT,AND ELSEWHERE AS INDICATED. C.ALL EQUIPMENT AND PRODUCTS TO BE THOROUGHLY CLEANED AT THE COMPLETION OF THE WORK WITH ALL STICKERS,MARKINGS AND THE LIKE SHALL BE REMOVED.REMOVE ALL RUBBISH,DEBRIS,SCRAPS 2.02 INPUT/OUTPUT INTERFACE: Q.INSTALL FLANGES IN PIPING,NPS 2-1/2 AND LARGER,AT FINAL CONNECTIONS OF EQUIPMENT AND AND THE LIKE FROM THE JOB SITE. A.HARDWIRED INPUTS AND OUTPUTS MAY TIE INTO SYSTEM THROUGH CONTROLLERS.PROTECT POINTS SO ELSEWHERE AS INDICATED. 3.02 FLUSHING AND CLEANING THAT SHORTING WILL CAUSE NO DAMAGE TO CONTROLLERS. R.INSTALL STRAINERS ON INLET SIDE OF EACH CONTROL VALVE,PRESSURE-REDUCING VALVE,SOLENOID END OF SECTION VALVE,IN-LINE PUMP,AND ELSEWHERE AS INDICATED.INSTALL NPS 3/4 NIPPLE AND BALL VALVE IN A.BEFORE FINAL CONNECTIONS ARE MADE IN THE PIPING SYSTEMS,SYSTEMS SHALL BE BLOWN OUT WITH B.BINARY INPUTS;ALLOW MONITORING OF ON-OFF SIGNALS WITHOUT EXTERNAL POWER. SLOWDOWN CONNECTION OF STRAINERS NPS 2AND LARGER.MATCH SIZE OF STRAINER BLOWOFF "OryA00 L/�F„ AIR AND THEN COMPLETELY WASHED OUT WITH CLEANING COMPOUNDS COMPATIBLE WITH FINAL FLUID C.ANALOG INPUTS;ALLOW MONITORING OF LOW-VOLTAGE(0-TO 10-V DC),CURRENT(4 TO 20 MA),OR CONNECTION FOR STRAINERS SMALLER THAN NPS 2. fy0�' .j. G:E•N.J•••. S TO AVOID CONTAMINATION.THE SYSTEMS SHALL THEN BE FLUSHED FOR THE COMPLETE REMOVAL OF RESISTANCE SIGNALS. 8 Oi•�U ALL FOREIGN MATERIALS.FURNISH ALL TEMPORARY CONNECTIONS,VALVES,ETC.,REQUIRED FOR THIS END OF SECTION rY •v• D.BINARY OUTPUTS:PROVIDE ON-OFF OR PULSED LOW-VOLTAGE SIGNAL,SELECTABLE FOR NORMALLY j p PURPOSE. / 3_, OPEN OR NORMALLY CLOSED OPERATION. / J END OF SECTION SECTION 29 2123-HYDRONIC PUMPS ///p. 44 E.ANALOG OUTPUTS:PROVIDE MODULATING SIGNAL,EITHER LOW VOLTAGE(0-TO 10-V DC)OR CURRENT(4 J)J-t• PART 1 GENERAL 1 F"•.•• :';ur SECTION 23059;-TESTING,ADJUSTING AND BALANCING TO 20 MA). 1.01SECTION INCLUDES IIIIISN I!'_ � PART 1 GENERAL F.TRI-STATE OUTPUTS:PROVIDE TWO COORDINATED BINARY OUTPUTS FOR CONTROL OF THREE-POINT, 1.01SUMMARY FLOATING-TYPE ELECTRONIC ACTUATORS. A.IN-LINE CIRCULATORS. Z-Ja-19 A.THE TESTING,ADJUSTING AND BALANCING OF THE SYSTEMS SHALL BE PART OF THIS CONTRACT,INCLUDE G.UNIVERSAL I/OS:PROVIDE SOFTWARE SELECTABLE BINARY OR ANALOG OUTPUTS. 