iiiLSubject: PlanCheck Where are the reception desk
^
Page: 3
__ Page Index: 3 and coffee station located and
Li0 .u'°"" Author: nickt where can I find drawings of
r"111Color: • them? Both must be
File Name: 0048-2019-ARBK_BuildingComments_1_Markup documented to demonstrate
Summary_RBresponse.pdf accessibility. LB_O.S4 appears
to only show lockers and a
cabinet-is this the coffee
station?
Subject: PlanCheck
Page:4 Make it clear on the plans how
Page Index: 4 you are complying with the
Author: nickt below.Your response says it is
v noted on the plans but does not
-_= Color: •
File Name: 0048-2019-ARBK_BuildingComments_1_Markup tell me where to look and I'm not
e-==u __ -- Summary_RBresponse.pdf seeing it:
L_== _ 5%of all lockers must be
-_— accessible(2015 IBC
1109.12.1). In addition to the
clearspace you've shown, this
also requires the following:
-The operable hardware must be
operable with one hand and not
require tight grasping, pinching,
or twisting of the wrist to
operate. (ICC A117.1-2009
section 309.4)
-The operable hardware no more
than 48"above the floor(ICC
A117.1-2009 section 308).
-Shelves and hooks between 15"
and 48"above floor(ICC
A117.1-2009 section 308).
611 E Durant_Full Permit Set Rev 2.pdf(4)
II �.." 1, // Subject: Group
1 T ,, \ Page:A2.1COPYRIGHT 2019 ROWLAND+BROUGHTON Dimension the clearances
- ,� - ARCHITECTURE AND URBAN DESIGN•50THE INFORMATIO quired on each side of door.
Ir..- - iii �- i: AND DESIGN INTENT CONTAINED ON THIS DOCUMENTI C/A117.1 2009 section
if- I104 • 404.2.3.2
IS I I XWILEVEL ONE•50FLOOR PLANcrAi c-n»
f , ".° Page Index: 9
- u•• : 7 - Author: nickt
. , Color: ■
,l M' ' File Name: 611 E Durant_Full Permit Set Rev 2.pdf
-w,.- - Subject: PlanCheck
•- E°°` € Page:A7.1 DETAILS Provide a clearspace for forward
Page Index: 11 approach to a lavatory.
Author: nickt
Color: •
File Name: 611 E Durant_Full Permit Set Rev 2.pdf
III , �..
-._ Subject: Group
° Page:A7.1 DETAILS Dimension the water closet
Page Index: 11
compartments and doors to
�.�d: demonstrate compliance with
ltr9ri "` Author: nickt
;WNW;_; t = Color: • ICC/A117.1-2009 section
.
Ir I, File Name: 611 E Durant_Full Permit Set Rev 2.pdf 604.9.2
Subject: PlanCheck
Page:AMC-LN-LR-1006 AMC- Lockers Room- Benches On the plans, clearly dimension
,. r< If_ Page Index: 18 the accessible benches
3^h SB Author: nickt (including cushions)to
Aso
o
Color: • demonstrate compliance with
File Name: 611 E Durant_Full Permit Set Rev 2.pdf ICC/A117.1-2009 section 903.
-T• Standard Imperial units rather
zthan metric please.
903.3 Size. Benches shall have
seats 42 inches minimum in
length, and 20 inches minimum
and 24 inches maximum in
depth.
903.4 Back Support. The bench
shall provide for back
support or shall be affixed to a
wall. Back support shall
be 42 inches minimum in length
and shall
extend from a point 2 inches
maximum above
the seat surface to a point 18
inches minimum
above the seat surface. Back
support shall be 21/2
inches maximum from the rear
edge of the
seat measured horizontally.
903.5 Height. The top of the
bench seat shall be 17
inches minimum and 19 inches
maximum above the floor,
measured to the top of the
seat.
Nolan Single Sconce.pdf(1)
Subject: PlanCheck
Page: 1 Label the Nolan single sconce
Page Index: 1 cutsheet to be light type ZF.S.
Author: nickt
„� me Color: • Revise Comcheck to show 60
File Name: Nolan Single Sconce.pdf watts to match.