1.02REFERENCE STANDARDS IN BID THE COST OF THIS WORK.THE BALANCING CONTRACTOR SHALL BE AABC CERTIFIED,NEBB 2.03 CONTROL VALVES A.UL 778-STANDARD FOR MOTOR-OPERATED WATER PUMPS;CURRENT EDITION,INCLUDING ALL REVISIONS. Drawing Title: CERTIFIED,TABS CERTIFIED OR A REGISTERED PROFESSIONAL ENGINEER. A.CONTROL VALVES:FACTORY FABRICATED,OF TYPE,BODY MATERIAL,AND PRESSURE CLASS BASED ON 1.03SUBMITTALS B.ALL REPORTS SHALL BE SUBMITTED ON STANDARD AABC,NEBB OR TABS FORMS. MAXIMUM PRESSURE AND TEMPERATURE RATING OF PIPING SYSTEM,UNLESS OTHERWISE INDICATED; A.PRODUCT DATA:PROVIDE CERTIFIED PUMP CURVES SHOWING PERFORMANCE CHARACTERISTICS WITH C.COMPLY WITH ASHRAE 111. MATCH BUILDING STANDARD. PUMP AND SYSTEM OPERATING POINT PLOTTED.INCLUDE NPSH CURVE WHEN APPLICABLE.INCLUDE PART 2 PRODUCTS(NOT APPLICABLE) 2.04 CONTROL CABLE ELECTRICAL CHARACTERISTICS AND CONNECTION REQUIREMENTS. I trl ECI-IA VICAI_ PART 3 EXECUTION A.ELECTRONIC AND FIBER-OPTIC CABLES FOR CONTROL WIRING SHALL COMPLY WITH THE REQUIREMENTS PART 2 PRODUCTS SPECIFICATIONS 3.01 TAB SPECIALISTS OF SECTION 271500'COMMUNICATIONS HORIZONTAL CABLING'AND THE REQUIREMENTS LISTED BELOW. 2.01 MANUFACTURERS IN CASE OF CONFLICT BETWEEN THE STATEMENTS HEREIN AND SECTION 271500 THE MOST STRINGENT A.SUBJECT TO COMPLIANCE WITH REQUIREMENTS,ENGAGE ONE OF THE FOLLOWING: REQUIREMENTS SHALL BE MET. A.ARMSTRONG PUMPS INC:WWW.ARMSTRONGPUMPS.COM. 1. GRIFFITH ENGINEERING SERVICE 1. ALL CONTROL DEVICES AND PANELS CONTAINING LOW VOLTAGE POWER SOURCES SHALL INHERENTLY B.BELL 8 GOSSETT,A XYLEM INC.BRAND:WWW.BELLGOGSETT.COM. 2. J.P.G.ENGINEERING COMPLY WITH NEC CLASS 2 REQUIREMENTS(CURRENT LIMITING),OR SHALL BE SUPPLIED WITH BRANCH 2.02 HVAC PUMPS-GENERAL CIRCUIT FUSING TO LIMIT CONTROL CIRCUIT CURRENT TO NEC CLASS 2.ALL CONTROL TRANSFORMERS Date: March 16,2018 3.PRECISION TEST 8 BALANCE,INC. A.PROVIDE PUMPS THAT OPERATE AT SPECIFIED SYSTEM FLUID TEMPERATURES WITHOUT VAPOR BINDING SHALL BE OF THE INHERENT CURRENT LIMITING TYPE,OR SHALL BE INSTALLED WITH PRIMARY 4.TAB SERVICES,INC. DISCONNECTS AND OVERLOAD PROTECTION. AND CAVITATION,ARE NON-OVERLOADING IN PARALLEL OR INDIVIDUAL OPERATION,AND OPERATE WITHIN 25 PERCENT OF MIDPOINT OF PUBLISHED MAXIMUM EFFICIENCY CURVE. Project No: 2018.01.0077 5. SUPERIOR BALANCE AND COMMISSIONING 2. SHIELDED CABLE:TWISTED SHIELDED CABLE SHALL BE USED WHERE CALLED FOR AND WHERE 6. JEDI BALANCING REQUIRED TO PROPERLY PROTECT THE DDC SYSTEM FROM FALSE SIGNALS AND ELECTRICAL NOISE. B.PRODUCTS REQUIRING ELECTRICAL CONNECTION:LISTED AND CLASSIFIED BY UL OR TESTING AGENCY Drawn by: ARD MJK SHIELDING SHALL BE FINE BRAIDED TINNED COPPER(90%COVERAGE)OR ALUMINUM FOIL(100% ACCEPTABLE TO AUTHORITY HAVING JURISDICTION AS SUITABLE FOR THE PURPOSE SPECIFIED AND 3.02 SUMMARY COVERAGE). INDICATED. Checked by: ARD MJK A.SET THE SYSTEM AIR FLOW RATES AND WATER FLOW RATES WITHIN THE FOLLOWING TOLERANCES:PLUS 3. MINIMUM REQUIREMENTS: 2.03 IN-LINE CIRCULATORS 10 PERCENT TO MINUS 5 PERCENT. a.COMMUNICATION CABLE:TWISTED SHIELDED PAIR,16 GAUGE. A.TYPE:HORIZONTAL SHAFT,SINGLE STAGE,DIRECT CONNECTED,WITH RESILIENTLY MOUNTED MOTOR FOR Sheet: B.THE AIR,HYDRONIC AND DOMESTIC HOT WATER RECIRCULATION SYSTEMS SHALL BE TESTED,ADJUSTED IN-LINE MOUNTING,OIL LUBRICATED,FOR 125 PSI(860 KPA)MAXIMUM WORKING PRESSURE. AND BALANCED TO THE QUANTITIES LISTED. b.ANALOG INPUT:TWISTED SHIELDED TWO,THREE,OR FOUR-WIRE AS REQUIRED,18 GAUGE C.A REPORT SHALL BE SUBMITTED TO THE OWNER AND ENGINEER FOR REVIEW. S.BINARY INPUT:18 GAUGE. B.CASING:CAST IRON,WITH FLANGED PUMP CONNECTIONS. M7• END OF SECTION U.ANALOG OUTPUT:TWISTED SHIELDED,18 GAUGE. C.IMPELLER:NON-FERROUS KEYED TO SHAFT. 1 e.BINARY OUTPUT;18 GAUGE. D.BEARINGS:OIL-LUBRICATED BRONZE SLEEVE. E.SHAFT ALLOY STEEL WITH BRONZE SLEEVE,INTEGRAL THRUST COLLAR. 02018/2019 PIERCE FRYE ARCHITECTS SECTION 23 3000-DUCTS AND ACCESSORIES PART GENERAL MKK CONSULTING PSINES,INC �IMEG 1.013UMMARY A.SECTION INCLUDES: 3.05 ACCESSORY INSTALLATION Mechanical,Electrical& 1. SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS. A.INSTALL DUCT ACCESSORIES ACCORDING TO APPLICABLE DETAILS IN SMACNA'S'HVAC DUCT Energy Consultants 2.SINGLE-WALL ROUND DUCTS AND FITTINGS. CONSTRUCTION STANDARDS-METAL AND FLEXIBLE'FOR METAL DUCTS AND IN NAIMA AH116,'FIBROUS 3.SHEET METAL MATERIALS. GLASS DUCT CONSTRUCTION STANDARDS;FOR FIBROUS-GLASS DUCTS. 4.DUCT LINER. 3.06 GRILLES,REGISTERS AND DIFFUSER INSTALLATION 5.SEALANTS AND GASKETS. A.INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. 6.HANGERS AND SUPPORTS. B.CHECK LOCATION OF OUTLETS AND INLETS AND MAKE NECESSARY ADJUSTMENTS IN POSITION TO PIERCE 7.MANUAL VOLUME DAMPERS. CONFORM WITH ARCHITECTURAL FEATURES,SYMMETRY,AND LIGHTING ARRANGEMENT. 8.COMBINATION FIRE AND SMOKE DAMPERS. C.CEILING-MOUNTED OUTLETS AND INLETS:DRAWINGS INDICATE GENERAL ARRANGEMENT OF DUCTS, 9.FLANGE CONNECTORS. FITTINGS,AND ACCESSORIES.AIR OUTLET AND INLET LOCATIONS HAVE BEEN INDICATED TO ACHIEVE + FRYE DESIGN REQUIREMENTS FOR AIR VOLUME,NOISE CRITERIA,AIRFLOW PATTERN,THROW,AND PRESSURE 10.TURNING VANES. DROP.MAKE FINAL LOCATIONS WHERE INDICATED,AS MUCH AS PRACTICAL.FOR UNITS INSTALLED IN 11.DUCT-MOUNTED ACCESS DOORS. LAY-IN CEILING PANELS,LOCATE UNITS IN THE CENTER OF PANEL.COORDINATE EXACT LOCATION WITH 12.FLEXIBLE CONNECTORS. ARCHITECTURAL REFLECTED CEILING PLAN.WHERE ARCHITECTURAL FEATURES OR OTHER ITEMS ARCHITECTS CONFLICT WITH INSTALLATION,NOTIFY ARCHITECT FOR A DETERMINATION OF FINAL LOCATION. 13.FLEXIBLE DUCTS. D.INSTALL DIFFUSERS TO DUCTWORK WITH AIR TIGHT CONNECTION. 14.GRILLES,REGISTERS AND DIFFUSERS. PART 2 PRODUCTS E.PROVIDE BALANCING DAMPERS ON DUCT TAKE-OFF TO DIFFUSERS,AND GRILLES AND REGISTERS,DESPITE San Francisco Office WHETHER DAMPERS ARE SPECIFIED AS PART OF THE DIFFUSER,OR GRILLE AND REGISTER ASSEMBLY. 2.01 SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS Tel:415.392.4433 F.INSTALL DIFFUSERS.REGISTERS,AND GRILLES WITH AIRTIGHT CONNECTIONS TO DUCTS AND TO ALLOW A.GENERAL FABRICATION REQUIREMENTS:COMPLY WITH SMACNA'S-HVAC DUCT CONSTRUCTION SERVICE AND MAINTENANCE OF DAMPERS,AIR EXTRACTORS,AND FIRE DAMPERS. STANDARDS-METAL AND FLEXIBLE"BASED ON INDICATED STATIC-PRESSURE CLASS UNLESS OTHERWISE Vail Office G.PAINT DUCTWORK VISIBLE BEHIND AIR OUTLETS AND INLETS MATTE BLACK.REFER TO SECTION 099123. INDICATED. Tel:970.949.0899 H.INSTALL AND SUPPORT ALL GRDS PER MANUFACTURER'S RECOMMENDATIONS. 2.02 SINGLE-WALL ROUND DUCTS AND FITTINGS 1. GRDS WEIGHING LESS THAN 20 POUNDS SHALL BE POSITIVELY ATTACHED TO CEILING SUSPENSION www.PlerReFrye.COm A.GENERAL FABRICATION REQUIREMENTS:COMPLY WITH SMACNA'S"HVAC DUCT CONSTRUCTION MAIN RUNNERS OR TO CROSS RUNNERS WITH THE SAME CARRYING CAPACITY AS THE MAIN RUNNERS. infa®PierceFrye.com STANDARDS-METAL AND FLEXIBLE,"CHAPTER 3,'ROUND,OVAL,AND FLEXIBLE DUCT,"BASED ON INDICATED STATIC-PRESSURE CLASS UNLESS OTHERWISE INDICATED. 2.GRDS WEIGHTING GREATER THAN 20 POUNDS,BUT NOT MORE THAN 56 POUNDS,IN ADDITION TO THE ABOVE,SHALL HAVE TWO NO.12 GAUGE HANGERS CONNECTED FROM THE TERMINAL OR SERVICE TO 2.03 SHEET METAL MATERIALS THE CEILING HANGERS OR TO THE STRUCTURE ABOVE.THESE WIRES MAY BE SLACK. A.GENERAL MATERIAL REQUIREMENTS:COMPLY WITH SMACNA'S"HVAC DUCT CONSTRUCTION STANDARDS- 3.GRDS WEIGHING GREATER THAN 56 POUNDS SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE METAL AND FLEXIBLE"FOR ACCEPTABLE MATERIALS,MATERIAL THICKNESSES,AND DUCT CONSTRUCTION '(OV BY_-P:FV•H4kG:5. 0,13 METHODS UNLESS OTHERWISE INDICATED.SHEET METAL MATERIALS SHALL BE FREE OF PITTING,SEAM 1 MARKS,ROLLER MARKS,STAINS,DISCOLORATIONS,AND OTHER IMPERFECTIONS. _ FE'TO.CH DU E F•-F -T R FO- AT ON. 2.04 DUCT LINER END OF SECTION QQ •A.FIBROUS-GLASS DUCT LINER:COMPLY WITH ASTM C 1071,NFPA 90A,OR NFPA 90B;AND WITH NAIMA AH124, 0 'FIBROUS GLASS DUCT LINER STANDARD." SECTION 233400-FANS 7-0 HANGERS AND SUPPORTS PART 1 GENERAL O) A.HANGER RODS FOR NONCORROSIVE ENVIRONMENTS:CADMIUM-PLATED STEEL RODS AND NUTS. 1.01SUMMARY O 0 B.STRAP AND ROD SIZES:COMPLY WITH SMACNNS"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND A.T • CL DES THE FOLLOWING: •P,/J U FLEXIBLE,"TABLE 5-1,'RECTANGULAR DUCT HANGERS MINIMUM SIZE,'AND TABLE 5-2,'MINIMUM HANGER ggingb 1 SIZES FOR ROUND DUCT." •C C PART 2 PRODUCTS a) C.STEEL CABLES FOR GALVANIZED-STEEL DUCTS:GALVANIZED STEEL COMPLYING WITH ASTM A 603. 2.01 FANS e�� 2.06 MANUAL VOLUME DAMPERS A.PROVIDE THE FAN INDICATED IN THE EQUIPMENT SCHEDULE OR AN EQUAL BY: cg C ® Q A.STANDARD,STEEL,MANUAL VOLUME DAMPERS AS DETAILED OR NOTED: 1. ACME ENGINEERING S MFG.CORP. 2.07 COMBINATION FIRE AND SMOKE DAMPERS 2. AEROVENT;A TWIN CITY FAN COMPANY � A.TYPE:DYNAMIC;RATED AND LABELED ACCORDING TO UL 555 AND UL 555S BY AN NRTL �^C 1 U B.CLOSING RATING IN DUCTS UP TO 4-INCH WG STATIC PRESSURE CLASS AND MINIMUM 2000-1��^^1�E �O.�VEQ BREIDERT AIR PRODUCTS.GREENHECK. Pl a••' C.FIRE RATING:1-1/2 HOURS. C Ntl, 5.LOREN COOK COMPANY. ®�, D.FRAMEHAT-SHAPED,0.094-INCH-THICK,GALVANIZED SHEET STEEL,WITH WELDED,INTERLOCIPI O 4I/2020 ®�® C 6.NUTONE INC. U GUSSETED OR MECHANICALLY ATTACHED CORNERS AND MOUNTING FLANGE. AcWpN T.PENNBARRY. Q) E. RATEDESPONSIVE DEVICE:ELECTRIC RESETTABLE DEVICE AND SWITCH PACKAGE,FACTORY,INSTFl16yEAR N+REFER TO SCHEDULE FOR CAPACITY AND CHARACTERISTICS F.BLADES:ROLL-FORMED,HORIZONTAL,INTERLOCKING,0.063-INCH-THICK,GALVANIZED SHEET STEEL UtCrY PARTS EXECUTION G.LEAKAGE:CLASS II. 3.01 INSTALLATION ® f_S 2.08 FLANGE CONNECTORS 3.02 CONNECTIONS 3� A.DUCT INSTALLATION AND CONNECTION REQUIREMENTS ARE SPECIFIED IN OTHER DIVISION 23 SECTIONS. CZ C A.DESCRIPTION:ADD-ON OR ROLL-FORMED,FACTORY-FABRICATED,SLIDE-ON TRANSVERSE FLANGE DRAWINGS INDICATE GENERAL ARRANGEMENT OF DUCTS AND DUCT ACCESSORIES.MAKE FINAL DUCT a) Es CONNECTORS,GASKETS,AND COMPONENTS. CONNECTIONS WITH FLEXIBLE CONNECTORS.FLEXIBLE CONNECTORS ARE SPECIFIED IN DIVISION 23 B.MATERIAL:GALVANIZED STEEL. SECTION"AIR DUCT ACCESSORIES.' Q �� C.GAGE AND SHAPE:MATCH CONNECTING DUCTWORK. 3.03 ADJUSTING C � 2.09 TURNING VANES A.ADJUST DAMPER LINKAGES FOR PROPER DAMPER OPERATION. •t L A.MANUFACTURED TURNING VANES FOR METAL DUCTS:CURVED BLADES OF GALVANIZED SHEET STEEL; B.ADJUST BELT TENSION. SUPPORT WITH BARS PERPENDICULAR TO BLADES SET;SET INTO VANE RUNNERS SUITABLE FOR DUCT ® N MOUNTING. C.REFER TO DIVISION 23 SECTION'TESTING,ADJUSTING,AND BALANCING FOR HVAC'FOR TESTING, ADJUSTING,AND BALANCING PROCEDURES. 2.10 DUCT-MOUNTED ACCESS DOORS D.REPLACE FAN AND MOTOR PULLEYS AS REQUIRED TO ACHIEVE DESIGN AIRFLOW. A.DUCT-MOUNTED ACCESS DOORS:FABRICATE ACCESS PANELS ACCORDING TO SMACNNS"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE";FIGURES 7-2,"DUCT ACCESS DOORS AND PANELS," E.LUBRICATE BEARINGS. Issue Date: AND 7-3,"ACCESS DOORS-ROUND DUCT." END OF SECTION 07/18/2018 Permit Set 2.11 DUCT ACCESS PANEL ASSEMBLIES 02/28/2019 Building P9rnit Re3Ubmigel A.LABELED ACCORDING TO UL 1978 BY AN NRTL. B.PANEL AND FRAME:MINIMUM THICKNESS 0.0428-INCH STAINLESS STEEL. C.FASTENERS: STAINLESS STEEL.PANEL FASTENERS SHALL NOT PENETRATE DUCT WALL. D.GASKET:COMPLY WITH NFPA 96;GREASE-TIGHT,HIGH-TEMPERATURE CERAMIC FIBER,RATED FOR MINIMUM 2000 DEG F. E.MINIMUM PRESSURE RATING:10-INCH WG,POSITIVE OR NEGATIVE. 2.12 FLEXIBLE DUCTS A.INSULATED,FLEXIBLE DUCT:UL 181,CLASS 1,ALUMINUM LAMINATE AND POLYESTER FILM WITH LATEX ADHESIVE SUPPORTED BY HELICALLY WOUND,SPRING-STEEL WIRE;FIBROUS-GLASS INSULATION; POLYETHYLENE VAPOR-BARRIER FILM. 1. PRESSURE RATING:10-INCH WG POSITIVE AND 1.0-INCH WG NEGATIVE. 2.MAXIMUM AIR VELOCITY:4000 FPM. 3.TEMPERATURE RANGE:MINUS 20 TO PLUS 210 DEG F. 4.INSULATION R-VALUE:R-6 MINIMUM INSTALLED PERFORMANCE(1-5/8 INCH MINIMUM THICKNESS). B.FLEXIBLE DUCT CONNECTORS: 1. CLAMPS:STAINLESS-STEEL BAND WITH CADMIUM-PLATED HEX SCREW TO TIGHTEN BAND WITH A WORM-GEAR ACTION IN SIZES 3 THROUGH 18 INCHES,TO SUIT DUCT SIZE. 2.13 GRILLES,REGISTERS AND DIFFUSRS ISCLADRC/0.�2•yy1}}}���• A.REFER TO SCHEDULE FOR REQUIREMENTS FOR GRILLES,REGISTERS AND DIFFUSERS. V,./c.N.UO��••SFVA PART 3 EXECUTION i. 3.01 DUCT INSTALLATION g¢,L; ` A.DRAWING PLANS,SCHEMATICS,AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF fI DUCT SYSTEM.INDICATED DUCT LOCATIONS,CONFIGURATIONS,AND ARRANGEMENTS WERE USED TO I FS•'• SIZE DUCTS AND CALCULATE FRICTION LOSS FOR AIR-HANDLING EQUIPMENT SIZING AND FOR OTHER Il Ski.' DESIGN CONSIDERATIONS.INSTALL DUCT SYSTEMS AS INDICATED UNLESS DEVIATIONS TO LAYOUT ARE APPROVED ON SHOP DRAWINGS AND COORDINATION DRAWINGS. 2- B.INSTALL DUCTS ACCORDING TO SMACNA'S"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE'UNLESS OTHERWISE INDICATED. Drawing Title: 3.02 DUCT SEALING A.SEAL DUCTS FOR DUCT STATIC-PRESSURE,SEAL CLASSES,AND LEAKAGE CLASSES SPECIFIED IN"DUCT SCHEDULE"ARTICLE CONTAINED WITHIN THIS SPECIFICATION ACCORDING TO SMACNNS"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE." C I•'C I• 3.03 HANGER AND SUPPORT INSTALLATION SPECIFICATIONS A.COMPLY WITH SMACNNS"HVAC DUCT CONSTRUCTION STANDARDS-METAL AND FLEXIBLE,'CHAPTER 5, 'HANGERS AND SUP•OR S." 3.04 DUCT SCHEDULE A.SUPPLY DUCTS: 1. DUCTS CONNECTED TO VAV TERMINALS(DOWNSTREAM): Date: March 16,2028 a PRESSURE CLASS:POSITIVE 2-INCH WG. b.MINIMUM SMACNA SEAL CLASS:A. Project No: 2018.01.0077 c.SMACNA LEAKAGE CLASS FOR RECTANGULAR:12. A tl. Drawn by: ARD MJK SMACNA LEAKAGE CLASS FOR ROUND.12. Checked by: ARD MJK Sheet: M7.2 02018/2019 PIERCE FRYE ARCHITECTS